This document outlines a federal contract opportunity to construct Devils Lake Substation, Stage 06 in North Dakota. The solicitation number is 89503420BWA000017 and is being issued by the Department of Energy Western Area Power Administration. The project involves constructing the Devils Lake Substation and has an estimated value between $1,000,000 to $5,000,000. The NAICS code for this project is 237130, with a small business size standard of $39.5 million. The document refers contractors to the Annual Representations and Certifications requirement on SAM.gov and provides no other salient details regarding response dates, award timing, or other requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEVILS LAKE SUBSTATION
STAGE 06
NORTH DAKOTA
SECTION C
DESCRIPTION/SPECIFICATIONS
Solicitation No. 89503420BWA000017 Spec. No. 20WC135416-974
PROJECT DRAWINGS
A. GENERAL:
CONSTRUCTION DRAWINGS: Construction drawings are the specification drawings and any additional drawings required for use in construction. The construction drawings will be issued after contract award and may include amendment changes and other details, which make the drawings suitable to use for construction purposes.
PROJECT DRAWINGS: Project drawings included herein are reduced reproductions and are not to scale. Some project drawings show details of fabrication and other information not a part of the work. Disregard information and details, which are not applicable.
STANDARD DRAWINGS: Where details shown on standard drawings included herein differ from construction or project drawings or text, the details of construction or project drawings or text shall govern. A complete set of standard drawings are available at https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx.
INFORMATIONAL DRAWINGS: Some project drawings have the words “FOR INFORMATION ONLY” appearing above the title block. These drawings show some information, which may be required for bidding purposes. These drawings do not show items to be furnished or work to be performed.
EXISTING INSTALLATION DRAWINGS: Some project drawings have the words “EXISTING INSTALLATION” appearing above the title block. These drawings show the existing installations prior to modifications and may show some new work to be performed.
REFERENCE DRAWINGS: Reference drawings referred to on project drawings and not included herein, are not necessary for bidding purposes.
CONTRACTOR'S RESPONSIBILITY: Check all drawings and advise Western of any errors or omissions.
B. LIST OF DRAWINGS:
LOCATION MAP:
1. DL 0015 Rev. B – Location and Vicinity Map
ELECTRICAL:
2. DL 0001 Rev. L EI – Switching Diagram (Existing Installation)
3. DL 0001 Rev. M – Switching Diagram
4. DL 0010 Rev. C EI – General Plot Plan (Existing Installation)
5. DL T0010 Rev. C FIO – General Plot Plan - Temporary Shoo Fly (For Information Only)
6. DL 0019 – General Plot Plan
7. DL 1002 Rev. B EI – 41.8-kV Bus Structure - Plan and Sections (Existing Installation)
8. DL 1002 Rev. C – 41.8-kV Bus Structure - Sections H-H, I-I and J-J
9. DL 1003 Rev. B – General Arrangement Plan
10. DL 1012 Rev. C EI – 12.47-kV Bus Structure (Existing Installation)
11. DL 1012 Rev. D – 41.8-kV and 12.47-kV Area - Plan
12. DL 1013 Rev. E EI – Shunt Capacitor Install - Plan and Sections (Existing Installation)
13. DL 1013 Rev. F – Shunt Capacitor Install - Sections
14. DL 1020 – 115-kV Yard - Area Plan
15. DL 1021 – 115-kV Yard Bays 1 & 2 - Area Arrangement Plan
16. DL 1022 – 115-kV Yard Bays 3 & 4 - XFMR KY14A - Area Arrangement Plan
17. DL 1023 – 115-kV Yard Bays 5 & 6 - Area Arrangement Plan
18. DL 1024 – 115-kV Yard Bays 7 & 8 - Area Arrangement Plan
19. DL 1103 – Equipment and Material Index
20. DL 1104 – Substation Signs
21. DL 1105 – Substation Signs
22. DL 1111 Rev. C EI – 115-kV Area - Sections M-M, Q-Q and S-S (Existing Installation)
23. DL 1115 – 12.47-kV Bus Structure - Sections D-D, E-E, F-F and G-G
24. DL 1121 – 115-kV Yard Bays 1 & 2 - Sections A-A and B-B
25. DL 1122 – 115-kV Yard Bays 3 & 4 - Sections H-H and I-I
26. DL 1123 – 115-kV Yard Bays 5 & 6 - Sections L-L and M-M
27. DL 1124 – 115-kV Yard Bays 7 & 8 - Sections R-R and S-S
28. DL 1125 – 115-kV Yard Transfer Bus - Section C-C
29. DL 1126 – 115-kV Yard Main Bus - Section D-D
30. DL 1127 – Instrument Transformers - Sections
31. DL 1128 – 115-kV Cap Bank Area - Sections P-P and Q-Q
32. DL 1500 Rev. B – Key Grounding Plan
33. DL 1510 Rev. C EI – 41.8-kV Bus Structures - Grounding, Conduit, and Buried Cable Plan (Existing Installation)
34. DL 1510 Rev. D – 41.8-kV Bus Structures - Grounding Plan
35. DL 1512 Rev. B FIO – 12.47-kV Area - Grounding, Conduit, and Buried Cable Plan (For Information Only)
36. DL 1520 – 115-kV Yard - General Grounding Plan
37. DL 1521 – 115-kV Yard Bays 1 & 2 - Area Grounding Plan
38. DL 1522 – 115-kV Yard Bays 3 & 4 - XFMR KY14A - Area Grounding Plan
39. DL 1523 – 115-kV Yard Bays 5 & 6 - Area Grounding Plan
40. DL 1524 – 115-kV Bays 7 & 8 - Area Grounding Plan
41. DL 1600 – Station Service - DWA and DWB Wiring Diagram https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx
PROJECT DRAWINGS
42. DL 1620 – Station Service - 240/120V Wiring Diagram
43. DL 1710 – 41.8-kV Bus Structures - Conduit and Buried Cable Plan
44. DL 1712 – 12.47-kV Area - Conduit and Buried Cable Plan
45. DL 1720 – 115-kV - General Conduit Plan
46. DL 1721 – 115-kV Yard Bays 1 & 2 - Area Conduit Plan
47. DL 1722 – 115-kV Yard Bays 3 & 4 - XFMR KY14A - Area Conduit Plan
48. DL 1723 – 115-kV Yard Bays 5 & 6 - Area Conduit Plan
49. DL 1724 – 115-kV Yard Bays 7 & 8 - Area Conduit Plan
50. DL 1730 – Pull Box PB1 - Plan and Sections
51. DL 1731 – Civil - Concrete Encased Duct Bank Section
CIVIL & SITE DRAWINGS:
52. DL 2050 Rev. C EI – Grading Plan (Existing Installation)
53. DL 2050 Rev. D – Grading Plan
54. DL 2051 Rev. B FIO – Grading - Sections and Details (For Information Only)
55. DL 2053 Rev. A FIO – Runoff Detention Details (For Information Only)
56. DL 2054 – Civil - Site Plan
57. DL 2055 – Civil - Grading Plan
58. DL 2056 – Grading at Service Building Details
59. DL 2057 – Civil - Sections(1 of 2)
60. DL 2058 – Civil - Sections (2 of 2)
61. DL 2059 – Civil - Details
62. DL 2060 Rev. C FIO – Site Oil Containment Plan (For information Only)
63. DL 2062 – Oil Containment - Plan, Section and Cover
64. DL 2063 – Oil Containment - Sections and Details
FOUNDATION AND STRUCTURAL DRAWING INDEX:
65. DL 2033 Rev. C – Foundation/Structural Data and Drawing Index
CONCRETE:
66. DL 2002 Rev. J EI – Foundation General Plan (Existing Installation)
67. DL 2002 Rev. K – Foundation General Plan
68. DL 2015 Rev. A EI – 115-kV Approach Structures - Steel Poles and Foundations Location, Outlines and Details (Existing Installation)
69. DL 2034 Rev. E EI – Foundation Plan - 115-kV, 41.6-kV, & 12.47-kV Areas (Existing Installation)
70. DL 2034 Rev. F – 115-kV, 41.6-kV, & 12.47-kV Areas - Foundation Plan
71. DL 2035 Rev. B EI – Foundation Plan - 115-kV & Shunt Capacitor Areas (Existing Installation)
72. DL 2035 Rev. C – Foundation Plan - 115-kV & Shunt Capacitor Areas
73. DL 2200 – 115-kV Yard Bays 1 & 2 - Area Foundation Plan
74. DL 2201 – 115-kV Yard Bays 3 & 4 - XFMR KY14A - Area Foundation Plan
75. DL 2202 – 115-kV Yard Bays 5 & 6 - Area Foundation Plan
76. DL 2203 – 115-kV Yard Bays 7 & 8 - Area Foundation Plan
77. DL 2003 Rev. D – Foundations - Outline and Reinforcement
78. DL 2005 Rev. C – Concrete Structures Foundations - Outline and Reinforcement
79. DL 2022 Rev. B – Concrete Foundations - Outline and Reinforcement
80. DL 2023 Rev. B – Foundations - Concrete Outline and Reinforcement
81. DL 2038 Rev. A – Foundations - Outline and Reinforcement
82. DL 2300 – Foundations - Outline and Reinforcement
83. DL 2301 – Foundations - Outline and Reinforcement
84. DL 2302 – Foundations - Outline and Reinforcement
85. DL 2303 – Foundations - Outline and Reinforcement
86. DL 2304 – Foundations - Outline and Reinforcement
87. DL 2305 – Foundations - Outline and Reinforcement
88. DL 2306 – Foundations - Outline and Reinforcement
CABLE TRENCH:
89. DL 2500 – Cable Trench Plan & Sections
TRANSMISSION LINE STEEL POLE STRUCTURES FOUNDATIONS:
90. DL-CA 2106 – Type 165D Steel Pole Structures – Foundations
91. RG-DL 2101 – Type 151D Steel Pole Structures – Foundations
STEEL STRUCTURES:
92. DL 2550 – Anchor Bolts
93. DL 2006-1 – Steel Structures -115-kV Bus Structure – General Plans and Elevations (Sheet 1 of 5)
PROJECT DRAWINGS
94. DL 2006-2 – Switchyard – Steel Structures - 115-kV Bus Structure - Column Assemblies (Sheet 2 of 5)
95. DL 2007 Rev. B – Steel Structures - 46-kV Bus Structure
96. DL 2600 – 115-kV Take-Off Structure - Type I - Elevations
97. DL 2601 – 115-kV Take-Off Structure - Type I - Assemblies and Connections
98. DL 2602 – 115-kV Take-Off Structure - Type I - Assemblies and Connections
99. DL 2603 – 115-kV Take-Off Structure - Type II - Elevations
100. DL 2604 – 115-kV Take-Off Structure - Type II - Assemblies and Connections
101. DL 2605 – Bus Tower -Type I - Elevations
102. DL 2606 – Bus Tower - Type I - Assemblies and Connections
103. DL 2607 – Bus Tower - Type II - Elevations
104. DL 2608 – Bus Tower - Type II - Assemblies and Connections
105. DL 2609 – Switch Supports
106. DL 2610 – Ground Switch Supports
107. DL 2611 – Bus Frames
108. DL 2612 – Bus Poles
109. DL 2613 – Tee Poles
110. DL 2614 – Equipment Supports
111. DL 2615 – 45-Ft. Ground Mast
112. DL 2041 – Switch Operating Platforms - Steel Design and Details
113. DL 2925 – Equipment Cabinet Platforms - Steel Design and Details
114. DL 2926 – Transformer Platforms - Steel Design and Details
TRANSMISSION LINE STEEL POLE STRUCTURES:
115. 43-139D 2200 FIO – 139D Pole Structures - Outline and Design (For Information Only)
116. 43-151D 2200 Rev. B – 151D Steel Pole Structures - Outline and Design Loads
117. 43-165D 2200 – 165D Steel Pole Structures - Outline and Design Loads
118. 41 2701 Rev. C – Steel Pole Structures - Fall Protection Anchorage Plates
119. 41 9027-2 Rev. A – Steel Pole Structures - Aerial Patrol Mile Marker and Structure Number Signs (Sh. 2 of 3)
120. 43 2206 Rev. H – Steel Pole Structures - Maintenance Provisions – Outlines
121. 43 2210 Rev. J – Steel Pole Structures - Maintenance Provisions – Details
122. 43 2214 Rev. A – Steel Pole Structures - Maintenance Provisions – Outlines
STRINGING REQUIREMENTS:
123. DL 2021 Rev. B – Stringing Requirements
124. DL 2900 – Stringing Requirements
SUBSTATION MICROWAVE TOWER:
125. DL 2880 – 120 Foot 3 Leg Tower Outline And Details
126. DL 2890 – 120 Foot 3 Leg Comm Tower - Tower Foundation Layout
127. DL 2891 – 120 Foot 3 Leg Comm Tower - Auger Type Foundation
128. DL 2892 – 120 Foot 3 Leg Comm Tower - Bridge Channel Support
SERVICE BUILDING:
129. DL 3025 – Architectural - Floor Plan
130. DL 3026 – Architectural - Reflected Ceiling Plan
131. DL 3027 – Architectural - Exterior Elevations
132. DL 3028 – Architectural - Building Sections
133. DL 3029 – Architectural - Detailed Sections
134. DL 3030 – Architectural - Details
135. DL 3031 – Architectural - Detailed Sections
136. DL 3032 – Architectural - Hollow Metal Door Details
137. DL 3200 – General Structural Notes, Abbreviations, & Reference Drawings
138. DL 3201 Rev. A – Structural - Foundation Plan
139. DL 3202 – Structural - Roof Framing Plan
140. DL 3203-1 – Structural - Foundation Sections & Details (Sheet 1 of 2)
141. DL 3203-2 – Structural - Foundation Sections & Details (Sheet 2 of 2)
142. DL 3204-1 – Structural - Foundation/Cable Entry Details (Sheet 1 of 3)
143. DL 3204-2 – Structural - Foundation/Cable Entry Details (Sheet 2 of 3)
144. DL 3204-3 – Structural - Foundation/Cable Entry Details (Sheet 3 of 3)
145. DL 3205-1 – Structural - Typical Wood-Framed Wall (Sheet 1 of 2)
146. DL 3205-2 – Structural - Typical Wood-Framed Wall (Sheet 2 of 2)
147. DL 3206 – Structural - Equipment Mounting Details
PROJECT DRAWINGS
148. 31 2051 Rev. B – Service Building - Structural - Building Entry Platforms
149. 01-2006-1 – Building Slabs-On-Ground - Specifications, Notes, Plans and Details (Sheet 1 of 3)
150. 01-2006-2 – Building Slabs-On-Ground - Specifications, Notes, Plans and Details (Sheet 2 of 3)
151. 01-2006-3 – Building Slabs-On-Ground - Specifications, Notes, Plans and Details (Sheet 3 of 3)
152. DL 3300 – Mechanical - General Notes and Legend
153. DL 3301 – Mechanical - HVAC Floor Plan
154. DL 3302 – Mechanical - HVAC Details I
155. DL 3303 – Mechanical - HVAC Details II
156. DL 3304 – Mechanical - Schedules
157. DL 3305 – Mechanical - HVAC Controls
158. DL 3306 – Mechanical - HVAC Sections I
159. DL 3307 – Mechanical - HVAC Sections II
160. DL 3400 – Electrical - Power Plan
161. DL 3401 – Electrical - Lighting Plan
162. DL 3402 – Electrical - Security Plan
163. DL 3403 – Electrical - Panelboards DHA, DHA1
164. DL 3404 – Electrical - Wiring Devices Schematic
165. DL 3405 – Electrical - Luminaire and Equipment Schedules
166. DL 4040 – Arrangement, Conduit, and Grounding
167. DL 6040 – 125VDC DC Distribution Panels - BHA1 & BHA2 - Wiring Diagram
CONTROLS:
168. DL T600 – Control Cable List
GEOLOGY:
169. DL 8027 – Borehole Location Plan
170. DL 8028 – Penetration and Resistance Log - BH19-1
171. DL 8029 - Penetration and Resistance Log - BH19-2
172. DL 8030 – Penetration and Resistance Log - BH19-3
173. DL 8031 – Penetration and Resistance Log - BH19-4
174. DL 8032 – Penetration and Resistance Log - BH19-5
175. DL 8033 – Penetration and Resistance Log – Key to Symbols
STANDARD DRAWINGS:
Following is a partial list of Standard Drawings needed for this specification that supersede WAPA Standard Drawings available at: https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx
176. 31 1085 Rev. I – Substation Standards - Terminal and Fuse Boxes
AutoCAD SHX Text
EXISTING INSTALLATION
AutoCAD SHX Text
EXPLANATION
AutoCAD SHX Text
INDICATES DEMO WORK FOR STAGE 06
AutoCAD SHX Text
KY1A
AutoCAD SHX Text
NOTE
AutoCAD SHX Text 1.
41.8KV PLAN AREA IS MOVED TO DRAWING DL 1012.
OTTERTAIL LINE
DL 341
DISC SW YX3A 41.8KV
OTTERTAIL LINE
DL 342
PCB JX3A 41.8KV
OTTERTAIL LINE
DL 343
DISC SW WX3A 41.8KV
OTTERTAIL LINE
DL 349
DISC SW XX3A 41.8KV
OTTERTAIL LINE
VX3A1
VOLTAGE XFMR 41.8KV
OTTERTAIL LINE
QX3A1
CURRENT XFMR 41.8KV
OTTERTAIL LINE
EX3A
VX3A SECONDARY FUSES
41.8KV BUS
VX1A1
VOLTAGE XFMR 41.8KV
TRANSFORMER KY14A
EX1A
VX1A SECONDARY FUSES
SHUNT CAPACITOR BANK
PX2A1
SHUNT CAPACITOR PX2A
VX2A1
VOLTAGE XFMR 41.8KV
SHUNT CAPACITOR PX2A
EX2A
VX2A SECONDARY FUSES
TRANSFORMER KY14A
DL 143
DISC SW WX1A 41.8KV
TRANSFORMER
KY14A
115KV TRANSFER BUS
VY11C1
CCVT 115KV
115KV TRANSFER BUS
EY11C
VY11C SECONDARY FUSES
115KV MAIN BUS
VY11B1
CCVT 115KV
115KV MAIN BUS
EY11B
VY11B SECONDAY FUSES
LEEDS LINE
DL 1160
GND SW ZY11A 115KV
LEEDS LINE
DL 1161
DISC SW YY11A 115KV
LEEDS LINE
DL 1162
PCB JY11A 115KV
LEEDS LINE
DL 1163
DISC SW WY11A 115KV
LEEDS LINE
DL 1165
DISC SW YY11B 115KV
LEEDS LINE
VY11A1
CCVT 115KV
LEEDS LINE
EY11A
VY11A SECONDARY FUSES
SHUNT CAPACITOR PY15A
DL 1560
GND SW ZY15A 115KV
SHUNT CAPACITOR PY15A
DL 1563
DISC SW WY15A 115KV
SHUNT CAPACITOR PY15A
DL 1564
PCB JY15A 115KV
SHUNT CAPACITOR PY16A
KY16A1
CURRENT LIMITING REACTOR
41.8KV BUS
VX1A2
VOLTAGE XFMR 41.8KV
41.8KV BUS
VX1A3
VOLTAGE XFMR 41.8KV
SHUNT CAPACITOR BANK
PX2A2
SHUNT CAPACITOR BANK
PX2A3
SHUNT CAPACITOR PX2A
VX2A2
VOLTAGE XFMR 41.8KV
SHUNT CAPACITOR PX2A
VX2A3
VOLTAGE XFMR 41.8KV
115KV MAIN BUS
VY11B2
CCVT 115KV
115KV MAIN BUS
VY11B3
CCVT 115KV
TRANSFER BAY
DL 1261
DISC SW WY12B 115KV
TRANSFER BAY
DL 1263
DISC SW WY12A 115KV
TRANSFER BAY
DL 1266
PCB JY12A 115KV
LAKOTA LINE
DL 1360
GND SW ZY13A 115KV
LAKOTA LINE
DL 1361
DISC SW YY13A 115KV
LAKOTA LINE
DL 1362
PCB JY13A 115KV
LAKOTA LINE
DL 1363
DISC SW WY13A 115KV
LAKOTA LINE
DL 1365
DISC SW YY13B 115KV
LAKOTA LINE
VY13A1
CCVT 115KV
LAKOTA LINE
EY13A
VY13A SECONDARY FUSES
TRANSFORMER KY14A
DL 1460
GND SW ZY14A 115KV
TRANSFORMER KY14A
DL 1461
DISC SW YY14A 115KV
TRANSFORMER KY14A
DL 1462
PCB JY14A 115KV
TRANSFORMER KY14A
DL 1463
DISC SW WY14A 115KV
TRANSFORMER KY14A
DL 1465
DISC SW YY14B 115KV
TRANSFORMER KY14A
VY14A1
CCVT 115KV
TRANSFORMER KY14A
EY14A
VY14A SECONDARY FUSES
SHUNT CAPACITOR PY16A
DL 1660
GND SW ZY16A 115KV
SHUNT CAPACITOR PY16A
DL 1663
DISC SW WY16A 115KV
SHUNT CAPACITOR PY16A
DL 1664
PCB JY16A 115KV
SHUNT CAPACITOR PY16A
KY16A2
CURRENT LIMITING REACTOR
SHUNT CAPACITOR PY16A
KY16A3
CURRENT LIMITING REACTOR
SHUNT CAPACITOR BANK
PY15A1
SHUNT CAPACITOR BANK
PY15A2
SHUNT CAPACITOR BANK
PY15A3
SHUNT CAPACITOR PY15A
VY15A1
VOLTAGE XFMR 115KV
SHUNT CAPACITOR PY15A
VY15A2
VOLTAGE XFMR 115KV
SHUNT CAPACITOR PY15A
VY15A3
VOLTAGE XFMR 115KV
SHUNT CAPACITOR PY15A
EY15A
VY15A SECONDARY FUSES
SHUNT CAPACITOR BANK
PY16A1
SHUNT CAPACITOR BANK
PY16A2
SHUNT CAPACITOR BANK
PY16A3
SHUNT CAPACITOR PY16A
VY16A1
VOLTAGE XFMR 115KV
SHUNT CAPACITOR PY16A
VY16A2
VOLTAGE XFMR 115KV
SHUNT CAPACITOR PY16A
VY16A3
VOLTAGE XFMR 115KV
SHUNT CAPACITOR PY16A
EY16A
VY16A SECONDARY FUSES
CARRINGTON LINE
DL 1760
GND SW ZY17A 115KV
CARRINGTON LINE
DL 1761
DISC SW YY17A 115KV
CARRINGTON LINE
DL 1762
PCB JY17A 115KV
CARRINGTON LINE
DL 1763
DISC SW WY17A 115KV
CARRINGTON LINE
DL 1765
DISC SW YY17B 115KV
OTTERTAIL LINE
VX3A3
VOLTAGE XFMR 41.8KV
OTTERTAIL LINE
QX3A3
CURRENT XFMR 41.8KV
OTTERTAIL LINE
EX3B
QX3A SHORTING BLOCKS
SHUNT CAPACITOR PX2A
DL 240
GND SW ZX2A 41.8KV
SHUNT CAPACITOR PX2A
DL 243
DISC SW WX2A 41.8KV
SHUNT CAPACITOR PX2A
DL 244
PCB JX2A 41.8KV
RAMSEY OTP2 LINE
DL 1860
GND SW ZY18A 115KV
RAMSEY OTP2 LINE
DL 1861
DISC SW YY18A 115KV
RAMSEY OTP2 LINE
DL 1862
PCB JY18A 115KV
RAMSEY OTP2 LINE
DL 1863
DISC SW WY18A 115KV
RAMSEY OTP2 LINE
DL 1865
DISC SW YY18B 115KV
RAMSEY OTP2 LINE
VY18A1
CCVT 115KV
RAMSEY OTP2 LINE
EY18A
VY18A1 SECONDARY FUSES
RAMSEY OTP2 LINE
QY18A1
CURRENT XFMR 115KV
RAMSEY OTP2 LINE
QY18A2
CURRENT XFMR 115KV
RAMSEY OTP2 LINE
QY18A3
CURRENT XFMR 115KV
RAMSEY OTP2 LINE
EY18B
QY18A SHORTING BLOCKS
STATION SERVICE
DW1A
MAIN BREAKER 240V
STATION SERVICE
GEN
EMER GENERATOR CABINET
TRANSFORMER KX4A
DL 441
DISC SW WX4A 41.8KV
TRANSFORMER KX4A
DL 443
FUSE FX4A 41.8KV
CARRINGTON LINE
VY17A1
CCVT 115KV
CARRINGTON LINE
EY17A
VY17A SECONDARY FUSES
STATION SERVICE XFMR
KW4A
12470-120/240V 112.5KVA
MINNKOTA POWER COOP
EW4A
VW4A SECONDARY FUSES
MINNKOTA POWER COOP
EW4B
QW4A SHORTING BLOCKS
30.00'
AutoCAD SHX Text 30.00'
AutoCAD SHX Text
PULL BOX
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
EXISTING GROUND
AutoCAD SHX Text
EXISTING GROUND
AutoCAD SHX Text
PULL BOX
AutoCAD SHX Text 17''x4'-6" DUCT BANK
AutoCAD SHX Text
6" NDDOT ROAD BASE
AutoCAD SHX Text
4" SCH 40 PVC CONDUIT
AutoCAD SHX Text
6" NDDOT ROAD BASE
AutoCAD SHX Text
WESTERN AREA POWER ADMINISTRATION
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF ENERGY
AutoCAD SHX Text
HEADQUARTERS - LAKEWOOD, COLORADO
AutoCAD SHX Text S:\projects\Substations\DevilsLake\DevilsLake.06\Drawings\DesignDrawings\C3D\dl_1731.dwg Last Saved By: VanDerPol, Brian (CONTR) on 3/30/2020 11:47 AM Last Saved By: VanDerPol, Brian (CONTR) on 3/30/2020 11:47 AMVanDerPol, Brian (CONTR) on 3/30/2020 11:47 AM on 3/30/2020 11:47 AM3/30/2020 11:47 AM
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
CIVIL ENGINEERING MANAGER
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text
DEVILS LAKE SUBSTATION
AutoCAD SHX Text
NORTH DAKOTA
AutoCAD SHX Text
CIVIL
AutoCAD SHX Text
CONCRETE ENCASED DUCT BANK SECTION
AutoCAD SHX Text
KYLE VAUGHN
AutoCAD SHX Text
GINA CRAWFORD
AutoCAD SHX Text
DL
AutoCAD SHX Text
AutoCAD SHX Text
XREF(S)=
AutoCAD SHX Text
XR
AutoCAD SHX Text
DL_9500, DL_9510
AutoCAD SHX Text
DL_9512.
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1"=10'-0"
AutoCAD SHX Text
AutoCAD SHX Text
VERT SCALE:1"=2'
AutoCAD SHX Text
FINISHED GRADE
MARCH 30, 2020
SU
IT
AB
LE
F O
R S
PE
C
IF
C
AT
IO
N S
AS
O
F:
A ug
4, 3-
1:
am
83 83 denton
FIO
"H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text
TYPE 151D (BP) (BASE-PLATED)
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text
TYPE 151D (DE) (DIRECT-EMBEDDED)
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text
SECTION D-D
AutoCAD SHX Text
TYPE 151D (BP) BASE DETAIL
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text
TYPICAL JUMPER ATTACHMENT SECTION C-CSECTION C-C
AutoCAD SHX Text
COVER PLATE NOT SHOWN
AutoCAD SHX Text
TYPICAL LOWER TENSION INSULATOR ATTACHMENT
AutoCAD SHX Text
SECTION A-A LINE POST INSULATOR ATTACHMENT
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text
TYPICAL OGW AND UPPER TENSION INSULATOR ATTACHMENT
AutoCAD SHX Text 3"
AutoCAD SHX Text 3"
AutoCAD SHX Text 3"
AutoCAD SHX Text
SECTION B-B LINE POST INSULATOR ATTACHMENT
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text E
AutoCAD SHX Text CASE A - NESC HEAVY INTACT WIND ON STRUCTURE = 10 PSF DEAD LOAD OF STRUCTURE x 1.5
AutoCAD SHX Text CASE B - HIGH WIND INTACT WIND ON STRUCTURE = 30 PSF DEAD LOAD OF STRUCTURE x 1.15
AutoCAD SHX Text CASE C - RIME ICE INTACT WIND ON STRUCTURE = 5 PSF DEAD LOAD OF STRUCTURE x 1.1
AutoCAD SHX Text
TYPE 151D (DE) BASE DETAIL
AutoCAD SHX Text "D"
AutoCAD SHX Text "D"
AutoCAD SHX Text "D"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
TRANSMISSION LINE STRUCTURES
AutoCAD SHX Text
151D STEEL POLE STRUCTURES
AutoCAD SHX Text
OUTLINE AND DESIGN LOADS
AutoCAD SHX Text
BOBBY HAGLER
AutoCAD SHX Text
DOUG HANSON
AutoCAD SHX Text
JANUARY 26, 2006
AutoCAD SHX Text 43-151D
AutoCAD SHX Text
AutoCAD SHX Text
CIVIL ENGINEERING MANAGER
AutoCAD SHX Text CASE D - NESC HEAVY DEADEND 45g LINE ANGLE WIND ON STRUCTURE = 10 PSF DEAD LOAD OF STRUCTURE x 1.5
AutoCAD SHX Text CASE E - RIME ICE DEADEND 45g LINE ANGLE WIND ON STRUCTURE = 5 PSF DEAD LOAD OF STRUCTURE x 1.1
AutoCAD SHX Text CASE F - NESC HEAVY DEADEND 0g LINE ANGLE WIND ON STRUCTURE = 10 PSF DEAD LOAD OF STRUCTURE x 1.5
AutoCAD SHX Text CASE G - RIME ICE DEADEND 0g LINE ANGLE WIND ON STRUCTURE = 5 PSF DEAD LOAD OF STRUCTURE x 1.1
AutoCAD SHX Text 7.1
AutoCAD SHX Text 7.1
AutoCAD SHX Text 7.1
AutoCAD SHX Text 21.1
AutoCAD SHX Text 7.0
AutoCAD SHX Text 18.7
AutoCAD SHX Text 18.7
AutoCAD SHX Text 18.7
AutoCAD SHX Text 3.0
AutoCAD SHX Text 3.0
AutoCAD SHX Text 3.0
AutoCAD SHX Text 12.9
AutoCAD SHX Text 2.5
AutoCAD SHX Text 14.2
AutoCAD SHX Text 14.2
AutoCAD SHX Text 14.2
AutoCAD SHX Text 10.6
AutoCAD SHX Text 10.6
AutoCAD SHX Text 10.6
AutoCAD SHX Text 22.5
AutoCAD SHX Text 13.9
AutoCAD SHX Text 16.9
AutoCAD SHX Text 16.9
AutoCAD SHX Text 16.9
AutoCAD SHX Text 3.9
AutoCAD SHX Text 3.9
AutoCAD SHX Text 3.9
AutoCAD SHX Text 10.6
AutoCAD SHX Text 3.5
AutoCAD SHX Text 9.4
AutoCAD SHX Text 9.4
AutoCAD SHX Text 9.4
AutoCAD SHX Text 20.0
AutoCAD SHX Text 20.0
AutoCAD SHX Text 20.0
AutoCAD SHX Text 21.9
AutoCAD SHX Text 5.6
AutoCAD SHX Text 5.6
AutoCAD SHX Text 5.6
AutoCAD SHX Text 11.3
AutoCAD SHX Text 7.0
AutoCAD SHX Text 8.4
AutoCAD SHX Text 8.4
AutoCAD SHX Text 8.4
AutoCAD SHX Text 18.2
AutoCAD SHX Text 18.2
AutoCAD SHX Text 18.2
AutoCAD SHX Text 23.5
AutoCAD SHX Text 3.9
AutoCAD SHX Text 3.9
AutoCAD SHX Text 3.9
AutoCAD SHX Text 1.5
AutoCAD SHX Text 3.5
AutoCAD SHX Text 1.1
AutoCAD SHX Text 1.1
AutoCAD SHX Text 1.1
AutoCAD SHX Text 21.7
AutoCAD SHX Text 21.7
AutoCAD SHX Text 21.7
AutoCAD SHX Text 23.7
AutoCAD SHX Text 5.6
AutoCAD SHX Text 5.6
AutoCAD SHX Text 5.6
AutoCAD SHX Text 1.6
AutoCAD SHX Text 7.0
AutoCAD SHX Text 0.9
AutoCAD SHX Text 0.9
AutoCAD SHX Text 0.9
AutoCAD SHX Text 19.7
AutoCAD SHX Text 19.7
AutoCAD SHX Text 19.7
AutoCAD SHX Text 25.4
AutoCAD SHX Text A
AutoCAD SHX Text 10-24-14
AutoCAD SHX Text
A7-BGH
AutoCAD SHX Text
UPDATED NOTES. MINOR REVISIONS.
AutoCAD SHX Text NOTES 1. LOADS ARE ULTIMATE VALUES AND INCLUDE OVERLOAD LOADS ARE ULTIMATE VALUES AND INCLUDE OVERLOAD FACTORS. 2. WIRE LOADS ARE IN KIPS AND ARE TOTAL FOR ALL WIRE LOADS ARE IN KIPS AND ARE TOTAL FOR ALL SPANS. 3. STRUCTURE AND ATTACHMENTS SHALL BE DESIGNED FOR STRUCTURE AND ATTACHMENTS SHALL BE DESIGNED FOR THE SIMULTANEOUS APPLICATION OF DEAD LOAD, WIND ON THE STRUCTURE, AND WIRE LOADS FOR EACH LOADING CASE. 4. STRUCTURE SHALL BE DESIGNED SELF SUPPORTING; GUYS STRUCTURE SHALL BE DESIGNED SELF SUPPORTING; GUYS ARE NOT PERMITTED. 5. WIND PRESSURE SHOWN ON LOADING DIAGRAMS ARE BASED WIND PRESSURE SHOWN ON LOADING DIAGRAMS ARE BASED ON A SHAPE FACTOR OF 1.0 FOR CIRCULAR SECTIONS. FOR SECTIONS OTHER THAN CIRCULAR, MULTIPLY THE PRESSURES BY THE FOLLOWING SHAPE FACTORS: ELLIPTICAL=1.2 (MAJOR AXIS) 0.9 (MINOR AXIS) 12-SIDED=1.1 8-SIDED=1.4 6-SIDED=1.4 4-SIDED=2.0 6. DESIGN LOADS ARE BASED ON 795 KCM ACSR 26/7 DESIGN LOADS ARE BASED ON 795 KCM ACSR 26/7 "DRAKE" CONDUCTOR AND TWO 1/2o, 7-STRAND, HIGH-STRENGTH STEEL OVERHEAD GROUND WIRES. 7. SUM OF ADJACENT SPANS 2400 FT SUM OF ADJACENT SPANS 2400 FT 2400 FT FT 8. LOW POINT DISTANCE 2000 FT LOW POINT DISTANCE 2000 FT 2000 FT FT 9. LINE ANGLE 0-45g LINE ANGLE 0-45g 0-45g 10. NESC HEAVY:1/2" RADIAL ICE, 4 PSF WIND AT 0gF. NESC HEAVY:1/2" RADIAL ICE, 4 PSF WIND AT 0gF. RULING SPAN 1000 FT 1000 FT FT TENSIONS: CONDUCTOR 13,130 LB CONDUCTOR 13,130 LB 13,130 LB LB OGW 7172 LB 7172 LB LB 11. HIGH WIND:100 MPH 3-SECOND GUST AT 60gF IN HIGH WIND:100 MPH 3-SECOND GUST AT 60gF IN ACCORDANCE WITH NESC C2-2012. TENSIONS: CONDUCTOR 12,302 LB CONDUCTOR 12,302 LB 12,302 LB OGW 5630 LB 5630 LB WIND ON WIRES 26 PSF 26 PSF 12. RIME ICE: 1 1/2" RADIAL RIME (40 PCF), 4 PSF RIME ICE: 1 1/2" RADIAL RIME (40 PCF), 4 PSF 1 1/2" RADIAL RIME (40 PCF), 4 PSF WIND AT 30gF. TENSIONS: CONDUCTOR 17,839 LB CONDUCTOR 17,839 LB 17,839 LB OGW 11,526 LB 11,526 LB 13. "H" INDICATES HEIGHT PORTION OF POLE STRUCTURE "H" INDICATES HEIGHT PORTION OF POLE STRUCTURE DESIGNATIONS LISTED IN SPECIFICATIONS. 14. EMBEDMENT DEPTH "E" SHALL BE AS LISTED IN EMBEDMENT DEPTH "E" SHALL BE AS LISTED IN SPECIFICATIONS. 15. MINIMUM AUGER DIAMETER "D" FOR DIRECT-EMBEDDED MINIMUM AUGER DIAMETER "D" FOR DIRECT-EMBEDDED STRUCTURES SHALL BE MAXIMUM POLE BASE DIAMETER PLUS 1 FOOT.
AutoCAD SHX Text S:\Engineering\Guides\Design Criteria\Steel Pole Design\All Drawings\Steel Pole Design Drawings (AutoCad)\43_151_d_2200b.dwg Last Saved By: Perry, Bronson on 8/21/2017 11:50 AM Last Saved By: Perry, Bronson on 8/21/2017 11:50 AMPerry, Bronson on 8/21/2017 11:50 AM on 8/21/2017 11:50 AM8/21/2017 11:50 AM
AutoCAD SHX Text
WESTERN AREA POWER ADMINISTRATION
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF ENERGY
AutoCAD SHX Text
HEADQUARTERS - LAKEWOOD, COLORADO
AutoCAD SHX Text c TRANSMISSION LINE
AutoCAD SHX Text B
AutoCAD SHX Text 03-21-16
AutoCAD SHX Text
A7-BGH
AutoCAD SHX Text
UPDATED NOTES. MINOR REVISIONS.
GROUND LINE
"D"
AutoCAD SHX Text "D"
AutoCAD SHX Text "D"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
TYPE 165D (DE)
AutoCAD SHX Text
(DIRECT-EMBEDDED)
AutoCAD SHX Text 3"
AutoCAD SHX Text 3"
AutoCAD SHX Text 3"
AutoCAD SHX Text
TYPICAL OGW AND TENSION
AutoCAD SHX Text
INSULATOR ATTACHMENT
AutoCAD SHX Text
SECTION C-C
AutoCAD SHX Text
SECTION A-A
AutoCAD SHX Text
LINE POST INSULATOR ATTACHMENT
AutoCAD SHX Text B
AutoCAD SHX Text B
AutoCAD SHX Text
SECTION B-B
AutoCAD SHX Text
LINE POST INSULATOR ATTACHMENT
AutoCAD SHX Text
TYPE 165D (BP)
AutoCAD SHX Text
(BASE-PLATED)
AutoCAD SHX Text 13.8
AutoCAD SHX Text 5.7
AutoCAD SHX Text 23.5
AutoCAD SHX Text 2.0
AutoCAD SHX Text 9.0
AutoCAD SHX Text 12.4
AutoCAD SHX Text 8.2
AutoCAD SHX Text 2.9
AutoCAD SHX Text 16.2
AutoCAD SHX Text 10.0
AutoCAD SHX Text 13.0
AutoCAD SHX Text 24.1
AutoCAD SHX Text 4.3
AutoCAD SHX Text 3.1
AutoCAD SHX Text 6.9
AutoCAD SHX Text 11.7
AutoCAD SHX Text 24.8
AutoCAD SHX Text 14.5
AutoCAD SHX Text NOTES 1. LOADS ARE ULTIMATE VALUES AND INCLUDE OVERLOAD LOADS ARE ULTIMATE VALUES AND INCLUDE OVERLOAD FACTORS. 2. WIRE LOADS ARE IN KIPS AND ARE TOTAL FOR ALL WIRE LOADS ARE IN KIPS AND ARE TOTAL FOR ALL SPANS. 3. STRUCTURE AND ATTACHMENTS SHALL BE DESIGNED FOR STRUCTURE AND ATTACHMENTS SHALL BE DESIGNED FOR THE SIMULTANEOUS APPLICATION OF DEAD LOAD, WIND ON THE STRUCTURE, AND WIRE LOADS FOR EACH LOADING CASE. STRUCTURE DESIGN SHALL ACCOUNT FOR TRANSVERSE WIRE AND WIND LOADS BEING APPLIED IN EACH DIRECTION; I.E., LEFT OR RIGHT. 4. STRUCTURE SHALL BE DESIGN SELF SUPPORTING; GUYS STRUCTURE SHALL BE DESIGN SELF SUPPORTING; GUYS ARE NOT PERMITTED. 5. WIND PRESSURE SHOWN ON LOADING DIAGRAMS ARE BASED WIND PRESSURE SHOWN ON LOADING DIAGRAMS ARE BASED ON A SHAPE FACTOR OF 1.0 FOR CIRCULAR SECTIONS. FOR SECTIONS OTHER THAN CIRCULAR, MULTIPLY THE PRESSURES BY THE FOLLOWING SHAPE FACTORS: ELLIPTICAL=1.2 (MAJOR AXIS) 0.9 (MINOR AXIS) 12-SIDED=1.1 8-SIDED=1.4 6-SIDED=1.4 4-SIDED=2.0 6. DESIGN LOADS ARE BASED ON 477 KCM ACSR 26/7 DESIGN LOADS ARE BASED ON 477 KCM ACSR 26/7 "HAWK" CONDUCTOR AND TWO 1/2"o, 7-STRAND, HIGH-STRENGTH STEEL OVERHEAD GROUND WIRES. 7. SUM OF ADJACENT SPANS 2320 FT SUM OF ADJACENT SPANS 2320 FT 2320 FT 8. LOW POINT DISTANCE 2320 FT LOW POINT DISTANCE 2320 FT 2320 FT 9. LINE ANGLE 0-45g LINE ANGLE 0-45g 0-45g 10. NESC HEAVY: 1/2" RADIAL ICE, 4 PSF AT 0gF. NESC HEAVY: 1/2" RADIAL ICE, 4 PSF AT 0gF. 1/2" RADIAL ICE, 4 PSF AT 0gF. RULING SPAN 1060 FT 1060 FT TENSIONS (HORZ.): CONDUCTOR 9500 LB CONDUCTOR 9500 LB OGW 8150 LB 11. HIGH WIND: 100 MPH 3-SECOND GUST AT 60gF IN HIGH WIND: 100 MPH 3-SECOND GUST AT 60gF IN 100 MPH 3-SECOND GUST AT 60gF IN ACCORDANCE WITH NESC C2-2012. TENSIONS (HORZ.): CONDUCTOR 8240 LB CONDUCTOR 8240 LB OGW 5995 LB WIND ON WIRES 25 PSF 12. RIME ICE: 1 1/2" RADIAL RIME (40 PCF), 4 PSF RIME ICE: 1 1/2" RADIAL RIME (40 PCF), 4 PSF 1 1/2" RADIAL RIME (40 PCF), 4 PSF AT 30gF. TENSIONS (HORZ.): CONDUCTOR 13,520 LB CONDUCTOR 13,520 LB 13,520 LB OGW 12,525 LB 12,525 LB 13. "H" INDICATES HEIGHT PORTION OF POLE STRUCTURE "H" INDICATES HEIGHT PORTION OF POLE STRUCTURE DESIGNATIONS LISTED IN SPECIFICATIONS. 14. CONTRACTOR SHALL DETERMINE EMBEDMENT DEPTH "E" CONTRACTOR SHALL DETERMINE EMBEDMENT DEPTH "E" BASED ON CRITERIA IN SPECIFICATIONS. 15. MINIMUM AUGER DIAMETER "D" FOR DIRECT-EMBEDDED MINIMUM AUGER DIAMETER "D" FOR DIRECT-EMBEDDED STRUCTURES SHALL BE MAXIMUM POLE BASE DIAMETER PLUS 1 FOOT.
AutoCAD SHX Text 8.2
AutoCAD SHX Text 5.2
AutoCAD SHX Text 6.5
AutoCAD SHX Text 12.0
AutoCAD SHX Text 25.5
AutoCAD SHX Text 13.7
AutoCAD SHX Text S:\projects\TransmissionLines\BigGeorge_NorthCody.2017\Drawings\DesignDrawings\Civil\43_165_d_2200.dwg Last Saved By: Denton, Debra on 4/19/2018 8:04 AM Last Saved By: Denton, Debra on 4/19/2018 8:04 AMDenton, Debra on 4/19/2018 8:04 AM on 4/19/2018 8:04 AM4/19/2018 8:04 AM
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "H"
AutoCAD SHX Text "D"
AutoCAD SHX Text "D"
AutoCAD SHX Text "D"
AutoCAD SHX Text
1/2" PLATE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 13.8
AutoCAD SHX Text 5.7
AutoCAD SHX Text 13.8
AutoCAD SHX Text 5.7
AutoCAD SHX Text 2.0
AutoCAD SHX Text 9.0
AutoCAD SHX Text 2.0
AutoCAD SHX Text 9.0
AutoCAD SHX Text 10.0
AutoCAD SHX Text 13.0
AutoCAD SHX Text 10.0
AutoCAD SHX Text 13.0
AutoCAD SHX Text 3.1
AutoCAD SHX Text 6.9
AutoCAD SHX Text 14.5
AutoCAD SHX Text 3.1
AutoCAD SHX Text 6.9
AutoCAD SHX Text 14.5
AutoCAD SHX Text 5.2
AutoCAD SHX Text 6.5
AutoCAD SHX Text 13.7
AutoCAD SHX Text 5.2
AutoCAD SHX Text 6.5
AutoCAD SHX Text 13.7
AutoCAD SHX Text 4.3
AutoCAD SHX Text 3.1
AutoCAD SHX Text 0.9
AutoCAD SHX Text 1.5
AutoCAD SHX Text 26.9
AutoCAD SHX Text 15.7
AutoCAD SHX Text 8.2
AutoCAD SHX Text 5.2
AutoCAD SHX Text 0.8
AutoCAD SHX Text 1.5
AutoCAD SHX Text 27.6
AutoCAD SHX Text 14.9
AutoCAD SHX Text 3.1
AutoCAD SHX Text 3.1
AutoCAD SHX Text 5.2
AutoCAD SHX Text 5.2
AutoCAD SHX Text 0.9
AutoCAD SHX Text 15.7
AutoCAD SHX Text 0.9
AutoCAD SHX Text 15.7
AutoCAD SHX Text 0.8
AutoCAD SHX Text 14.9
AutoCAD SHX Text 0.8
AutoCAD SHX Text 14.9
AutoCAD SHX Text
TYPE 165D (DE)
AutoCAD SHX Text
BASE DETAIL
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text "E"
AutoCAD SHX Text 1'-6"e
AutoCAD SHX Text 1'-6"e
AutoCAD SHX Text 1'-6"e
AutoCAD SHX Text 1'-6"e
AutoCAD SHX Text 1'-6"e
AutoCAD SHX Text 1'-6"e
AutoCAD SHX Text
CASE F
AutoCAD SHX Text
NESC HEAVY DEADEND
AutoCAD SHX Text 0g LINE ANGLE
AutoCAD SHX Text
WIND ON STRUCTURE = 10 PSF
AutoCAD SHX Text DEAD LOAD OF STRUCTURE x 1.5
AutoCAD SHX Text
CASE G
AutoCAD SHX Text
RIME ICE DEADEND
AutoCAD SHX Text 0g LINE ANGLE
AutoCAD SHX Text
WIND ON STRUCTURE = 5 PSF
AutoCAD SHX Text DEAD LOAD OF STRUCTURE x 1.1
AutoCAD SHX Text
CASE A
AutoCAD SHX Text
NESC HEAVY INTACT
AutoCAD SHX Text
WIND ON STRUCTURE = 10 PSF
AutoCAD SHX Text DEAD LOAD OF STRUCTURE x 1.5
AutoCAD SHX Text
CASE B
AutoCAD SHX Text
HIGH WIND INTACT
AutoCAD SHX Text
WIND ON STRUCTURE = 32 PSF
AutoCAD SHX Text DEAD LOAD OF STRUCTURE x 1.1
AutoCAD SHX Text
CASE C
AutoCAD SHX Text
RIME ICE INTACT
AutoCAD SHX Text
WIND ON STRUCTURE = 5 PSF
AutoCAD SHX Text DEAD LOAD OF STRUCTURE x 1.1
AutoCAD SHX Text
CASE D
AutoCAD SHX Text
NESC HEAVY DEADEND
AutoCAD SHX Text 45g LINE ANGLE
AutoCAD SHX Text
WIND ON STRUCTURE = 10 PSF
AutoCAD SHX Text DEAD LOAD OF STRUCTURE x 1.5
AutoCAD SHX Text
CASE E
AutoCAD SHX Text
RIME ICE DEADEND
AutoCAD SHX Text 45g LINE ANGLE
AutoCAD SHX Text
WIND ON STRUCTURE = 5 PSF
AutoCAD SHX Text DEAD LOAD OF STRUCTURE x 1.1
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text
WESTERN AREA POWER ADMINISTRATION
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF ENERGY
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
TRANSMISSION LINE STRUCTURE
AutoCAD SHX Text
165D STEEL POLE STRUCTURES
AutoCAD SHX Text
OUTLINE AND DESIGN LOADS
AutoCAD SHX Text
B.E. PERRY
AutoCAD SHX Text
GINA CRAWFORD
AutoCAD SHX Text 43-165D
AutoCAD SHX Text
AutoCAD SHX Text
CIVIL ENGINEERING MANAGER
AutoCAD SHX Text
HEADQUARTERS - LAKEWOOD, COLORADO
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text April 19, 2018
AutoCAD SHX Text
TYPE 165D (BP)
BASE DETAIL
HVAC LEGEND
M
CONTROL DAMPER, MOTOR
OPERATED
MANUAL BALANCE DAMPER
BD
BACKDRAFT DAMPER
AD
AD
ACCESS DOOR (AD)
ACCESS PANEL (AP)
S
AD S
DAMPERS:
FIRE (F) -
SMOKE (S) -
FIRE SMOKE (F/S) -
AD
SECURITY BARS
FLEXIBLE DUCT
CONNECTION
RECTANGLUAR ELBOW WITH
TURNING VANES
RECTANGULAR TEE WITH
TURNING VANES
RECTANGULAR RADIUS
ELBOW
R RISE IN RESPECT TO
AIR-FLOW
D DROP IN RESPECT TO
AIR-FLOW
SQUARE OR RECTANGULAR
TO ROUND TRANSITION
SUPPLY AIR OR OUTSIDE AIR
RECTANGULAR DUCT
SECTION
RETURN AIR RECTANGULAR
DUCT SECTION
EXHAUST AIR RECTANGULAR
DUCT SECTION
ROUND FLEXIBLE DUCT
(5'-0" MAX LENGTH)
SQUARE OR RECTANGULAR
SUPPLY DIFFUSER
RETURN AIR DIFFUSER
EXHAUST AIR DIFFUSER
T THERMOSTAT
CO2 CARBON DIOXIDE SENSOR
H HUMIDISTAT
LINEAR SLOT DIFFUSER
VAV- VARIABLE AIR VOLUME
TERMINAL BOX
(3'-0") FINNED TUBE RADIATION.
LENGTH OF ELEMENT SHOWN
IN PARENTHESIS
ESS EMERGENCY SHUT-OFF
SWITCH
M MOTOR
FCP FAN CONTROL PANEL
AIRFLOW ARROW
BA BREATHING AIR DROP
CA COMPRESSED AIR DROP
SUPPLY AIR OR OUTSIDE AIR
ROUND DUCT SECTION
RETURN AIR ROUND DUCT
SECTION
EXHAUST AIR ROUND DUCT
SECTION
DP DIFFERENTIAL PRESSURE
SENSOR
S STATIC PRESSURE SENSOR
OCC OCCUPANCY SENSOR
ROUND & RECTANGULAR
DUCT TAKEOFF
CO CARBON MONOXIDE SENSOR
HS HYDROGEN SENSOR
PIPE LINE ACCESSORIES
3-WAY VALVE
2-WAY VALVE
ANGLE VALVE
AV AUTOMATIC AIR VENT
ASSEMBLY
BFP BACKFLOW PREVENTION
ASSEMBLY
BALANCING VALVE /
CIRCUIT SETTER
BALL VALVE
BLIND FLANGE
BUTTERFLY VALVE
CHECK VALVE
FLEX CONNECTION
FLOW ARROW
FM FLOW METER
GATE VALVE
GLOBE VALVE
HOSE GATE DRAIN VALVE
IF
INSULATING FLANGE
MV
MANUAL AIR VENT ASSEMBLY
- SEE SPECIFICATIONS FOR
APPROPRIATE VALVE TYPE
M METER
M MOTORIZED CONTROL VALVE
OS&Y OUTSIDE SCREW & YOKE
VALVE
PIPE WITH HEAT TRACE
PLUG VALVE
PRESSURE GUAGE
SELF CONTAINED PRESSURE
REDUCING (REGULATING)
VALVE
PUMP
REDUCER (CONCENTRIC)
RELIEF, SAFETY OR THERMAL
RELIEF VALVE
REMOVABLE CAP
REMOVABLE PLUG
S STRAINER
SUCTION DIFFUSER
TEST CONNECTION
THERMOMETER
UNION
Y-TYPE STRAINER
SRC SPRING RETURN CLOSED
BALL VALVE
PIPE SYMBOLS
PIPE ELBOW
PIPE DOWN
PIPE UP
PIPE CONTINUATION
PIPELINE ABBREVIATIONS
MECHANICAL ABBREVIATIONS GENERAL NOTES:
DETAIL / ENLARGED
CALLOUT SYMBOL
A M-001
INDICATES
LIMITS OF
DETAIL/SECTION
DETAIL/SECTION
DESIGNATOR
SHEET WHERE
DETAIL/SECTION
IS SHOWN
DETAIL/SECTION TITLE
TITLEA1
LOCATION WHERE
DETAIL / SECTION IS
SHOWN ON SHEET
SECTION CUT SYMBOL
A
M001
INDICATES
PERSPECTIVE AND
LIMITS OF SECTION
SECTION DESIGNATOR
DRAWING WHERE
SECTION IS SHOWN
CONSTRUCTION
INTERFACE
DEMOLITION
EXISTING
NEW
EXISTING
EXISTING
NEW
DEMOLITION
AIR DISTRIBUTION
DEVICE IDENTIFICATION
AIR
FLOW
NECK SIZE
QUANTITY
SYSTEM TYPE SPEC. TYPE
SA-A
(2)175-8Ø
1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS
APPLICABLE TO PROJECT. SEE PLANS FOR SPECIFIC SYMBOLS AND
ABBREVIATIONS.
2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND PERFORM
ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL
SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND AS REQUIRED
BY CODE.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE
WITH MANUFACTURERS RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH STRUCTURAL,
CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT
DRAWINGS.
5. UNLESS OTHERWISE INDICATED MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO
UNDERSIDE OF PIPES, CONDUITS, ETC., THROUGHOUT ACCESS ROUTES AND IN
MECHANICAL ROOMS.
6. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT
ACCESS PANELS, CONTROLS, AND VALVING.
7. VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT.
8. ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, EQUIPMENT,
PIPE, OR PIPE INSULATION UNLESS NOTED OTHERWISE.
9. DUCT DIMENSIONS INDICATED REFER TO SHEET METAL DIMENSIONS. SHEET
METAL SIZE SHALL BE AIR OPENING DIMENSION PLUS THE THICKNESS OF
ACOUSTICAL LINER WHERE LINER IS INSTALLED. WHERE LINER IS NOT
INSTALLED, AIR OPENING SIZE AND SHEET METAL SIZE SHALL BE THE SAME.
10. COORDINATE ALL WALL AND ROOF PENETRATIONS WITH STRUCTURAL AND
ARCHITECTURAL PLANS.
11. INSTALL TEMPERATURE CONTROLS AT 48" ABOVE FINISHED FLOOR AND
COORDINATE WITH OTHER DEVICES LOCATED ON WALLS. COORDINATE WITH
ARCHITECTURAL WALL FINISHES.
12. PROVIDE STRUCTURAL EQUIPMENT PADS IN ACCORDANCE WITH STRUCTURAL
DRAWINGS AND SPECIFICATIONS.
13. CONTRACTOR SHALL AIR BALANCE ALL GRILLES AND EQUIPMENT TO CFM'S
SHOWN ON PLANS.
14. MOUNT ALL OVERHEAD MECHANICAL EQUIPMENT AND FIXTURES WEIGHING 31
POUNDS OR MORE TO SUPPORTS THAT SHALL RESIST FORCES OF 0.5 TIMES
THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES THE
EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION.
15. BASIS OF DESIGN MANUFACTURER AND MODEL ARE INCLUDED FOR
COORDINATION PURPOSES. PROVIDE BASIS OF DESIGN EQUIPMENT OR
APPROVED EQUAL.
BLWDN BLOWDOWN
CD CONDENSATE DRAIN
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CR CONDENSATE RETURN
CT CHEMICAL TREATMENT
CTB COOLING TOWER BLOWDOWN
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
DI DEIONIZED WATER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
HPS HIGH PRESSURE STEAM
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
MPS MEDIUM PRESSURE STEAM
MW MAKEUP WATER (AFTER BACKFLOW
PREVENTER)
N NITROGEN
NG NATURAL GAS
O OXYGEN
PCR PUMPED CONDENSATE RETURN
V VACUUM
LR LONG RADIUS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKEUP AIR UNIT
MFR MANUFACTURER
MJ MECHANICAL JOINT
MW MAKE-UP WATER (AFTER BACKFLOW PREVENTER)
NC NORMALLY CLOSED (FAIL POSITION)
NG NATURAL GAS
NO NORMALLY OPEN (FAIL POSITION)
OA OUTSIDE AIR
OB OPPOSED BLADE
OD OVERFLOW DRAIN
PB PARALLEL BLADE
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
RA RETURN AIR
RED REDUCER-REDUCING
RL REFRIGERANT LIQUID
RMJ RESTRAINED MECHANICAL JOINT
RS REFRIGERANT SUCTION
SA SUPPLY AIR
SCH SCHEDULE
SCR SPRING RETURN CLOSED
SHR SHORT RADIUS
SP STATIC PRESSURE SENSOR
SR SUPPLY REGISTER
SW SOCKET WELD
TA TRANSFER AIR
TAB TESTING, ADJUSTING AND BALANCING
TOA TREATED OUTSIDE AIR
TOC TOP OF CONCRETE
TOD TOP OF DUCT
TOS TOP OF STEEL
UH UNIT HEATER
V VENT
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB WET BULB
WE WELD END
WN WELD NECK
12"Ø ROUND DUCT DIMENSION
24x12 RECTANGULAR DUCT DIMENSION (INCHES)
ACU AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ARF ABOVE RAISED FLOOR
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
CD CONTROL DAMPER
CFM CUBIC FEET PER MINUTE
CH CONVECTION HEATER
CL CENTER LINE OF PIPE ELEVATION
CONC CONCENTRIC
COND COOLING COIL CONDENSATE DRAIN
CRAC COMPUTER ROOM AIR CONDITIONER
CTR CONTROLLER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
DB DRY BULB
DH DEHUMIDIFIER
DN DOWN
DRG DIFFUSER, REGISTER, GRILLE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
EL ELEVATION
ELL ELBOW
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
FCU FAN COIL UNIT
FF FLAT FACED
FO FLAT OVAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
I.E. INVERT ELEVATION
IH INFRARED HEATER
IN.
W.C
INCHES WATER COLUMN
LAT LEAVING AIR TEMPERATURE
OVERHEAD CABLE TRAY
C O
M M
R
AC
KS
VERTICAL SWITCHBOARDS
VERTICAL SWITCHBOARDS
C O
M M
B
AT
TE
R
Y
5V
B
AT
TE
R
Y
DOORSTOP POSTCONCRETE SLAB
CONCRETE SLAB
CABLE ENTRY BOX (REFER TO
STRUCTURAL)
MECHANICAL EQUIPMENT
CONCRETE SLAB
450-12x12
SA-B
12x12 SA
ERU-1
FCU-1
CH-1 CU-1
(6)200-10x10
SA-B
WEATHERHOOD
CU-2CU-3
FCU-2FCU-3
16x14 SA
9' - 4" BOD EL
HS 1
1/4" RL
1/4" RS
T
5 5
3/4" COND12
3/4" COND 3
3/4" COND 3
450-12x12
RA-A
12x12 RA
12x12 EA
OCC
OCC
450-12x12
TA-A
A
B x1
O A
LVR-1
18x18
C
A
3/8" RL
CD-1
CD-2
ZT-2
ZT-1
CTR-1
OT-1
HT-117
T
TH
T
T TST-1
ST-2
CONTROL ROOM
BATTERY ROOM
NOTES:
KEYED NOTES:
1.
2.
3.
4.
CONTRACTOR SHALL LOCATE EQUIPMENT SUCH THAT ALL REQUIRED MAINTENANCE
CLEARANCE/ACCESS ARE COORDINATED WITH WORK BY OTHER TRADES.
ALL HORIZONTAL DUCTWORK SHALL BE SUPPORTED PER SMACNA USING
UNISTRUT AND MIN 3/8" ALL-THREAD ROD, SPACED NO MORE THAN 6'-0"
APART. DUCT SHALL BE SECURED TO UNISTRUT BY 24 GAUGE 1-1/2" STRAP.
TESTING, ADJUSTING, AND BALANCING (TAB) SHALL BE PERFORMED FOLLOWING
COMPLETION AND APPROVAL OF EACH HVAC SYSTEM.
REFRIGERANT PIPE SIZES AND ROUTING ARE DIAGRAMMATIC AND MUST BE
VERIFIED WITH EQUIPMENT MANUFACTURER PRIOR TO INSTALLATION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
FURNISH AND INSTALL SBS-H2 HYDROGEN SENSOR OR APPROVED EQUAL. AUX
RELAY ACCESSORY PROVIDED BY CONTRACTOR SHALL OPERATE ON 24VDC AND
CONTROL 120VAC. INSTALL HYDROGEN SENSOR AT MOUNTING ELEVATION PER
MANUFACTURER'S RECOMMENDATIONS, OR WHERE NOT PROVIDED, MOUNT 0'-6"
BELOW CEILING. INTERLOCK WITH ERU-1. REFER TO CONTROL SCHEMATIC ON
DWG 3305 FOR DETAILS.
PROVIDE WITH MANUFACTURER'S STANDARD 12"x12" 45° WEATHERHOOD, GREENHECK MODEL WTHD-12 OR APPROVED EQUAL. REFER TO DETAIL 4 ON
DWG 3302. MOUNT AT UNDERSIDE OF SOFFIT.
PROVIDE WEATHER RESISTANT LINESET COVER AND FITTINGS WITH UV INHIBITORS
FOR PIPING THROUGH SOFFIT TO INDOOR UNIT. APPLY CAULKING TO SEAL
WHERE THE LINESET ENTERS AND EXITS THE EXTERIOR WALL.
PROVIDE ZONE TRANSMITTER ACCORDING TO SCHEDULE ON DWG 3304. WALL
MOUNT 60" AFF.
INSTALL CONDENSING UNIT WITH MANUFACTURER'S STANDARD 12" EQUIPMENT
STAND ON CONCRETE PAD WITH HILTI KWIK BOLT3 EXPANSION ANCHORS 3/8"Ø
WITH 3 1/2" EMBEDMENT IN CONCRETE.
INSTALL ERU AT 9'-5" AFF TO BASE OF CABINET.
PROVIDE WITH MOTORIZED DAMPER AT OUTLET OF LOUVER PER DETAIL 1 ON DWG
3302.
INSTALL CONVECTION HEATER AT 0'-0" AFF BELOW BATTERY ROOM UNIT PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS. MOUNT TAMPERPROOF
THERMOSTAT IN THE RIGHT HAND TERMINAL BOX AND INITIALLY SET TO ENERGIZE
AT 68°F (ADJ.).
MOUNT CONTROL ROOM UNIT ON FAN COIL SUPPORT AS DETAILED ON DWG 3303,
DETAILS 4 AND 5, AND ON MANUFACTURER'S STANDARD PLENUM STAND. INSTALL
PIPING PER DETAIL 2 ON DWG 3302.
WALL MOUNT BATTERY ROOM UNIT 7'-6" AFF. INSTALL PIPING PER DETAIL 2 ON
DWG 3302.
INSTALL TRANSFER GRILLE WITH 1 HOUR FIRE DAMPER AT 1'-0" AFF. REFER TO
DETAIL 3 ON DWG 3303.
CONDENSATE PIPE SHALL EXTEND PAST CONCRETE SLAB TO DRAIN ON GRAVEL
SURFACING. TURN DOWN TO SPLASH BLOCK.
FURNISH AND INSTALL OCCUPANCY SENSOR, WATTSTOPPER MODEL DT355 OR
APPROVED EQUAL. MOUNT ON CEILING.
INSTALL SUPPLY GRILLE WITH 1 HOUR FIRE DAMPER AT 9'-7" AFF. REFER TO
DETAIL 3 ON DWG 3303. MANUAL BALANCING DAMPER IS NOT REQUIRED AT THIS
GRILLE.
INSTALL OUTDOOR AIR TEMPERATURE SENSOR ACCORDING TO
SENSOR/TRANSMITTER SCHEDULE ON DWG 3304. MOUNT AT 8'-0" ABOVE
GRADE, BELOW SOFFIT.
INSTALL CONTROLLER ACCORDING TO SENSOR/TRANSMITTER SCHEDULE ON DWG
3304. MOUNT 60" AFF TO TOP OF CONTROLLER.
PROVIDE HUMIDITY TRANSMITTER ACCORDING TO SCHEDULE ON DWG 3304. WALL
MOUNT 60" AFF.
PROVIDE SUPPLY AIR TRANSMITTER ACCORDING TO SCHEDULE ON DWG 3304.
MOUNT IN SUPPLY DUCT.
PENETRATIONS THROUGH BATTERY ROOM WALL SHALL BE SEALED WITH FIRESTOP
SEALANT PER ARCH. CONTRACTOR TO PROVIDE FIRE-STOPPING DETAILS FOR
PENETRATIONS THROUGH FIRE WALL. INCLUDE UL SYSTEM NUMBERS FOR EACH
DETAIL.
SCALE IN FEET
0 2' 4' 8'
NORTH
MECHANICAL FLOOR PLAN
ACTUATED DAMPER
J-MOLDING
AND CAULKING
ALL AROUND
5/8" GYPSUM BOARD
WOOD FRAMED WALL
WOOD BLOCKING ALL
AROUND OPENING
MASONRY VENEER
MASONRY TIE
20 GA GALVANIZED
STEEL FLASHING
WRAP MOISTURE BARRIER
AROUND OPENING
20 GA GALVANIZED STEEL
CLOSURE, REFER TO
ARCH DOOR DETAILS
LOUVER WITH
INTEGRAL FLANGE
MASONRY VENEER
BEYOND
SOFFIT
CHARGING VALVE
LIQUID PIPING
SUCTION PIPING
FILTER-DRIER
SIGHT GLASS
PROVIDE OIL TRAP
INSTALL SENSING BULB
45° ABOVE BOTTOM OF
PIPING, AS CLOSE TO
COIL AS POSSIBLE
CONDENSATE DRAIN
NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR COORDINATING
REFRIGERANT LIQUID AND SUCTION PIPING, SIZES, ROUTING,
AND ALL ACCESSORIES WITH EQUIPMENT MANUFACTURER.
MAINTAIN UNIFORM SLOPE TO PREVENT OIL FROM POOLING IN
LOW POINTS IN THE REFRIGERANT PIPING SYSTEM.
EVAPORATOR COIL
ISOLATION VALVE (TYP.)
EXPANSION VALVE
EQUALIZATION LINE
AIR COOLED
CONDENSING UNIT
STRAP HANGERS
60" MAX.
HANGER
STRAPS
UNLESS FOOT OF STRAP
IS PLACED UNDER A
BOTTOM REINFORCEMENT
SCREWS
SCREWS MAY
BE OMITTED
IF HANGER LOOPS 1" MIN.
1.
2.
REFER TO STRUCTURAL
DRAWING 3206 FOR UNISTRUT
SUPPORT DETAIL.
REINFORCEMENT MAY BE USED
FOR ATTACHMENT IF IT
QUALIFIES FOR BOTH DUTIES
DO NOT EXCEEED ALLOWABLE
LOAD LIMITS
NOTES:
TRAPEZE HANGERS
STRAP OR
ANGLE
ROD
SIZE BOLT (S)
FOR LOAD
SOFFIT
WEATHER HOOD
MASONRY
VENEER BEYOND
20 GA GALVANIZED
STEEL FLASHING
MASONRY TIE
MASONRY VENEER
20 GA GALVANIZED STEEL
CLOSURE, REFER TO
ARCH DOOR DETAILS
WOOD FRAMED WALL
5/8" GYPSUM BOARD
J-MOLDING AND
CAULKING ALL
AROUND
DUCT
WRAP MOISTURE BARRIER
AROUND OPENING
WOOD BLOCKING ALL
AROUND OPENING
BIRDSCREEN
NOT TO SCALE
LOUVER DETAIL 1
NOT TO SCALE
DX SPLIT SYSTEM PIPING 2
NOT TO SCALE
LOWER DUCT HANGAR
ATTACHMENTS 3
NOT TO SCALE
WEATHERHOOD DETAIL 4
1/4"
PIPE SLEEVE
BACKUP MATERIAL
SEALANT
INSULATION
CENTER OF PIPE
3/8"
PIPE
ESCUTCHEON
INTERIOR SIDE OF
EXTERIOR WALL
STEEL SLEEVE : 16 GAUGE 24" MAX.
14 GAUGE OVER 24"
SECURE DAMPER TO SLEEVE ON 8"
CENTERS WITH:
1. 1/4" BOLTS AND NUTS IN HOLES
PROVIDED.
2. NO. 10 STEEL SCREWS.
NOTES:
TRANSFER/SUPPLY GRILLE (TYP.)
FUSIBLE LINK
FIRE DAMPER
BATTERY ROOM CONTROL ROOM
STEEL SLEEVE : 16 GAUGE 24" MAX.
14 GAUGE OVER 24"
TRANSFER/SUPPLY
GRILLE (TYP.)
FUSIBLE LINK
FIRE DAMPER
BATTERY ROOM CONTROL ROOM
SUPPLY AIR
DUCT
HANGER ROD
LOCKING NUT
SUPPORT NUT
INSULATION
PIPE
HEAVY DUTY
CLEVIS HANGER
INSULATION SHIELD MIN. 6" LONG
UNISTRUT P1498 ANGLE
FITTINGS, TYP. 2 EACH
LEG
FILTER ACCESS PANELUNISTRUT P1001
CHANNEL, TYP. 4
UNISTRUT P2073
POST BASE, TYP. 4
NOTE:
1. SECURE FAN COIL UNITS TO SUPPORTS WITH AT LEAST FOUR
ANGLE FITTINGS. CONNECT ANGLE FITTINGS TO CHANNEL WITH
1/4"Ø HEX SLOTTED SCREWS AND P1006 NUTS WITH SPRINGS AND
TO UNIT WITH 1/4"Ø SLOTTED WASHER SHEET METAL SCREWS.
UNISTRUT P1001 C3
CHANNEL
UNISTRUT P1498 ANGLE
FITTING, TYP.
FILTER ACCESS PANEL
GASKET TAPE SEE SECTION ON LEFT
CONNECT ANGLE
FITTINGS TO OPEN SIDE
OF CHANNEL, TYP.
UNISTRUT P1036 PLATE
FITTING, TYP. EACH
CORNER
APPLY GASKET TAPE TO
SMOOTH SIDE OF
CHANNEL
UNISTRUT P1001 C3
CHANNEL, TYP. 4 SIDES
NOT TO SCALE
PIPE PENETRATIONS THROUGH
EXTERIOR WALLS 1
NOT TO SCALE
FIRE DAMPER IN WALL WITH
GRILLE 3
NOT TO SCALE
PIPE HANGER - CLEVIS TYPE 2
NOT TO SCALE
FAN COIL SUPPORT 4
NOT TO SCALE
CHANNEL SECTION 5
FAN COIL UNIT SCHEDULE
TAG NO. SERVICE
BASIS OF DESIGN
ALTITUDE
(FT.)
TOTAL
AIRFLOW
(CFM)
EXTERNAL
STATIC
PRESSURE
FAN HP
COOLING
ELECTRIC
HEAT
(KW)
ELECTRICAL
FILTER
SIZE
(INxIN)
FILTER
THICKNES
S (IN)
WEIGHT
(LBS) REMARKS
MAN. MODEL NO.
SENSIBLE
CAPACITY
(MBTUH)
EAT
DB
(°F)
LAT
DB
(°F)
VOLTS PHASE
FCU-1
BATTERY
ROOM MITSUBISHI PKA 1450 320 N/A 30 W 18 78.5 55 0 230 1 N/A N/A 29 1,3,5,6,7
FCU-2
CONTROL
ROOM TRANE GAF2 1450 1200 0.3 1/2 36 78.5 55 10 230 1 16x20 1 98 1,2,3,4,7
FCU-3
CONTROL
ROOM TRANE GAF2 1450 1200 0.3 1/2 36 78.5 55 10 230 1 16x20 1 98 1,2,3,4,7
NOTES:
1. PROVIDE VERTICAL FLOOR MOUNT EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE ENERGY STAR NAME AND MARK.
2. PROVIDE WITH MANUFACTURER'S STANDARD PLENUM STAND. MOUNT ON PLENUM STAND PER MANUFACTURER'S RECOMMENDATIONS.
3. POWER PROVIDED BY OUTDOOR UNIT, CONNECT PER MANUFACTURER'S RECOMMENDATIONS.
4. PROVIDE WITH SEPARATE CONTROLLER ALLOWING LEAD/LAG CONTROL, ZONE TEMPERATURE MONITORING, AND ALARMING TO SCADA SYSTEM.
5. PROVIDE WITH MANUFACTURER'S STANDARD REMOTE PROGRAMMABLE THERMOSTAT.
6. PROVIDE WITH MANUFACTURER'S STANDARD WALL MOUNT KIT. MOUNT UNIT ON WALL PER MANUFACTURER'S RECOMMENDATIONS.
7. PROVIDE BASIS OF DESIGN FAN COIL UNIT OR APPROVED EQUAL.
DIFFUSER, REGISTER, & GRILLE SCHEDULE (DRG)
TAG DESCRIPTION MOUNTING
THROW
PATTERN
PROVIDE
DAMPER?
BASIS OF DESIGN:
REMARKS
MFR.
MODEL
NO.
A
RECTANGULAR RETURN
OR TRANSFER AIR GRILLE SURFACE - NO TITUS 350-FL 1,2,5
B
RECTANGULAR SUPPLY
AIR GRILLE SURFACE - YES TITUS 300-FL 1,2,3,4,5
NOTES:
1. DIFFUSER SIZES ARE NOTED IN DRAWINGS.
2. COLOR SHALL MATCH ACOUSTICAL CEILING TILES OR WALL. COORDINATE WITH ARCH
PLANS.
3. DIFFUSERS SHALL BE INITIALLY ADJUSTED FOR DISCHARGE OF AIR DOWNWARD AT
APPROXIMATELY 30° BELOW HORIZONTAL AND IN A HORIZONTALLY SPREAD PATTERN.
4. SUPPLY AIR GRILLE SERVING ERU-1 SHOULD NOT BE PROVIDED WITH DAMPER.
5. PROVIDE BASIS OF DESIGN DIFFUSERS AND GRILLES OR APPROVED EQUAL.
ENERGY RECOVERY UNIT SCHEDULE 1/2
TAG NO. SERVICE
ALTITUDE
(FT)
OUTSIDE
AIRFLOW (CFM)
OUTSIDE AIR
SUMMER DB
(°F)
OUTSIDE AIR
SUMMER WB
(°F)
OUTSIDE AIR
WINTER DB
(°F)
SUPPLY FAN EXHAUST FAN
EXTERNAL
STATIC
PRESSURE
(IN. W.C.)
TOTAL
STATIC
PRESSURE
(IN. W.C.)
FAN RPM TYPE
MOTOR
HP
EXTERNAL
STATIC
PRESSURE
(IN.W.C)
TOTAL
STATIC
PRESSURE
(IN.W.C.)
FAN RPM TYPE
MOTOR
HP
ERU-1
BATTERY AND
CONTROL ROOMS 1450 450 86 69.6 -20.7 0.5 0.563 1392
FORWARD
CURVE 1/4 0.5 0.55 1550
FORWARD
CURVE 1/4
ENERGY RECOVERY UNIT SCHEDULE 2/2
TAG NO.
COOLING HEATING
APPROX. UNIT
WEIGHT (LBS)
UNIT ELECTRICAL BASIS OF DESIGN
REMARKS
EAT DB
(°F)
EAT WB
(°F)
LAT
DB
(°F)
LAT WB
(°F)
TOTAL CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EAT
(°F)
LAT
(°F)
TOTAL CAPACITY
(MBH) VOLTS PHASE MOP MCA MAN. MODEL
ERU-1 86 69.6 78.5 65.6 6.683 6.683 -20.7 40.8 30.138 215 115 1 15 6.4 GREENHECK MINICORE-5-VG-FM 1-7
NOTES:
1. PROVIDE EQUIPMENT COMPLYING WITH ENERGY STAR PROGRAM REQUIREMENTS. EQUIPMENT SHALL BE ENERGY STAR CERTIFIED AND BEAR THE ENERGY STAR NAME AND MARK.
2 PROVIDE WITH MANUFACTURER'S STANDARD 2" MERV 8 FILTERS FOR OUTDOOR AND EXHAUST AIR OPENINGS.
3. PROVIDE ENERGY RECOVERY UNIT IN CONFIGURATION WITH END CONNECTIONS.
4. THE ENERGY RECOVERY UNIT SHALL BE PROVIDED FROM THE FACTORY WITH AN INTEGRAL CONTROL CENTER INCLUDING A SINGLE NON-FUSED DISCONNECT, 24 VAC TRANSFORMER, TERMINAL STRIP, AND FAN STARTERS (CONTACTOR AND OVERLOAD).
5. PROVIDE WITH INTERNAL BACKDRAFT DAMPERS.
6. STANDARD SINGLE POINT POWER TO BE PROVIDED BY MANUFACTURER.
7. PROVIDE BASIS OF DESIGN ENERGY RECOVERY UNIT OR APPROVED EQUAL.
LOUVER SCHEDULE
TAG SERVICE
SIZE
(INXIN)
AIRFLOW
(CFM)
PRESSURE
DROP
(IN.W.C)
BASIS OF DESIGN
MANF/MODEL REMARKS
LVR-1 OA INTAKE 18x18 450 0.057 RUSKIN ELF375X 1,2,3
CONDENSING UNIT SCHEDULE
TAG NO. SERVICE
COMPRESSOR
TY…