2017_Annual_Firefighting_Equipment.pdf
PDF 97 KB Posted
- Attached to
- TS FREEDOM STAR FY18 REPAIR PACKAGE
- Solicitation number
- 6933A218Q000020
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Diesel_Oil_Pump_Motor.pdf | ||
| Liferaft_Certificates_2017.pdf | ||
| Jacket_Water_Heaters.docx | DOCX document | |
| Tees_Gill_Parts_List.pdf | ||
| 6933A218Q000020_combined_synp_sol.pdf | ||
| FY_18_TSFS_WD_Pier_Side_Repairs.pdf | ||
| Data-Sheet-CSM-DS-CSM-E.pdf | ||
| SCBAs_Parts_List.pdf | ||
| Safety_Radio_Parts_List.pdf | ||
| 1427-555,_Rev_-,_TV_FREEDOM_STAR,_FIRE_AND_SAFETY_PLAN.pdf | ||
| Attmt_II_Vendor_Price_Sheet.xls | XLS spreadsheet | |
| Diesel_Oil_Pump.pdf | ||
| Attmt_I_SOW_TSFS_2018_Fall_Items.docx | DOCX document | |
| Mooring_Line_Parts_List.pdf | ||
| Freedom_Star_Imm_Suit_Inv_2018.docx | DOCX document | |
| Tach_Installation_Manual.pdf | ||
| 10-2017_Radio_Survey.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Flag: IMO #
USA 7925314 HFPM- 2017290-1
Michael Harty
CO
High Pressure Installation
CO
Low Pressure Installation
Hydrostatic Pressure Test
Foam Compound Tests
X
X
X Breathing Apparatus Cylinders
X
X
X
Gas Detection
Medical Oxygen Equipment
Compressed Gas Cylinders
P as per attached report as per attached report as per attached report as per attached report as per attached report
Galley systems
Summary harrisfireco@aol.com
HARRIS FIRE PROTECTION, CO., INC.
50 Kane St
BALTIMORE, MD 21224
(410) 285-7272
(410) 282-9377 (Fax) as per attached report
Clean Agent System
Foam Station
Fire Station as per attached report L / B
Gas per attached report
I as per attached report as per attached report as per attached report as per attached report as per attached report
H as per attached report as per attached report
C as per attached report as per attached report
WE HEREBY CERTIFY THAT THE EQUIPMENT SPECIFIED BELOW HAS BEEN INSPECTED AND SERVICED.
as per attached report as per attached report
Breathing Air Compressor
Detector/Alarm System
Dry Powder Installation
Portable Fire Extinguishers
Escape Sets
Breathing Apparatus
Type and Name of Vessel/Unit: Certificate No.
Piney Point, MD
Technician's Signature:Ship's Representative:
TV FREEDOM STAR
Place of Service:
Date
2017/10/17
HFPM-CERT REV 07-15
HFPM
SERIAL
NO.
TARE
WEIGHT
NET
WEIGHT
GROSS
WEIGHT
TEST
DATE
HYDRO
DUE
SERIAL
NO.
TARE
WEIGHT
NET
WEIGHT
GROSS
WEIGHT
TEST
DATE
HYDRO
DUE
15868 19.4 15 34.4 Mar-15 Mar-27
227918 57 45 102 Sep-15 Sep-27
4189284 110 50 160 Aug-15 Aug-27
2809 158 186 344 Sep-15 Sep-27
2814 164 186 350 Sep-15 Sep-27
16573 19.4 15 34.4 Feb-14 Feb-26
687288 80 80 160 May-14 May-26
Harris Fire Protection Company, Inc. Signature
50 Kane St
SERVICE CHART B
2017290-1
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT:
2017-10-17 TV FREEDOM STAR
(410) 282-9377 (Fax) harrisfireco@aol.com
CERTIFICATE NO.:
(410) 285-7272
Michael Harty
Baltimore, MD 21224 CYLINDER RECORD
Bowthruster FM-200
Engine Room Halon
Sternthruster FM-200
HFPM-B REV 1-16
mailto:harrisfireco@aol.com mailto:harrisfireco@aol.com
50 Kane St
Types of Extinguishers
CO2
W
AFFF
K
NO.
SERIAL
NO.
LOCATION
TYPE
CAP.
(lb.)
DESC.OF
WORK (*)
6 YR
MAINT
HYDRO
DATE
NEXT
MAINT
COMM
1 WHEEL HOUSE HAL 13 1 Oct-16 Oct-22
2 WHEELHOUSE CO2 15 1 Jul-15 Jul-20
3 01 LVL PASSAGE CO2 15 1 Jul-15 Jul-20
4 01 LVL PASSAGE CO2 15 1 Jul-15 Jul-20
5 LAUNDRY CO2 15 1 Jul-15 Jul-20
6 LAUNDRY CO2 15 1 Jul-15 Jul-20
7 LAUNDRY CO2 15 1 Jul-15 Jul-20
8 LAUNDRY CO2 15 1 Jul-15 Jul-20
9 LAUNDRY CO2 15 1 Jul-15 Jul-20
10 LAUNDRY CO2 15 1 Jul-15 Jul-20
11 GALLEY CO2 15 1 Jul-15 Jul-20
12 MAIN DECK CO2 15 1 Jul-15 Jul-20
13 WORK SHOP MAIN DECK CO2 15 1 Jul-15 Jul-20
14 WORK SHOP MAIN DECK CO2 15 1 Jul-15 Jul-20
15 WORK SHOP MAIN DECK CO2 15 1 Jul-15 Jul-20
16 MAIN DECK CO2 15 1 Jul-15 Jul-20
17 LOWER DECK CO2 15 1 Jul-15 Jul-20
18 LOWER DECK CO2 15 1 Jul-15 Jul-20
19 LOWER DECK HAL 13 1 Jul-15 Jul-21
20 LOWER DECK CO2 15 1 Jul-15 Jul-20
21 LOWER DECK ABC 5 1 Jan-15 Jan-21
22 ENGINE WORKSHOP CO2 15 1 Jul-15 Jul-20
23 ENGINE ROOM CO2 15 1 Jul-15 Jul-20
24 ENGINE ROOM CO2 15 1 Jul-15 Jul-20
25 ENGINE ROOM CO2 15 1 Jul-15 Jul-20
26 EDG CO2 15 1 Jul-15 Jul-20
27 OUTSIDE EDG CO2 15 1 Jul-15 Jul-20
28 DC LOCKER CO2 15 1 Jul-15 Jul-20
30 CRANE ABC 10 1 Sep-14 Jan-09 Sep-20
29 DC LOCKER CO2 15 1 Jun-14 Jun-19
DC LOCKER CO2 15 1 Jul-14 Jul-19
DC LOCKER CO2 15 1 Jul-14 Jul-19
RESCUE BOAT ABC 2.5 1,6,7 Oct-17 Oct-23
Harris Fire Protection Company, Inc. Signature
Michael Harty
2017290-1
PKP HAL
BC
BC/CO23 - Hydrostatic Testing
4 - 6 Year Maintenance
6 - New Extinguisher
2017-10-17
2 - Recharge
TV FREEDOM STAR
7 - New Bracket
8 - Rejected/Condemned
FIRE EXTINGUISHER
INSPECTION
(410) 285-7272
1 - Internal/External Inspection ABC
(*) DESCRIPTION OF WORKING CODES
5 - Repair
(410) 282-9377 (Fax)
SERVICE CHART C
Baltimore, MD 21224
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
harrisfireco@aol.com
HFPM-C REV 1-16
mailto:harrisfireco@aol.com
NO.
SERIAL
NO.
LOCATION
TYPE
CAP.
(lb.)
DESC.OF
WORK (*)
6 YR
MAINT
HYDRO
DATE
NEXT
MAINT
COMM
Harris Fire Protection Company, Inc. Signature
(410) 285-7272 FIRE EXTINGUISHER
Michael Harty
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
2017-10-17 TV FREEDOM STAR 2017290-1
Baltimore, MD 21224 (410) 282-9377 (Fax) INSPECTION harrisfireco@aol.com SERVICE CHART C
HFPM-C REV 1-16
mailto:harrisfireco@aol.com
No. Test Date
1 Oct-16
2 Oct-16
1 - INSPECTION
2 - FLOWTEST (SEE REPORT)
3 - REPAIR
4 - REJECTED
SCBA SUMMARY
SERVICE CHART G
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
2017-10-17 TV FREEDOM STAR 2017290-1
Description of Work
1,2
1,2
Harris Fire Protection Company, Inc. Signature
MSA FIREHAWK 4500 PSI / 45 MIN
Michael Harty
(410) 285-7272
Baltimore, MD 21224 (410) 282-9377 Fax harrisfireco@aol.com
MSA FIREHAWK 4500 PSI / 45 MIN
Make Capacity Serial No.
HFPM-G REV 11-14
mailto:harrisfireco@aol.com
Location Manufacture Material Capacity Pressure Serial No. Manu. Date Test Date
DC LKR MSA / LUXFER CF 45 MIN 4100 PSI AJK11200 Oct-14 Oct-14
DC LKR MSA / LUXFER CF 45 MIN 4000 PSI AJK11161 Oct-14 Oct-14
DC LKR MSA / LUXFER CF 30 MIN 4300 PSI ACT163098 Apr-15 Apr-15
DC LKR MSA / LUXFER CF 30 MIN 4300 PSI ACT163049 Apr-15 Apr-15
DC LKR MSA / LUXFER CF 60 MIN 4500 PSI AGD47483 May-17 May-17
DC LKR MSA / LUXFER CF 60 MIN 4500 PSI AGD47546 May-17 May-17
WORK CODES
1 - INSPECTION 5 - REJECTED
2 - RECHARGE
3 - HYDROTEST
4 - REPAIR
Harris Fire Protection Company, Inc. Signature
(410) 285-7272
Baltimore, MD 21224 (410) 282-9377 Fax SCBA CYLINDERS harrisfireco@aol.com SERVICE CHART H
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
2017-10-17 TV FREEDOM STAR 2017290-1
Description of Work
Michael Harty
HFPM-H REV 11-14
mailto:harrisfireco@aol.com
DESCRIPTION OF SYSTEM:
MAKE:
MODEL:
LOCATION:
POWER SUPPLY VOLTAGE: NUMBER OF ZONES
BATTERY BACKUP SIZE: ANNUNCIATOR LOCATION:
SUBPANEL LOCATIONS:
SUPPORTING DOCUMENTS AVAIL: SUPPORTING DOC LOCATION:
ZONE TYPE PASS/FAIL
1 MP PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 MP PASS
1 SD PASS
1 SD PASS
1 SD PASS
2 HD PASS
1 SD PASS
1 HD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 MP PASS
1 SD PASS
1 SD PASS
2 HD PASS
Legend:
Harris Fire Protection Company, Inc. Stamp and Signature harrisfireco@aol.com SERVICE CHART
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
2017-10-17 TV FREEDOM STAR 2017290-1
50 Kane St (410) 285-7272
Baltimore, MD 21224 (410) 282-9377 (Fax) FIRE/SMOKE ALARM
WHEEL HOUSE NUMBER OF ANNUNCIATORS 1
110V 2
12V 7AH x 2 LOWER DECK PASSAGE
FIREBOY-XINTEX NUMBER OF DETECTORS: 40
ELITE RSM NUMBER OF PULL STATIONS 4
WHEELHOUSE
YES CHIEF ENGINEER OFFICE
LOCATION MODEL # COMMENTS
CAPTAIN OFFICE
SCIENTIST STATEROOM
WHEELHOUSE
CAPTAIN STATEROOM
01 LEVEL PASSAGEWAY
HOSPITAL
01 LEVEL PASSAGEWAY
FWD STOREROOM
BOW THRUSTER
FOC'SLE LOCKER
LAUNDRY
MESS DECK
STEWARD STATEROOM
DRY GOOD STOREROOM
MESS DECK
GALLEY
DECK WORKSHOP
MAIN DECK
CLASS ROOM
MP - Manual Pull SD - Smoke Detector AHU - Air Handling Unit
HD - Heat Detector ID - Ionization Detector SB - Smoke Beam SA - Smoke Accumulator
EMERGENCY DIESEL GENERATOR
Special Comments:
Michael Harty
HFPM-I REV 11-14
ZONE TYPE PASS/FAIL
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 SD PASS
1 HD PASS
1 SD PASS
1 SD PASS
2 MP PASS
2 HD PASS
2 HD PASS
2 HD PASS
2 HD PASS
2 HD PASS
2 SD PASS
2 HD PASS
2 SD PASS
1 MM PASS
2 MM PASS
2 MM PASS
Legend:
Harris Fire Protection Company, Inc. Signature
50 Kane St (410) 285-7272
2017-10-17 TV FREEDOM STAR 2017290-1
LOCATION MODEL # COMMENTS
Baltimore, MD 21224 (410) 282-9377 (Fax) FIRE/SMOKE ALARM harrisfireco@aol.com SERVICE CHART
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
STATEROOM #3
STATEROOM #4
STATEROOM #1
STATEROOM #2
STATEROOM #7
STATEROOM #5
STATEROOM #6
ENGINE WORKSHOP
LOWER LEVEL PASSAGE FWD
STATEROOM #8
CHIEF ENGINEER STATEROOM
PORT ENGINE
STBD ENGINE
LOWER LEVEL PASSAGE AFT
ENGINE ROOM ACCESS
ENGINE ROOM CENTERLINE
SWITCHBOARD
PORT GENERATOR
STBD GENERATOR
BOWTHRUSTER FM200 DISCH
E/R HALON DISCHARGE
STERN THRUSTER
STEERING GEAR ROOM
STERNTHRUSTER FM200 DISCH
Special Comments:
MP - Manual Pull SD - Smoke Detector AHU - Air Handling Unit
HD - Heat Detector ID - Ionization Detector SB - Smoke Beam SA - Smoke Accumulator
Michael Harty
HFPM-I REV 11-14
CARRIED
OUT
NOT
CARRIED
OUT
SAT /
UNSAT /
N/A
X
X
X
X
X
X
X
X
N/A
X
X
SET TIME: 30 SEC TESTED TIME 32 SEC TEM/PRESS:
1 # OF ELECT 6 X
QTY 6 X
QTY 0 N/A
X
17) HEAT ACTUATION DEVICES TESTED QTY 0 N/A
QTY 2 X
X
Harris Fire Protection Company, Inc. Signature
18) PNEUMATIC ACTUATION DEVICES TESTED
19) SYSTEM SEALED / REARMED / TAGGED / READY FOR USE
10) ENGINE / FUEL INTERLOCK CHECKED
11) OTHER SHUTDOWNS CHECKED (LIST IN COMMENTS BLOCK)
12) TIME DELAY CHECKED AND TESTED
13) ALARMS CHECKED # OF PNEUMATIC
14) VISUAL INDICATORS CHECKED
50 Kane St (410) 285-7272 CLEAN AGENT
Baltimore, MD 21224 (410) 282-9377 (Fax) INSTALLATION harrisfireco@aol.com SERVICE CHART L
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
Sep-15
CYLINDER QUANTITY: 2 FLEX HOSE HYDRO: Sep-15
MANUFACTURE: ANSUL PILOT CYLINDER HYDRO:
2017-10-17 TV FREEDOM STAR 2017290-1
PILOT CYLINDER SIZE:
SPACE PROTECTED: ENGINE ROOM PILOT CYLINDER QTY: 1
SYSTEM LOCATION: ENGINE WORKSHOP 50# CO2/ CV-98
Michael Harty
CYLINDER SIZE: 186 # HALON 1301 ROOM TEMP: 53 deg F
HYDROTEST DATE OF CYLINDERS: Sep-15 TEST PRESSURE: 750 PSI
9) VENTIATION DAMPER OPERATION CHECKED
1) SYSTEM DISARMED PRIOR TO INSPECTION
2) CYLINDER CONTENTS CHECK BY WEIGHT / LIQUID LEVEL
3) CONDITION OF CYLINDERS ( SAT / UNSAT)
4) SYSTEM DESIGN VERIFIED AGAINST BUILD DRAWINGS / MANUF. SPECIFICATIONS
5) SYSTEM ACTUATION METHODS CHECKED
6) FLEXIBLE HOSE AND CYLINDER CONNECTIONS CHECKED
7) PRESSURE SWITCH / REMOTE OPERATED GEAR CHECKED
8) VENTILATION SHUDOWN / INTERLOCKS CHECKED
DESCRIPTION OF INSPECTION/TESTS:
16) REMOTE OPERATION STATIONS TESTED
15) STOP VALVES CHECKED
COMMENTS
PRESSURE SWITCH TIED TO FIREBOY PANEL FOR ELECTRONIC ALARM THROUGHOUT SHIP. ADDITIONALLY, FIREBOY PANEL TRIPS OUT ENGINE ROOM EMERGENCY SHUTDOWN BUS FOR SECONDARY SHUTDOWNS
HFPM-L REV 1-16
CARRIED
OUT
NOT
CARRIED
OUT
SAT /
UNSAT /
N/A
X
X
X SAT
X
X
X
X
X
N/A
X
X
SET TIME: 30+ SEC TESTED TIME 37 SEC TEM/PRESS: 65/1000
0 # OF ELECT 6 X
QTY 6 X
QTY 0 N/A
X
17) HEAT ACTUATION DEVICES TESTED QTY 1 COMMENT
QTY 1 X
X
Harris Fire Protection Company, Inc. Signature harrisfireco@aol.com SERVICE CHART L
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
50 Kane St (410) 285-7272 CLEAN AGENT
Baltimore, MD 21224 (410) 282-9377 (Fax) INSTALLATION
SYSTEM LOCATION: BOWTHRUSTER PILOT CYLINDER SIZE: 15# CO2
MANUFACTURE: BSCO PILOT CYLINDER HYDRO: Mar-15
2017-10-17 TV FREEDOM STAR 2017290-1
SPACE PROTECTED: BOWTHRUSTER PILOT CYLINDER QTY: 1
HYDROTEST DATE OF CYLINDERS: Sep-15 TEST PRESSURE: 1000 PSI
CYLINDER QUANTITY: 1 FLEX HOSE HYDRO: Sep-15
CYLINDER SIZE: 45# FM-200 ROOM TEMP: 65 deg F
5) SYSTEM ACTUATION METHODS CHECKED
6) FLEXIBLE HOSE AND CYLINDER CONNECTIONS CHECKED
7) PRESSURE SWITCH / REMOTE OPERATED GEAR CHECKED
8) VENTILATION SHUDOWN / INTERLOCKS CHECKED
9) VENTIATION DAMPER OPERATION CHECKED
DESCRIPTION OF INSPECTION/TESTS:
1) SYSTEM DISARMED PRIOR TO INSPECTION
2) CYLINDER CONTENTS CHECK BY WEIGHT / LIQUID LEVEL
3) CONDITION OF CYLINDERS ( SAT / UNSAT)
4) SYSTEM DESIGN VERIFIED AGAINST BUILD DRAWINGS / MANUF. SPECIFICATIONS
14) VISUAL INDICATORS CHECKED
15) STOP VALVES CHECKED
16) REMOTE OPERATION STATIONS TESTED
18) PNEUMATIC ACTUATION DEVICES TESTED
19) SYSTEM SEALED / REARMED / TAGGED / READY FOR USE
10) ENGINE / FUEL INTERLOCK CHECKED
11) OTHER SHUTDOWNS CHECKED (LIST IN COMMENTS BLOCK)
12) TIME DELAY CHECKED AND TESTED
13) ALARMS CHECKED # OF PNEUMATIC
COMMENTS
PRESSURE SWITCH TIED TO FIREBOY PANEL FOR ELECTRONIC ALARM THROUGHOUT SHIP. ADDITIONALLY, FIREBOY PANEL TRIPS OUT LAUNDRY AND BOW THRUSTER ROOM SHUNT TRIP BREAKERS FOR VENTILATION
SHUTDOWNS. HEAT DETECTOR IS 165deg F FRANGIBLE BULB
Michael Harty
HFPM-L REV 1-16
CARRIED
OUT
NOT
CARRIED
OUT
SAT /
UNSAT /
N/A
X
X
X SAT
X
X
X
X
X
N/A
X
X
SET TIME: 30+ SEC TESTED TIME 36 SEC TEM/PRESS: 65/1000
0 # OF ELECT 6 X
QTY 6 X
QTY 0 N/A
X
17) HEAT ACTUATION DEVICES TESTED QTY 1 COMMENT
QTY 1 X
X
Harris Fire Protection Company, Inc. Signature
Baltimore, MD 21224 (410) 282-9377 (Fax) INSTALLATION harrisfireco@aol.com SERVICE CHART L
50 Kane St (410) 285-7272 CLEAN AGENT
SPACE PROTECTED: STERN THRUSTER PILOT CYLINDER QTY: 1
SYSTEM LOCATION: STERN THRUSTER PILOT CYLINDER SIZE: 15# CO2
YEAR/MONTH/DAY TYPE AND NAME OF VESSEL/UNIT: CERTIFICATE NO.:
2017-10-17 TV FREEDOM STAR 2017290-1
CYLINDER SIZE: 80# FM-200 ROOM TEMP: 65 deg F
HYDROTEST DATE OF CYLINDERS: Sep-15 TEST PRESSURE: 1000 PSI
MANUFACTURE: BSCO PILOT CYLINDER HYDRO: Mar-15
CYLINDER QUANTITY: 1 FLEX HOSE HYDRO: Sep-15
4) SYSTEM DESIGN VERIFIED AGAINST BUILD DRAWINGS / MANUF. SPECIFICATIONS
5) SYSTEM ACTUATION METHODS CHECKED
6) FLEXIBLE HOSE AND CYLINDER CONNECTIONS CHECKED
7) PRESSURE SWITCH / REMOTE OPERATED GEAR CHECKED
8) VENTILATION SHUDOWN / INTERLOCKS CHECKED
DESCRIPTION OF INSPECTION/TESTS:
1) SYSTEM DISARMED PRIOR TO INSPECTION
2) CYLINDER CONTENTS CHECK BY WEIGHT / LIQUID LEVEL
3) CONDITION OF CYLINDERS ( SAT / UNSAT)
COMMENTS
PRESSURE SWITCH TIED TO FIREBOY PANEL FOR ELECTRONIC ALARM THROUGHOUT SHIP. ADDITIONALLY, FIREBOY PANEL TRIPS OUT ENGINE ROOM EMERGENCY SHUTDOWN BUS FOR VENTILATION SHUTDOWNS.
HEAT DETECTOR IS 165deg F FRANGIBLE BULB
Michael Harty
14) VISUAL INDICATORS CHECKED
15) STOP VALVES CHECKED
16) REMOTE OPERATION STATIONS TESTED
18) PNEUMATIC ACTUATION DEVICES TESTED
19) SYSTEM SEALED / REARMED / TAGGED / READY FOR USE
9) VENTIATION DAMPER OPERATION CHECKED
10) ENGINE / FUEL INTERLOCK CHECKED
11) OTHER SHUTDOWNS CHECKED (LIST IN COMMENTS BLOCK)
12) TIME DELAY CHECKED AND TESTED
13) ALARMS CHECKED # OF PNEUMATIC
HFPM-L REV 1-16