657-19-117JB - Bid Documents - Part 3.pdf

PDF 8 MB Posted

Attached to
Implement Sterile Processing Service Ventilation Requirements PN:657-19-117JB Federal contract opportunity
Solicitation number
36C25520R0082
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This federal solicitation is seeking proposals for a construction project to implement sterile processing service ventilation requirements at a VA medical center. The contractor will be responsible for demolition, site preparation, and furnishing all labor, materials, tools and equipment to complete the project drawings and specifications. The project cost is estimated between $500,000 to $1 million. Proposals are due by June 5, 2020, with award planned for fall 2020. The NAICS code is 238220 with a small business size standard of $16.5 million. The project duration is 365 calendar days from notice to proceed. The solicitation will be posted on beta.sam.gov on June 5 and the offeror must monitor the site for any amendments. A pre-solicitation site visit is scheduled and attendance is encouraged. Questions must be submitted by email with the subject line specifying the project number. The opportunity is a total SDVOSB set-aside pursuant to applicable public law and regulation.

View the file

Other files for this federal contract opportunity

Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FLOOR 00

527' - 6"

FLOOR 01

539' - 6"

01-MP-300

01-MP-300

2"ø MPR

3/4"ø MPR

2"ø MPR /4

"ø M

P S

/4

"ø M

P S

/4

"ø M

P R

/2 "ø

L P

R

1 1/2"ø LPR

"ø

M P

S th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :1

P

M

01-MP-301

MECHANICAL ROOM SECTIONS

23 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

DD ZM03/26/2020

1/2" = 1'-0"

EAST SECTION - GE26

EXISTING CONDITIONS PHOTO EXISTING CONDITIONS PHOTO

COMMUNICATION GENERAL NOTES:

A. FOR WHEEL CHAIR PATIENT. USE, MOUNT TELEPHONE OUTLET 35" AFF TO BOTTOM OF OUTLET BOX.

B. DESK PHONES - MOUNT OUTLET 1'-6" AFF

C. PAY PHONES - MOUNT OUTLET 4'-0" AFF

D. HEIGHT OF TELECART OUTLETS SHALL BE AS INDICATED ON BED WALLS OR PBPU DETAILS.

E. SEE VA. BARRIER FREE DESIGN GUIDE PG-18-13

ELECTRICAL GENERAL NOTES - DEMOLITION:

A. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF DEMOLITION AND

CONSTRUCTION. COORDINATE WITH GENERAL CONSTRUCTION.

B. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES AND LIGHTING FIXTURES IN DEMOLITION AREAS

UNLESS NOTED OTHERWISE. DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY CUT/CAP CONDUITS IN CONCRETE SLAB AND IN THE AREA OF WORK PERIMETER. DISCONNECT AND REMOVE ALL ABANDONED CIRCUITS AND CONDUITS.

PROVED CONDUIT AND WIRE AS REQUIRED FOR CONTINUITY OF CIRCUITS TO ANY EXISTING DEVICES TO

REMAIN. COORDINATE AND VERIFY REQUIREMENTS WITHIN NEW AREA OF WORK.

C. DISCONNECT AND REMOVE ALL WIRES AND CONDUIT BACK TO THE OVERCURRENT DEVICE AND RELABEL

AS A SPARE.

D. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH

RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

E. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABEL IN JUNCTION BOX FOR

RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC CODE.

F. REPLACE ALL EXISTING MULTI-PHASE BRANCH CIRCUIT BREAKERS WITH HANDLE TIE BREAKERS ON ALL

MULTI-PHASE CIRCUITS.

ELECTRICAL GENERAL NOTES:

A. SPECIFICATIONS TAKE PRECEDENT OVER DRAWINGS.

B. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE

ARCHITECTURAL REFLECTED CEILING PLAN, AS REQUIRED.

C. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT

HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

D. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH

WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

E. ALL WIRING SHALL BE (3)#12 THWN/THHN COPPER 3/4C" UNLESS OTHERWISE NOTED.

F. MINIMUM SIZE CONDUIT FOR CONTROL CIRCUITS SHALL BE 1/2".

G. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS. SEAL REMAINING

ANULUS WITH FIRE CAULK.

H. FURNISH ACCESS DOORS OR PANELS FOR INSTALLATION BY GENERAL CONTRACTOR IN WALLS AND

CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED ELECTRICAL BOXES AND DEVICES.

I. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN FIXTURE PIGTAILS. ARMORED CABLE (AC) SHALL NOT BE USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED CABLE (AC) SHALL NOT BE USED WHERE MORE THAN THREE CONDUCTORS (PHASE/NEUTRAL/GROUND) ARE REQUIRED, WHERE EXPOSED; OR IN LENGTHS

EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.

J. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE AND

THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION.

K. COORDINATE ALL OUTAGES WITH VA COR PER SPECS PRIOR TO WORK BEING DONE.

L. REUSE ALL EXISTING PANELS.

M. ALL VAV'S TO REUSE EXISTING CIRCUITS. ALL CIRCUITING ON SHEETS IS TO BE UPDATED WITH ON AS BUILTS WITH CORRECT CIRCUIT AND ALL PANEL SCHEDULES TO BE UPDATED WITH UPDATED VAV

NUMBERS AND BREAKER SIZES AND CIRCUITS.

ELECTRICAL EQUIPMENT AND DISTRIBUTION SYSTEM

(RACEWAYS) 2015 IBC AND ASCE 7-10 NONSTRUCTURAL

SEISMIC RESTRAINT, BRACING AND ANCHORAGE NOTES:

REFERENCE SPECIFICATION: SECTION 13 05 41

SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS

SEISMIC DESIGN DATA FOR ANALYSIS AND DESIGN:

H-18-8 SEISMICITY = HIGH

SEISMIC RISK CATEGORY BASED UPON CRITICAL OCCUPANCY = IV

COMPONENT IMPORTANCE FACTORS:

IP=1.0 FOR NON-ESSENTIAL COMPONENTS NOT REQUIRED FOR CONTINUED OPERATION OR IF ITS

FAILURE WILL NOT IMPAIR THE CONTINUED OPERATION OF THE FACILITY

IP=1.5 FOR LIFE SAFETY AND DESIGNATED SEISMIC SYSTEMS (DSS) AND PERMANENT EQUIPMENT AND

COMPONENTS REQUIRING SPECIAL SEISMIC CERTIFICATION PER H-18-8.

FOR MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS AND DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS: SEE GENERAL STRUCTURAL NOTES AND DESIGN CRITERIA AS SPECIFIED ON

DRAWING NUMBER S-000.

SITE CLASS = C (PER GEOTECHNICAL REPORT)

SEISMIC DESIGN CATEGORY (SDC) = D

NONSTRUCTURAL SEISMIC EXCEPTIONS AND EXEMPTIONS SHALL BE DETERMINED IN ACCORDANCE WITH

H-18-8 AND CHAPTER 13 OF ASCE 7 FOR SDC = D.

H-18-8 EQUIPMENT AND COMPONENTS SPECIAL SEISMIC CERTIFICATION (SSC) REQUIREMENT:

IN STRUCTURES ASSIGNED TO SEISMIC DESIGN CATEGORY C, D, E, OR F, PERMANENT EQUIPMENT AND COMPONENTS ARE TO HAVE SPECIAL SEISMIC CERTIFICATION IN ACCORDANCE WITH REQUIREMENTSW OF SECTION 13.2.2 OF ASCE 7 EXCEPT FOR EQUIPMENT AND COMPONENTS THAT ARE CONSIDERED RUGGED AS LISTED IN SECTION 2.2 OF OSHPD CODE APPLICATION NOTICE CAN NO. 2-1708A.5, AND SHALL COMPLY WITH

SECTION 13.2.6 OF ASCE 7.

CLARIFICATION OF ASCE 7 "12 INCH RULE" SUSPENDED SEISMIC BRACING CODE EXCEPTION FOR PIPING AND

HVAC DUCTWORK.:

ALL PIPING OR DUCTWORK SUSPENDED BY INDIVIDUAL HANGER RODS 12" OR LESS AS MEASURED FROM THE TOP OF THE PIPING OR DUCTWORK TO THE BOTTOM OF THE SUPPORT WHERE THE HANGER IS ATTACHED. IF THE 12" LIMIT IS EXCEEDED BY ANY HANGER IN THE RUN, SEISMIC BRACING IS REQUIRED FOR THE RUN. A SINGLE SUPPORT LOCATION THAT MEETS THE REQUIREMENT OF THIS EXCEPTION DOES NOT CONSTITUTE A

SEISMIC SWAY BRACE LOCATION.

IN ADDITION, TO MEET THE CODE REQUIREMENTS, ALL OF THE FOLLOWING CONDITIONS MUST ALSO BE

SATISFIED:

1. LATERLA MOTION OF PIPING OR DUCTWORK WILL NOT CAUSE DAMAGING IMPACT WITH SURROUND SYSTEMS (E.G. OTHER CONDUIT, TRAY, PIPE, DUCT, EQUIPMENT, SPRINKLER HEADS ETC.) OR CAUSE LOSS

OF SYSTEM VERTICAL SUPPORT.

2. PIPING OR DUCTWORK MUST BE MADE OF DUCTILE MATERIAL WITH DUCTILE CONNECTIONS.

3. VERTICAL SUPPORT CONNECTIONS CANNOT DEVELOP MOMENTS (E.G. SWIVEL JOINTS, EYE BOLTS, VIBRATION ISOLATION HANGERS, ETC.)

KEY NOTES:

KEY NOTE00

NEW - EXISTING AND DEMO LINE TYPES:

NEW LINE TYPE

EXISTING LINE TYPE

DEMO LINE TYPE

DEMO HATCH

LIGHTING GENERAL NOTES:

A. ALL RECESSED LIGHTING FIXTURE IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6' LONG FLEXIBLE METAL

CONDUIT.

B. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE DIMENTIONED TO THE BOTTOM OF THE FIXTURES

UNLESS INDICATED OTHERWISE.

C. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR LIGHTING FIXTURES.

D. CIRCUIT WIRING IS NOT SHOWN. SWITCH AND CIRCUITING INTENT SHALL BE AS DESIGNATED AT

EACH LIGHT FIXTURE.

E. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUITING AND SWITCHING SHOWN.

F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD

SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS

INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT SCHEDULE.

ELECTRICAL SEISMIC GENERAL NOTES:

A. GC SHALL HAVE SEISMIC-FORCE-RESTRAINT SHOP DRAWINGS AND, CALCULATIONS PREPARED BY PROFESSIONAL STRUCTURAL ENGINEER EXPERIENCED IN THE AREA OF SEISMIC FORCE RESTRAINTS.THE PROFESSIONAL STRUCTURAL ENGINEER SHALL BE REGISTERED IN THE STATE WHERE THE PROJECT IS

LOCATED.

B. SUBMIT DESIGN TABLES AND INFORMATION USED FOR THE DESIGN-FORCE LEVELS, STAMPED AND SIGNED BY A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS

LOCATED.

C. "DO NOT INSTALL" SEISMIC RESTRAINT SUBMITTALS ARE APPROVED BY THE COR. COORDINATE AND

INSTALL TRAPEZE OR OTHER MULTI-PIPE HANGER SYSTEMS PRIOR TO PIPE INSTALLATION.

D. IN STRUCTURES ASSIGNED TO IBC SEISMIC DESIGN CATEGORY C, D, E, OR F, PERMANENT EQUIPMENTS AND COMPONENTS ARE TO HAVE SPECIAL SEISMIC CERTIFICATION IN ACCORDANCE WITH REQUIREMENTS OF SECTION 13.2.2 OF THE ASCE 7 EXCEPT FOR EQUIPMENT THAT ARE CONSIDERED RUGGED AS LISTED IN SECTION 2.2 OSHPD CODE APPLICATION NOTICE CAN NO. 2-1708A.5 AND SHALL COMPLY WITH SECTION

13.2.6 OF ASCE 7.

E. GC AND MC SHALL REVIEW AND COMPLETE ALL SEISMIC RESTRAINT REQUIREMENTS PER SPECIFICATION

SECTION 13 05 41.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :2

P

M

01-EG-001

ELECTRICAL ABBREVIATIONS AND

GENERAL NOTES

24 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

TL GG03/26/2020

N

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

O

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P

P POLE

PA PUBLIC ADDRESS

PB PULL BOX OR PANEL BOARD

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

R

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

REQ REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

S

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SES SERVICE ENTRANCE SECTION

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

T

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

U

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V

V VOLT

VA VOLT-AMPERE

VAR VOLT-AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W

W WATT

WH WATER HEATER

WP WEATHERPROOF

X

XFER TRANSFER

XFMR TRANSFORMER

E

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXST EXISTING

F

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

FLUOR FLUORESCENT

FLUOR FIXT FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

G OR GND ELECTRICAL GROUND

GC GENERAL CONTRACTOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

H

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

I

IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH

AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J

J-BOX JUNCTION BOX

K

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAH KILOVOLT-AMPERE PER HOUR

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

L

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

M

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

1P SINGLE POLE

1PH SINGLE PHASE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE PHASE

4/C FOUR-CONDUCTOR

4W FOUR WIRE

A

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT / ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT OR ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE FAULT

CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE-HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

B

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BYPASS

C

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA OR CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED / CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED / OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

CO CONTRACTING OFFICER

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

D

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

ELECTRICAL ABBREVIATIONS

CARD READERBRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER OF

CIRCUITS,NEUTRAL, AND SWITCH LEG CONDUCTORS. ONE

SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE

PROVIDED FOR EACH HOMERUN; NOT SHOWN

P

A bx

A b x

A b x

A b x

DT

ELECTRICAL SYMBOLS - DIAGRAM COMMUNICATION SYMBOLS: ELECTRICAL SYMBOLS - LIGHTING PLANELECTRICAL SYMBOLS - POWER PLAN

SWITCH, MULTIPOSITION

SWITCH, NORMALLY CLOSED FLOAT

SWITCH, NORMALLY CLOSED FOOT OPERATED

SWITCH, NORMALLY CLOSED LIMIT

SWITCH, NORMALLY CLOSED TIME DELAY

SWITCH, NORMALLY CLOSED TEMPERATURE

ACTIVATED

SWITCH, NORMALLY OPEN FLOAT

SWITCH, NORMALLY OPEN LIMIT

SWITCH, NORMALLY OPEN TEMPERATURE

ACTIVATED

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

PULL BOX

PRESSURE SWITCH-CLOSE ON INCREASE

PRESSURE SWITCH-OPEN ON INCREASE

MANHOLE

TIME CLOCK

VENTILATOR OR FAN COIL UNIT OUTLET

CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED

FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.

RECEPTACLE,

SWITCHED DUPLEX

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE

CORD (CENTER LINE OF OUTLET: 6'-6" AFF. (MINIMUM).

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS

DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.

3-GANG COMPARTMENT BOX IN FLOOR FOR

TELEPHONE, DATA & RECEPTACLE.

RECEPTACLE, SPECIAL PURPOSE

A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.

H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

ELECTRIC DOOR STRIKE

MAGNETIC DOOR POSITION SWITCH

VANDAL RESISTANT 1080P DOME IP CAMERA

FOUR SQUARE JUNCTION BOX

SECURITRON iMXDa MAGNETIC LOCK

OUTLET, COMBINATION TELEPHONE/DATA

COMMUNICATION

CABLE TELEVISION LINE = CATV

CLOSED CIRCUIT TELEVISION LINE = CCTV.

MINIMUM 1" CONDUIT

FIBER OPTICS LINE = FO

FLOOR RECEPTACLE, TELEPHONE

OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:

J = JACK TYPE W = WALL TYPE

SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE,

PROVIDE SCHEDULE ON LEGEND

SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE,

PROVIDE SCHEDULE ON LEGEND. MTD.

7'-6" AFF UNLESS OTHERWISE NOTED.

OUTLET DATA ONLY

TELEPHONE LINE = T

INTERCOM LINE = I. MINIMUM 3/4" CONDUIT.

SOUND LINE = S

NURSE CALL LINE = NC. MINIMUM 3/4" CONDUIT.

OUTLET; LETTER INDICATES AS FOLLOWS:

A = AUDIO V = VIDEO I = INTERCOM

RADIO CONDUIT RUN, MINIMUM 3/4" CONDUIT.

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6"

AFF UNLESS OTHERWISE NOTED.

SPEAKER PROGRAM SELECTOR SWITCH & VOLUME

CONTROL MTD. 4'-6" AFF UNLESS OTHERWISE NOTED.

OUTLET, TELEVISION

BLANK= 4 11/16" MASTER ANTENNA OUTLET BOX W/BLANK

COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.

C = CAMERA (CCTV SYSTEM), MTD 18" AFF

M = MONITOR (CCTV SYSTEM).

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER

TOP UNLESS OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS

AT MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED.

D = DUTY STATION. MTD 5'-0" AFF UNLESS NOTED OTHERWISE.

E = MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF FOR TUB

LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION.

P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH

S = AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS

OTHERWISE NOTED.

U = UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED.

NURSE CALL STATION.

2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF LAMP)

MTD 6" ABOVE DOOR.

D = CORRIDOR DOME LIGHT.

I = AUXILIARY INTERSECTIONAL DOME LIGHT.

TELEPHONE TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" AFF.

REMOTE DICTATING OUTLET MTD 1'-6" AFF. UNLESS OTHERWISE NOTED.

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL OPERATION

OF INSTRUMENT & TYPE REQUIRED).

INTERCOM STAFF STATION.

TELECOMMUNICATIONS MANHOLE

DATA BOX

DURESS BUTTON

CCTV SYSTEM WORKSTATION

REQUEST TO EXIT MOTION DETECTOR

USP HUB2SA REMOTE DOOR RELEASE BUTTON

CODE BLUE BUTTON INTEGRATED NURSE CALL SYSTEM

NURSE CALL MASTER CONSOLE

ETHERNET NETWORK SWITCH

WIRELESS ACCESS POINT

SWITCH

F = FUSED SWITCH

K = KEY OPERATED

L = LOCK

LM= LOW VOLTAGE MASTER

M = MANUAL MOTOR STARTING

MC= MOMENTARY CONTACT

MP= MOTOR SNAP WITH PILOT LIGHT

P = WITH PILOT LIGHT (THERMAL TYPE)

X = EXPLOSION PROOF

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE

LVD = LOW VOLTAGE DIMMER

LV= LOW VOLTAGE SWITCH

GS= GRAPHIC SCREEN CONTROL STATION

PB= PUSH BUTTON STATION

WP= WEATHER PROOF

T = TIMER OPERATED

LOS= OCCUPANCY SENSOR

LIGHTING, ONE HEAD EMERGENCY BATTERY POWER

STREET LIGHT WITH BRACKET

LIGHT POLE, ONE MAST ARM, ONE LUMINAIRE

LIGHT POLE, TWO MAST ARMS, TWO LUMINAIRES

LIGHT POLE, POST TOP MOUNT LUMINAIRE

LIGHT POLE, ONE LUMINAIRE

LIGHTING, EXTERIOR BUILDING

LIGHTING, TWO HEAD EMERGENCY BATTERY POWER

LIGHTING, THREE HEAD EMERGENCY BATTERY POWER

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

LIGHT POLE, TWO LUMINAIRES

RECESSED DOWNLIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE

INFORMATION.

JUNCTION BOX

TRANSFORMER, PLAN

WYE CONNECTION

DUCT, CELL FLOOR HEADER

DUCT, TROLLEY

DUCT, UNDERFLOOR

JUNCTION BOX

EARTH GROUND

LADDER CABLE TRAY

WIREWAY

RIGID CONDUIT LINE = RC

SUBSTATION

BUSWAY

FLOOR OUTLET, DATA COMMUNICATION

OUTLET, DATA COMMUNICATION

PUSH BUTTON

DISTRIBUTION PANEL

LIGHTING PANEL

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

RECEPTACLE, CLOCK HANGER

RECEPTACLE, DUPLEX (MOUNT 18"AFF. UNLESS NOTED OTHERWISE)

RECEPTACLE, DUPLEX ON EMERGENCY POWER

(MOUNT 18" AFF. UNLESS NOTED OTHERWISE)

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT

INTERRUPTER (MOUNT 18" AFF. UNLESS NOTED OTHERWISE)

RECEPTACLE, QUADRAPLEX

RECEPTACLE, SINGLE

RECEPTACLE, SINGLE WITH SWITCH

DIRECT BURIAL CABLE = DB

POWER DUCT = P

HI VOLTAGE SWITCH ON CONCRETE PAD

LOW VOLTAGE SWITCH ON CONCRETE PAD

DUAL POWER AND TELECOMMUNICATIONS MANHOLE

SWITCH, NORMALLY OPEN TIME DELAY

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

MEDIUM-VOLTAGE OIL CIRCUIT BREAKER

MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

FUSIBLE LINK

VARIABLE FREQUENCY DRIVE

GENERATOR, POWER

BATTERY

CAPACITOR

LIGHTNING ARRESTOR

RECTIFIER, CATHODIC PROTECTION

RELAY; LETTER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE

51 = AC-TIME OVERCURRENT

67 = AC-DIRECTIONAL OVERCURRENT

86 = LOCK OUT

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED, VAV

STARTER, COMBINATION W/DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

POTHEAD

STRESS CONE

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

RECEPTACLE, DUPLEX COUNTER HEIGHT

BLANK OUTLET BOX

RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER

(MOUNT 18" AFF. UNLESS NOTED OTHERWISE

DUAL PASSIVE INFRARED / MICROPHONIC

TECHNOLOGY (ULTRASONIC NOT ALLOWED)

FLOOR OUTLET, RECEPTACLE

GROUNDING BAR

HEADWALL

LIGHT FIXTURE POWER CONNECTION DESIGNATIONS:

OPEN - NORMAL POWER CIRCUIT

SHADED - LIFE SAFETY EMERGENCY POWER CIRCUIT

HATCHED - CRITICAL POWER CIRCUIT

RECESSED TROFFER LIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULES FOR MORE

INFORMATION.

CEILING SURFACE MOUNTED LIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE

INFORMATION.

WALL SURFACE MOUNTED LIGHT FIXTURE.

NOMENCLATURE EXAMPLE :

('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO

DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE

INFORMATION.

EXTERIOR FLOOD LIGHT

LIGHT FIXTURE, BOLLARD

LIGHT FIXTURE, DIRECTIONAL

DUEL TECHNOLOGY (NOT ULTRA SONIC)

M

PB

P

VFD

G

R

A

V

W

WH

T

T T

J

C C

W W

RC

DB

P

S

HVS

LVS

P T

B B

DP#__

LP

C

C

S

H

S

TC

M

CR

ES

F

FIX

J

ML

RRB

RX

WS

DB

CB

NCM

NWS

WAP

CATV

CCTV

FO

T

I

S

NC

R

$x

$x

B

C w

X S

X S

R

R M

C

NCM

NCT

N D

N

TTB

R M

S

DT

M

OCB

D th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :2

P

M

01-EG-002

ELECTRICAL SYMBOLS

25 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

RA GG03/26/2020

CLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

JCLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

R.3

S

U

T

V

1 2 3 4 5 7 9 10

MECH. RM.

GE26

MEDICAL

RECORDS

GE28

CORRIDOR

H004

MEDICAL

RECORDS

GE21

MEDICAL

RECORDS

GE20

TOILET

GE22

TOILET

GE23

HAC

GE24

CORRIDOR

GE31

CORRIDOR

H005

MEDICAL

RECORDS

GE19

OFFICE

GE17

CORRIDOR

H003

HAC

GE34

HAC

GE35

ELEVATOR #2

E2

MEDICAL

RECORDS

GC09

D.W.

E3

CHASE

CH-C-1

MEDICAL

RECORDS

GE32

STORAGE

GE32A

MEDICAL

RECORDS

GE29

1P4

AV

48"AFF

R.1

R.2

V.3

V.2

V.1

01-VAV-1 01-VAV-2 01-VAV-3

01-VAV-4 01-VAV-5

01-VAV-6

01-HX-01

01-HP-01

01-EF-1

AV-23

01-AHU-01

AV-38,40,42

01-GMP-01

1P4-24

AV-32

AV-31,33

1P4-20

KEY NOTES:

WORK TO BE PERFORMED IN THIS PANEL COORDINATE WITH VA COR

FOR LOCK OUT TAG OUT.

ELECTRICAL CONTRACTOR SHALL PROVIDE A 50VA, 120V/24V CONTROL

TRANSFORMER FOR VAV'S AND A 20A, 120V CIRCUIT FROM EXISTING

PANEL AV-23.

DUPLEX OUTLET FOR COMPUTER MOUNTED AT 48" AFF

ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING LIGHTING IN

MECHANICAL ROOM AND REPLACE WITH LED LIGHTING AND RE-USE

EXISTING CIRCUIT.

1. FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS SEE SHEET

01-EG-001 AND 01-EG-002.

GENERAL NOTES:

P la n N o rt h

T ru e N o rt h

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :3

P

M

01-EP-100

ELECTRICAL POWER PLAN - FLOOR 00

26 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

RA GG03/26/2020

1/4" = 1'-0"

ELECTRICAL POWER PLAN - FLOOR 00

1 3

Plan North

True North

CLNG

J

CLNG

J

CLNG

J

CR

CR

ML

ML

T

T

T

T

T

T

T

CLNG

JCLNG

J

CLNG

J

ML

C R

C R

ML

ML

CR

CR

ML

CLNG

J

CLNG

J

AT

AT

AT

AT

AT

AT

AT

CLNG

J

R.3

S

U

T

V

1 2 3 4 5 7 9 10

MEDICAL

RECORDS

GC09

MEDICAL

RECORDS

GE19

OFFICE

GE17

HAC

GE34

HAC

GE35

CORRIDOR

H003

CORRIDOR

H005

MEDICAL

RECORDS

GE21

MEDICAL

RECORDS

GE20

TOILET

GE22

CORRIDOR

GE31

MEDICAL

RECORDS

GE32

MECH. RM.

GE26

MEDICAL

RECORDS

GE28

CORRIDOR

H004

TOILET

GE23

HAC

GE24

STORAGE

GE16

1P4

AV

MEDICAL

RECORDS

GE29

GE29

X1

01-VAV-4

01-VAV-5 01-VAV-6

R.1

R.2

V.3

V.2

V.1

01-VAV-1

01-VAV-2

01-VAV-3 01-VAV-7

01-HX-01

01-HP-01

01-EF-1

01-AHU-01

CO2

CO2

CO2

CO2

CO2

CO2

CO2

KEY NOTES:

CARD READERS AND MAG LOCK FOR ACCESS TO MEDICAL RECORDS

TO BE TIED TO EXISTING PACS SYSTEM

VAV'S AND AIR HANDLER TO BE TIED BACK TO EXISTING BMS SYSTEM

1. FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS SEE SHEET

01-EG-001 AND 01-EG-002.

GENERAL NOTES:

P la n N o rt h

T ru e N o rt h

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :3

P

M

01-EI-100

ELECTRICAL INSTRUMENTATION PLAN -

FLOOR 00

27 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

RA GG03/26/2020

1/4" = 1'-0"

ELECTRICAL INSTRUMENTATION PLAN - FLOOR 00

Plan North

True North

CLNG

J

CLNG

J

CLNG

J

CLNG

JCLNG

J

CLNG

J

CLNG

J

CLNG

J

CLNG

J

R.3

S

U

T

V

1 2 3 4 5 7 9 10

MECH. RM.

GE26

MEDICAL

RECORDS

GE28

CORRIDOR

H004

MEDICAL

RECORDS

GE21

MEDICAL

RECORDS

GE20

TOILET

GE22

TOILET

GE23

HAC

GE24

CORRIDOR

GE31

CORRIDOR

H005

MEDICAL

RECORDS

GE19

OFFICE

GE17

CORRIDOR

H003

HAC

GE34

HAC

GE35

ELEVATOR #2

E2

MEDICAL

RECORDS

GC09

D.W.

E3

CHASE

CH-C-1

MEDICAL

RECORDS

GE32

STORAGE

GE32A

MEDICAL

RECORDS

GE29

1P4

AV

R.1

R.2

V.3

V.2

V.1

01-VAV-2

01-VAV-1

01-VAV-3

01-VAV-7

01-VAV-4

01-VAV-5 01-VAV-6

01-AHU-01

KEY NOTES:

ELECTRICAL CONTRACTOR SHALL PROVIDE A 3/4" DEDICATED EMT

CONDUIT OR CABLE TRAY OR CABLE HOOK FOR SIGNAL TO VAV'S FROM

BMS SYSTEM.

NEW DATA PORT AT 48" AFF FOR COMPUTER.

ELECTRICAL CONTRACTOR SHALL PROVIDE A 3/4" DEDICATED EMT

CONDUIT OR CABLE TRAY OR CABLE HOOK FOR SIGNAL TO

MECHANICAL EQUIPMENET FROM BMS SYSTEM.

1. FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS SEE SHEET

01-EG-001 AND 01-EG-002.

GENERAL NOTES:

P la n N o rt h

T ru e N o rt h

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :3

P

M

01-ET-100

ELECTRICAL TELECOMMUNICATIONS

PLAN - FLOOR 00

28 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

RA GG03/26/2020

1/4" = 1'-0"

ELECTRICAL TELECOMMUNICATIONS PLAN - FLOOR 00

48"AFF

Plan North

True North

TO 1-ATS1-ELEV-WEST

TO 1-ATS1-ELEV-EAST

1-PANEL-P-4

208.0 V

225.0 A

50.0 ft 1 pe r phase

300 kcmil

Copper

1-PANEL-AV

208.0 V

225.0 A

50.0 ft 1 pe r phase

300 kcmil

Copper

PD1-P-4

CUTLER-HAMMER

DA

400.0 A

PD1-AV

CUTLER-HAMMER

DA

400.0 A

SPARE

ECB

CBL1-PANEL-L13R

5.0 ft

1 per phase

4/0 AWG

Copper

1-PANEL-GC18

208.0 V

100.0 A

PD1-GC18

CUTLER-HAMMER

DG

100.0 A

1-ATS1-ELEV EAST-N

208.0 V

0.0 A

1-ATS1-ELEV-WEST-N

208.0 V

0.0 A

PD1-1PPC

WESTINGHOUSE

HLB

400.0 A

PD1-SERV.ROM 6614

WESTINGHOUSE

HKB

200.0 A

PD1-GC17

WESTINGHOUSE

HKB

200.0 A

PD1-1E-15H

CUTLER-HAMMER

HCA

225.0 A

PD1-1-L15

CUTLER-HAMMER

HCA

225.0 A

PD1-SPARE

HJD

350.0 A

PD1-ATS1-ELEV EAST-N

CUTLER-HAMMER

DA

400.0 A

PD1-ATS1-ELEV-WEST-N

CUTLER-HAMMER

DA

400.0 A

PD1-ATS1-E

MDP-N

WESTINGHOUSE

NB

700.0 A

WESTINGHOUSE

PD1-ATS1-CDP-N

CUTLER-HAMMER

LD

600.0 A

PD1-ATS-EDP25-N

WESTINGHOUSE

HKB

250.0 A

PD1-ATS1-LSA-N

WESTINGHOUSE

FDB

100.0 A

PD1-24-B(LIGHTS)

CUTLER-HAMMER

LSB-E

400.0 A

PD1-E3 LAB

CUTLER-HAMMER

KDB

400.0 A

PD1-L13A

WESTINGHOUSE

HKB

250.0 A

PD1-1P2

WESTINGHOUSE

HJD

250.0 A

PD1-RISER-1P

CUTLER-HAMMER

LSB-E

400.0 A

PD1-PANEL-H1

WESTINGHOUSE

FD

100.0 A

PD1-N1

CUTLER-HAMMER

HKD

300.0 A

PD1-L4-RISER

CUTLER-HAMMER

LSB-E

400.0 A

PD1-L3-RISER

WESTINGHOUSE

HLA

400.0 A

PD1-L2-RISER

WESTINGHOUSE

HLA

400.0 A

CBL1-L2-RISER-1

50.0 ft

1 per phase

500 kcmil

Copper

CBL1-L3-RISER-1

50.0 ft

1 per phase

500 kcmil

Copper

CBL1-L4-RISER-1

177.0 ft

1 per phase

500 kcmil

Copper

CBL1-N1

72.0 ft

1 per phase

350 kcmil

Copper

CBL1-H1

76.0 ft

1 per phase

2 AWG

Copper

CBL1-RISER-1P-1

50.0 ft

2 per phase

3/0 AWG

Copper

CBL1-1P2

338.0 ft

1 per phase

3/0 AWG

Copper

CBL1-L13A

88.0 ft

1 per phase

3/0 AWG

Copper

CBL1-E3 LAB

50.0 ft

1 per phase

500 kcmil

Copper

CBL1-24-B(LIGHTS)

50.0 ft

1 per phase

500 kcmil

Copper

CBL1-ATS1-LSA-N

50.0 ft

1 per phase

2 AWG

Copper

CBL1-ATS-EDP25-N

50.0 ft

1 per phase

300 kcmil

Copper

CBL1-ATS1-CDP-N

100.0 ft

1 per phase

8 AWG

Copper

CBL1-ATS1-EMDP-N

50.0 ft

2 per phase

350 kcmil

Copper

CBL1-ATS1-ELEV-WEST-N

50.0 ft 1 per phase 300 kcmil Copper

CBL1-ATS1-ELEV-EAST-N

50.0 ft 1 per phase

300 kcmil

Copper

1-PANEL-1-L15

208.0 V

225.0 A

CBL1-1-1-L15

270.0 ft

1 per phase

250 kcmil

Copper

1-PANEL-1E-15H

208.0 V

200.0 A

CBL1-1-1E-15H

258.0 ft

1 per phase

250 kcmil

Copper

1-PANEL-PHARMACY "A"

208.0 V

225.0 A

CBL1-1-PHARMACY

230.0 ft

1 per phase

2 AWG

Copper

PD1-PHARMACY

CUTLER-HAMMER

EB

100.0 A

1-PANEL- GC17

208.0 V

225.0 A

CBL1-GC-17

174.0 ft

1 per phase

2/0 AWG

Copper

PD1-GC17-MCB

GE

THQD

225.0 A

1-PANEL-SERV. ROM 6614

208.0 V

200.0 A

CBL1-1-SERV.ROM 6614

50.0 ft

1 per phase

2/0 AWG

Copper

CBL1-1PPC

291.0 ft

1 per phase

600 kcmil

Copper

1-MTR-0007

NumMotors 1

Total 7.5 hp

CBL1-MTR-0007

50.0 ft

1 per phase

6 AWG

Copper

PD1-MTR-0007

SIEMENS

HBL

70.0 A

1-MTR-0006

NumMotors 1

Total 15 hp

CBL1-MTR-0006

50.0 ft

1 per phase

2 AWG

Copper

PD1-MTR-0006

SIEMENS

HBL

100.0 A

1-MTR-0005

NumMotors 1

Total 7.5 hp

CBL1-MTR-0005

50.0 ft

1 per phase

6 AWG

Copper

PD1-MTR-0005

SIEMENS

HBL

70.0 A

PD-0062

SIEMENS

HBL

100.0 A

1-PANEL-1PPC

208.0 V

400.0 A

1-MTR-0004

NumMotors 1

Total 3 hp

CBL1-MTR-0004

50.0 ft

1 per phase

10 AWG

Copper

PD1-MTR-0004

SIEMENS

HBL

40.0 A

1-PANEL-E3 (SECT 2)

208.0 V

100.0 A

CBL-1-E3(SECT 2)

50.0 ft

1 per phase

4 AWG

Copper

PD1-E3(SECT 2)

CUTLER-HAMMER

EB

60.0 A

1-PANEL-E3 LAB

208.0 V

400.0 A

PD1-E3 LAB-MCB

CUTLER-HAMMER

LSB-E

400.0 A

1-PANEL-L13A

208.0 V

225.0 A

1-PANEL-1P1

208.0 V

225.0 A

CBL1-1P1

136.0 ft

1 per phase

3/0 AWG

Copper

1-PANEL-1P2

208.0 V

225.0 A

1-MTRI-0003

NumMotors 1

Total 10 hp

CBL1-MTRI-0003

50.0 ft

1 per phase

8 AWG

Copper

PD1-MTRI-0003

CUTLER-HAMMER

EB

30.0 A

CBL1-GC18-2

3.0 ft

1 per phase

2 AWG

Copper

1-MTRI-0002

NumMotors 1

Total 30 hp

CBL1-MTRI-0002

55.0 ft

1 per phase

1 AWG

Copper

PD1-MTRI-0002

SIEMENS

NGB

125.0 A

1-MTRI-0001

NumMotors 1

Total 30 hp

CBL1-MTRI-0001

52.0 ft

1 per phase

1 AWG

Copper

PD1-MTRI-0001

SIEMENS

NGB

125.0 A

1-PANEL-1P3

208.0 V

250.0 A

PD1-1P3

SIEMENS

HQJ2H

225.0 A

CBL1-1P3

50.0 ft

1 per phase

250 kcmil

Copper

CBL1-1P5-2

55.0 ft

1 per phase

250 kcmil

Copper

CBL1-GC18-1

45.0 ft

1 per phase

2 AWG

Copper

1-PANEL-1P5

208.0 V

225.0 A

1-PANEL-H1

208.0 V

100.0 A

1-PANEL-N1A

208.0 V

225.0 A

CBL1-N1A

5.0 ft

1 per phase

350 kcmil

Copper

1-PANEL-N1

208.0 V

400.0 A

PD1-L34-MCB

CUTLER-HAMMER

LSB-E

400.0 A

1-PANEL-L43

208.0 V

100.0 A

CBL1-L43

186.0 ft

1 per phase

8 AWG

Copper

PD1-L43

CUTLER-HAMMER

EB

30.0 A

1-PANEL-L32A

208.0 V

225.0 A

CBL1-L32A

155.0 ft

1 per phase

3/0 AWG

Copper

PD1-L32A

CUTLER-HAMMER

ED

225.0 A

1-PANEL-3LL1-

208.0 V

225.0 A

CBL-1-3LL1

88.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-L33

208.0 V

225.0 A

CBL1-L33

5.0 ft

1 per phase

500 kcmil

Copper

PANEL-L34

208.0 V

225.0 A

1-PANEL-L23

208.0 V

225.0 A

CBL1-PANEL-L23

88.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-1-L14)

208.0 V

225.0 A

CBL1-1-L14

134.0 ft

1 per phase

3/0 AWG

Copper

PD1-1-L14

CUTLER-HAMMER

ED

150.0 A

PANEL-L13R

208.0 V

400.0 A

1-PANEL-L13L

208.0 V

400.0 A

PD1-PANEL-L13L-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-PANEL-L13L

76.0 ft

1 per phase

4/0 AWG

Copper

CBL1-L3-RISER-2

50.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-L05

208.0 V

225.0 A

CBL1-L05

92.0 ft

1 per phase

3/0 AWG

Copper

PD1-L05

CUTLER-HAMMER

ED

150.0 A

1-PANEL-L03

208.0 V

225.0 A

PD1-PANEL-L03-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-L03

50.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-L22L

208.0 V

225.0 A

CBL1-L22L

5.0 ft

1 per phase

3/0 AWG

Copper

1-PANEL-L32R

208.0 V

225.0 A

CBL1-PANEL-L32R

5.0 ft

1 per phase

3/0 AWG

Copper

1-PANEL-L42

208.0 V

50.0 A

CBL-1-L42

266.0 ft

1 per phase

8 AWG

Copper

PD1-L42

CUTLER-HAMMER

EB

50.0 A

PD1-L32L-MCB

CUTLER-HAMMER

ED

200.0 A

1-PANEL-L32L

208.0 V

225.0 A

CBL1-PANEL-L32L

98.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-L22R

208.0 V

225.0 A

PD1-L22R-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-L22R

88.0 ft

1 per phase

3/0 AWG

Copper

CBL1-L2-RISER-2

50.0 ft

1 per phase

500 kcmil

Copper

CBL1-PANEL-L02R

44.0 ft

1 per phase

1 AWG

Copper

1-PANEL-L02R

208.0 V

225.0 A

1-PANEL-L02L

208.0 V

225.0 A

PD1-L02L-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-L02L

48.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-L31B

208.0 V

225.0 A

CBL1-L31B

8.0 ft

1 per phase

250 kcmil

Copper

1-PANEL-L31A

208.0 V

225.0 A

PD1-L31A-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-L31A

196.0 ft

1 per phase

500 kcmil

Copper

CBL1-L21R

5.0 ft

1 per phase

3/0 AWG

Copper

CBL1-L1-RISER-3

50.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-L21L

208.0 V

225.0 A

PD1-L21L-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-L21L

175.0 ft

1 per phase

500 kcmil

Copper

CBL1-L1-RISER-2

50.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-1-L11R1

208.0 V

50.0 A

PD1-1-L11R1-MCB

CUTLER-HAMMER

EB

50.0 A

CBL1-1-L11R1

219.0 ft

1 per phase

8 AWG

Copper

1-PANEL-1-L11R

208.0 V

225.0 A

PD1-1-L11R-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-1-L11R

214.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-L01A

208.0 V

50.0 A

PD1-PANEL-L01A-MCBCBL1-PANEL-L01-MCB

250.0 ft

1 per phase

8 AWG

Copper

1-PANEL-L01

208.0 V

225.0 A

PD1-PANEL-L01-MCB

GE

THQDL

200.0 A

CBL1-PANEL-L01

245.0 ft

1 per phase

500 kcmil

Copper

CBL1-L1-RISER-1

50.0 ft

1 per phase

500 kcmil

Copper

PD1-L1-RISER

WESTINGHOUSE

HLA

400.0 A

1-PANEL-X1

480.0 V

400.0 A

PD1-X1-MCB

SQUARE D

LCL

350.0 A

CBL1-X1

230.0 ft

1 per phase

500 kcmil

Copper

1-XF2-PANEL-X1

225 kVA

Pri 208 V

Sec 480 V

5.1810 %

CBL1-XF2-0034

35.0 ft

2 per phase

500 kcmil

Copper

PD1-XF2-0034

CUTLER-HAMMER

MDL

800.0 A

1-SWBD-MSB-01

208.0 V

2500.0 A

CBL1-MSB-01

28.0 ft

6 per phase

400 kcmil

Copper

1A-PANEL-X1

208.0 V

350.0 A

CBL1A-X1

265.0 ft

2 per phase

350 kcmil

Copper

PD1A-X1

100.0 A

CBL1A-PD1A-X1

10.0 ft

2 per phase

350 kcmil

Copper

1A-XF2-BLDG 1A

167 kVA

Pri 4160 V

Sec 208 V

7.0000 %

PD1A-XF2-BDLG 1A

15.0 A

CBL1A-XF2-1A

125.0 ft

1 per phase

4/0 AWG

Copper

CBL1-1P5-1

145.0 ft

1 per phase

250 kcmil

Copper

CBL-1-L2-RISER-3

50.0 ft

1 per phase

500 kcmil

Copper

1-PANEL-1-L12R

208.0 V

200.0 A

CBL1-1-L12R

5.0 ft

1 per phase

3/0 AWG

Copper

1-PANEL-1-L12L

208.0 V

225.0 A

PD1-1-L12L-MCB

CUTLER-HAMMER

ED

200.0 A

CBL1-1-L12L

214.0 ft

1 per phase

500 kcmil

Copper

1-24-B(LIGHTS)

PD1-A-MCB

100.0 A

TO 1-ATS1-LSA TO 1-ATS1-EDP25 TO 1-ATS1-EMDP TO 1-ATS1-CDP

1-PANEL-L21R

208.0 V

225.0 A

CUTLER-HAMMER

EB

50.0 A

1-XF2-BLDG-1-MSB

167 kVA

Pri 4160 V

Sec 208 V

7.0000 %

PD1A-XF2-BDLG 1A

FUSE-SG1-1A-4

200.0 AF/

15.0 AT

FUSE-SG1-1A-3

200.0 AF/

200.0 AT

CBL1-XF2-BLDG1-MSB

80.0 ft

1 per phase

4/0 AWG

Copper

KEY NOTES:

WORK TO BE PERFORMED IN THIS PANEL.

1. FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS SEE SHEET

01-EG-001 AND 01-EG-002.

GENERAL NOTES:

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :3

P

M

01-EG-601

ONE-LINE DIAGRAM & FEEDER

SCHEDULE

29 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

1 1

EXPANSION FITTING

WITH BONDING JUMPER

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

SEISMIC OR EXPANSION JOINT.

FIELD VERIFY ACTUAL

CONDITIONS & LOCATIONS.

STRUCTURAL MEMBER

(BEAM, JOIST, SECT.),

TYP.

STEEL

EXPANSION

ANCHOR

CONDUIT

TRAPEZE

PER DETAIL 3

ON THIS

SHEET, TYP.

CONDUIT,

TYP.

SPRING NUT

BEAM

CLAMP, TYP.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

GENERAL NOTES:

1. INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL 1 ON THIS SHEET.

2. INSTALLATION IS REQUIRED FOR CONDUIT 3" OR LARGER.

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND PERIMETER.

(3'-0") MAX

HEAD

INSULATING

BUSHING

PROVIDE (5") OF SLACK AT MIDPOINT

BETWEEN TWO END OF FLEXIBLE

GALVANIZED STEEL CONDUIT.

PROVIDE GREEN INSULATED COPPER

EQUIPMENT GROUNDING CONDUCTOR

WITH FLEXIBLE CONDUIT.

FLOOR OR ROOF STRUCTURE. FIELD

VERIFY ACTUAL CONDITIONS, TYP.

SEISMIC OR EXPANSION JOINT.

FIELD VERIFY ACTUAL

CONDITIONS & LOCATIONS.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

STEEL

EXPANSION

ANCHOR

CONDUIT

TRAPEZE

PER DETAIL 3

ON THIS

SHEET, TYP.

CONDUIT,

TYP.

(3' - 0") MAX

SPRING NUT

BEAM

CLAMP, TYP.

GENERAL NOTE:

DETAIL IS APPLICABLE

ONLY FOR CONDUIT

SMALLER THAN (3").

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND PERIMETER.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

(3/8") MIN GALVANIZED

THREADED ROD, TYP.

LOCKING SQUARE

WASHER & LOCKNUT

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

WASHER & LOCKNUT

GENERAL NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL

LONGER THAN (36") SHALL BE INSTALLED WITH CENTER

SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION SECTION 26 05 33, RACEWAY

AND BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT

CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO

SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT

REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.

REFER TO PLANS

FOR QUANTITY &

SIZE OF CONDUITS

CONDUIT CLAMP.

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

CONDUIT, TYP

FIRESTOP SEALANT

PER SPECIFICATION

SECTION 07 84 00,

FIRE STOPPING

FLOOR SLAB, TYP.

JUNCTION BOX (SIZE AS REQUIRED)

SPRING NUT, TYP

(3/8") MAX

CONDUIT FITTING

MINERAL WOOL (FIRMLY PACKED)

INTEGRAL

GALVANIZED LIPPED

STEEL MOUNTING

CHANNEL, TYP.

STEEL EXPANSION

ANCHOR, TYP

NTS

CONDUIT EXPANSION JOINT CROSSING DETAIL - EXPANSION FITTING

NTS

CONDUIT EXPANSION JOINT CROSSING DETAIL - FLEXIBLE CONDUIT

NTS

CONDUIT TRAPEZE MOUNTING DETAIL

NTS

FLOOR SLAB PENETRATION DETAIL

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :2

P

M

01-EG-501

ELECTRICAL DETAILS

30 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

Revision 1 Date 1

DOOR FRAME

PREP BY

OTHERS

RECESSED DOOR CONTACT

(SEE DETAIL 1)

3/4" CONDUIT TYPE "C" CABLE

DOOR CONTACT

J-BOX

ENTRY CARD READER

MOUNTED ON UNSECURED

SIDE 40" AFF TO CENTER

3/4" CONDUIT TYPE "J" CABLE

CARD READER

3/4" CONDUIT TYPE "B"

CABLE LOCK POWER

3/4" CONDUIT TYPE

"F" CABLE IR

POWER, REX SIGNAL

ELECTRIC STRIKE

REQUEST TO EXIT PIR

MOUNTED ON SECURE

SIDE OF DOOR

HOMERUN TO DGP IN

SECURITY EQUIPMENT CLOSET

(TYPICAL) BANANA CABLE

CEILING LINE

(1'-6")

NOTES:

1. INSTALL READER MODULE CAN BE SURFACE MOUNTED AT DOOR LOCATION, ABOVE ACCESSIBLE

CEILING ON SECURE SIDE OF DOOR, AS INDICATED ON THE PLANS.

2. STUB CONDUIT INTO HEAD DOOR FRAME FOR DOOR POSITION SWITCH.

3. STUB CONDUIT DOWN DOOR FRAME AND CONNECT TO ELECTRIC STRIKE.

4. STUB CONDUIT INTO CENTERLINE OF DOOR FRAME FOR REQUEST-TO-EXIT MOTION SENSOR.

5. PROVIDE 4" x 4" x 2 1/8" DEEP BOX WITH SINGLE GANG DEVICE RING FLUSH MOUNTED FOR CARD

READER.

DOOR FRAME

PREP BY

OTHERS

RECESSED DOOR

CONTACT (SEE DETAIL 1)

3/4" CONDUIT TYPE "C"

CABLE DOOR CONTACT

J-BOX

ENTRY CARD READER

MOUNTED ON

UNSECURED SIDE 40"

AFF TO CENTER

3/4" CONDUIT TYPE "J"

CABLE CARD READER

3/4" CONDUIT TYPE "B"

CABLE LOCK POWER

ELECTRIC STRIKE

HOMERUN TO DGP IN

SECURITY EQUIPMENT

CLOSET (TYPICAL)

BANANA CABLE

CEILING LINE

NOTES:

1. INSTALL READER MODULE CAN BE SURFACE MOUNTED AT DOOR LOCATION, ABOVE ACCESSIBLE

CEILING ON SECURE SIDE OF DOOR, AS INDICATED ON THE PLANS.

2. STUB CONDUIT INTO HEAD DOOR FRAME FOR DOOR POSITION SWITCH.

3. STUB CONDUIT DOWN DOOR FRAME AND CONNECT TO ELECTRIC STRIKE.

4. STUB CONDUIT INTO CENTERLINE OF DOOR FRAME FOR REQUEST-TO-EXIT MOTION SENSOR.

5. PROVIDE 4" x 4" x 2 1/8" DEEP BOX WITH SINGLE GANG DEVICE RING FLUSH MOUNTED FOR CARD

READER.

ENTRY CARD

READER MOUNTED

ON SECURED SIDE

40" AFF TO CENTER

DOOR FRAME

PREP BY OTHERS

RECESSED DOOR

CONTACT (SEE DETAIL 1)

TIME DELAY

ELECTROMAGNETIC

LOCK

J-BOX

ENTRY CARD

READER MOUNTED

ON UNSECURED SIDE

40" AFF TO CENTER

3/4" CONDUIT

TYPE "J" CABLE

CARD READER

PUSH BAR (BY OTHERS)

HOMERUN TO DGP IN SECURITY EQUIPMENT

CLOSET (TYPICAL) BANANA CABLE

CEILING LINE

NOTES:

1. INSTALL READER MODULE CAN BE SURFACE MOUNTED AT DOOR LOCATION, ABOVE ACCESSIBLE

CEILING ON SECURE SIDE OF DOOR, AS INDICATED ON THE PLANS.

2. STUB CONDUIT INTO HEAD DOOR FRAME FOR DOOR POSITION SWITCH. WIRE DOOR POSITION

SWITCHES IN SERIES.

3. STUB CONDUIT DOWN DOOR FRAME AND CONNECT TO ELECTRIC STRIKE.

4. STUB CONDUIT INTO CENTERLINE OF DOOR FRAME FOR REQUEST-TO-EXIT MOTION SENSOR.

5. PROVIDE 4" x 4" x 2 1/8" DEEP BOX WITH SINGLE GANG DEVICE RING FLUSH MOUNTED FOR CARD

READER.

BOTH SIDES

1' - 6" (TYP.)

NTS

TYPICAL SINGLE DOOR DETAIL WITH DOOR POSITION SWITCH, REQUEST TO EXIT CARD

READER & ELECTRIC STRIKE

NTS

TYPICAL SINGLE DOOR DETAIL WITH DOOR POSITION SWITCH, TWO CARD READERS &

ELECTRIC STRIKE

NTS

TYPICAL DOUBLE DOOR DETAIL WITH TIME-DELAY MAGNETIC LOCK, TWO CARD READERS &

DOOR POSITION SWITCH

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :2

P

M

01-EG-502

ELECTRICAL DETAILS

31 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

REBAR

GROUNDING

ELECTRODE

CONDUCTOR

GROUNDING ELECTRODES

GROUNDING CONDUCTOR

INTERCONNECTING GROUNDING

ELECTRODES BELOW GRADE

EFFECTIVELY GROUNDED

BUILDING STEEL

EQUIPMENT

PANEL

ANTENNA

DISCHARGE UNIT

TGB

ANTENNA

HEADED

EQUIPMENT

ROOM

ELECTRICAL SERVICE

EQUIPMENT OR METER

CABINET

MAIN ELECTRICAL

DISTRIBUTION PANEL

ELECTRICAL ENTRANCE

INTERSYSTEM BONDING

TERMINATIONS FOR CONNECTING

INTERSYSTEM BONDING CONDUCTORS

TMGB

TELECOMMUNICATIONS ROOM

TGB

GROUND

PRIMARY

CABLE

PROTECTORS

DEMARC

DEMARC ROOM

(TELECOMMUNICATIONS

ENTRANCE FACILITY)

TELECOMMUNICATIONS ROOM

ROOF

CONDUIT SLEEVES (TYP.)

TELECOMMUNICATIONS

BONDING BACKBONE

BONDING CONDUCTOR

TELECOMMUNICATIONS

TELECOMMUNICATIONS MAIN

GROUNDING BUSSBAR

PRIMARY

PROTECTION

GROUNDING

CONDUCTOR

RAISED FLOOR

ANTENNA MAST (TYP.)

TELECOMMUNICATIONS

BONDING BACKBONE

TELECOMMUNICATIONS BONDING BACKBONE

GROUNDING EQUALIZER

TGB

AC

ELECTRICAL

PANEL

TGB

TGB

TGB

CONDUIT

SLEEVES

(TYP.)

TGB

BACKBONE UPPER LEVEL

CABLE TRAY (TYP.)

TELECOMMUNICATIONS ROOM

TELECOMMUNICATIONS ROOM

TELECOMMUNICATIONS ROOM

ELECTROSTATIC DISCHARGE

FLOORING (TYP.)

TELECOMMUNICATIONS ROOM

HORIZONTAL LOWER

LEVEL CABLE TRAY (TYP.)

CABINETS

OR RACKS

RACKS OR

CABINETS

RACKS OR

CABINETS

RACKS OR

CABINETS

RACKS OR

CABINETS

AC

ELECTRICAL

PANEL

AC

ELECTRICAL

PANEL

AC

ELECTRICAL

PANEL

AC

ELECTRICAL

PANEL

AC

ELECTRICAL

PANEL

NTS

TELECOMMUNICATIONS GROUNDING AND BONDING (FOR REFERENCE)

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :2

P

M

01-EG-503

ELECTRICAL DETAILS

32 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

PROVIDE CONDUIT SUPPORTS

IN ACCORDANCE WITH NEC

SPACING REQUIREMENTS FOR

TYPE OF RACEWAY REQUIRED.

AS REQUIRED FOR

TYPE

OF CONSTRUCTION.

TYPICAL

OUTLET

BOXBAR STRAPS

TYPICAL

OUTLET

BOX

BAR STRAPS

BAR STRAPS

TYPICAL

WALL

OUTLETS

BRACED TRAPEZE

STRUT

CABLE TRAY BOLTED TO TRAPEZE

THREADED ROD

ANGLE OR STRUT BRACING

(ALTERNATE: CABLE BRACING EACHSIDE)

SEE FIGURE 6.4.1.5-6 ROD STIFFENER

AS REQUIRED

THREADED ROD

STIFFENER

(2 PER TRAPEZE)

LONGITUDINAL

BRACE

STRUT OR ANGLE

OPTIONAL TWO PIECE

CONDUIT CLAMP

DOUBLE

STRUT

STRUT

CLAMP

ONE TRANSVERSE

BRACE ON EITHER SIDE

TRANSVERSE

BRACE

SEISMIC

BRACE

BOLT WITH

SPRING NUT

CONCRETE ANCHOR

LONGITUDINAL

BRACE

OPTIMUM ANGEL

45° ± 15°

CONNECTION TO STRUCTURAL

SUPPORTING MEMBER TO BE

SAME FOR VERT., DIAG. &

LONG.

CONCRETE ANCHOR

FOR ALTERNATE CONNECTIONS

AS REQUIRED

THREADED ROD

STIFFENER

THREADED ROD

LONGITUDINAL

BRACE

BOLT WITH

SPRING NUT

SEISMIC

BRACKET

CONDUIT CLAMP OR

RISER CLAMP

OPTIMUM ANGEL

45° ± 15°

TYPICAL

VOICE/DAT

A

OUTLET

TYPICAL

DATA

OUTLET

LAY-IN CEILING GRID SYSTEM

CABLE TRAY

(2) 1"

CONDUITS

TO

CABLE TRAY

(2) 1"

CONDUITS

TO

CABLE TRAY

(1) 1"

CONDUITS

TO

CABLE TRAY

TYPICAL VOICE OUTLET

DATA

ROOM

RACK

WIRE HANGER AT EACH

CORNER OF FIXTURE (TYP.)

INDEPENDENT OF CEILING

SUPPORT SYSTEM. FIXTURE CLAMP - PROVIDE

ONE PER SIDE OF FIXTURE

RECESSED TROFFER

SPEED LOCK

CLEVIS HANGER

"J" HANGER

STANDARD DUTY

CLEVIS HANGER

CONCRETE ANCHOR FOR ALTERNATE CONNECTIONS

AS REQUIRED

THREADED ROD

STIFFENER

THREADED ROD

OPTIMUM ANGEL

45° ± 15°TRANSVERSE

BRACE

BOLT WITH

SPRING NUT

SEISMIC

BRACKET

1/4" LARGER THAT

ADD PIPE SLEEVE

THAT HAS A INSIDE DIAMETER

OUTSIDE DIAMETER OF BOLT

FREE-STANDING

45° TO 60°

CONTROL PANEL

BOLTED TO ANGLE

SUPPORT FRAME

WELD SUPPORTS

TO VERTICAL LEG

ANGLE BRACED

ANCHOR TO

CONCRETE

WELD BRACE

TO BASE PLATE

WELD ANGLE

TO BASE PLATE

CONCRETE ANCHORS

(2 PER LEG)

(2 PER SUPPORT)

ANGLE

FRAME OR

STRUT

45° TO 60°

ANGLE MAY BE REQUIRED

FOR BRACING DEPENDING ON

PANEL HEIGHT AND WEIGHT

WALL-MOUNTED

STRUT

EXPANSION ANCHOR TO CONCRETE OR MASONRY WALLS;

SHEET METAL SCREW OR TOGGLE BOLT TO METAL STUD,

LAG SCREW TO WOOD STUD (3 MINIMUM PER STRUT)

ELECTRICAL

PANEL

(TURN

POWER OFF)

ALTERNATE: ANCHOR

DIRECTLY

THROUGH BACK TO CONCRETE

OR MASONRY WALL

BOLT THROUGH CABINET

TO STRUT, EACH

CORNER

VERIFY THAT WALL IS

CAPABLE RESISTING

IMPOSED

LOADS

P la n N o rt h

T ru e N o rt h

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID…