This federal contract opportunity notice seeks proposals for a project to implement sterile processing service ventilation requirements at a Veterans Health Administration facility. The project scope includes demolishing existing structures, installing new ventilation systems, and performing related construction work. The cost is estimated between $500,000 to $1,000,000, and the work must be completed within 365 calendar days of the notice to proceed. The North American Industry Classification code is 238220 with a small business size standard of $16.5 million. As a total small business set-aside, at least 25% of the general construction labor must be performed by a service-disabled veteran-owned small business. Proposals are due by June 2020 and award will be made using the best value tradeoff source selection process.

View the file

Other files for this federal contract opportunity

Show all 18

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4 160 VO LTS

D UST CO LLECTO R

LIQ

UEFIED PETRO

LEUM

G

AS

FLAM

M

ABLE G

AS 2

TRASH CO M PACTO R

P S

ILVER

B

UILDING

1 23

B UILDING 23

VA PO LICE

E LECTR IC AC CESS

TRANSFO RM ER

TRANSFO RM ER

TRANSFO RM ER

H VAC UNIT

E LECTRI C PANEL

H VAC UNIT

S&C PAD M O UNTED G EAR

CATALO G # 55152-C3DG IG 2P1V M O DEL# PM H-9E E13299 SG -52

13278

1CC

56G

3T 183

1CC

321G

1CC

5 4

4T

60G

51T

60T

52SG

52G

53G

53T

1CC

104T

102T

101T

1CC 55G

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :0

A

M

01-GI-001

COVER SHEET

01 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

MVP SB03/26/2020

U.S. DEPARTMENT OF VETERANS AFFAIRS

VA ST. LOUIS HEALTHCARE SYSTEM

VA PROJECT NUMBER: 657-19-117JB

##-XX-###

DISCIPLINE DESIGNATORS EXAMPLES

GI = GENERAL INFORMATION

GC = GENERAL CONTRACT

CS = CIVIL SITE

AD = ARCHITECTURAL DEMOLITION

AS = ARCHITECTURAL SITE

AE = ARCHITECTURAL ELEMENTS

FLOOR PLANS, ELEVATIONS, DETAILS

AI = ARCHITECTURAL INTERIORS

AG = ARCHITECTURAL GRAPHICS

AF = ARCHITECTURAL FINISHES

AC = ARCHITECTURAL CEILING PLAN

AW = ARCHITECTURAL WAYFINDING

AP = ARCHITECTURAL SPACE PLANNING

FLOOR PLANS & SCHEDULES

AL = ARCHITECTURAL LIFE SAFETY

DRAWINGS

SG = STRUCTURAL GENERAL

SF = STRUCTURAL FRAMING

MG = MECHANICAL GENERAL

MP = MECHANICAL PIPING

MH = MECHANICAL HVAC

PG = PLUMBING MEDICAL GAS

PL = PLUMBING FIXTURES

EG = ELECTRICAL GENERAL

EL = ELECTRICAL LIGHTING

DRAWING INDEX LEGEND

SHEET TYPE DESIGNATORS

0 = GENERAL

1 = PLANS

2 = ELEVATIONS

3 = SECTIONS

4 = LARGE-SCALE VIEWS

5 = DETAILS

6 = SCHEDULES & DIAGRAMS

7 = USER DEFINED

8 = USER DEFINED

9 = 3D REPRESENTATIONS

BUILDING NUMBER

FLOOR NUMBER ON PLAN SHEETS

SHEET NUMBER

JEFFERSON BARRACKS

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION

REQUIREMENTS

OVERALL CAMPUS SITE PLAN, BUILDING NUMBER, AND PROJECT LOCATOR

Plan North

True North

SHEET LIST

Sheet Number Sheet Name

01-GI-001 COVER SHEET

01-GI-002 GENERAL INFORMATION AND SYMBOLS

01-AD-100 ARCHITECTURAL DEMOLITION PLAN - FLOOR 00

01-AE-100 ARCHITECTURAL FLOOR PLAN - FLOOR 00

01-AE-501 ARCHITECTURAL WALL TYPES AND DETAILS

01-MG-001 MECHANICAL ABBREVIATIONS AND GENERAL NOTES

01-MG-002 MECHANICAL SYMBOLS

01-MG-501 MECHANICAL DETAILS

01-MG-502 MECHANICAL DETAILS

01-MG-503 MECHANICAL DETAILS

01-MG-504 MECHANICAL DETAILS

01-MG-505 MECHANICAL DETAILS

01-MG-506 MECHANICAL DETAILS

01-MG-507 MECHANICAL DETAILS

01-MG-601 MECHANICAL SCHEDULES

01-MG-701 MECHANICAL CONTROLS

01-MG-702 MECHANICAL CONTROLS

01-MD-100 MECHANICAL DEMO HVAC PLAN - FLOOR 00

01-MD-101 MECHANICAL PIPING DEMO PLAN - FLOOR 00

01-MH-100 MECHANICAL HVAC PLAN - FLOOR 00

01-MP-100 MECHANICAL PIPING PLAN - FLOOR 00

01-MP-300 MECHANICAL ROOM SECTIONS

01-MP-301 MECHANICAL ROOM SECTIONS

01-EG-001 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES

01-EG-002 ELECTRICAL SYMBOLS

01-EP-100 ELECTRICAL POWER PLAN - FLOOR 00

01-EI-100 ELECTRICAL INSTRUMENTATION PLAN - FLOOR 00

01-ET-100 ELECTRICAL TELECOMMUNICATIONS PLAN - FLOOR 00

01-EG-601 ONE-LINE DIAGRAM & FEEDER SCHEDULE

01-EG-501 ELECTRICAL DETAILS

01-EG-502 ELECTRICAL DETAILS

01-EG-503 ELECTRICAL DETAILS

01-EG-504 ELECTRICAL SEISMIC DETAILS

01-EG-505 MECHANICAL EQUIPMENT SCHEDULE

01-EG-506 PANEL SCHEDULES

Valhalla Engineer Image th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :0

A

M

01-GI-002

GENERAL INFORMATION AND SYMBOLS

02 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

MVP SB03/26/2020

GENERAL NOTESABBREVIATIONS SYMBOLS LEGEND

ACCESSIBILITY GUIDELINES

CODE DATA

SECTION, DETAIL, OR ELEVATION TITLE EXAMPLE

ELEVATION CALLOUT EXAMPLE

DETAIL CALLOUT EXAMPLE

SECTION CALLOUT EXAMPLE

SECTION, DETAIL, OR ELEVATION

SYMBOL IDENTIFIERS

DETAIL NAME

LETTER OR NUMBER DESIGNATOR

DRAWING SEQUENCE

NUMBER INDICATES WHERE

TITLE IS LOCATED

ONE OR TWO CHARACTER

DISCIPLINE DESIGNATOR

(MAY NOT BE PRESENT IF

CALLOUT AND TITLE ARE ON

DRAWINGS WITHIN THE SAME

DISCIPLINE)

A

A101

AE101

AE101

AE101

DOOR NUMBER TAG

WALL TYPE TAG

WINDOW TYPE TAG

CENTER LINE

WALL FINISH TAG

COLUMN BUBBLE

ROOM TAG

WALL COLOR

BASE TYPE /

COLOR

MATCH LINE

DETAIL

NUMBER

ON SHEET

SHEET NUMBER

DETAIL

NUMBER

ON SHEET

SHEET NUMBER

NEW LINE TYPE.

EXISTING LINE TYPE.

DEMO LINE TYPE.

DEMO HATCH TYPE.

FIRE RESISTIVE RATED WALL, 1 HOUR

FIRE RESISTIVE RATED WALL, 2 HOUR

FIRE RESISTIVE RATED WALL, 3 HOUR

FIRE RESISTIVE RATED WALL, 4 HOUR

S

S

S

S

FIRE RATED, SMOKE BARRIER WALL, 1 HOUR

FIRE RATED, SMOKE BARRIER WALL, 1 HOUR

FIRE RATED, SMOKE BARRIER WALL, 1 HOUR

FIRE RATED, SMOKE BARRIER WALL, 1 HOUR

A

ROOM NAME

P2

RB3

W-3

View Name 1/8" = 1'-0"1

MIRROR

CLEAR

FLOOR

SPACE

MIRROR

TOILET PAPER

(H) ACCESSIBLE TOILET WITH GRAB BAR (I) ACCESSIBLE TOILET WITH GRAB BAR

PULL SIDE PUSH SIDE

(D) FRONT APPROACHES - SWING DOORS

4'-0" MIN. IF

DOOR HAS

BOTH LATCH

AND CLOSER

* IF DOOR HAS BOTH A

CLOSER AND LATCH

IF WIDTH IS 5', CLR. LENGTH IS 3'-0" MIN.

IF WIDTH IS 4'-6", CLR. LENGTH IS 3'-6" MIN.

4'-0" MAX. IF DOOR

HAS BOTH A CLOSER

AND LATCH.

(G) HINGE-SIDE APPROACHES - SWING DOORS

4'-6" MIN. IF DOOR HAS CLOSER

(K) LATCH-SIDE APPROACHES - SWING DOORS

4'-0" MIN. IF

DOOR HAS

BOTH A LATCH

AND CLOSER

(A) CLEAR FLOOR SPACE, PARALLEL APPROACH (B) HIGH AND LOW SIDE REACH

(C) MAXIMUM SIDE REACH

OVER OBSTRUCTIONS

(E) LAVATORY CLEARANCES (F) DRINKING FOUNTAIN SPOUT HEIGHT

AND KNEE CLEARANCES

(J) ROLL-IN SHOWER WITH FOLDING SEAT

DRAIN

NAPKIN DISPOSAL

2'-0" 2'-2"

M A

X

0'-10"

MAX.

2'-6"

M A

X

M

IN

M

IN

M

IN

.3

M A

X

1'-5"

MIN.

M

IN

4'-0"

MIN.

19"

MAX.

0'-6"

MAX.

0'-8"

MIN.

1'-5"

MIN.

M A

X

M

IN

M

IN

0'-6"

MAX.

0'-8"

MIN.

T O

1'-0"

MAX.

T O

3'-6"

MIN.

3'-0" 1'-6"

TYP.

1'-0"1'-0"

3'-0"

MIN.

T O

T O

1'-6" MIN.

2'-0" PREFERRED.

M

IN

M

IN

1'-0"

MIN.

W

ID

T H

CLR. LENGTH

M

IN

4'-6"

MIN.

M

IN

2'-0"

MIN.

2'-0"

MIN.

M

IN

2'-0"

MIN.

3'-0"

MIN.

& AND

@ AT

AB ANCHOR BOLT

ACFL ACCESS FLOOR

ACT ACOUSTIC CEILING TILE

AD AREA DRAIN

ADJ ADJUSTABLE

ADJT ADJACENT

ADMIN ADMINISTRATION

AFF ABOVE FINISH FLOOR

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

AP ACCESS PANEL

APROX APPROXIMATE

ARCH ARCHITECTURAL

AT ACOUSTICAL CEILING TILE

AUTO AUTOMATIC

AWT ACOUSTICAL WALL TREATMENT

BD BOARD

BFE BOTTOM FOOTING ELEVATION

BG BUMPER GUARD

BKT BRACKET

BLDG BUILDING

BM BEAM

BOT BOTTOM

BP BRICK PAVING

BR BRICK

BRG BEARING

BSMT BASEMENT

C CHANNEL

CAB CABINET

CANTL CANTILEVER

CAP CAPACITY

CAT CATEGORY

CIP CAST-IN-PLACE

CCTV CLOSED CIRCUIT TELEVISION

CG COILING GRILLE

CGD CORNER GUARD

CH COAT HOOK

CJT CONTROL JOINT

CL CENTER LINE

CLS CLASS

CLG CEILING

CLR CLEAR

CM CONSTRUCTION MANAGER

CMU CONCRETE MASONRY UNIT

CO CASED OPENING

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CONN CONNECT/-ED/-ION

CONST CONSTRUCTION

CONT CONTINUE/CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

CORR CORRIDOR

CP CARPET

CPT CARPET MODULE TILE

CR-1 CHAIR RAIL

CR-2 CRASH RAIL

CT CERAMIC TILE

CTR CENTER

CW CURTAIN WALL

CWR COLD WATER

CYL CYLINDER

D DEPTH OR DEEP

DEMO DEMOLITION

DEPR DEPRESSION

DBL DOUBLE

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIFF DIFFUSER

DIM DIMENSION

DISP DISPENSER

DIST DISTRIBUTION

DIV DIVISION

DN DOWN

DP DATA PROCESSING

DR DOOR

DS DOWNSPOUT

DWG DRAWING

ELC ELECTRICAL CABINET

EC EPOXY COATING

EF EXHAUST FAN

EFTR EXISTING FINISH TO REMAIN

EJT EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

EMERG EMERGENCY

EO ELECTRICAL OUTLET

EPDM ETHYLENE PROPYLENE DIENE

MONOMER

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXH EXHAUST HOOD

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

EXT-P EXTERIOR PAINT

EXT-ST EXTERIOR STAIN

FA FIRE ALARM

FAP FIRE ALARM PANEL

FB FIRE BLANKET

FD FLOOR DRAIN

FDN FOUNDATION

FDV FIRE DEPARTMENT VALVE

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FGS FOAM GASKET SEAL

FH FIRE HOSE

FHV FIRE HOSE VALVE

FIN FINISH

FIXT FIXTURE

FLR FLOOR

FL FLOW LINE

FP FIRE PROOFING

H HIGH

HB HOSE BIB

HD HAND DRYER

HDCP HANDICAP

HDR HEADER

HDW HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HPT HIGH POINT

HR HANDRAIL

HT HEIGHT

HTR HEATER

HVAC HEATING, VENTILATING,

AIR CONDITIONING

HW HOT WATER

HWD HARDWOOD

IB INTEGRATED BASE

ID INSIDE DIAMETER

IN INCH

INSUL INSULATION

INT INTERIOR

ISO ISOLATION

JAN JANITOR

JB JUNCTION BOX

JST JOIST

JT JOINT

KO KNOCK OUT

L LAVATORY

LB POUND

LCD LINEAR CEILING DIFFUSER

LF LINE FIGURED

LIN LINEAR

LKR LOCKER

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LMC LINEAR METAL CEILING

LOC LOCATION OR LOCATE

LPT LOW POINT

LS LAWN SPRINKLING

LT LIGHT

LTG LIGHTING

LVR LOUVER

LWC LINEAR WOOD CEILING

MAT MATERIAL

MAX MAXIMUM

MBD MARKER BOARD

MC MEDICINE CABINET

MCU MODULAR COOLING UNIT

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MRF MANUFACTURER

MH MANHOLE

MIL MILLIMETER

MN MINIMUM

MR MIRROR

MISC MISCELLANEOUS

MO MASONRY OPENING

MONO MONOLITHIC

MPU MULTI- PURPOSE UNIT

MTD MOUNTED

MTL METAL

MTR MOTOR

MULL MULLION

PNL PANEL

PNT PAINT

PRELIM PRELIMINARY

PRES PLASTIC RESIN

PRESS PRESSURE

PRIM PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PTC PAPER TOWEL CABINET

PTR PRINTER

PVC POLYVINYL CHLORIDE

R RADIUS

RI RISER

RA RETURN AIR

RB RESILIENT BASE/RUBBER BASE

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REFR REFRIGERATOR

REG REGISTER

REIN REINFORCE/-ED/-ING

REM REMOVE

REQD REQUIRED

RET RETAINING

REVS REVERSE

REV REVISE

RF RESILIENT FLOOR

RFI REQUEST FOR INFORMATION

RH ROOF HATCH

RM ROOM

RO ROUGH OPENING

RS ROUGH SLAB

RSF RESILIENT SHEET FLOOR

RWC RAIN WATER CONDUCTOR

SI SINK

SCHED SCHEDULE

SD SHOWER DRAIN

SDR SMOKE DAMPER

SDISP SOAP DISPENSER

STF STORE FRONT

SF SQUARE FOOT

SH SHOWER

SHT SHEET

SHTG SHEATHING

SIM SIMILAR

SM SURFACE MOUNTED

SNC SANITARY NAPKIN CABINET

SND SANITARY NAPKIN DISPOSER

SP STANDPIPE

SPEC SPECIFICATIONS

SPR SINGLE PLY ROOF

SQ SQUARE

SQ YD SQUARE YARD

SR SERVICE RECEPTOR

SS SERVICE SINK

SST STAINLESS STEEL

STR STREET

ST STONE TILE

STC SOUND TRANSMISSION

STD STANDARD

STL STEEL

STOR STORAGE

STRUC STRUCTURAL

T TOP

TAN TANGENT

TCAB TOWEL CABINET

TDR TRENCH DRAIN

TEL TELEPHONE

TEMP TEMPERATURE

TER TERRAZZO

TG TONGUE & GROVE

THRES THRESHOLD

TOIL TOILET

TPH TOILET PAPER HOLDER

TR TREAD

TRANSF TRANSFORMER

TS TUBE SECTION

TV TELEVISION

TYP TYPICAL

U URINAL

UCT UNDERCUT

UCR UNDERCOUNTER

UFD UNDER FLOOR DUCT

UG UNDERGROUND

UH UNIT HEATER

UNFIN UNFINISHED

UNO UNLESS NOTED OTHERWISE

US UTILITY SHELF

UTIL UTILITY

VIF VERIFY IN FIELD

VC VALVE CABINET

VCT VINYL COMPOSITION TILE

VENT VENTILATION

VERT VERTICAL

VEST VESTIBULE

VR VAPOR RETARDER

VTR VENT THROUGH ROOF

WCV WALL COVERING

W WIDTH/WIDE

WF WIDE FLANGE

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WD WOOD

WDW WINDOW

WG WALL GUARD

WH WALL HYDRANT

WHCH WHEELCHAIR

WHTR WATER HEATER

WPL WALL PANEL

WP WATERPROOF

WR WASTE RECEPTACLE

WS WEATHERSTRIP

WSCT WAINSCOT

WSF WELDED SEAM-RESILIENT

SHEET FLOORING

WDT WINDOW TREATMENT

WT WEIGHT

WW WOOD WINDOW

WWF WELD WIRE FABRIC

NA NOT APPLICABLE

NC NURSE CALL

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NRC NOISE REDUCTION COEFFICIENT

NT NOTE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OH OVERHEAD

OP OPERABLE PARTITION

OPER OPERATOR

OPNG OPENING

OPP OPPOSITE

OFD OVERFLOW ROOF DRAIN

FRMG FRAMING

FSTOP FIRE STOPPING

FT FOOT/FEET

FTG FOOTING

FURR FURRING

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GB GRAB BAR

GBM GRADE BEAM

GC GENERAL CONTRACTOR

GENL GENERAL

GENR GENERATOR

GL GLASS

GR GRADE

GRT GROUT

GWB GYPSUM WALLBOARD

GYP GYPSUM

PART PARTITION

PB PORCELAIN BASE

PC PRECAST CONCRETE

PCD PAPER CUP DISPENSER

PED PEDESTAL

PLT PLATE

PROP PROPERTY LINE

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PLS PLASTER

PLW PLYWOOD

COR CONTRACTING OFFICER'S

REPRESENTATIVE

1. ALL CONTRACTORS AND THEIR SUPERVISORY PERSONNEL MUST REVIEW THE GENERAL AND

SUPPLEMENTARY CONDITIONS TO THE CONTRACT.

2. ALL WORK MUST CONFORM WITH APPLICABLE BUILDING CODES, REGULATIONS AND ORDINANCES.

3. CONTRACTOR MUST OBTAIN ALL REQUIRED BUILDING AND OCCUPANCY PERMITS, WHEN APPLICABLE.

4. CONTRACTOR MUST BECOME FULLY ACQUAINTED WITH CONDITIONS RELATED TO THE WORK.

5. CONTRACTOR MUST BE SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF

CONSTRUCTION AND THE SAFETY OF ALL CONSTRUCTION PERSONNEL AND VISITORS.

6. DRAWINGS CONTAINED IN THIS SET MUST NOT BE REPRODUCED FOR SHOP DRAWINGS. COPIES OF THESE DRAWINGS SUBMITTED AS SHOP DRAWINGS WILL BE REJECTED AND RETURNED TO THE CONTRACTOR.

7. EACH INSTALLER MUST EXAMINE SUBSTRATE AND/OR CONDITIONS UNDER WHICH THE WORK WILL BE INSTALLED AND REPORT TO THE COR IN WRITING ANY CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY EXECUTION OF THAT INSTALLER'S WORK. DO NOT PROCEED UNTIL UNSATISFACTORY CONDITIONS ARE CORRECTED. COMMENCING WITH INSTALLATION WILL CONSTITUTE ACCEPTANCE OF THE

SUBSTRATE AND/OR CONDITIONS.

8. DO NOT SCALE DRAWINGS. FOLLOW WRITTEN DIMENSIONS AND NOTES. CONTACT COR FOR CLARIFICATIONS, IF REQUIRED.

9. DIMENSIONS SHOWN ON THE FLOOR PLAN ARE TO THE FACE OF GYP. BOARD/ WALL (FOG), FACE OF MASONRY (FOM), FACE OF CONCRETE WALLS (FOC) AND COLUMN GRID LINES, UNLESS OTHERWISE NOTED OR

INDICATED.

10. WALL THICKNESSES ARE NOMINAL DIMENSIONS, NOT ACTUAL DIMENSIONS. ALL STUD WALL THICKNESSES

ARE 5 INCHES, UNLESS DIMENSIONED OTHERWISE.

11. ALL MASONRY WALL THICKNESSES ARE 8 INCHES, UNLESS DIMENSIONED OTHERWISE.

12. "TYPICAL", AS USED IN THESE DOCUMENTS, MEANS THAT THE CONDITION OR DIMENSION IS REPRESENTATIVE

OF, OR THE SAME AS, FOR SIMILAR CONDITIONS THROUGHOUT.

13. IF THERE IS A DISCREPANCY BETWEEN SMALL SCALE AND LARGE SCALE DRAWINGS, (PLAN, SECTION, & DETAIL DRAWINGS, ETC.), CONTACT COR FOR CLARIFICATION. FOR BIDDING PURPOSES, THE MOST EXPENSIVE AND/OR STRICTEST REQUIREMENTS MUST GOVERN. FOR CLARIFICATIONS DURING CONSTRUCTION, THE MOST

EXPENSIVE AND/OR STRICTEST REQUIREMENTS, AS INDICATED BY THE COR, MUST GOVERN.

14. IF THERE ARE ANY DISCREPANCIES BETWEEN THE DRAWINGS AND SPECIFICATIONS, CONTACT COR FOR CLARIFICATION. FOR BIDDING PURPOSES, THE MOST EXPENSIVE AND/OR STRICTEST REQUIREMENTS MUST GOVERN. FOR CLARIFICATIONS DURING CONSTRUCTION, THE MOST EXPENSIVE AND/OR STRICTEST

REQUIREMENTS, AS INDICATED BY THE COR, MUST GOVERN.

15. ANY AND ALL DISCREPANCIES MUST BE REPORTED TO THE COR IN WRITING FOR RESOLUTION PRIOR TO PROCEEDING WITH THE WORK. IN THESE INSTANCES, NO CHANGE ORDERS OR EXTENSIONS OF TIME WILL BE ALLOWED OR ACCEPTED FOR PROCEEDING WITH THE WORK WITHOUT THE COR'S WRITTEN DIRECTION AND APPROVAL. ALSO, CONTRACTOR MUST REPAIR AND/OR REPLACE ANY UNAUTHORIZED WORK, AS INDICATED

BY THE COR, AT NO ADDITIONAL COST TO THE OWNER.

16. ALL DISSIMILAR METAL MATERIALS MUST BE ISOLATED WITH AN APPROVED NONMETAL ISOLATION MATERIAL.

17. OPEN EXTERIOR JOINTS AROUND WINDOW AND DOOR FRAMES, BETWEEN WALLS AND FOUNDATIONS, BETWEEN WALL PANELS AND AT PENETRATIONS OF UTILITIES THROUGH THE BUILDING ENVELOPE, ETC, MUST BE SEALED, CAULKED, FLASHED OR WEATHER-STRIPPED, AS REQUIRED, FOR COMPATIBILITY WITH ADJACENT

MATERIALS AND TO ELIMINATE AIR LEAKAGE AND WATER ENTRY.

18. PROVIDE SEALANT AND/OR CAULKING BETWEEN DISSIMILAR ADJOINING INTERIOR MATERIALS. (I.E. WINDOW

SILLS TO GYP. BD., ACT CEILINGS TO MASONRY WALLS, ETC.)

19. DOOR OPENINGS NOT LOCATED BY DIMENSION MUST BE CENTERED IN WALL SHOWN OR LOCATED 2 INCHES FROM FINISH WALL TO FINISH JAMB, ALWAYS ALLOWING A MINIMUM OF 18" FROM THE PULL SIDE OF THE DOOR

TO THE INTERSECTING WALL.

20. CONTRACTOR MUST VERIFY THE LOCATIONS OF ALL EXISTING UNDERGROUND UTILITIES AND THEIR SERVICE

CONNECTIONS WITH THE PROPER UTILITY COMPANY.

21. CONTRACTOR MUST COORDINATE SIZE, LOCATIONS AND NUMBER OF ALL ROOF OPENINGS AND ROOF ACCESSORIES WITH ALL OTHER TRADES. REFER TO THE ARCHITECTURAL, STRUCTURAL, PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS.

22. LOCATIONS AND SIZES OF ALL CONCRETE MECHANICAL AND ELECTRICAL PADS MUST BE COORDINATED BY

THE MECHANICAL AND ELECTRICAL CONTRACTORS WITH THE SELECTED EQUIPMENT

MANUFACTURER/SUPPLIER AND ARE TO BE APPROVED BY THE COR PRIOR TO PROCEEDING WITH THE WORK.

23. EXCEPT AT FIRE-RATED PARTITIONS, ALL WALL AND COLUMN GYPSUM BOARD FACING MUST BE HELD AT 5/8

INCH BELOW STRUCTURE, UNLESS DETAILED OR NOTED OTHERWISE.

24. AT ALL TELECOMMUNICATION ROOMS: PROVIDE 3/4" X 8'-0" HIGH FIRE-RETARDANT-TREATED WOOD SHEATHING OR PROVIDE PLYWOOD OVER NON-COMBUSTIBLE SHEATHING. BOTTOM TO BE LOCATED AT 4"

A.F.F. VERIFY LENGTHS AND LOCATIONS WITH ELECTRICAL DRAWINGS.

25. GLASS DOORS, ADJACENT PANELS AND ALL GLAZED OPENINGS WITHIN 1'-6" OF THE FLOOR AND WITHIN A 24- INCH ARC OF EITHER VERTICAL EDGE OF A DOOR, ETC., MUST BE SAFETY GLAZING AS APPROVED FOR IMPACT

BY APPLICABLE BUILDING CODES, AND MUST BE LABELED AS SUCH.

26. ALL CEILING HEIGHTS AS SHOWN ON PLANS AND DETAILS ARE FROM SLAB OR TILE FLOOR (FINISHED FLOOR)

TO FINISHED CEILING.

27. PROVIDE INDEPENDENT FRAMING AND ATTACHMENTS TO THE STRUCTURE, ADEQUATE TO SUPPORT THE CEILING SYSTEM, LIGHT FIXTURES, DUCTS, DIFFUSERS, SPRINKLER PIPING AND BUS DUCTS.

28. ALL CLOSETS AND ALCOVES WITHOUT A SPACE IDENTIFICATION NUMBER MUST HAVE THE SAME FINISHES AS

ADJOINING SPACES.

29. CONTRACTOR TO INSTALL WOOD BLOCKING AND PLYWOOD, AS REQUIRED, FOR THE MOUNTING OF ALL TOILET ACCESSORIES, MILLWORK/ CASEWORK, AV EQUIPMENT, MEP ITEMS AND RADIOLOGY EQUIPMENT, ETC.

30. REFER TO SPECIFICATIONS FOR ALL REQUIRED TESTING AND INSPECTIONS.

31. ANY/ ALL PROPRIETARY PRODUCTS DESCRIBED AND/OR DRAWN IN THE DOCUMENTS (BUT NOT SPECIFIED) ARE TO MEET THE MANUFACTURER'S STANDARD CRITERIA WHICH IS NOT LIMITED TO THE FOLLOWING:

PERFORMANCE REQUIREMENTS, QUALITY ASSURANCE REQUIREMENTS, APPLICABLE CODES AND INDUSTRY STANDARDS, FABRICATION, ASSEMBLY, HANDLING, DELIVERY, STORAGE, INSTALLATION, OPERATION, ADJUSTMENTS, ETC. PROVIDE THE MANUFACTURER'S STANDARD WARRANTY AND STANDARD FINISH WARRANTY. PROVIDE PRODUCT DATA, SHOP DRAWINGS, SAMPLES AND MAINTENANCE DATA, AS REQUIRED.

REFER TO DIVISION 01 SPECIFICATION SECTIONS WHICH ALSO APPLY, SUCH AS SUBSTITUTION PROCEDURES, SUBMITTAL PROCEDURES, QUALITY REQUIREMENTS, REFERENCES, EXECUTION AND CLOSEOUT PROCEDURE.

ANY SUBSTITUTIONS MUST MEET THE DESIGN INTENT, AS WELL AS THE CRITERIA DESCRIBED ABOVE.

AE101

DETAIL

NUMBER

ON SHEET

SHEET NUMBER

INTERIOR EXTERIOR

PT PORCELAIN TILE

STN STAIN

PR PAIR

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD

APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL)

(WWW.CFM.VA.GOV/TIL/)

• INTERNATIONAL BUILDING CODE (IBC)

(ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

• VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• NATIONAL ELECTRICAL CODE (NEC)

• INTERNATIONAL PLUMBING CODE

• ASME CODE FOR PRESSURE PIPING

• ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS) INCLUDING VA SUPPLEMENT, BARRIER FREE DESIGN GUIDE (PG-18-13)

• ENERGY POLICY ACT OF 2005 (EPAct)

• EXECUTIVE ORDER13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND

TRANSPORTATION MANAGEMENT

• THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS

SECTION 01 00 00 OF THE VA MASTER CONSTRUCTION SPECIFICATION

• VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY -- ASHRAE STANDARD 62.1-2004

LOCAL CODES:

AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.

HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN

OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT THE VA DOES NOT PAY FOR REVIEW OR

INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY

CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS

REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED IN THE PROGRAM GUIDE PG-18-3.

FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A

DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT

REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC

REQUIREMENTS ARE DIFFERENT).

2. SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED

CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE VA.

THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR

THE VA TO ENSURE CONSISTENCY SYSTEM WIDE.

APPLICABLE CODES AND STANDARDS

BUILDING CONSTRUCTION: TYPE I-B

BUILDING OCCUPANCY: B - BUISINESS

BUILDING IS FULLY SPRINKLERED

PROJECT DESCRIPTION: RENOVATION OF MULTIPLE SPACES, HOWEVER THERE ARE NO CHANGES TO

OCCUPANCY TYPE OR OCCUPANCY LOAD.

CODE INFORMATION

R.3

R.1

R.2

S

U

V.3

T

V.2

V

V.1

1 2 3 4 5 7 9 10

RECEIVING

GE17

STORAGE

GE19

OFFICE

GE20

OFFICE

GE21

PREP. RM.

GE32

DECONTAMINATION

AREA

GE29

STEAM

RM.

GE28

R.3

R.1

R.2

S

U

V.3

T

V.2

V

V.1

1 2 3 4 5 7 9 10

CORRIDOR

H003

ELEVATOR

#2 E2

HAC

GE35

HAC

GE34

CORRIDOR

H004

TOILET

GE22

TOILET

GE23

CORRIDOR

GE31

CORRIDOR

H005

MECH.

RM.

GE26

MEDICAL

RECORDS

GC09

STORAGE

GE32A

HAC

GE24

D.W.

E3

CHASE

CH-C-1

FE

1 DEMOLISH EXISTING DOOR AND HOLLOW

METAL FRAME.

DEMOLISH A PORTION OF THE EXISTING

CONCRETE MASONRY WALL AND

ASSOCIATED CONSTRUCTION TO

FACILITATE INSTALLATION OF NEW DOOR

OPENING. PREP SUBFLOOR FOR NEW

FLOORING.

REMOVE EXISTING FLOORING AND PREP

SUBFLOOR FOR NEW FLOORING.

DEMOLISH TWO EXISTING GLASS BLOCKS IN

UPPER ROW TO FACILITATE INSTALLATION

OF NEW 16" X 8" EXHAUST LOUVER.

DEMOLISH EXISTING LOUVER AND

ASSOCIATED CONSTRUCTION TO

FACILITATE INSTALLATION OF NEW LOUVER

IN EXISTING OPENING.

DEMOLITION KEYNOTES

1. EXISTING FLOOR PLAN AND LAYOUT IS PER VA

JOB # 657-19-JBAB DATED 03/19/2019.

DIMENSIONS FOR ROOM GE17 - RECEIVING

HAVE BEEN VERIFIED AND UPDATED. OTHER

DIMENSIONS SHOULD BE FIELD VERIFIED BY

GC, AS REQUIRED. REPORT ANY

DISCREPENCIES FROM THE DRAWINGS TO COR

BEFORE PROCEEDING WITH WORK.

2. REFER TO ELECTRICAL AND MECHANICAL

PLANS FOR ADDITIONAL INFORMATION AND

EXTENT OF ELECTRICAL AND MECHANICAL

DEMOLITION

GENERAL NOTES

P la n N o rt h

T ru e N o rt h

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :0

A

M

01-AD-100

ARCHITECTURAL DEMOLITION PLAN -

FLOOR 00

03 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

MVP SB03/26/2020

1/4" = 1'-0"

ARCHITECTURAL DEMOLITION PLAN - FLOOR 00

1 Plan North

True North

R.3

R.1

R.2

S

U

V.3

T

V.2

V

V.1

1 2 3 4 5 7 9 10

CORRIDOR

H003

ELEVATOR

#2 E2

HAC

GE35

HAC

GE34

OFFICE

GE17

MEDICAL

RECORDS

GE19

CORRIDOR

H004

MEDICAL

RECORDS

GE21

MEDICAL

RECORDS

GE20

MEDICAL

RECORDS

GE32

TOILET

GE22

TOILET

GE23

CORRIDOR

GE31

CORRIDOR

H005

MEDICAL

RECORDS

GE29

MECH.

RM.

GE26

MEDICAL

RECORDS

GC09

STORAGE

GE32A

MEDICAL

RECORDS

GE28

HAC

GE24

D.W.

E3

CHASE

CH-C-1

FE

A

A

A

A

8 EXISTING FLOORNEW FLOOR

1. EXISTING FLOOR PLAN AND LAYOUT IS PER VA

JOB # 657-19-JBAB DATED 03/19/2019.

DIMENSIONS FOR ROOM GE17 - RECEIVING

HAVE BEEN VERIFIED AND UPDATED. OTHER

DIMENSIONS SHOULD BE FIELD VERIFIED BY

GC, AS REQUIRED. REPORT ANY

DISCREPENCIES FROM THE DRAWINGS TO COR

BEFORE PROCEEDING WITH WORK.

GENERAL NOTES

1 INFILL WITH NEW CONCRETE MASONRY

UNITS IN ACCORDANCE WITH

SPECIFICATION SECTION 04 20 00. PAINT TO

MATCH EXISTING. MATCH EXISTING BOND

PATTERN.

PROVIDE NEW (PR) 3'-0" X 7'-0" WOOD DOOR

AND HM FRAME. INSTALL NEW 9" ALUMINUM

DOOR THRESHOLD PER SPECIFICATION

SECTION 08 71 00 SECTION 2.23. BASIS OF

DESIGN: NGP 913 UTILITY THRESHOLD, MILL

FINISH ALUMINUM.

UPDATE FINISHES PER FINISH SCHEDULE.

REFER TO SHEET 01-AE-501.

EXISTING FURNITURE PROVIDED BY THE VA

TO BE RELOCATED FROM THE EXISTING

DECONTAMINATION AREA.

INSTALL NEW 16" X 8" EXHAUST LOUVER.

INSTALL PER MANUFACTURER'S

RECOMMENDATIONS AND SEAL ALL

AROUND TO PREVENT WATER

INFILTRATION. REPLACE IN KIND ANY

GLASS BLOCK DAMAGED DURING

INSTALLATION. SEE MECHANICAL

DRAWINGS FOR MORE INFORMATION.

INSTALL NEW LOUVER IN EXISTING

OPENING. INSTALL PER MANUFACTURER'S

RECOMMENDATIONS AND SEAL ALL

AROUND TO PREVENT WATER

INFILTRATION. SEE MECHANICAL

DRAWINGS FOR MORE INFORMATION.

INSTALL NEW STEEL ANGLE LOOSE LINTEL

IN ACCORDANCE WITH SPECIFICATION

SECTION 05 50 00. IF EXISTING

REINFORCEMENT IS CUT DURING

INSTALLATION, INSTALL #4 VERTICAL REBAR

ON EITHER SIDE OF OPENING IN

ACCORDANCE WITH SPECIFICATION

SECTION 04 20 00. THE GENERAL

CONTRACTOR SHALL PROVIDE SHORING,

AS REQUIRED, DURING INSTALLATION.

CONSTRUCT NEW RATED WALL ON TOP OF

EXISTING CMU WALL. REFER TO EALL TYPE

SCHEDULE ON SHEET 01-AE-501.

KEYNOTES

P la n N o rt h

T ru e N o rt h

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :0

A

M

01-AE-100

ARCHITECTURAL FLOOR PLAN - FLOOR

04 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

MVP SB03/26/2020

1/4" = 1'-0"

ARCHITECTURAL FLOOR PLAN - FLOOR 00

1 Plan North

True North

(2) LAYERS 5/8" TYPE X GYP.

BD. EACH SIDE. FINISH WITH

TAPE AND JOINT COMPOUND

ONLY

4" METAL STUD @ 24" O.C. W/

HORIZ. BRACING AS REQ'D

3 1/2" SOUND BATT INSULATION

METAL RUNNERS TOP AND

BOTTOM

BOTTOM OF DECK

CEILING HEIGHT

VIF

FLOOR

DEEP LEG DEFLECTION/ SLIP

TRACK

INSTALL FIRESAFING SEALANT

TO SEAL TOP & BOTTOM OF

NEW WALL

EXISTING CMU WALL

ANCHOR NEW WALL TO EXISTING

WITH POWER ACTUATED

FASTENERS @ 16" OC INTO CMU

HEAD JOINT

SUSPENDED CEILING (WHERE

APPLIES)

MECHANICAL ROOM

LVT / VCT

WSF

B.O.D. SCHLUTER-

RENO-T

CAPPING STRIP

SHEET VINYL FLOORING WITH INTEGRAL

COVE BASE AS SCH.

MANUF. STANDARD COVE FILLER

EXISTING CMU WALL

PROVIDE NEW STEEL ANGLE

LINTEL PER SPECIFICATION

SECTION 05 50 00

ELASTORMERIC SEALANT

(ALL AROUND, BOTH SIDES)

6" HM RENOVATION FRAME

(PAINTED)

COUNTERSUNK FASTENER

INTO STEEL LINTEL @ 24" OC

SCHEDULED DOOR

SCHEDULED DOOR

6" HM RENOVATION

FRAME (PAINTED

EXISTING CMU WALL

COUNTERSUNK FASTENER INTO

MORTAR BED JOINT AT 24" OC

VERT

ELASTORMERIC SEALANT (ALL

AROUND, BOTH SIDES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :0

A

M

01-AE-501

ARCHITECTURAL WALL TYPES AND

DETAILS

05 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

MVP SB03/26/2020

WALL TYPE A

WALL DESCRIPTIONTYPE

A

• UL-U403

• (2) LAYERS 5/8" TYPE X GYPSUM BOARD

• 3 5/8" 25 GA. STEEL STUDS @ 16" O.C.

• 3 1/2" GLASS FIBER INSULATION

• (2) LAYERS 5/8" TYPE X GYPSUM BOARD

FINISH LEGEND

SYMBOL MATERIAL MANUFACTURER TYPE COLOR TYP. AREA / REMARKS

FLOOR FINISH

WSF WELDED SEAM SHEET FLOORING ARMSTRONG MEDINTECH - -

WALL BASE

IB INTEGRAL SHEET VINYL COVE BASE W/ METAL

TERMINATION STRIP - 4" H. COVE

ARMSTRONG MEDINTECH -

WALL FINISH

PNT PAINT SHERWIN WILLIAMS EPOXY - -

CEILING FINISH

ACT 24" X 48" ACOUSTIC CEILING TILE ARMSTRONG DUNE: 1851 WHITE MINERAL FIBER, SMOOTH

6" = 1'-0"

WSF TO VINYL / VCT

3" = 1'-0"

INTEGRAL COVE BASE DETAIL

1 1/2" = 1'-0"

TYP. INTERIOR DOOR HEAD DETAIL

1 1/2" = 1'-0"

TYP. INTERIOR DOOR JAMB DETAIL

GENERAL NOTES

1. CONTRACTOR SHALL PROVIDE AN INFECTION CONTROL RISK ASSESSMENT

BARRIER AROUND THE PROJECT AREA CONSISTENT WITH THE CONTRACTOR'S

PHASING PLAN AS APPROVED BY THE VA.

HVAC GENERAL NOTES

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN

A FURRED CHASE OR ABOVE THE HARD SUSPENDED CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR

INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES,

TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE

FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS.

4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,

TERMINAL UNITS, FILTERS, COILS, ETC.

5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE

EQUIPMENT DETAILS.

6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK

SIZES.

7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE

TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE

INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED FLOOR.

9. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE.

10. ALL CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING

BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL

SYSTEM TO INCLUDE ALL OF THE CONTROLS AND SEQUENCES SHOWN.

11. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DIFFUSERS.

MECHANICAL ASCE 7 NONSTRUCTURAL

SEISMIC RESTRAINT AND ANCHORAGE NOTES:

REFERENCE SPECIFICATION: SECTION 13 05 41

SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS

SEISMIC DESIGN DATA FOR ANALYSIS AND DESIGN

SEISMIC RISK CATEGORY = IV

COMPONENT IMPORTANCE FACTOR IP = 1.5

MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:

SS = 0.475G S1 = 0.166G

SITE CLASS D (ASSUMED)

DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:

SDS = 0.449G SD1 = 0.253G

SEISMIC DESIGN CATEGORY D BASED UPON SD1 > 0.20G

CLARIFICATION OF ASCE 7 "12 INCH RULE" SUSPENDED SEISMIC BRACING CODE

EXCEPTION FOR PIPING AND HVAC DUCTWORK:

ALL PIPING SUSPENDED BY INDIVIDUAL HANGER RODS 12" OR LESS AS MEASURED

FROM THE TOP OF THE PIPE TO THE BOTTOM OF THE SUPPORT WHERE THE HANGER

IS ATTACHED. IF THE 12" LIMIT IS EXCEEDED BY ANY HANGER IN THE RUN, SEISMIC

BRACING IS REQUIRED FOR THE RUN. NOTE: A SINGLE SUPPORT LOCATION THAT

MEETS THE REQUIREMENT OF THIS EXCEPTION DOES NOT CONSTITUTE A SEISMIC

SWAY BRACE LOCATION.

THE EXCEPTION ALSO APPLIES FOR TRAPEZE SUPPORTED SYSTEMS IF THE DISTANCE

AS MEASURED FROM THE POINT OF ATTACHMENT TO THE TRAPEZE TO THE POINT OF

ATTACHMENT TO THE STRUCTURE IS LESS THAN 12". NOTE: IF DIRECTIONAL CHANGES

OR OFFSETS TO EQUIPMENT CONNECTIONS DO NOT ALLOW FOR FLEXIBILITY OF THE

TRAPEZED SYSTEM (E.G. LONG OFFSETS OR FLEXIBLE CONNECTORS) THEN THE

SYSTEM MUST BE BRACED REGARDLESS OF PIPE DIAMETER OR DISTANCE TO THE

STRUCTURE IF THE COMBINED WEIGHT PER FOOT (METER) OF ALL ITEMS IS GREATER

THAN 10 LBS/FT.

IN ADDITION, TO MEET THE CODE REQUIREMENTS, ALL OF THE FOLLOWING

CONDITIONS MUST ALSO BE SATISFIED:

1. LATERAL MOTION OF PIPING OR DUCTWORK WILL NOT CAUSE DAMAGING IMPACT

WITH SURROUNDING SYSTEMS (E.G. OTHER PIPE, DUCT, EQUIPMENT, SPRINKLER

HEADS ETC.) OR CAUSE LOSS OF SYSTEM VERTICAL SUPPORT.

2. PIPING MUST BE MADE OF DUCTILE MATERIAL WITH DUCTILE CONNECTIONS (E.G.

WELDED STEEL PIPE, BRAZED COPPER PIPE, ETC.)

3. VERTICAL SUPPORT CONNECTIONS CANNOT DEVELOP MOMENTS (E.G. SWIVEL

JOINTS, EYE BOLTS, VIBRATION ISOLATION HANGERS, ETC.)

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :4

P

M

01-MG-001

MECHANICAL ABBREVIATIONS AND

GENERAL NOTES

06 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

DD ZM03/26/2020

MECHANICAL ABBREVIATIONS

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

RDS ROOM DATA SHEETS

REA RELIEF AIR

RF RADIO FREQUENCY

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SD-1 SCHEMATIC DESIGN SUBMISSION 1

SD-2 SCHEMATIC DESIGN SUBMISSION 2

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND DISTRIBUTION

SPRV STEAM PRESSURE REDUCING VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SV STEAM PRESSURE REDUCING VALVE

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE

TAB TESTING, ADJUSTING, AND BALANCING

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

UC UNIT COOLER

UCT UNDERCUT

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

URV UPBLAST UNIT VENTILATOR

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

W WASTE

WAG WASTE ANESTHESIA GAS

WB WET BULB

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCPU WATER COOLED HEAT PUMPS

WEF WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFCV WATER FLOW CONTROL VALVE

WFM WATER FLOWMETER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

YR YEAR

MECHANICAL ABBREVIATIONS

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCHES OF WATER COLUMN

IN WG INCHES OF WATER, GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

KG KILOGRAM

KG/H KILOGRAMS PER HOUR

KPA KILOPASCAL

KW KILOWATT

KWH KILOWATT HOURS

L LITER

L/H LITERS PER HOUR

L/M LITERS PER MINUTE

L/S LITERS PER SECOND

LAT LEAVING AIR TEMPERATURE

LB/H POUND PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPG LIQUID PROPANE GAS

LPR LOW PRESSURE RETURN (STEAM CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER

M/S METERS PER SECOND

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING UNIT

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOW METER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTER DIAMETER

OFM OIL FLOWMETER

OR OPERATING ROOM

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT

PD PRESSURE DROP

PEF PROPELLER TYPE EXHAUST FAN

PF PRE-FILTER

PG PRESSURE GAUGE

PGW PROPYLENE GLYCOL-WATER SOLUTION

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING VALVE STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH, ABSOLUTE

PSIG POUNDS PER SQUARE INCH, GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

MECHANICAL ABBREVIATIONS

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOHX FUEL OIL HEAT EXCHANGER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FINNED TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

H HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVD HOISTWAY VENT DAMPER

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING WATER PUMP

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

MECHANICAL ABBREVIATIONS

A/E ARCHITECT/ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AAV AUTOMATIC AIR VENT

AB AIR BLENDER

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

ACCU AIR-COOLED CONDENSING UNIT

ACD AUTOMATIC CONTROL DAMPER, MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION

ACFM ACTUAL CUBIC FEET PER MINUTE

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMD AIR FLOW MEASURING DEVICE

AFW AIR FOIL WHEEL (FAN)

AHU AIR HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B BOILER

BAS BUILDING AUTOMATION SYSTEMS

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BR BOTTOM REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION 1)

CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION 2)

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFP CHEMICAL FEED PUMP

CFT CUBIC FEET

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CHW CHILLED WATER

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CTR CONTRACTOR

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO COOLING TOWER)

CWS CONDENSER WATER SUPPLY (FROM COOLING TOWER)

D DAMPER -AUTOMATIC

D-1 OUTDOOR AIR DAMPER

D-2 RETURN AIR DAMPER

D-3 RELIEF AIR DAMPER

Db DRY BULB TEMPERATURE dB DECIBEL

DD-1 DESIGN DEVELOPMENT SUBMISSION 1

DD-2 DESIGN DEVELOPMENT SUBMISSION 2

DDC DIRECT DIGITAL CONTROLS

DEG DEGREES

DF DIFFUSER

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-117JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.23

100% BID DOCUMENTS

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/2

/2

:2 :4

P

M

01-MG-002

MECHANICAL SYMBOLS

07 35

IMPLEMENT STERILE PROCESSING

SERVICE VENTILATION REQUIREMENTS

DD ZM03/26/2020

T

TT

M

MT

PT

TT

FT

IT

CT

SPS

SD

PDT

KR

TSL

HS

ZC

LC

LT

PDS

TSH

EPT

AT

CO2

AT

CO

AT

OC

LTCP

HVAC

ECC

TC

VSMC

PC

SC

FC

PSH

FSH

PSL

26-SF 3

26-TU-I-I

H4

H7

A

BDD

FD

VD

SUPPLY

RETURN45°

45°

N

2 1

1/24

F/S DPR

FE

AV

MV

RH

SCH

SH

TH

PS

RC

WB

CSH

SS

VR

CTPS

CTPD

FWPS

FWPD

CF

FWS

BWS

CBD

BO

TC

A

OFL

HW

SW

CW

FOR

FOS

LPG(I)

G(I)

G

HPS

HPR

MPS

MPR

LPS

LPR

PC

HWS

HWR

GHS

GHR

V

SWS

SWR

CWR

CHR

GCR

RL

RS

RHG

CWS

CHS

GCS

MW

D

GRR

GRS

X

A

PTAC

A TWU

A

FCU

FCU

A

PTACA

MB

KC

FSL

A

M

BAS

DN

DN

UP

UP

D

R

DNUP

FC

10x8

LC

M

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

SUPPLY FAN NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NO. 1

DRAWING NUMBER WHERE DRAWN

BUILDING NO. WHERE EQUIPMENT IS LOCATED

* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD

PRACTICE SP-58

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

MANUAL AIR VENT

QUICK-COUPLE HOSE CONNECTOR

CONNECT TO EXISTING

LIMIT OF DEMOLITION

AIR SEPERATOR

TERMINAL UNIT WITH REHEAT COIL

DOUBLE DUCT MIXING BOX.

FAN POWERED VARIABLE VOLUME

TERMINAL UNIT WITH HEATING COIL.

EXISTING DUCT TO BE REMOVED

LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL

SECTION.)

FLEXIBLE DUCTWORK (INSULATED)

DUCT WITH SOUND LINING

MANUAL VOLUME DAMPER

FIRE DAMPER

BACK DRAFT DAMPER

COMBINATION FIRE/SMOKE DAMPER

POINT OF CHANGE IN DUCT CONSTRUCTION BY

STATIC PRESSURE CLASS. THE NUMBER ASSIGNS

PRESSURE CLASS (IN. OF WATER) WHICH WILL

ACCOMMODATE MAXIMUM OPERATING PRESSURE

IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES

THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR

ANOTHER SYMBOL APPEARS. AN "N" SUPERSCRIPT

INDICATES NEGATIVE PRESSURE.

AUTOMATIC CONTROL DAMPER MODULATING

AUTOMATIC CONTROL DAMPER TWO POSITION

MANUAL SPLITTER DAMPER

STANDARD BRANCH SUPPLY OR RETURN, NO

SPLITTER (45° TAP)

DUCT MOUNTED COIL (HOT WATER OR STEAM

COIL)

DUCT MOUNTED COIL (ELECTRIC)

CONVECTOR OR RADIATOR (RECESSED)

CONVECTOR OR RADIATOR (WALL HUNG)

FLOOR MOUNTED VERTICAL RECESSED FAN COIL UNIT.

LETTER INDICATES UNIT SIZE.

FLOOR MOUNTED VERTICAL CABINET FAN

COIL UNIT. LETTER INDICATES UNIT SIZE.

THRU WALL AIR CONDITIONING UNIT.

LETTER INDICATES UNIT SIZE.

WINDOW TYPE AIR CONDITIONING UNIT.

LETTER INDICATES UNIT SIZE.

FLOOR MOUNTED HEAT PUMP. LETTER

INDICATES UNIT SIZE.

AIR CURTAIN

UNIT HEATER (HORIZONTAL)

UNIT HEATER (VERTICAL)

2'x2' RADIANT CEILING PANEL

2'x4' RADIANT CEILING PANEL

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

RETURN DUCT (UP & DOWN)

ROUND AND SQUARE 4-WAY CEILING DIFFUSERS

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

SQUARE 1-WAY CEILING DIFFUSERS

LINEAR SLOT DIFFUSER

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING

REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM

REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN REGISTER OR TOP GRILLE

(WALL TYPE)

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

LIMIT OF DEMOLITION

FLEXIBLE CONNECTION, EQUIPMENT, VIBRATION,

OR SEISMIC

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

EXISTING DUCT TO REMAIN

GATE VALVE - THREADED/FLANGED

GLOBE VALVE - THREADED/FLANGED

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE

FLEXIBLE CONNECTION

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

MODULATING CONTROL VALVE

MODULATING CONTROL BUTTERFLY VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

THREE-WAY TWO POSITION CONTROL VALVE

PRESSURE REGULATING VALVE

PRESSURE SAFETY VALVE

AUTOMATIC BALANCING CONTROL VALVE

WATER BALANCE DEVICE

CIRCUIT SETTER VALVE

GATE VALVE WITH GLOBE-VALVED BYPASS

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

PRESSURE REDUCING VALVE (PRV)

WATER LEVEL CONTROLLER

FLOW METER

ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT

ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL

MOUNT

TEMPERATURE TRANSMITTER

TEMPERATURE TRANSMITTER, AVERAGING ELEMENT

MOISTURE (HUMIDITY) TRANSMITTER

PRESSURE TRANSMITTER

STATIC PRESSURE SENSOR

FLOW TRANSMITTER

CURRENT TRANSMITTER

CONDUCTIVITY TRANSMITTER

SMOKE DETECTOR

PRESSURE DIFFERENTIAL TRANSMITTER

PRESSURE DIFFERENTIAL SWITCH

HAND SWITCH (HAND-OFF-AUTO SWITCH)

VALVE OR DAMPER POSITION CONTROLLER

LOCAL RECORDING TIME CLOCK (RUNTIME)

TEMPERATURE SWITCH, LOW (FREEZESTAT)

TEMPERATURE SWITCH, HIGH (FREEZESTAT)

LEVEL CONTROLLER

LEVEL TRANSMITTER

PRESSURE SWITCH HIGH

PRESSURE SWITCH LOW

ELECTRONIC TO PNEUMATIC TRANSDUCER

CARBON DIOXIDE TRANSMITTER

CARBON MONOXIDE TRANSMITTER

OCCUPANCY SENSOR

LOCAL TEMPERATURE CONTROL PANEL

HVAC CONTROL PANEL

VARIABLE SPEED MOTOR CONTROLLER

INTEGRATE CONTROL POINT ON REMOTE

GRAPHICS WORKSTATION AT ENERGY

CONTROL CENTER

TEMPERATURE CONTROLLER. SEE

SEQUENCE OF OPERATION

PRESSURE CONTROLLER. SEE SEQUENCE

OF OPERATION

SPEED CONTROLLER. SEE SEQUENCE OF

OPERATION

FLOW CONTROLLER. SEE SEQUENCE OF

OPERATION

FLOW SWITCH HIGH

FLOW SWITCH LOW

TIME CLOCK CONTROLLING EQUIPMENT ON

A SCHEDULE

TEMPERATURE SENSING ELEMENT FOR

TRANSMITTING TEMPERATURE TO EMCS

(PROVIDE 12 INCHES MINIMUM

LENGTH IN DUCT WHEN SPACE PERMITS.)

SENSOR WITH AVERAGING ELEMENT

TO TRANSMIT TEMPERATURE TO EMCS

MOTOR STARTER

ELECTRIC OPERATED CONTROL

DAMPER/OR VALVE

BUILDING AUTOMATION SYSTEM

CONTROLS SYMBOLS

DRAWING SYMBOLS

DUCTWORK SYMBOLS GENERAL PIPING SYMBOLSHVAC PIPING SYMBOLS

TERMINAL UNIT SYMBOLS

AIR TERMINAL SYMBOLS

VALVE SYMBOLS

FLOOR-SUPPORTED PIPE STAND

RISER CLAMP (TYPE 42)*

WALL BRACKET (TYPE 31, 32, 33)*

CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*

SLIDING SUPPORTS (TYPE 35)*

TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT

TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)

HOT WATER

ROLLER-TYPE HANGER

VARIABLE SPRING-TYPE HANGER (TYPE 51)*

SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*

CLEVIS-TYPE HANGER

HIGH PRESSURE STEAM (60 PSIG AND ABOVE)

HIGH PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

LOW PRESSURE STEAM CONDENSATE RETURN

CONDENSATE PUMP DISCHARGE

HEATING WATER SUPPLY

HEATING WATER RETURN

GLYCOL-WATER HEATING SUPPLY

GLYCOL-WATER HEATING RETURN

SOLAR WATER SUPPLY

SOLAR WATER RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

CONDENSER WATER SUPPLY (FROM TOWER)

CONDENSER WATER RETURN (TO TOWER)

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CHILLED GLYCOL-WATER SUPPLY

CHILLED GLYCOL-WATER RETURN

MAKE-UP WATER

DRAIN LINE

VENT LINE

GLYCOL-WATER RUN AROUND SUPPLY

GLYCOL-WATER RUN…