654-20-117 Mental Health EOC_Part6.pdf

PDF 3 MB Posted

Attached to
Y1DA--Mental Health EOC Compliance Federal contract opportunity
Solicitation number
36C26121R0072
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

This document package includes construction drawings and specifications for the Inpatient Mental Health EOC Compliance Renovations project at the Reno VA Medical Center.

The project involves renovations and door frame and door replacements to address EOC compliance issues at the facility. The construction drawings provide details on the electrical work required, including existing and proposed panel schedules. Specification section E-600 through E-603 outline load testing requirements for various normal and emergency power panels to verify capacity.

The related federal contract opportunity is solicitation number 36C26121R0072 for the Inpatient Mental Health EOC Compliance project and a separate but related project for inpatient mental health door frames and doors. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration VISN 21. The document package provides technical information for contractors to prepare bids for the renovations and system replacement work defined in the solicitation.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:2

P

M

E-600

ELECTRICAL ONE-LINE - NORMAL POWER 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

1. Contractor shall provide a 30-day load test on the following panels: Building 12 (5NLA, 5NLB, 5NLC, 5NLD, 5ELA, 5ELB, 5ECA, GNLDP1, GNLDP2, GELL, GELC). Contractor shall provide load monitoring data to the COR/AE. All panels, at the time of design survey (January 2021) had the required capacity. This test is required by NEC 220.87 for verification that no loads have been added since the design level survey.

KEYNOTES-

Revisions: Date:

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:3

P

M

E-601

ELECTRICAL ONE-LINE - EMERGENCY POWER 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

1. Contractor shall provide a 30-day load test on the following panels: Building 12 (5NLA, 5NLB, 5NLC, 5NLD, 5ELA, 5ELB, 5ECA, GNLDP1, GNLDP2, GELL, GELC). Contractor shall provide load monitoring data to the COR/AE. All panels, at the time of design survey (January 2021) had the required capacity. This test is required by NEC 220.87 for verification that no loads have been added since the design level survey.

KEYNOTES-

1 1

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:3

P

M

E-602

ELECTRICAL EXISTING PANEL SCHEDULES -

NORMAL POWER

654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

Notes:

Total Est. Demand: 30 A

Total Conn.: 31 A

Total Est. Demand: 10850 VA

Receptacle 10620 VA 97.08% 10310 VA Total Conn. Load: 11160 VA

Lighting 540 VA 100.00% 540 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 41 A 21 A 35 A

Total Load: 4680 VA 2520 VA 3960 VA

41 0 VA 1 20 A SPARE 42

39 DRYER B6205 20 A 1 180 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 1080... 1 20 A CORRIDOR 26

23 SPARE 20 A 1 0 VA 1260... 1 20 A CORRIDOR 24

21 SPARE 20 A 1 0 VA 900 VA 1 20 A QUIET ROOM / NOURISH KITCH. / WASHER... 22

19 AUTO SINKS 20 A 1 180 VA 720 VA 1 20 A QUIET ROOM / TELE. ROOM 20

17 MED ROOM 20 A 1 540 VA 180 VA 1 20 A CLEAN UTILITY 18

15 SPARE 20 A 1 0 VA 180 VA 1 20 A CLEAN UTILITY 16

13 SPARE 20 A 1 0 VA 1080... 1 20 A NURSES OFFICE 14

11 SPARE 20 A 1 0 VA 900 VA 1 20 A NURSES OFFICE / SOILED UTILITY 12

9 SPARE 20 A 1 0 VA 900 VA 1 20 A NURSES OFFICE 10

7 SPARE 20 A 1 0 VA 900 VA 1 20 A NURSES OFFICE 8

5 DISP UNIT -- -- 0 VA 1080... 1 20 A NURSES OFFICE 6

3 DISP UNIT -- -- 0 VA 360 VA 1 20 A NURSE STATION 4

1 SPARE 20 A 1 0 VA 720 VA 1 20 A NURSE STATION 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Bus Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: ELEC EQUIP B6139 Volts: 208Y/120 A.I.C. Rating:

Panelboard: 5NLA

Notes:

Total Est. Demand: 15 A

Total Conn.: 15 A

Total Est. Demand: 5580 VA

Total Conn. Load: 5580 VA

Receptacle 5580 VA 100.00% 5580 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 20 A 12 A 15 A

Total Load: 2340 VA 1440 VA 1800 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A 2 POLE 30 AMP 42

39 SPARE 20 A 1 0 VA 180 VA 1 20 A RANGE TOP 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 180 VA 1 20 A TELE-CART 16

13 SPARE 20 A 1 0 VA 180 VA 1 20 A TELE-CART 14

11 SPARE 20 A 1 0 VA 540 VA 1 20 A KITCHEN RECEPT 12

9 SPARE 20 A 1 0 VA 720 VA 1 20 A KITCHEN RECEPT 10

7 SPARE 20 A 1 0 VA 1260... 1 20 A DINNING ROOM 8

5 SPARE 20 A 1 0 VA 1260... 1 20 A EQUIPMENT STORAGE 6

3 SPARE 20 A 1 0 VA 360 VA 1 20 A BATHROOM 4

1 SPARE 20 A 1 0 VA 900 VA 1 20 A BMS 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Bus Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: ELEC EQUIP B6259 Volts: 208Y/120 A.I.C. Rating:

Panelboard: 5NLD

Notes:

Total Est. Demand: 33 A

Total Conn.: 38 A

Total Est. Demand: 11930 VA

Total Conn. Load: 13860 VA

Receptacle 13860 VA 86.08% 11930 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 39 A 41 A 36 A

Total Load: 4680 VA 4860 VA 4320 VA

41 SPARE 20 A 1 0 VA 720 VA 1 20 A WAITING ROOM 42

39 SPARE 20 A 1 0 VA 720 VA 1 20 A WAITING ROOM 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A FLUSH VALVES 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A OFFICES 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A OFFICES 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A OFFICES / 5C145 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A OFFICES 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A OFFICES 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A OFFICES 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A OFFICES 22

19 RM B6260A RECEPS, Bed Barn 20 A 1 1080... 0 VA 1 20 A LOCKER ROOMS 20

17 RM B6260A RECEPS, Bed Barn 20 A 1 540 VA 0 VA 1 20 A LOCKER ROOMS 18

15 RM B6260A RECEPS, Bed Barn 20 A 1 540 VA 720 VA 1 20 A OFFICES 16

13 RM B6260A RECEPS, Bed Barn 20 A 1 720 VA 720 VA 1 20 A OFFICES 14

11 RM B6260A RECEPS, Bed Barn 20 A 1 720 VA 720 VA 1 20 A OFFICES 12

9 RM B6260A RECEPS, Bed Barn 20 A 1 720 VA 720 VA 1 20 A OFFICES 10

7 RM B6260A RECEPS, Bed Barn 20 A 1 720 VA 720 VA 1 20 A CLASSROOM 8

5 RM B6260A RECEPS, Bed Barn 20 A 1 900 VA 720 VA 1 20 A CLASSROOM 6

3 RM B6260A RECEPS, Bed Barn 20 A 1 900 VA 540 VA 1 20 A CORRIDOR 4

1 RM B6260A RECEPS, Bed Barn 20 A 1 0 VA 720 VA 1 20 A CORRIDOR 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Bus Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: ELEC EQUIP B6259 Volts: 208Y/120 A.I.C. Rating:

Panelboard: 5NLC

Notes:

Total Est. Demand: 48 A

Total Conn.: 69 A

Total Est. Demand: 17420 VA

Total Conn. Load: 24840 VA

Receptacle 24840 VA 70.13% 17420 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 78 A 70 A 62 A

Total Load: 9180 VA 8280 VA 7380 VA

41 B6192 (LEAVE OFF PER O&M) 20 A 1 900 VA 0 VA 1 20 A SPARE 42

39 B6194 BATHROOM 20 A 1 540 VA 0 VA 1 20 A HOT CIRC PUMP ABOVE B6106 40

37 PATIENT BATHROOM 20 A 1 540 VA 180 VA 1 20 A PATIENT ROOM RECEP. 38

35 PATIENT BATHROOM 20 A 1 540 VA 360 VA 1 20 A PATIENT ROOM RECEP. 36

33 B6206 BATHROOM 20 A 1 900 VA 360 VA 1 20 A B6135 (LEAVE OFF PER O&M) 34

31 B6150 BATHROOM 20 A 1 720 VA 720 VA 1 20 A B6131 (LEAVE OFF PER O&M) 32

29 B6149/B6147 BATHROOM 20 A 1 720 VA 540 VA 1 20 A B6135/B6131 (LEAVE OFF PER O&M) 30

27 B6135/B6137 BATHROOM 20 A 1 1080... 360 VA 1 20 A B6137 (LEAVE OFF PER O&M) 28

25 PT ROOM 20 A 1 720 VA 720 VA 1 20 A B6149/B6147 (LEAVE OFF PER O&M) 26

23 WASHER 20 A 1 0 VA 540 VA 1 20 A B6149/B6147 (LEAVE OFF PER O&M) 24

21 ICE MAKER 20 A 1 180 VA 360 VA 1 20 A B6150 (LEAVE OFF PER O&M) 22

19 KITCHEN 20 A 1 360 VA 720 VA 1 20 A REC 5C118 GFCI 20

17 REFRIGERATOR 20 A 1 180 VA 540 VA 1 20 A B6150 (LEAVE OFF PER O&M) 18

15 SPARE 20 A 1 720 VA 720 VA 1 20 A B6206 (LEAVE OFF PER O&M) 16

13 SPARE 20 A 1 900 VA 720 VA 1 20 A B2604 (LEAVE OFF PER O&M) 14

11 SPARE 20 A 1 900 VA 720 VA 1 20 A B6204/B6206 (LEAVE OFF PER O&M) 12

9 SPARE 20 A 1 900 VA 720 VA 1 20 A B6200 (LEAVE OFF PER O&M) 10

7 CLASSROOM 20 A 1 720 VA 720 VA 1 20 A B6194/B6200 (LEAVE OFF PER O&M) 8

5 B6204 BATHROOM 20 A 1 720 VA 720 VA 1 20 A B6194/B6200 (LEAVE OFF PER O&M) 6

3 B6135 BATHROOM 20 A 1 720 VA 720 VA 1 20 A SPARE 4

1 PT BATHROOMS 20 A 1 900 VA 360 VA 1 20 A SPARE 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Bus Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: ELEC EQUIP B6139 Volts: 208Y/120 A.I.C. Rating:

Panelboard: 5NLB

1. Contractor shall provide a 30-day load test on the following panels: Building 12 (5NLA, 5NLB, 5NLC, 5NLD, 5ELA, 5ELB, 5ECA, GNLDP1, GNLDP2, GELL, GELC). Contractor shall provide load monitoring data to the COR/AE. All panels, at the time of design survey (January 2021) had the required capacity. This test is required by NEC 220.87 for verification that no loads have been added since the design level survey.

KEYNOTES-

1 1

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:3

P

M

E-603

ELECTRICAL EXISTING PANEL SCHEDULES -

EMERGENCY POWER

654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

Notes:

Total Est. Demand: 1 A

Total Conn.: 1 A

Total Est. Demand: 540 VA

Total Conn. Load: 540 VA

Receptacle 540 VA 100.00% 540 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 3 A 2 A 0 A

Total Load: 360 VA 180 VA 0 VA

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 PATIENT BATHROOM 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 PATIENT BATHROOM 20 A 1 0 VA 0 VA 1 20 A PATIENT BATHROOM 16

13 NURSE STATION 20 A 1 0 VA 0 VA 1 20 A PATIENT BATHROOM 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SIGN WEST/ATLANTIS 12

9 DOOR CONTROL/NURSE STATION 20 A 1 0 VA 0 VA 1 20 A SIGNS WEST 10

7 DOOR CONTROL/MAIN ENTRANCE 20 A 1 0 VA 0 VA 1 20 A CORRIDOR LIGHT/EXIST SIGNS 8

5 DOOR CONTROL/STAIR #2 20 A 1 0 VA 0 VA 1 20 A NURSE/EGRESS 6

3 DOOR CONTROL/END OF CORR SOUTH 20 A 1 0 VA 180 VA 1 20 A SIGN EAST/CENTER SHOP 4

1 DOOR CONTROL/CENTER CORR 20 A 1 0 VA 360 VA 1 20 A SIGNS EAST 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Bus Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: ELEC EQUIP B6139 Volts: 208Y/120 A.I.C. Rating:

Panelboard: 5ELA

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 0 A 0 A 0 A

Total Load: 0 VA 0 VA 0 VA

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A RECEPTACLE 10

7 SPARE 20 A 1 0 VA 0 VA 1 20 A RECEPTACLE 8

5 LOUNGE LIGHTS 20 A 1 0 VA 0 VA 1 20 A SPARE 6

3 CORRIDOR/EXIST SIGNS 20 A 1 0 VA 0 VA 1 20 A SMOKE DAMPERS 4

1 CORRIDOR 20 A 1 0 VA 0 VA 1 20 A SMOKE DAMPERS 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Bus Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: ELEC EQUIP B6259 Volts: 208Y/120 A.I.C. Rating:

Panelboard: 5ELB

Notes:

Total Est. Demand: 26 A

Total Conn.: 26 A

Total Est. Demand: 9540 VA

Total Conn. Load: 9540 VA

Receptacle 9540 VA 100.00% 9540 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 24 A 30 A 26 A

Total Load: 2880 VA 3600 VA 3060 VA

41 SPARE IN JBOX ABOVE 20 A 1 0 VA 180 VA 1 20 A PATIENT REST ROOM 42

39 SPARE IN JBOX ABOVE 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 40

37 SPARE IN JBOX ABOVE 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 38

35 SPARE IN JBOX ABOVE 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 36

33 SPARE IN JBOX ABOVE 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 34

31 ANTI-LIGATURE ALARM SYSTEM 20 A 1 0 VA 180 VA 1 20 A PATIENT REST ROOM 32

29 PATIENT ROOM/ELEC ROOM LTS. 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 30

27 BATHROOM 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 28

25 BATHROOM 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 26

23 NL PAT RMS / NITE LITES WEST 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 24

21 NL PAT RMS / NITE LITES EAST 20 A 1 0 VA 360 VA 1 20 A PATIENT REST ROOM 22

19 NURSE STATION 20 A 1 180 VA 540 VA 1 20 A CCTV 6TH FLOOR 20

17 NURSE STATION 20 A 1 180 VA 540 VA 1 20 A CCTV 6TH FLOOR 18

15 NURSE STATION 20 A 1 720 VA 360 VA 1 20 A PAT ROOM 16

13 SIGNAL ROOM / IRM 20 A 1 180 VA 0 VA 1 20 A NURSE STATION 14

11 SIGNAL ROOM / IRM 20 A 1 360 VA 0 VA 1 20 A PAT BR / B6135 LIGHT 12

9 SIGNAL ROOM / IRM 20 A 1 360 VA 0 VA 1 20 A PAT BR-TOILET TRANSFORMER 10

7 ELECTRICAL ROOM 20 A 1 360 VA 0 VA 1 20 A PATIENT REST ROOM 8

5 NURSE STATION 6TH FLOOR 20 A 1 720 VA 0 VA 1 20 A SPAREPATIENT REST ROOM 6

3 NURSE STATION 6TH FLOOR 20 A 1 720 VA 0 VA 1 20 A PATIENT REST ROOM 4

1 NURSE STATION 6TH FLOOR 20 A 1 720 VA 0 VA 1 20 A PATIENT REST ROOM 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: Type 1

Mounting: Surface Wires: 4 Bus Rating: 225 A

Supply From: Phases: 3 Mains Type: MLO

Location: ELEC EQUIP B6139 Volts: 208Y/120 A.I.C. Rating:

Panelboard: 5ECA

1. Contractor shall provide a 30-day load test on the following panels: Building 12 (5NLA, 5NLB, 5NLC, 5NLD, 5ELA, 5ELB, 5ECA, GNLDP1, GNLDP2, GELL, GELC). Contractor shall provide load monitoring data to the COR/AE. All panels, at the time of design survey (January 2021) had the required capacity. This test is required by NEC 220.87 for verification that no loads have been added since the design level survey.

KEYNOTES-

File details come from the government source that posted it. Updated .