654-20-117 Mental Health EOC_Part5.pdf
PDF 10 MB Posted
- Attached to
- Y1DA--Mental Health EOC Compliance Federal contract opportunity
- Solicitation number
- 36C26121R0072
About this file
This federal contract opportunity solicitation seeks compliance services for inpatient mental health facilities. Solicitation number 36C26121R0072 was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21 for projects 654-20-141 and 654-17-713 related to inpatient mental health EOC compliance and door frames/doors. The solicitation involves assessing and ensuring compliance of inpatient mental health facilities with Emergency Operations Center requirements and replacing or upgrading door frames and doors. The response due date and award date were not provided. Pricing terms and set-asides were also not specified. The federal agency involved is the Department of Veterans Affairs.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAX
AIRFLOW
H O
T W
ATER
FLO
W
R E
L A
T
IV
E A
IR
F
L O
W
100%
0%
CONTROL SIGNAL, PERCENT
0 10050
VARIABLE AIR VOLUME CONTROL
MIN COOLING
AIRFLOW
VARIABLE AIR VOLUME (VAV) TERMINAL UNIT SEQUENCE OF OPERATION:
OPERATION:
The occupied period will be scheduled through the Energy Management System (EMS). During the unoccupied mode, the VAV box will maintain required temperature and flow setpoints.
The unit shall maintain zone setpoints [+/- 2 degree F.] by controlling the air and water flow through one of the following:
Occupied:
• If the VAV box room temperature (RM-T) is higher than the room temperature setpoint (RM-TSET), the VAV controller will reset the CFM setpoint upwards from the minimum CFM setpoint to the maximum CFM setpoint.
• When zone temperature is greater than its cooling setpoint, the zone damper shall modulate between the minimum occupied airflow (adj.) and the maximum cooling airflow (adj.)
until the zone is satisfied.
• When the zone temperature is between the cooling setpoint and the heating setpoint, the zone damper shall maintain the minimum required zone ventilation (adj.).
• If the VAV box room temperature (RM-T) is lower than the room temperature setpoint (RM-TSET), the VAV controller shall modulate the VAV box reheat valve to achieve the setpoint. The VAV controller shall modulate the damper in order to maintain the minimum setpoint.
• If the VAV is at minimum airflow position and the zone temperature continues to be below setpoint; increase the supply air temperature up to be 15 deg F greater than RM-TSET.
• If the supply air temperature is 15 deg F higher than RM-TSET and the zone temperature remains below RM-TSET, increase the airflow setpoint up to the heating maximum.
• Modulate the HHW valve as required to maintain the supply air temperature setpoint.
• Reverse the heating sequence above as zone temperature rises.
Unoccupied:
• When the zone is unoccupied the zone damper shall control to its minimum unoccupied airflow (adj.).
• When the zone temperature is greater than its cooling setpoint, the zone damper shall modulate between the minimum unoccupied airflow (adj.) and the maximum cooling airflow
(adj.) until the zone is satisfied.
• When zone temperature is less than its unoccupied heating setpoint, the controller shall enable heating to maintain the zone temperature at the setpoint. Additionally, if warm air is available from the AHU, the zone damper shall modulate between the minimum unoccupied airflow (adj.) and the auxiliary heating airflow (adj.) until the zone is satisfied.
Run Conditions - Scheduled:
The unit shall run according to a user definable time schedule in the following modes:
• Occupied Mode: The unit shall maintain
• A 75°F (adj.) cooling setpoint
• A 70°F (adj.) heating setpoint.
• Unoccupied Mode (night setback): The unit shall maintain
• A 85°F (adj.) cooling setpoint.
• A 55°F (adj.) heating setpoint.
ROOM TEMPERATURE AND RETURN AIR TEMPERATURE SETPOINTS:
The room temperature setpoint (RM-TSET) will be adjustable by the user at the wall mounted room temperature sensor or by the the facilities operations staff for all duct mounted temperature sensors. The existing EMS shall be programmed by the contractor to provide RM-TSET set points as indicated on this sheet for each type of space.
Note: For areas with mental health patient access, existing thermostats shall be replaced with return air duct temperature probes and all set point adjustment shall be through the FMS and not wall-mounted thermostats. To avoid over-cooling the room, return air sensor setpoints shall be calibrated such that the room temperature at 60" above finish floor meets room setpoint requirements.
ALARMS AND WARNING:
An alarm shall be sent to the EMS system upon any of the following conditions:
• The room temperature is greater than 86 degrees F. (adj.) or less than 54 degrees F. (adj.)
• Supply airflow is 30% or more below setpoint, delay time 5 minutes.
• Temperature or flow sensor not reporting a value.
A warning shall be sent to the EMS system under any of the following conditions:
• The room temperature rises more than 5 degrees F. (adj.) above the room temperature setpoint.
• The room temperature falls more than 5 degrees F. (adj.) below the room temperature setpoint.
REHEATING - HIGH DISCHARGE AIR TEMPERATURE LIMIT:
The controller shall measure the discharge air temperature and limit reheating if the discharge air temperature is more than 95°F (adj.).
DISCHARGE AIR TEMPERATURE:
The controller shall monitor the discharge air temperature.
Alarms shall be provided as follows:
• High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).
• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.).
NOTES:
1. TERMINAL UNIT SHALL PROVIDE
THE FLOW CHARACTERISTICS
SHOWN ON THE GRAPH. EACH
TERMINAL SHALL BE EQUIPPED
WITH ITS OWN STAND ALONE
CONTROLLER WHICH SHALL HAVE
THE CAPABILITIES DESCRIBED IN
THE SPECIFICATION. THE WIRING
SHOWN IS PROVIDED AS A
GENERAL DESCRIPTION AND IS
NOT A DETAILED WIRING DIAGRAM
WHICH VARIES WITH THE
MANUFACTURER.
2. CONTRACTOR TO MATCH EXISTING
AIR AND WATER FLOW SET POINTS
FROM PRE-CONSTRUCTION TAB
REPORT .
R E
L A
T
IV
E H
H W
F L O
W
MAX HEATING
AIRFLOW
100%
0%
TT
FCV
CONTROL POWER
FROM LAST UNIT ON LAN
TO NEXT UNIT ON LAN
C
H
CONTROLLER
DDC
AIR
SUPPLY
TCV
HWR
N.C.
HWS
SUPPLY
AIR FLOW
SENSOR
DUCT MOUNTED
TEMPERATURE SENSOR
TT
NEW DUCT MOUNTED RETURN
AIR TEMPERATURE SENSOR
LOCATE WITHIN 5' OF THE
RETURN AIR GRILLE AND
ADJACENT TO EXISTING ACCESS
PANELS FOR FUTURE
MAINTENANCE AND ADJUSTMENT
AIR
RETURN
FOR MENTAL HEALTH PATIENT AREAS
(OTHER SPACES SHALL USE WALL-
MOUNTED THERMOSTATS)
50 1000
CONTROL SIGNAL, PERCENT
0%
100%
R E
L A
T
IV
E A
IR
F
L O
W
HO
T W
ATER FLO
W
CONSTANT AIR VOLUME CONTROL
CONSTANT AIR VOLUME (CAV) TERMINAL UNIT SEQUENCE OF OPERATION:
OPERATION:
The occupied period will be scheduled through the Energy Management System (EMS). During the unoccupied mode, the CAV box will maintain required temperature and flow setpoints. The unit shall maintain zone temperature setpoints [+/- 2 degree F.] with constant airflow through one of the following:
Occupied:
• The zone damper shall modulate to maintain a constant occupied airflow (adj.) distributed into the zone.
• When the CAV box room temperature is lower than the room temperature setpoint (RM-TSET), the CAV controller shall modulate the CAV box reheat valve to achieve the setpoint. Increase CAV supply temperature measured by TT. Reheat valve modulates to maintain setpoint.
• Reverse sequence above as temperature in space rises.
Unoccupied:
• The zone damper shall modulate to a constant unoccupied airflow (adj.) distributed into the zone.
• When zone temperature is less than its heating setpoint, the controller shall enable heating to maintain the zone temperature at its unoccupied heating setpoint.
Night Setback:
• The CAV box, associated Air Handling Unit, and associated CAV boxes will be indexed to the occupied mode if the CAV box room temperature is greater than the unoccupied cooling setpoint of 85 degrees F. (adj.), or lower than the unoccupied heating setpoint of 55 degrees F. (adj.). the Air Handling Unit and associated boxes will return to the unoccupied mode once the cooling and heating setpoints are satisfied [+/- 2 degree F.].
Run Conditions - Scheduled:
The unit shall run according to a user definable time schedule in the following modes:
• Occupied Mode: The unit shall maintain
• A 75°F (adj.) cooling setpoint
• A 70°F (adj.) heating setpoint.
• Unoccupied Mode (night setback): The unit shall maintain
• A 85°F (adj.) cooling setpoint.
• A 55°F (adj.) heating setpoint.
ROOM TEMPERATURE SETPOINT:
The room temperature setpoint (RM-TSET) will be adjustable by the facilities operations staff. The existing EMS shall be programmed by the contractor to provide RM- TSET set points as indicated on this sheet for each type of space.
Note: For areas with mental health patient access, existing thermostats shall be replaced with return air duct temperature probes and all set point adjustment shall be through the FMS and not wall-mounted thermostats. To avoid over-cooling the room, return air sensor setpoints shall be calibrated such that the room temperature at 60" above finish floor meets room setpoint requirements.
FLOW CONTROL:
The CAV controller will modulate the damper in order to maintain the CFM setpoint.
ALARMS AND WARNING:
An alarm shall be sent to the EMS system upon any of the following conditions:
• The room temperature is greater than 86 degrees F. (adj.) or less than 54 degrees F. (adj.)
• Supply airflow alarm: is 15% below setpoint, delay time 5 minutes.
• Temperature or flow sensor not reporting a value.
A warning shall be sent to the EMS system under any of the following conditions:
• The room temperature rises more than 5 degrees F. (adj.) above the room temperature setpoint.
• The room temperature falls more than 5 degrees F. (adj.) below the room temperature setpoint.
REHEATING COIL VALVE:
The controller shall measure the zone temperature and modulate the reheating coil valve open on dropping temperature to maintain its heating setpoint. Controller should increase zone supply air temperature setpoint to meet zone temperature. Reheat coil modulates to maintain supply air temperature setpoint.
DISCHARGE AIR TEMPERATURE:
The controller shall monitor the discharge air temperature.
Alarms shall be provided as follows:
• High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).
• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.).
NOTES:
1. TERMINAL UNIT SHALL PROVIDE THE
FLOW CHARACTERISTICS SHOWN ON
THE GRAPH. EACH TERMINAL SHALL BE
EQUIPPED WITH ITS OWN STAND ALONE
CONTROLLER WHICH SHALL HAVE THE
CAPABILITIES DESCRIBED IN THE
SPECIFICATION. THE WIRING SHOWN IS
PROVIDED AS A GENERAL DESCRIPTION
AND IS NOT A DETAILED WIRING
DIAGRAM WHICH VARIES WITH THE
MANUFACTURER.
2. CONTRACTOR TO MATCH EXISTING AIR
AND WATER FLOW SET POINTS FROM
PRE-CONSTRUCTION TAB REPORT .
R E
L A
T
IV
E H
H W
F L O
W
0%
100%
DESIGN AIR FLOW
TT
FCV
CONTROL POWER
FROM LAST UNIT ON LAN
TO NEXT UNIT ON LAN
C
H
CONTROLLER
DDC
AIR
SUPPLY
TCV
HWR
N.C.
HWS
SUPPLY
AIR FLOW
SENSOR
TT
NEW DUCT MOUNTED RETURN
AIR TEMPERATURE SENSOR
LOCATE WITHIN 5' OF THE
RETURN AIR GRILLE AND
ADJACENT TO EXISTING ACCESS
PANELS FOR FUTURE
MAINTENANCE AND ADJUSTMENT
AIR
RETURN
FOR MENTAL HEALTH PATIENT AREAS
(OTHER SPACES SHALL USE WALL-
MOUNTED THERMOSTATS)
DUCT MOUNTED
TEMPERATURE SENSOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
1345 CAPITAL BLVD. SUITE A
RENO, NA 89502
MAT PERKINS
520-481-8548
/12
/20
B
IM
/6
-2
-1
I n p a ti e n t M e n ta l H e a lt h E
O C
C o m p lia n c e R e n o v a ti o n s /6
-2
-1
.1
.M
E P
F .r v t
/1
/2
:2
:3
P
M
M-802
MECHANICAL CONTROL DIAGRAMS 654-20-117
02/12/2021 M. PERKINS K. LUKE
BID DOCUMENT
SUBMITTAL
INPATIENT MENTAL HEALTH EOC
COMPLIANCE RENOVATIONS
975 KIRMAN AVENUE RENO, NV 89502-0993
SCALE: NOT TO SCALE
F8
TYPICAL VAV TERMINAL UNIT
CONTROL DIAGRAM
SCALE: NOT TO SCALE
F5
TYPICAL CAV TERMINAL UNIT
CONTROL DIAGRAM
Revisions: Date:
LOW VOLTAGE (BELOW 50 VOLTS)
L-L
L-N
LTG
LV
LIGHTING
LINE TO LINE
LINE TO NEUTRAL X
XFMR
% Z
WP
WHM
1000 CIRCULAR mils
KILOVOLTS (THOUSAND VOLTS)
KILOWATTS (THOUSAND WATTS)
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)
ISOLATED GROUND
KWH
LAN
LA
KW
KVA
Kcmil
KV
KILOWATT-HOURS
INCAND
KEY INTERLOCK
JUNCTION BOX
INCH/INCHES (")
INCANDESCENT
W/
W/O
W
VFD
VA
V
UPS
UL
UON
UG
UGS
UGT
UGP
GROUND FAULT INTERRUPTER
HAND-OFF-AUTOMATIC
HIGH PRESSURE SODIUM
HEATING VENTILATION AND AIR CONDITIONINGHERTZ
HVAC
HZ
HTR
HR
HT
HPS
HOA
HP
HEATER
HEIGHT
HORSEPOWER
HOUR
GFI
G, GND, GRD
GEN
FLUOR
FL, FLR
GROUND
GENERATOR
FOOT/FEET (')
FLUORESCENT
FLOOR
TYP
TV
TP
TEL,TELE
TELECOM
TC
SPST
SWBD
SYM
STD
SW
SPEC(S)
SPDT
SPKR
SF
SEC
PERCENT IMPEDANCE
TRANSFORMER
REMOVE DEVICE
WATT HOUR METER
WEATHERPROOF
VOLTS
VARIABLE FREQUENCY DRIVE/
VARIABLE FREQUENCY MOTOR
CONTROLLER
WITHOUT
WITH
WIRE
VOLT-AMPERES
UNDERGROUND PRIMARY
UNDERGROUND SECONDARY
UNDERGROUND TELEPHONE
UNDERWRITER'S LABORATORY
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
UNDERGROUND
TELECOMMUNICATIONS
TYPICAL
TELEVISION
TAMPERPROOF
TIME CLOCK
TELEPHONE
SINGLE POLE SINGLE THROW
SINGLE POLE DOUBLE THROW
SYMMETRICAL
SWITCHBOARD
STANDARD
SWITCH
SECONDARY
SQUARE FOOT
SPECIFICATION(S)
SPEAKER
CATV
PRI
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FIRE ALARM ANNUNCIATOR PANEL
ELECTRIC, ELECTRICAL
ELECTRIC METALLIC CONDUIT
EQUIPMENT GROUND
EWC
FAAP
FLA
FDR
EWH
FA
FULL LOAD AMPS
FEEDER
FIRE ALARM
FUSE
ELEC
EQ, EQUIP
EM, EMERG
EMT
ELEV
ENCL
EG
EQUIPMENT
ELEVATOR
EMERGENCY
ENCLOSURE
RCLP
RM
SCH, SCHED
RP
REF
RCPT
RSC
RLA
RF
R, RE
QTY
PWR
PT
PVC
DISTRIBUTION PANEL
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
DPDT
DWG
DPST
DIST
DISC
DC
DP
DN
DRAWING
DISTRIBUTION
DIRECT CURRENT
DISCONNECT
DOWN
CPT
CU
CT
COM, COMM
CKT
CLG
COPPER
COMMUNICATIONS
CIRCUIT
CEILING
PA
PH, ∅
PF
PNL
PE
PB
P
OPP
OHE/T
OH
OFOI
OFCI
NO., NUM, #
OC
NTS
CABLE TELEVISION
AMERICAN WIRE GAUGE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTOMATIC TRANSFER SWITCH
AMPERE INTERRUPTING CAPACITY
ALTERNATING CURRENT
ABOVE FINISHED COUNTER
AWG
CB
BLDG
BRKR, BKR
CIRCUIT BREAKER
CONDUIT
BUILDING
BREAKER
AUTO
AUX
ARCH
AT
ATS
ALT
AFG
AIC
AFC
AFF
AC
AF
AUXILIARY
ALTERNATE
ARCHITECT
AUTOMATIC
AMPERES TRIP
AMPERE FRAME (BREAKER RATING)
MTG
NC
NEMA
NO
NIC
NEC
N
MV
MH
MOCP
MTD
MLO
MIN
MISC
MECH
MCC
MFR
MCA
MCB
RIGID STEEL CONDUIT
RATED (RUNNING) LOAD AMPS
RECEPTACLE PANELBOARD
ROOM
SCHEDULE
RADIO FREQUENCY
RECEPTACLE
REFRIGERATOR
RELOCATE AS SHOWN
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
REMOTE CONTROL LIGHTING PANEL
QUANTITY
POWER
PUBLIC ADDRESS
PANEL
PRIMARY
PULL BOX
POWER FACTOR
PHOTO ELECTRIC
PHASE
POLE
OPPOSITE
OWNER FURNISHED, CONTRACTOR INSTALLED
OWNER FURNISHED, OWNER INSTALLED
OVERHEAD ELECTRIC/TELEPHONE
OVERHEAD
ON CENTER
NOT TO SCALE
NUMBER
MOUNTING
NATIONAL ELECTRICAL CODE
MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)
NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NORMALLY CLOSED
NORMALLY OPEN
NOT IN CONTRACT
NEUTRAL
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAXIMUM OVERCURRENT PROTECTION
MOUNTED
MISCELLANEOUS
MAIN LUGS ONLY
MINIMUM
MANHOLE
MANUFACTURER
MECHANICAL
FIRE ALARM CONTROL PANELFACP
FIRE ALARM EXTENDER PANELFAEP
SWGR SWITCHGEAR
AIR HANDLING UNITAHU
CCTV CLOSED CIRCUIT TELEVISION
CP CONTROL PANEL
FLEX FLEXIBLE
HAND HOLEHH
LIGHTING CONTROL PANELLC, LCP
LIGHTING PANEL
L-G LINE TO GROUND
MTS MANUAL TRANSFER SWITCH
PDP POWER DISTRIBUTION PANEL
TB TERMINAL BLOCK
TBB TELEPHONE BACKBOARD
AMPERESAMP
C
F
EXISTINGE, EX, EXIST
FT
IN
IG
JB, JBOX
K
LP
FOOT CANDLEFC
DIV DIVISION
OCPD OVERCURRENT PROTECTION DEVICE
ELECTRICAL ABBREVIATIONS
A M
B
C
D
E
F
G
H
I
J
K
N
O
P
Q
R
S
T
U
V
W
X
L
Z
J J
J
M
V
SP
R
GB
VFD
LCP
LRP
AFB
NCC
MS
1P
2P
E
DS
SS
B
MO
FBX
ET
M
M
C
DTDT
A-1
PH
D
P
K a
L
OS
R
B
CB
MD
MD
SP
VP
TV
XX
DC
C
CCTV
DM
R/D
CCTV
DGP
RX
ELM
DO
AC
K
AC
E
K
ATS
TBB
T
TMH
EMH
EHH
X
PSD
EMU
FB
UG
GB
G
PB
SR-X
6-30R
UPS
CT
DOOR CONTACT SWITCH
ACCESS FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)
FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)
CONTACTOR
VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER
MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.
PUSHBUTTON STATION
CCTV SURVEILLANCE CAMERA OUTLET - WALL MTD, UON
CCTV SURVEILLANCE CAMERA OUTLET - CEILING MTD
DOOR MONITOR SWITCH
RECEIVER/DRIVER UNIT
NURSE CALL CONTROL EQUIPMENT PANEL (RECESSED/SURFACE)
NURSE CALL EMERGENCY STATION - PULL CORD TYPE IN
TOILETS & SHOWERS, PUSH-BUTTON TYPE IN ALL OTHER
PLACES
NURSE CALL BEDSIDE STATION, DOUBLE PATIENT
NURSE CALL BEDSIDE STATION, SINGLE PATIENT
NURSE CALL MASTER STATION
GLASS BREAK DETECTOR
NURSE CALL DOME LIGHT
PATIENT MONITORING OUTLET
CODE BLUE CALL STATION
NURSE CALL STAFF STATION
NURSE CALL DUTY STATION
LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE
EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL
ARROWS AS INDICATED SHADING INDICATES ILLUMINATED
FACE
LIGHTING TRACK - "X" DENOTES TYPE
UTILITY LIGHTING FIXTURE - TYPE AS INDICATED
WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED
SITE LIGHTING FIXTURE TYPE AS INDICATED
LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)
JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE
ALARM SYSTEMS PLANS.
DIRECT CONNECTION TO EQUIPMENT
SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)
DIMMER SWITCH
SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE
THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)
KEY OPERATED SWITCH
SINGLE POLE SWITCH WITH PILOT LIGHT
FOUR - WAY SWITCH
FUSED SWITCH
DELTA CONNECTION
CPT
PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)
ELECTRIC INTERLOCK SYSTEM
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
PHOTO CELL
KEY INTERLOCKING SYSTEM
WYE CONNECTION - SOLID GROUND
SWITCH - SINGLE THROW
TELECOMMUNICATIONS BACKBOARD
MOTOR CONTROL CENTER
TELEPHONE MANHOLE
ELECTRIC MANHOLE
FUSE
BUS DUCT PLUG-IN UNIT
GROUND
AUTOMATIC TRANSFER SWITCH
DRAWOUT TYPE, CIRCUIT BREAKER
STATIONARY CIRCUIT BREAKER
DISCONNECT SWITCH, FUSED.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY,
UON
GROUND ROD
DISCONNECT SWITCH, NON-FUSED
PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, FLOOR MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)
TELECOMMUNICATIONS DATA OUTLET, FLOOR MTD SERVICE FITTING, SURFACE TYPE
("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)
TELECOMMUNICATIONS VOICE OUTLET, FLOOR MTD SERVICE FITTING, SURFACE TYPE
("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, WALL MTD.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
TRANSFORMER - TYPE AND RATING AS INDICATED
COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER
AMPACITY, UON
PANELBOARD - (FLUSH/SURFACE)
DISTRIBUTION PANELBOARD
TELECOMMUNICATIONS VOICE OUTLET, WALL MTD
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER, "W" INDICATES WALL PHONE HEIGHT,
"PY" INDICATES PAY PHONE)
TELECOMMUNICATIONS DATA OUTLET, WALL MTD
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER, "W" INDICATES WALL PHONE HEIGHT)
ELECTRIC HANDHOLE
LIGHTING CONTROL PANEL, SURFACE MTD. UON.
LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON
UNINTERRUPTIBLE POWER SUPPLY
SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]
[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]
[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]
SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH
(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]
a
LOW VOLTAGE SWITCH
JUNCTION BOX - FLOOR MOUNTED
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, CEILING MTD SERVICE
FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE)
MOTOR AND CONNECTION
EMERGENCY POWER OFF
REQUEST-FOR-EXIT SENSOR
ELECTRIC LOCKING/LATCHING AND MONITORING HARDWARE
ACCESS CONTROL STATION - KEYPAD TYPE
ACCESS CONTROL STATION - CARD TYPE
DOOR OPERATING EQUIPMENT
DATA GATHERING PANEL
NURSE CALL DOME LIGHT CEILING MTD
("Z" SUBSCRIPT DENOTES ZONE DOME LIGHT)
CODE BLUE WITH RED PHONE, WALL MTD, MOUNTED 48" AFF
CODE BLUE WITH BLUE LIGHT, WALL MTD, MOUNTED 48" AFF
MOTION DETECTOR - CEILING MTD
MOTION DETECTOR - WALL MTD
TELECOMMUNICATIONS DATA OUTLET, CEILING MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE)
TELECOMMUNICATIONS VOICE OUTLET, CEILING MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE)
POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE
CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.
COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.
SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
FLOOR MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,
2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON
FACEPLATE.
FLOOR MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX
RECEPTACLES WITH A COMMON FACEPLATE.
FLOOR MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. PROVIDE CORE
DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT
AND WIRING IN CEILING SPACE OF FLOOR BELOW TO ELECTRICAL CLOSET
OR PANELBOARD.
FLOOR MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,
2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.
FLOOR MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.
SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P,
3W. (SLASH INDICATES MOUNTING ABOVE FINISH
COUNTER)
QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,
DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON
FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
RECEPTACLES MOUNTED ABOVE THE CEILING.
QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES
WITH A COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH
COUNTER)
CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX
RECEPTACLES WITH A COMMON FACEPLATE.
GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
ELECTRONIC METERING UNIT
GROUND BUS
GROUND CABLE, SIZE AS INDICATED
PLUG-IN BUSWAY
FEEDER BUSWAY
UNDERGROUND CONDUIT/DUCTBANK
CABLE TRAY
CONDUIT TURNED DOWN
CONDUIT TURNED UP
CONDUIT CAST IN CONCRETE OR BELOW SLAB
CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED
AREAS OR BELOW ACCESS FLOORS
HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED
TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING
COMBINATION TV OUTLET AND DUPLEX RECEPTACLE ON SINGLE
FACEPLATE
SPEAKER - WALL MTD
PA VOLUME CONTROL
MICROPHONE OUTLET - CEILING MTD
MICROPHONE OUTLET - WALL MTD
MICROPHONE OUTLET - FLOOR MTD
SPEAKER - CEILING MTD
RECORDING OUTLET
COMBINATION VIDEO PROJECTOR OUTLET AND DUPLEX RECEPTACLE
CLOCK OUTLET, W/RECPT AND HANGER
CLOCK OUTLET, MASTER CLOCK
CLOCK OUTLET, ELAPSED TIME
GENERATORG
SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)
WALLWASH LIGHT FIXTURE,
DEMOLITION WORK
OCCUPANCY SENSOR WALL SWITCH
M
HC ADA PUSH BUTTON.
ELECTRICAL LIGHTING SYMBOLS ELECTRICAL POWER SYMBOLS GENERAL NOTES
A INTERCOMMUNICATION SYSTEM ( AI PHONE)
A B C A B C
SPD SURGE PROTECTIVE DEVICE
P P
PD PD
D D
POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE
SYSTEM AS SPECIFIED.
COMBINATION POWER AND TELECOMMUNICATIONS FLOOR OR WALL MOUNTED BOX FOR
POWER AND DATA CONNECTION - INDICATED IN POWER & SPECIAL SYSTEMS PLANS.
JUNCTION BOX FLOOR OR WALL MOUNTED FOR CONNECTION TO FURNITURE SYSTEM.
MOUNTING HEIGHT NOTES:
1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.
2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH
CASEWORK.
3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.
4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE
MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.
WALL SWITCHES
RECEPTACLES
TELECOMMUNICATIONS OUTLETS
TELECOMMUNICATIONS OUTLETS - WALL PHONE
CLOCK OUTLETS
TV OUTLETS
PUSHBUTTONS
VOLUME CONTROLS
NURSE CALL STATIONS
NURSE CALL DOME LIGHTS
DIMMERS
ACCESS CONTROL DEVICES
VANITY LIGHT IN TOILET
INTERCOM
FIREMAN'S PHONE
FIRE ALARM - PULL STATIONS
FIRE ALARM DEVICES HORN/SPEAKERS/STROBES
(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR
6" BELOW CEILING WHICH IS LOWER)
4'-0" AFF
1'-6" AFF
1'-6" AFF
4'-0" AFF
7'-0" AFF
1'-6" AFF
4'-0" AFF
4'-0" AFF
4'-0" AFF
7'-6" AFF
4'-0" AFF
4'-0" AFF
6" ABOVE THE MIRROR, UON
4'-0" AFF
4'-0" AFF
4'-0" AFF
7'-2" AFF TO TOP
HORIZONTAL MOUNTINGH
PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF
THREE CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL
DRAWINGS PRIOR TO ROUGH-IN.
PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR
SLABS, WALLS AND CEILINGS TO MAINTAIN FIRE RATING.
INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CODE AND LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE
MANNER.
LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE
DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.
REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING
MOUNTED DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL
PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS
AND A COMMON FACEPLATE.
WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING
HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS
FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED
IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES,
UON.
WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE
EXIT SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP
OF DOOR FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM
OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED
EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT. COORDINATE WITH
ARCHITECTURAL DETAILS.
EXIT SIGNS ARE TO BE TYPE "X1", UON.
PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.
PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR
GREATER THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.
FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL
LOCATION OF ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND
FINAL FURNITURE PLANS PRIOR TO INSTALLATION.
MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE
DRAWINGS AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC.
PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL
SYSTEMS.
WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY
CONNECT RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.
A.
B.
C.
D.
E.
F.
G.
H.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
ELTD EMERGENCY LIGHTING TRANSFER DEVICE
SECURITY SYSTEM SYMBOLS
TELECOMMUNICATION SYMBOLS
NURSE CALL SYSTEM SYMBOLS
MOUNTING HEIGHTS
ELECTRICAL EQUIPMENT SYMBOLS
ELECTRICAL WIRING SYMBOLS
DISTRIBUTION AND DIAGRAM SYMBOLS
REFERENCE SYMBOLS
SECTION NUMBER
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
E1-1.0
KEY NOTE
1 DEMO KEY NOTE
SPECIAL SYSTEM OUTLET SYMBOLS
CB
E1-1.0
DISCONNECT SWITCHES
MOTOR STARTERS
PANELBOARDS & CABINETS
INDIVIDUAL CIRCUIT BREAKERS
5'-6" AFF
5'-6" AFF
6'-0" AFF TO TOP
5'-6" AFF
x
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
1345 CAPITAL BLVD. SUITE A
RENO, NA 89502
MAT PERKINS
520-481-8548
/12
/20
B
IM
/6
-2
-1
I n p a ti e n t M e n ta l H e a lt h E
O C
C o m p lia n c e R e n o v a ti o n s /6
-2
-1
.1
.M
E P
F .r v t
/1
/2
:2
:5
P
M
E-000
ELECTRICAL ABBREVIATIONS AND SYMBOLS 654-20-117
02/12/2021 M. PERKINS G. WEAVER
BID DOCUMENT
SUBMITTAL
INPATIENT MENTAL HEALTH EOC
COMPLIANCE RENOVATIONS
975 KIRMAN AVENUE RENO, NV 89502-0993
C P
E
N
E
N
E
N
E N
E
N
E
N
E N
E
N
E
N
E N
E N
E
N
E
N
E
N
NNNNN
N N
N
N
N
N
N
5NLB- 36
5NLC- 42
5NLC- 42
5NLC- 405NLC- 40
5NLC- 40
5NLC- 40
5NLC- 42
5NLC- 42
5NLB- 36
5NLB- 25
5NLB- 25
5NLB- 1
5NLB- 38
5ECA- 16
5ECA- 16
5NLB- 1 5NLB- 1
5NLB- 1
5NLB- 25
5NLB- 25
5NLB- 27
5NLB- 30
5NLB- 32
5NLB- 32
5NLB- 32
5NLB- 32 5NLB- 34
5NLB- 34
5ECA- 40
5ECA- 40
5ECA- 42
5NLB- 3
5NLB- 3
5NLB- 3
5NLB- 3
5NLB- 15
5NLB- 15
5NLB- 15
5NLB- 15
5NLB- 41
5NLD- 8
5NLD- 12
5NLD- 12
5NLD- 12
5NLB- 27
5NLB- 27
5NLB- 27
5NLB- 39
5NLB- 39
5NLB- 41
5NLB- 41
5NLB- 41
5ECA- 22
5NLB- 2
5NLB- 4
5NLB- 4
5ECA- 22
5NLB- 4
5NLB- 4
5NLB- 2
5NLB- 41
5NLA- 26
5NLA- 26
5NLA- 12
5NLA- 8
5NLA- 8
5NLA- 12
5NLA- 26
5NLA- 8
5NLA- 8
5NLA- 17 5NLA- 175NLA- 17
5NLA- 6
5NLA- 6
5NLA- 6
5NLA- 8
5NLA- 6
5NLA- 6
5NLA- 6
5NLA- 2
5NLA- 2
5ECA- 5
5ECA- 5
5ECA- 5
5ECA- 5
5ECA- 3
5ECA- 3
5ECA- 3
5ECA- 3 5E
C
A
5E C
A
5E C
A
5E C
A
5N L
A
5E C
A
5E C
A
5ECA- 17 5ECA- 19
5ECA- 15
5ECA- 15
5NLA- 10
5NLA- 10
5N
LA
5N
LA
5NLA- 2
5NLA- 2
5NLD- 65NLD- 6
5NLD- 6
5NLD- 6
5NLD- 6
5NLD- 8
5NLD
5NLD- 6
5NLA- 10
5NLA- 10
5NLA- 26
5NLD- 8
5NLD- 8
5NLD- 8
5NLD- 14
5NLD- 16
5NLC
5NLC
5NLC- 3
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLD- 10
5NLD- 10
5NLD
5NLD
5NLD
5NLD- 10
5NLD- 10
5NLD
5NLD
5NLD
5ECA- 18
5NLB- 30 5NLB- 30
5NLB- 27
5NLB- 1
5ECA- 18
5ECA- 18
5NLD- 8
5NLD- 8
5NLB- 27
5ECB
5NLC
5NLD
5EHEB
5NHB
5ELB
5NLC- 19
5NLC- 19
5NLD
5NLC
5NLC
5NLC 5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLD- 40
F
7.6
9.4
G
RECIEVING
B6127
BATH
B6131A
BATH
B6127A
TWO BED
B6131
ONE BED
B6135
HAC
B6133 BATH
B6137A
BATH
B6135A
BATH
B6192A
BATH
B6194A
TWO BED
B6192
SUN DECK
B6188
SECLUSION
B6134A
ANTE RM
B6134
TOILET
B6134B
TOILET
B6193B
SECLUSION
B6193A ANTE RM
B6193
NURSE STATION
B6128
MEDICATION
B6128A
WORK RM HOUSE
STAFF
B6104
STAFF TOILET
B6125
COPY
B6124
HAC
B6184A
DAY RM
RECREATION
B6184
NON-FOOD STRG
5C139
TOILET
5C138
TOILET
5C137
PSYCHIATRIST
OFFICE
5C144
HEAD NURSE
5C143
TELE
B6184C
ADL KITCHEN
5C133C
CORRIDOR
B6C06
ELEVATOR
LOBBY
B6EGD
CORRIDOR
B6C01
SOCIAL WORK
OFFICE
5C147
PSYCHIATRIST
OFFICE
5C146
NURSE CLINICIAN
PHYSICIAN
ASSISTANT
5C142
CORRIDOR
5C-C9
HYDRO TANK
5C140
TRAY CART
STORAGE
5C133B
DINING
5C133A
BMS
5C159
CORRIDOR
B6C05
CORRIDOR
B6C02
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
AREA A
TRIPLE C - The A/E Group
1345 CAPITAL BLVD. SUITE A
RENO, NA 89502
MAT PERKINS
520-481-8548
/12
/20
B
IM
/6
-2
-1
I n p a ti e n t M e n ta l H e a lt h E
O C
C o m p lia n c e R e n o v a ti o n s /6
-2
-1
.1
.M
E P
F .r v t
/1
/2
:2
:4
P
M
ED106A
ELECTRICAL PLAN - LEVEL 6 - AREA A -
DEMOLITION
654-20-117
02/12/2021 M. PERKINS G. WEAVER
BID DOCUMENT
SUBMITTAL
INPATIENT MENTAL HEALTH EOC
COMPLIANCE RENOVATIONS
975 KIRMAN AVENUE RENO, NV 89502-0993
SCALE: 1/4" = 1'-0"
F5
ELECTRICAL PLAN - LEVEL 6 - AREA A
- DEMOLITION
A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS
PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR
TO ROUGH-IN.
D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS
AND CEILINGS TO MAINTAIN FIRE RATING.
E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL
BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.
F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING
FACTOR FOR ROOF-MOUNTED CONDUITS.
G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES
AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE
INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.
I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE
INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN
ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME
AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.
K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN
BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND
CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.
COORDINATE WITH ARCHITECTURAL DETAILS.
L. EXIT SIGNS ARE TO BE TYPE "X1", UON.
M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.
N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN
THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.
O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF
ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR
TO INSTALLATION.
P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN
MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL
COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.
R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT
RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.
S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR
CLARITY.
1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH
PUSHBUTTON NURSE CALL STATION AT EACH LOCATION.
2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS
(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE
REMAINING EMERGENCY OUTLET IN PATIENT ROOM, ONE NORMAL POWER OUTLET PER BED AND
ONE OUTLET IN PATIENT TOILET ROOM WITH NURSE MANAGER.
3. REMOVE ALL POWER AND DATA DEVICES IN NURSES STATION ROOM, RETAIN EXISTING CONDUIT FOR
NEW DEVICES.
4. RELOCATE EXISTING DOOR ANTI-LIGATURE CONTROL PANEL. PROTECT AND REINSTALL IN
RENOVATED NURSES STATION.
5. RELOCATE LIGHT SWITCHES IN THIS ROOM TO NURSES STATION ROOM. PROVIDE NEW DIMMABLE
SWITCHES.
6. TEMPORARY WALL OPENING FOR ACCESS TO MEDICAL ROOM DURING PHASING. CONTRACTOR
SHALL COORDINATE TEMPORARY RELOCATION OF ELECTRICAL UTILITIES AS NECESSARY. RETURN TO EXISTING CONDITIONS AFTER INFILL. TEMPORARILY RELOCATE EXISTING POWER RECEPTACLES
AS REQUIRED
E
N
E
N
E N
E N
E
N
E N
E
N
E
NE N
E N
E N
E
N
E
N
E
N
E
N
E
N
E NE N
N
NNNN
N N N
N N
N
J J
J
7.6
9.4
H I K L
5NLB- 3
5NLB- 3
5NLB- 15
5NLB- 15
5NLB- 27
5NLB- 27
5NLB- 39
5NLB- 39
5NLA- 12
5NLA- 8
5NLA- 8
5NLA- 12
5NLA- 26
5NLB- 11
5NLB- 11
5NLB- 11
5NLB- 11
5NLB- 11
5NLB- 9
5NLB- 9
5NLB- 9
5NLB- 9
5NLB- 9
5NLB- 13
5NLB- 13
5NLB- 13
5NLB- 13
5NLB- 28
5NLB- 24
5NLB- 28
5NLB- 7
5NLB- 7 5NLB- 7
5NLB- 5
5NLB- 5
5NLB- 55NLB- 5
5NLB- 7
5NLB- 26
5NLB- 26
5NLB- 24
5ECA- 36
5NLB- 29
5NLB- 29
5NLB- 29
5NLB- 29
5NLB- 26
5NLB- 26
5NLB- 24
5ECA- 36
5E C
A
5N L
B
5N L
B
5N L
B
5NLB- 315NLB- 31
5N L
B
5N L
B
5N L
B
5N L
B
5N L
B
5N L
B
5E C
A
5E C
A
5NLB- 31
5NLB- 31 5NLB- 33 5NLB- 33
5NLB- 335NLB- 33
5N L
B
5N L
B
5N L
B
5N L
B
5N L
B
5E C
A
5NLB- 33
5NLA- 24
5NLA- 24
5NLB- 14
5NLB- 14
5NLB- 12
5NLB- 14
5NLB- 14
5NLB- 12
5ECA- 28
5NLB- 35
5NLB- 355NLB- 37
5NLB- 37
5NLB- 13
5NLB- 37
5NLB- 10
5NLB- 10
5NLB- 6
5NLB- 10
5NLB- 10
5NLB- 6
5ECA- 265ECA- 24
5NLB- 6
5NLB- 8
5NLB- 8
5NLB- 8
5NLB- 8
5NLB- 6
5NLB- 39 5NLB- 35
5NLA- 24
5NLA- 24
5NLA- 24
5NLA- 24
5NLA- 20
5NLA- 20
5NLA- 20
5NLA- 20
5NLA- 22
5NLA- 22
5NLB- 19
5NLB- 19
5NLB- 21
5NLA- 22
5NLB- 17
5NLA- 26
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 12
5NLA- 26
5ECA- 7
5NLA- 12 5ECA- 9
5ECA- 9
5E C
A
5E C
A
5E
LA
5E
LA
5ELA- 4
5ECA- 13
5NLA- 12
5NLA- 24
5N L
B
5NLA- 22
5NLA- 22
5ECA- 20
5ECA- 20 5ECA- 20
5ECA- 7
5EHEA
5ELA
5ECA
5NLA
5NLB
5NHA
2 2
5NLA- 39
DEDUCT #1
7.6
9.4
H I K L
BATH
B6137A
BATH
B6135A
ELEC EQUIP
B6139
GROUP THERAPY
B6143
ONE BED
B6147
ONE BED
B6149
BATH
B6147A
BATH
B6149A
ONE BED
B6150
BATH
B6150A
TWO BED
B6208
QUIET
B6146
TWO BED
B6206
BATH
B6206A
BATH
B6208A
WASHER DRYER
B6205
NOURISH
KITCHEN
B6203
CLEAN UTILITY
B6201
CLEAN LINEN
B6199
OFFICE
B6140
TELE
B6142
RED BAG
STORAGE
B6138
SOILED UTILITY
B6136
LOCKER ROOM
B6195
TELE EQUIP
B6197
TWO BED
B6204
TWO BED
B6200
BATH
B6200A
BATH
B6204A
STAIR 2
BS2
TWO BED
B6194
BATH
B6192A
BATH
B6194A
CORRIDOR
B6C06
ONE BED
B6137
CORRIDOR
B6C03
CORRIDOR
B6C04
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
AREA B
TRIPLE C - The A/E Group
1345 CAPITAL BLVD. SUITE A
RENO, NA 89502
MAT PERKINS
520-481-8548
/12
/20
B
IM
/6
-2
-1
I n p a ti e n t M e n ta l H e a lt h E
O C
C o m p lia n c e R e n o v a ti o n s /6
-2
-1
.1
.M
E P
F .r v t
/1
/2
:2
:5
P
M
ED106B
ELECTRICAL PLAN - LEVEL 6 - AREA B -
DEMOLITION
654-20-117
02/12/2021 M. PERKINS G. WEAVER
BID DOCUMENT
SUBMITTAL
INPATIENT MENTAL HEALTH EOC
COMPLIANCE RENOVATIONS
975 KIRMAN AVENUE RENO, NV 89502-0993
SCALE: 1/4" = 1'-0"
F3
ELECTRICAL PLAN - LEVEL 6 - AREA B
- DEMOLITION
A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS
PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR
TO ROUGH-IN.
D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS
AND CEILINGS TO MAINTAIN FIRE RATING.
E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL
BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.
F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING
FACTOR FOR ROOF-MOUNTED CONDUITS.
G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES
AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE
INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.
I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE
INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN
ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME
AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.
K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN
BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND
CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.
COORDINATE WITH ARCHITECTURAL DETAILS.
L. EXIT SIGNS ARE TO BE TYPE "X1", UON.
M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.
N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN
THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.
O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF
ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR
TO INSTALLATION.
P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN
MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL
COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.
R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT
RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.
S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR
CLARITY.
1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH
PUSHBUTTON NURSE CALL STATION AT EACH LOCATION.
2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS
(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE
REMAINING EMERGNECY POWER OUTLET IN PATIENT ROOM AND ONE NORMAL POWER OUTLET PER
BED AND ONE OUTLET IN PATIENT TOILET ROOM WITH NURSE MANAGER.
E
E N
NNNNN
N
N
N
N
N
N
E N
E
N
E
N
E
N
E
N
E
N
E N
E N
E
N
E N
E
N
E N
J
J
J
J J
J
F
7.6
9.4
G4
RECEIVING
B6127
BATH
B6131A
BATH
B6127A
TWO BED
B6131
ONE BED
B6135
HAC
B6133
BATH
B6137A
BATH
B6135A
BATH
B6192A
BATH
B6194A
TWO BED
B6192
SUN DECK
B6188
SECLUSION
B6134A
ANTE RM
B6134
TOILET
B6134B
TOILET
B6193B
SECLUSION
B6193A ANTE RM
B6193
NURSE STATION
B6128
MEDICATION
B6128A
WORK RM HOUSE
STAFF
B6104
STAFF TOILET
B6125
COPY
B6124
HAC
B6184A
DAY RM
RECREATION
B6184
NON-FOOD STRG
5C139
TOILET
5C138
TOILET
5C137
GOLD ELEVATOR
SILVER
ELEVATOR
PSYCHIATRIST
OFFICE
5C144
HEAD NURSE
5C143
TELE
B6184C
ADL KITCHEN
5C133C
CORRIDOR
B6C06
ELEVATOR
LOBBY
B6EGD
CORRIDOR
B6C01
SOCIAL WORK
OFFICE
5C147
PSYCHIATRIST
OFFICE
5C146
NURSE CLINICIAN
PHYSICIAN
ASSISTANT
5C142
REHABILITATION
THERAPIST
OFFICE
5C141
DEMOSTRATION
CLASSROOM
5C158
CORRIDOR
5C-C11
CORRIDOR
5C-C9
HYDRO TANK
5C140
TRAY CART
STORAGE
5C133B
DINING
5C133A
BMS
5C159
CORRIDOR
B6C02
SALLY PORT
B6C02A
ANTE RM
B6134
ANTE RM
B6193
CORRIDOR
B6C05
33 3
5NLC- 42
5NLC- 42
5NLC- 405NLC- 40
5NLC- 40
5NLC- 40
5NLC- 42
5NLC- 42
5NLB- 36
5NLB- 1
5ECA- 16
5ECA- 16
5NLB- 32
5NLB- 32 5NLB- 34
5ECA- 40 5ECA- 42
5NLB- 41
5NLD- 8
5NLD- 12
5NLD- 12
5NLD- 12
5NLB- 4
5ECA- 22
5NLB- 4
5NLA- 26
5NLA- 26
5NLA- 8
5NLA- 8
5NLA- 8
5NLA- 175NLA- 17
5NLA- 6
5NLA- 6
5NLA- 6
5NLA- 8
5NLD- 65NLD- 6
5NLD- 6
5NLD- 6
5NLD- 6
5NLD- 8
5NLD- 6
5NLD- 6
5NLA- 10
5NLA- 26
5NLD- 8
5NLD- 8
5NLD- 8
5NLD- 14
5NLD- 16
5NLC
5NLC
5NLC- 3
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLD- 10
5NLD- 10
5NLD
5NLD
5NLD
5NLD- 10
5NLD- 10
5NLD
5NLD
5NLD
5ECA- 18
5ECA- 18
5ECA- 18
5NLD- 8
5NLD- 8
5NLB- 27
5NLC- 19
5NLC- 19
5NLD
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5NLC
5ECB
5NLC
5NLD
5EHEB
5NHB
5ELB
5NLA- 8
5NLA- 8
5NLA- 26
5NLD- 40
5ECA-15
5NLA-2
5NLA-2
5ECA-15
5ECA-15
5NLA-2
5NLA-2
ECA-14
ECA-14
ECA-14
ECA-14
5NLA-10
5NLA-10
5ECA-16
5ECA-16
5NLA-6
5NLA-6
5ECA-15
5E C
A -1
5E C
A -1
5N L
A -4
5N L
A -4
5E C
A -1
5E C
A -1
5N L
A -1
5E C
A -1
5E C
A -1
5N L
B -3
5N L
B -3
5N L
B -5
5N L
B -5
5N L
B -2
5N L
B -2
5NLA- 17
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
AREA A
TRIPLE C - The A/E Group
1345 CAPITAL BLVD. SUITE A
RENO, NA 89502
MAT PERKINS
520-481-8548
/12
/20
B
IM
/6
-2
-1
I n p a ti e n t M e n ta l H e a lt h E
O C
C o m p lia n c e R e n o v a ti o n s /6
-2
-1
.1
.M
E P
F .r v t
/1
/2
:2
:0
P
M
E-106A
ELECTRICAL PLAN - LEVEL 6 - AREA A - NEW 654-20-117
02/12/2021 M. PERKINS G. WEAVER
BID DOCUMENT
SUBMITTAL
INPATIENT MENTAL HEALTH EOC
COMPLIANCE RENOVATIONS
975 KIRMAN AVENUE RENO, NV 89502-0993
SCALE: 1/4" = 1'-0"
F5
ELECTRICAL PLAN - LEVEL 6 - AREA A
- NEW
1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH
PUSHBUTTON NURSE CALL STATION AT EACH LOCATION
2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS
(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE
REMAINING EMERGENCY POWER OUTLET AND ONE NORMAL POWER OUTLET PER BED IN EACH
PATIENT ROOM AND PROVIDE ONE GFCI OUTLET IN PATIENT TOILET ROOM, COORDINATE ROUGH-IN
LOCATIONS WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED
ON/OFF CONTROL.
3. PROVIDE NEW ANTI-LIGATURE DOOR SENSOR ON BOTTOM OF DOOR. INTEGRATE WITH EXISTING
SENSOR LOCATED ON TOP OF DOOR. WIRE TO EXISTING POWER SUPPLY AND CONTROLS. MAIN
PANEL LOCATED IN THE NURSES STATION. SEE SPECIFICATION 08 71 00 FOR ADDITIONAL
REQUIRMENTS.
4. PROVIDE NEW POWER, DATA AND COAXIAL CONNECTIONS FOR NEW TV MONITOR AT 84" ABOVE
FINISHED FLOOR, COORDINATE ROUGH-IN LOCATIONS WITH NURSE MANAGER.
5. PROVIDE NEW POWER AND DATA AS SHOWN IN RENOVATED NURSES STATION.
6. PROVIDE NEW CAT 6A CABLING FOR ALL NEW DEVICES. PROVIDE NEW CAT 6A PATCH PANEL AND
LOCATE ON EXISTING RACK, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
7. PROVIDE NEW HARD-WIRED 120V/24V CONNECTION AND TRANSFORMER FOR INFRARED FLUSH
VALVE OPERATION.
8. TEMPORARY WALL OPENING FOR ACCESS TO MEDICAL ROOM DURING PHASING. CONTRACTOR
SHALL COORDINATE TEMPORARY RELOCATION OF ELECTRICAL UTILITIES AS NECESSARY. RETURN
TO EXISTING CONDITIONS AFTER INFILL.
9. RECONFIGURE RECEPTACLE LAYOUT IN MEDICATION ROOM. RELOCATE ONE NORMAL POWER
RECEPTACLE TO NORTH WALL AND ONE EMERGENCY POWER RECEPTACLE TO SOUTH WALL.
10. PROVIDE NEW ANTI-LIGATURE CAMERA (BASIS OF DESIGN AXIS Q92160-SLV)AND CONNECT TO EXISTING HEAD END EQUIPMENT. CONFIRM FINAL LOCATION WITH OWNER TO ENSURE ADQQUATE
COVERAGE.
A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS
PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR
TO ROUGH-IN.
D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS
AND CEILINGS TO MAINTAIN FIRE RATING.
E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL
BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.
F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING
FACTOR FOR ROOF-MOUNTED CONDUITS.
G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES
AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE
INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.
I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE
INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN
ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME
AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.
K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN
BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND
CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.
COORDINATE WITH ARCHITECTURAL DETAILS.
L. EXIT SIGNS ARE TO BE TYPE "X1", UON.
M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.
N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN
THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.
O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF
ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR
TO INSTALLATION.
P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN
MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL
COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.
R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT
RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.
S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR
CLARITY.
NNNN
N N N
N N
N
E N
E
N
E N
E N
E
N
E
N
E
N
E NE N
E
N
E N
E
N
E
N
E
N
E
N
E
N
E N
E
N
J J
J
J
J
J
J
J
J
J
J
J
7.6
9.4
H I K L
BATH
B6137A
BATH
B6135A
RED BAG
STORAGE
B6138
SOILED UTILITY
B6136
LOCKER ROOM
B6195
TWO BED
B6194
BATH
B6192A
BATH
B6194A
CORRIDOR
B6C06
ONE BED
B6137
CORRIDOR
B6C03
ELEC EQUIP
B6139
GROUP THERAPY
B6143
ONE BED
B6147
ONE BED
B6149
BATH
B6147A
BATH
B6149A
ONE BED
B6150
BATH
B6150A
TWO BED
B6208
QUIET
B6146
TWO BED
B6206
BATH
B6206A
BATH
B6208A
WASHER DRYER
B6205
NOURISH
KITCHEN
B6203
CLEAN UTILITY
B6201
CLEAN LINEN
B6199
OFFICE
B6140
TELE
B6142
TELE EQUIP
B6197
TWO BED
B6204
TWO BED
B6200
BATH
B6200A
BATH
B6204A
STAIR 2
BS2
CORRIDOR
B6C04
5ELA
5ECA
5NLA
5NLB
5NHA
5EHEA
5 5 5 5
5NLA- 85NLA- 8
5NLA- 8
5NLA- 26
5NLB- 28
5ECA- 38
5NLB- 7
5NLB- 5
5NLB- 26
5ECA- 36
5NLB- 26
5ECA- 36
5E C
A
5N L
B
5N L
B
5N L
B
5E C
A
5N L
B
5N L
B
5E C
A
305NLA- 24
5NLA- 24
5NLB- 14
5ECA- 28
5NLB- 14
5NLB- 10
5ECA- 26
5NLB- 10
5ECA- 24
5NLB- 8
5NLB- 8
5NLA- 24 5NLA- 24
5NLA- 24
5NLA- 24
5NLA- 20
5NLA- 20
5NLA- 20
5NLA- 20
5NLA- 22
5NLA- 22
5NLB- 19
5NLB- 19
5NLB- 21
5NLA- 22
5NLB- 17
5NLA- 26
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 14
5NLA- 12
5NLA- 26
5ECA- 7
5NLA- 12 5ECA- 9
5ECA- 9
5E C
A
5E C
A
5E
LA
5E
LA
5ELA- 4
5ECA- 13
5NLA- 12
5NLA- 24
5NLA- 22
5NLA- 22
5ECA- 20
5ECA- 20
5ECA- 20
5ECA- 7
2 2
1 1
5NLA- 39
5N L
B -5
5N L
B -2
5N L
B -2
5N L
B -2
5N L
B -1
5N L
B -1
5NLB-12
5NLB-13
5NLB-13
2 2
2 2
2 2
DEDUCT #1
5ECA- 38
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
AREA B
TRIPLE C - The A/E Group
1345 CAPITAL BLVD. SUITE A
RENO, NA 89502
MAT PERKINS
520-481-8548
/12
/20
B
IM
/6
-2
-1
I n p a ti e n t M e n ta l H e a lt h E
O C
C o m p lia n c e R e n o v a ti o n s /6
-2
-1
.1
.M
E P
F .r v t
/1
/2
:2
:1
P
M
E-106B
ELECTRICAL PLAN - LEVEL 6 - AREA B - NEW 654-20-117
02/12/2021 M. PERKINS G. WEAVER
BID DOCUMENT
SUBMITTAL
INPATIENT MENTAL HEALTH EOC
COMPLIANCE RENOVATIONS
975 KIRMAN AVENUE RENO, NV 89502-0993
SCALE: 1/4" = 1'-0"
F3
ELECTRICAL PLAN - LEVEL 6 - AREA B
- NEW
1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH
PUSHBUTTON NURSE CALL STATION AT EACH LOCATION.
2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS
(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE
REMAINING EMERGENCY POWER OUTLET AND ONE NORMAL POWER OUTLET PER BED IN EACH
PATIENT ROOM AND PROVIDE ONE GFCI OUTLET IN PATIENT TOILET ROOM, COORDINATE ROUGH-IN
LOCATIONS WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED
ON/OFF CONTROL.
3. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS
(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT GROUP THERAPY ROOM. COORDINATE 1
REMAINING OUTLET FOR TV WITH NURSE MANAGER.
4. REMOVE CONVENIENCE OUTLETS, BLANK FACES JUNCTION BOXES, AND ASSOCIATED CONDUCTORS
(CONDUIT TO REMAIN AND ABANDONED IN PLACE) IN PROCEDURE ROOM AS NECESSARY.
COORDINATE WITH NURSE MANAGER OUTLETS TO REMAIN FOR EQUIPMENT.
5. PROVIDE NEW ANTI-LIGATURE DOOR SENSOR ON BOTTOM OF DOOR. INTEGRATE WITH EXISTING
SENSOR LOCATED ON TOP OF DOOR. WIRE TO EXISTING POWER SUPPLY AND CONTROLS. MAIN
PANEL LOCATED IN THE NURSES STATION. SEE SPECIFICATION 08 71 00 FOR ADDITIONAL
REQUIRMENTS.
6. PROVIDE NEW CAT 6A CABLING FOR ALL NEW DEVICES. PROVIDE NEW CAT 6A PATCH PANEL AND
LOCATE ON EXISTING RACK, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
7. PROVIDE NEW HARD-WIRED 120V/24V CONNECTION AND TRANSFORMER FOR INFRARED FLUSH
VALVE OPERATION.
8. NEW EMERGENCY POWER OUTLET WIRED TO PANEL AND CIRCUIT SHOWN, COORDINATE ROUGH-IN
LOCATION WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED
ON/OFF CONTROL.
A.
This is the start of the file's text. The full file is on GovTribe.