This federal contract opportunity solicitation seeks compliance services for inpatient mental health facilities. Solicitation number 36C26121R0072 was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21 for projects 654-20-141 and 654-17-713 related to inpatient mental health EOC compliance and door frames/doors. The solicitation involves assessing and ensuring compliance of inpatient mental health facilities with Emergency Operations Center requirements and replacing or upgrading door frames and doors. The response due date and award date were not provided. Pricing terms and set-asides were also not specified. The federal agency involved is the Department of Veterans Affairs.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAX

AIRFLOW

H O

T W

ATER

FLO

W

R E

L A

T

IV

E A

IR

F

L O

W

100%

0%

CONTROL SIGNAL, PERCENT

0 10050

VARIABLE AIR VOLUME CONTROL

MIN COOLING

AIRFLOW

VARIABLE AIR VOLUME (VAV) TERMINAL UNIT SEQUENCE OF OPERATION:

OPERATION:

The occupied period will be scheduled through the Energy Management System (EMS). During the unoccupied mode, the VAV box will maintain required temperature and flow setpoints.

The unit shall maintain zone setpoints [+/- 2 degree F.] by controlling the air and water flow through one of the following:

Occupied:

• If the VAV box room temperature (RM-T) is higher than the room temperature setpoint (RM-TSET), the VAV controller will reset the CFM setpoint upwards from the minimum CFM setpoint to the maximum CFM setpoint.

• When zone temperature is greater than its cooling setpoint, the zone damper shall modulate between the minimum occupied airflow (adj.) and the maximum cooling airflow (adj.)

until the zone is satisfied.

• When the zone temperature is between the cooling setpoint and the heating setpoint, the zone damper shall maintain the minimum required zone ventilation (adj.).

• If the VAV box room temperature (RM-T) is lower than the room temperature setpoint (RM-TSET), the VAV controller shall modulate the VAV box reheat valve to achieve the setpoint. The VAV controller shall modulate the damper in order to maintain the minimum setpoint.

• If the VAV is at minimum airflow position and the zone temperature continues to be below setpoint; increase the supply air temperature up to be 15 deg F greater than RM-TSET.

• If the supply air temperature is 15 deg F higher than RM-TSET and the zone temperature remains below RM-TSET, increase the airflow setpoint up to the heating maximum.

• Modulate the HHW valve as required to maintain the supply air temperature setpoint.

• Reverse the heating sequence above as zone temperature rises.

Unoccupied:

• When the zone is unoccupied the zone damper shall control to its minimum unoccupied airflow (adj.).

• When the zone temperature is greater than its cooling setpoint, the zone damper shall modulate between the minimum unoccupied airflow (adj.) and the maximum cooling airflow

(adj.) until the zone is satisfied.

• When zone temperature is less than its unoccupied heating setpoint, the controller shall enable heating to maintain the zone temperature at the setpoint. Additionally, if warm air is available from the AHU, the zone damper shall modulate between the minimum unoccupied airflow (adj.) and the auxiliary heating airflow (adj.) until the zone is satisfied.

Run Conditions - Scheduled:

The unit shall run according to a user definable time schedule in the following modes:

• Occupied Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint

• A 70°F (adj.) heating setpoint.

• Unoccupied Mode (night setback): The unit shall maintain

• A 85°F (adj.) cooling setpoint.

• A 55°F (adj.) heating setpoint.

ROOM TEMPERATURE AND RETURN AIR TEMPERATURE SETPOINTS:

The room temperature setpoint (RM-TSET) will be adjustable by the user at the wall mounted room temperature sensor or by the the facilities operations staff for all duct mounted temperature sensors. The existing EMS shall be programmed by the contractor to provide RM-TSET set points as indicated on this sheet for each type of space.

Note: For areas with mental health patient access, existing thermostats shall be replaced with return air duct temperature probes and all set point adjustment shall be through the FMS and not wall-mounted thermostats. To avoid over-cooling the room, return air sensor setpoints shall be calibrated such that the room temperature at 60" above finish floor meets room setpoint requirements.

ALARMS AND WARNING:

An alarm shall be sent to the EMS system upon any of the following conditions:

• The room temperature is greater than 86 degrees F. (adj.) or less than 54 degrees F. (adj.)

• Supply airflow is 30% or more below setpoint, delay time 5 minutes.

• Temperature or flow sensor not reporting a value.

A warning shall be sent to the EMS system under any of the following conditions:

• The room temperature rises more than 5 degrees F. (adj.) above the room temperature setpoint.

• The room temperature falls more than 5 degrees F. (adj.) below the room temperature setpoint.

REHEATING - HIGH DISCHARGE AIR TEMPERATURE LIMIT:

The controller shall measure the discharge air temperature and limit reheating if the discharge air temperature is more than 95°F (adj.).

DISCHARGE AIR TEMPERATURE:

The controller shall monitor the discharge air temperature.

Alarms shall be provided as follows:

• High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).

• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.).

NOTES:

1. TERMINAL UNIT SHALL PROVIDE

THE FLOW CHARACTERISTICS

SHOWN ON THE GRAPH. EACH

TERMINAL SHALL BE EQUIPPED

WITH ITS OWN STAND ALONE

CONTROLLER WHICH SHALL HAVE

THE CAPABILITIES DESCRIBED IN

THE SPECIFICATION. THE WIRING

SHOWN IS PROVIDED AS A

GENERAL DESCRIPTION AND IS

NOT A DETAILED WIRING DIAGRAM

WHICH VARIES WITH THE

MANUFACTURER.

2. CONTRACTOR TO MATCH EXISTING

AIR AND WATER FLOW SET POINTS

FROM PRE-CONSTRUCTION TAB

REPORT .

R E

L A

T

IV

E H

H W

F L O

W

MAX HEATING

AIRFLOW

100%

0%

TT

FCV

CONTROL POWER

FROM LAST UNIT ON LAN

TO NEXT UNIT ON LAN

C

H

CONTROLLER

DDC

AIR

SUPPLY

TCV

HWR

N.C.

HWS

SUPPLY

AIR FLOW

SENSOR

DUCT MOUNTED

TEMPERATURE SENSOR

TT

NEW DUCT MOUNTED RETURN

AIR TEMPERATURE SENSOR

LOCATE WITHIN 5' OF THE

RETURN AIR GRILLE AND

ADJACENT TO EXISTING ACCESS

PANELS FOR FUTURE

MAINTENANCE AND ADJUSTMENT

AIR

RETURN

FOR MENTAL HEALTH PATIENT AREAS

(OTHER SPACES SHALL USE WALL-

MOUNTED THERMOSTATS)

50 1000

CONTROL SIGNAL, PERCENT

0%

100%

R E

L A

T

IV

E A

IR

F

L O

W

HO

T W

ATER FLO

W

CONSTANT AIR VOLUME CONTROL

CONSTANT AIR VOLUME (CAV) TERMINAL UNIT SEQUENCE OF OPERATION:

OPERATION:

The occupied period will be scheduled through the Energy Management System (EMS). During the unoccupied mode, the CAV box will maintain required temperature and flow setpoints. The unit shall maintain zone temperature setpoints [+/- 2 degree F.] with constant airflow through one of the following:

Occupied:

• The zone damper shall modulate to maintain a constant occupied airflow (adj.) distributed into the zone.

• When the CAV box room temperature is lower than the room temperature setpoint (RM-TSET), the CAV controller shall modulate the CAV box reheat valve to achieve the setpoint. Increase CAV supply temperature measured by TT. Reheat valve modulates to maintain setpoint.

• Reverse sequence above as temperature in space rises.

Unoccupied:

• The zone damper shall modulate to a constant unoccupied airflow (adj.) distributed into the zone.

• When zone temperature is less than its heating setpoint, the controller shall enable heating to maintain the zone temperature at its unoccupied heating setpoint.

Night Setback:

• The CAV box, associated Air Handling Unit, and associated CAV boxes will be indexed to the occupied mode if the CAV box room temperature is greater than the unoccupied cooling setpoint of 85 degrees F. (adj.), or lower than the unoccupied heating setpoint of 55 degrees F. (adj.). the Air Handling Unit and associated boxes will return to the unoccupied mode once the cooling and heating setpoints are satisfied [+/- 2 degree F.].

Run Conditions - Scheduled:

The unit shall run according to a user definable time schedule in the following modes:

• Occupied Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint

• A 70°F (adj.) heating setpoint.

• Unoccupied Mode (night setback): The unit shall maintain

• A 85°F (adj.) cooling setpoint.

• A 55°F (adj.) heating setpoint.

ROOM TEMPERATURE SETPOINT:

The room temperature setpoint (RM-TSET) will be adjustable by the facilities operations staff. The existing EMS shall be programmed by the contractor to provide RM- TSET set points as indicated on this sheet for each type of space.

Note: For areas with mental health patient access, existing thermostats shall be replaced with return air duct temperature probes and all set point adjustment shall be through the FMS and not wall-mounted thermostats. To avoid over-cooling the room, return air sensor setpoints shall be calibrated such that the room temperature at 60" above finish floor meets room setpoint requirements.

FLOW CONTROL:

The CAV controller will modulate the damper in order to maintain the CFM setpoint.

ALARMS AND WARNING:

An alarm shall be sent to the EMS system upon any of the following conditions:

• The room temperature is greater than 86 degrees F. (adj.) or less than 54 degrees F. (adj.)

• Supply airflow alarm: is 15% below setpoint, delay time 5 minutes.

• Temperature or flow sensor not reporting a value.

A warning shall be sent to the EMS system under any of the following conditions:

• The room temperature rises more than 5 degrees F. (adj.) above the room temperature setpoint.

• The room temperature falls more than 5 degrees F. (adj.) below the room temperature setpoint.

REHEATING COIL VALVE:

The controller shall measure the zone temperature and modulate the reheating coil valve open on dropping temperature to maintain its heating setpoint. Controller should increase zone supply air temperature setpoint to meet zone temperature. Reheat coil modulates to maintain supply air temperature setpoint.

DISCHARGE AIR TEMPERATURE:

The controller shall monitor the discharge air temperature.

Alarms shall be provided as follows:

• High Discharge Air Temp: If the discharge air temperature is greater than 120°F (adj.).

• Low Discharge Air Temp: If the discharge air temperature is less than 40°F (adj.).

NOTES:

1. TERMINAL UNIT SHALL PROVIDE THE

FLOW CHARACTERISTICS SHOWN ON

THE GRAPH. EACH TERMINAL SHALL BE

EQUIPPED WITH ITS OWN STAND ALONE

CONTROLLER WHICH SHALL HAVE THE

CAPABILITIES DESCRIBED IN THE

SPECIFICATION. THE WIRING SHOWN IS

PROVIDED AS A GENERAL DESCRIPTION

AND IS NOT A DETAILED WIRING

DIAGRAM WHICH VARIES WITH THE

MANUFACTURER.

2. CONTRACTOR TO MATCH EXISTING AIR

AND WATER FLOW SET POINTS FROM

PRE-CONSTRUCTION TAB REPORT .

R E

L A

T

IV

E H

H W

F L O

W

0%

100%

DESIGN AIR FLOW

TT

FCV

CONTROL POWER

FROM LAST UNIT ON LAN

TO NEXT UNIT ON LAN

C

H

CONTROLLER

DDC

AIR

SUPPLY

TCV

HWR

N.C.

HWS

SUPPLY

AIR FLOW

SENSOR

TT

NEW DUCT MOUNTED RETURN

AIR TEMPERATURE SENSOR

LOCATE WITHIN 5' OF THE

RETURN AIR GRILLE AND

ADJACENT TO EXISTING ACCESS

PANELS FOR FUTURE

MAINTENANCE AND ADJUSTMENT

AIR

RETURN

FOR MENTAL HEALTH PATIENT AREAS

(OTHER SPACES SHALL USE WALL-

MOUNTED THERMOSTATS)

DUCT MOUNTED

TEMPERATURE SENSOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:3

P

M

M-802

MECHANICAL CONTROL DIAGRAMS 654-20-117

02/12/2021 M. PERKINS K. LUKE

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: NOT TO SCALE

F8

TYPICAL VAV TERMINAL UNIT

CONTROL DIAGRAM

SCALE: NOT TO SCALE

F5

TYPICAL CAV TERMINAL UNIT

CONTROL DIAGRAM

Revisions: Date:

LOW VOLTAGE (BELOW 50 VOLTS)

L-L

L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL X

XFMR

% Z

WP

WHM

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

INCAND

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INCANDESCENT

W/

W/O

W

VFD

VA

V

UPS

UL

UON

UG

UGS

UGT

UGP

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONINGHERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

TYP

TV

TP

TEL,TELE

TELECOM

TC

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

PERCENT IMPEDANCE

TRANSFORMER

REMOVE DEVICE

WATT HOUR METER

WEATHERPROOF

VOLTS

VARIABLE FREQUENCY DRIVE/

VARIABLE FREQUENCY MOTOR

CONTROLLER

WITHOUT

WITH

WIRE

VOLT-AMPERES

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

CATV

PRI

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FIRE ALARM ANNUNCIATOR PANEL

ELECTRIC, ELECTRICAL

ELECTRIC METALLIC CONDUIT

EQUIPMENT GROUND

EWC

FAAP

FLA

FDR

EWH

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

ELEC

EQ, EQUIP

EM, EMERG

EMT

ELEV

ENCL

EG

EQUIPMENT

ELEVATOR

EMERGENCY

ENCLOSURE

RCLP

RM

SCH, SCHED

RP

REF

RCPT

RSC

RLA

RF

R, RE

QTY

PWR

PT

PVC

DISTRIBUTION PANEL

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DPDT

DWG

DPST

DIST

DISC

DC

DP

DN

DRAWING

DISTRIBUTION

DIRECT CURRENT

DISCONNECT

DOWN

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

PA

PH, ∅

PF

PNL

PE

PB

P

OPP

OHE/T

OH

OFOI

OFCI

NO., NUM, #

OC

NTS

CABLE TELEVISION

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

CB

BLDG

BRKR, BKR

CIRCUIT BREAKER

CONDUIT

BUILDING

BREAKER

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

NC

NEMA

NO

NIC

NEC

N

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

SCHEDULE

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

REMOTE CONTROL LIGHTING PANEL

QUANTITY

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

ON CENTER

NOT TO SCALE

NUMBER

MOUNTING

NATIONAL ELECTRICAL CODE

MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)

NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

SWGR SWITCHGEAR

AIR HANDLING UNITAHU

CCTV CLOSED CIRCUIT TELEVISION

CP CONTROL PANEL

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

MTS MANUAL TRANSFER SWITCH

PDP POWER DISTRIBUTION PANEL

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

AMPERESAMP

C

F

EXISTINGE, EX, EXIST

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDLEFC

DIV DIVISION

OCPD OVERCURRENT PROTECTION DEVICE

ELECTRICAL ABBREVIATIONS

A M

B

C

D

E

F

G

H

I

J

K

N

O

P

Q

R

S

T

U

V

W

X

L

Z

J J

J

M

V

SP

R

GB

VFD

LCP

LRP

AFB

NCC

MS

1P

2P

E

DS

SS

B

MO

FBX

ET

M

M

C

DTDT

A-1

PH

D

P

K a

L

OS

R

B

CB

MD

MD

SP

VP

TV

XX

DC

C

CCTV

DM

R/D

CCTV

DGP

RX

ELM

DO

AC

K

AC

E

K

ATS

TBB

T

TMH

EMH

EHH

X

PSD

EMU

FB

UG

GB

G

PB

SR-X

6-30R

UPS

CT

DOOR CONTACT SWITCH

ACCESS FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

CONTACTOR

VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER

MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.

PUSHBUTTON STATION

CCTV SURVEILLANCE CAMERA OUTLET - WALL MTD, UON

CCTV SURVEILLANCE CAMERA OUTLET - CEILING MTD

DOOR MONITOR SWITCH

RECEIVER/DRIVER UNIT

NURSE CALL CONTROL EQUIPMENT PANEL (RECESSED/SURFACE)

NURSE CALL EMERGENCY STATION - PULL CORD TYPE IN

TOILETS & SHOWERS, PUSH-BUTTON TYPE IN ALL OTHER

PLACES

NURSE CALL BEDSIDE STATION, DOUBLE PATIENT

NURSE CALL BEDSIDE STATION, SINGLE PATIENT

NURSE CALL MASTER STATION

GLASS BREAK DETECTOR

NURSE CALL DOME LIGHT

PATIENT MONITORING OUTLET

CODE BLUE CALL STATION

NURSE CALL STAFF STATION

NURSE CALL DUTY STATION

LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE

EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL

ARROWS AS INDICATED SHADING INDICATES ILLUMINATED

FACE

LIGHTING TRACK - "X" DENOTES TYPE

UTILITY LIGHTING FIXTURE - TYPE AS INDICATED

WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED

SITE LIGHTING FIXTURE TYPE AS INDICATED

LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)

JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE

ALARM SYSTEMS PLANS.

DIRECT CONNECTION TO EQUIPMENT

SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)

DIMMER SWITCH

SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE

THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT LIGHT

FOUR - WAY SWITCH

FUSED SWITCH

DELTA CONNECTION

CPT

PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)

ELECTRIC INTERLOCK SYSTEM

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

PHOTO CELL

KEY INTERLOCKING SYSTEM

WYE CONNECTION - SOLID GROUND

SWITCH - SINGLE THROW

TELECOMMUNICATIONS BACKBOARD

MOTOR CONTROL CENTER

TELEPHONE MANHOLE

ELECTRIC MANHOLE

FUSE

BUS DUCT PLUG-IN UNIT

GROUND

AUTOMATIC TRANSFER SWITCH

DRAWOUT TYPE, CIRCUIT BREAKER

STATIONARY CIRCUIT BREAKER

DISCONNECT SWITCH, FUSED.

PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY,

UON

GROUND ROD

DISCONNECT SWITCH, NON-FUSED

PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, FLOOR MTD SERVICE FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)

TELECOMMUNICATIONS DATA OUTLET, FLOOR MTD SERVICE FITTING, SURFACE TYPE

("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)

TELECOMMUNICATIONS VOICE OUTLET, FLOOR MTD SERVICE FITTING, SURFACE TYPE

("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, WALL MTD.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

TRANSFORMER - TYPE AND RATING AS INDICATED

COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.

PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER

AMPACITY, UON

PANELBOARD - (FLUSH/SURFACE)

DISTRIBUTION PANELBOARD

TELECOMMUNICATIONS VOICE OUTLET, WALL MTD

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER, "W" INDICATES WALL PHONE HEIGHT,

"PY" INDICATES PAY PHONE)

TELECOMMUNICATIONS DATA OUTLET, WALL MTD

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER, "W" INDICATES WALL PHONE HEIGHT)

ELECTRIC HANDHOLE

LIGHTING CONTROL PANEL, SURFACE MTD. UON.

LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON

UNINTERRUPTIBLE POWER SUPPLY

SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]

[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]

[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]

SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH

(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]

a

LOW VOLTAGE SWITCH

JUNCTION BOX - FLOOR MOUNTED

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, CEILING MTD SERVICE

FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE)

MOTOR AND CONNECTION

EMERGENCY POWER OFF

REQUEST-FOR-EXIT SENSOR

ELECTRIC LOCKING/LATCHING AND MONITORING HARDWARE

ACCESS CONTROL STATION - KEYPAD TYPE

ACCESS CONTROL STATION - CARD TYPE

DOOR OPERATING EQUIPMENT

DATA GATHERING PANEL

NURSE CALL DOME LIGHT CEILING MTD

("Z" SUBSCRIPT DENOTES ZONE DOME LIGHT)

CODE BLUE WITH RED PHONE, WALL MTD, MOUNTED 48" AFF

CODE BLUE WITH BLUE LIGHT, WALL MTD, MOUNTED 48" AFF

MOTION DETECTOR - CEILING MTD

MOTION DETECTOR - WALL MTD

TELECOMMUNICATIONS DATA OUTLET, CEILING MTD SERVICE FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE)

TELECOMMUNICATIONS VOICE OUTLET, CEILING MTD SERVICE FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE)

POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE

CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.

COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.

SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE.

FLOOR MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX

RECEPTACLES WITH A COMMON FACEPLATE.

FLOOR MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. PROVIDE CORE

DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT

AND WIRING IN CEILING SPACE OF FLOOR BELOW TO ELECTRICAL CLOSET

OR PANELBOARD.

FLOOR MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.

FLOOR MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P,

3W. (SLASH INDICATES MOUNTING ABOVE FINISH

COUNTER)

QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,

DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

RECEPTACLES MOUNTED ABOVE THE CEILING.

QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES

WITH A COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH

COUNTER)

CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX

RECEPTACLES WITH A COMMON FACEPLATE.

GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

ELECTRONIC METERING UNIT

GROUND BUS

GROUND CABLE, SIZE AS INDICATED

PLUG-IN BUSWAY

FEEDER BUSWAY

UNDERGROUND CONDUIT/DUCTBANK

CABLE TRAY

CONDUIT TURNED DOWN

CONDUIT TURNED UP

CONDUIT CAST IN CONCRETE OR BELOW SLAB

CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED

AREAS OR BELOW ACCESS FLOORS

HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED

TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING

COMBINATION TV OUTLET AND DUPLEX RECEPTACLE ON SINGLE

FACEPLATE

SPEAKER - WALL MTD

PA VOLUME CONTROL

MICROPHONE OUTLET - CEILING MTD

MICROPHONE OUTLET - WALL MTD

MICROPHONE OUTLET - FLOOR MTD

SPEAKER - CEILING MTD

RECORDING OUTLET

COMBINATION VIDEO PROJECTOR OUTLET AND DUPLEX RECEPTACLE

CLOCK OUTLET, W/RECPT AND HANGER

CLOCK OUTLET, MASTER CLOCK

CLOCK OUTLET, ELAPSED TIME

GENERATORG

SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)

WALLWASH LIGHT FIXTURE,

DEMOLITION WORK

OCCUPANCY SENSOR WALL SWITCH

M

HC ADA PUSH BUTTON.

ELECTRICAL LIGHTING SYMBOLS ELECTRICAL POWER SYMBOLS GENERAL NOTES

A INTERCOMMUNICATION SYSTEM ( AI PHONE)

A B C A B C

SPD SURGE PROTECTIVE DEVICE

P P

PD PD

D D

POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE

SYSTEM AS SPECIFIED.

COMBINATION POWER AND TELECOMMUNICATIONS FLOOR OR WALL MOUNTED BOX FOR

POWER AND DATA CONNECTION - INDICATED IN POWER & SPECIAL SYSTEMS PLANS.

JUNCTION BOX FLOOR OR WALL MOUNTED FOR CONNECTION TO FURNITURE SYSTEM.

MOUNTING HEIGHT NOTES:

1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.

2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH

CASEWORK.

3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.

4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE

MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.

WALL SWITCHES

RECEPTACLES

TELECOMMUNICATIONS OUTLETS

TELECOMMUNICATIONS OUTLETS - WALL PHONE

CLOCK OUTLETS

TV OUTLETS

PUSHBUTTONS

VOLUME CONTROLS

NURSE CALL STATIONS

NURSE CALL DOME LIGHTS

DIMMERS

ACCESS CONTROL DEVICES

VANITY LIGHT IN TOILET

INTERCOM

FIREMAN'S PHONE

FIRE ALARM - PULL STATIONS

FIRE ALARM DEVICES HORN/SPEAKERS/STROBES

(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR

6" BELOW CEILING WHICH IS LOWER)

4'-0" AFF

1'-6" AFF

1'-6" AFF

4'-0" AFF

7'-0" AFF

1'-6" AFF

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-6" AFF

4'-0" AFF

4'-0" AFF

6" ABOVE THE MIRROR, UON

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-2" AFF TO TOP

HORIZONTAL MOUNTINGH

PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF

THREE CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL

DRAWINGS PRIOR TO ROUGH-IN.

PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR

SLABS, WALLS AND CEILINGS TO MAINTAIN FIRE RATING.

INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL

CODE AND LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE

MANNER.

LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE

DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.

REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING

MOUNTED DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL

PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS

AND A COMMON FACEPLATE.

WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING

HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS

FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED

IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES,

UON.

WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE

EXIT SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP

OF DOOR FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM

OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED

EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT. COORDINATE WITH

ARCHITECTURAL DETAILS.

EXIT SIGNS ARE TO BE TYPE "X1", UON.

PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR

GREATER THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL

LOCATION OF ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND

FINAL FURNITURE PLANS PRIOR TO INSTALLATION.

MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE

DRAWINGS AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC.

PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL

SYSTEMS.

WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY

CONNECT RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

A.

B.

C.

D.

E.

F.

G.

H.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

ELTD EMERGENCY LIGHTING TRANSFER DEVICE

SECURITY SYSTEM SYMBOLS

TELECOMMUNICATION SYMBOLS

NURSE CALL SYSTEM SYMBOLS

MOUNTING HEIGHTS

ELECTRICAL EQUIPMENT SYMBOLS

ELECTRICAL WIRING SYMBOLS

DISTRIBUTION AND DIAGRAM SYMBOLS

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0

KEY NOTE

1 DEMO KEY NOTE

SPECIAL SYSTEM OUTLET SYMBOLS

CB

E1-1.0

DISCONNECT SWITCHES

MOTOR STARTERS

PANELBOARDS & CABINETS

INDIVIDUAL CIRCUIT BREAKERS

5'-6" AFF

5'-6" AFF

6'-0" AFF TO TOP

5'-6" AFF

x

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:5

P

M

E-000

ELECTRICAL ABBREVIATIONS AND SYMBOLS 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

C P

E

N

E

N

E

N

E N

E

N

E

N

E N

E

N

E

N

E N

E N

E

N

E

N

E

N

NNNNN

N N

N

N

N

N

N

5NLB- 36

5NLC- 42

5NLC- 42

5NLC- 405NLC- 40

5NLC- 40

5NLC- 40

5NLC- 42

5NLC- 42

5NLB- 36

5NLB- 25

5NLB- 25

5NLB- 1

5NLB- 38

5ECA- 16

5ECA- 16

5NLB- 1 5NLB- 1

5NLB- 1

5NLB- 25

5NLB- 25

5NLB- 27

5NLB- 30

5NLB- 32

5NLB- 32

5NLB- 32

5NLB- 32 5NLB- 34

5NLB- 34

5ECA- 40

5ECA- 40

5ECA- 42

5NLB- 3

5NLB- 3

5NLB- 3

5NLB- 3

5NLB- 15

5NLB- 15

5NLB- 15

5NLB- 15

5NLB- 41

5NLD- 8

5NLD- 12

5NLD- 12

5NLD- 12

5NLB- 27

5NLB- 27

5NLB- 27

5NLB- 39

5NLB- 39

5NLB- 41

5NLB- 41

5NLB- 41

5ECA- 22

5NLB- 2

5NLB- 4

5NLB- 4

5ECA- 22

5NLB- 4

5NLB- 4

5NLB- 2

5NLB- 41

5NLA- 26

5NLA- 26

5NLA- 12

5NLA- 8

5NLA- 8

5NLA- 12

5NLA- 26

5NLA- 8

5NLA- 8

5NLA- 17 5NLA- 175NLA- 17

5NLA- 6

5NLA- 6

5NLA- 6

5NLA- 8

5NLA- 6

5NLA- 6

5NLA- 6

5NLA- 2

5NLA- 2

5ECA- 5

5ECA- 5

5ECA- 5

5ECA- 5

5ECA- 3

5ECA- 3

5ECA- 3

5ECA- 3 5E

C

A

5E C

A

5E C

A

5E C

A

5N L

A

5E C

A

5E C

A

5ECA- 17 5ECA- 19

5ECA- 15

5ECA- 15

5NLA- 10

5NLA- 10

5N

LA

5N

LA

5NLA- 2

5NLA- 2

5NLD- 65NLD- 6

5NLD- 6

5NLD- 6

5NLD- 6

5NLD- 8

5NLD

5NLD- 6

5NLA- 10

5NLA- 10

5NLA- 26

5NLD- 8

5NLD- 8

5NLD- 8

5NLD- 14

5NLD- 16

5NLC

5NLC

5NLC- 3

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLD- 10

5NLD- 10

5NLD

5NLD

5NLD

5NLD- 10

5NLD- 10

5NLD

5NLD

5NLD

5ECA- 18

5NLB- 30 5NLB- 30

5NLB- 27

5NLB- 1

5ECA- 18

5ECA- 18

5NLD- 8

5NLD- 8

5NLB- 27

5ECB

5NLC

5NLD

5EHEB

5NHB

5ELB

5NLC- 19

5NLC- 19

5NLD

5NLC

5NLC

5NLC 5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLD- 40

F

7.6

9.4

G

RECIEVING

B6127

BATH

B6131A

BATH

B6127A

TWO BED

B6131

ONE BED

B6135

HAC

B6133 BATH

B6137A

BATH

B6135A

BATH

B6192A

BATH

B6194A

TWO BED

B6192

SUN DECK

B6188

SECLUSION

B6134A

ANTE RM

B6134

TOILET

B6134B

TOILET

B6193B

SECLUSION

B6193A ANTE RM

B6193

NURSE STATION

B6128

MEDICATION

B6128A

WORK RM HOUSE

STAFF

B6104

STAFF TOILET

B6125

COPY

B6124

HAC

B6184A

DAY RM

RECREATION

B6184

NON-FOOD STRG

5C139

TOILET

5C138

TOILET

5C137

PSYCHIATRIST

OFFICE

5C144

HEAD NURSE

5C143

TELE

B6184C

ADL KITCHEN

5C133C

CORRIDOR

B6C06

ELEVATOR

LOBBY

B6EGD

CORRIDOR

B6C01

SOCIAL WORK

OFFICE

5C147

PSYCHIATRIST

OFFICE

5C146

NURSE CLINICIAN

PHYSICIAN

ASSISTANT

5C142

CORRIDOR

5C-C9

HYDRO TANK

5C140

TRAY CART

STORAGE

5C133B

DINING

5C133A

BMS

5C159

CORRIDOR

B6C05

CORRIDOR

B6C02

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:4

P

M

ED106A

ELECTRICAL PLAN - LEVEL 6 - AREA A -

DEMOLITION

654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F5

ELECTRICAL PLAN - LEVEL 6 - AREA A

- DEMOLITION

A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS

PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR

TO ROUGH-IN.

D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS

AND CEILINGS TO MAINTAIN FIRE RATING.

E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL

BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING

FACTOR FOR ROOF-MOUNTED CONDUITS.

G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES

AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE

INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.

I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE

INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN

ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN

BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND

CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.

COORDINATE WITH ARCHITECTURAL DETAILS.

L. EXIT SIGNS ARE TO BE TYPE "X1", UON.

M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN

THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF

ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR

TO INSTALLATION.

P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN

MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL

COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT

RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR

CLARITY.

1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH

PUSHBUTTON NURSE CALL STATION AT EACH LOCATION.

2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE

REMAINING EMERGENCY OUTLET IN PATIENT ROOM, ONE NORMAL POWER OUTLET PER BED AND

ONE OUTLET IN PATIENT TOILET ROOM WITH NURSE MANAGER.

3. REMOVE ALL POWER AND DATA DEVICES IN NURSES STATION ROOM, RETAIN EXISTING CONDUIT FOR

NEW DEVICES.

4. RELOCATE EXISTING DOOR ANTI-LIGATURE CONTROL PANEL. PROTECT AND REINSTALL IN

RENOVATED NURSES STATION.

5. RELOCATE LIGHT SWITCHES IN THIS ROOM TO NURSES STATION ROOM. PROVIDE NEW DIMMABLE

SWITCHES.

6. TEMPORARY WALL OPENING FOR ACCESS TO MEDICAL ROOM DURING PHASING. CONTRACTOR

SHALL COORDINATE TEMPORARY RELOCATION OF ELECTRICAL UTILITIES AS NECESSARY. RETURN TO EXISTING CONDITIONS AFTER INFILL. TEMPORARILY RELOCATE EXISTING POWER RECEPTACLES

AS REQUIRED

E

N

E

N

E N

E N

E

N

E N

E

N

E

NE N

E N

E N

E

N

E

N

E

N

E

N

E

N

E NE N

N

NNNN

N N N

N N

N

J J

J

7.6

9.4

H I K L

5NLB- 3

5NLB- 3

5NLB- 15

5NLB- 15

5NLB- 27

5NLB- 27

5NLB- 39

5NLB- 39

5NLA- 12

5NLA- 8

5NLA- 8

5NLA- 12

5NLA- 26

5NLB- 11

5NLB- 11

5NLB- 11

5NLB- 11

5NLB- 11

5NLB- 9

5NLB- 9

5NLB- 9

5NLB- 9

5NLB- 9

5NLB- 13

5NLB- 13

5NLB- 13

5NLB- 13

5NLB- 28

5NLB- 24

5NLB- 28

5NLB- 7

5NLB- 7 5NLB- 7

5NLB- 5

5NLB- 5

5NLB- 55NLB- 5

5NLB- 7

5NLB- 26

5NLB- 26

5NLB- 24

5ECA- 36

5NLB- 29

5NLB- 29

5NLB- 29

5NLB- 29

5NLB- 26

5NLB- 26

5NLB- 24

5ECA- 36

5E C

A

5N L

B

5N L

B

5N L

B

5NLB- 315NLB- 31

5N L

B

5N L

B

5N L

B

5N L

B

5N L

B

5N L

B

5E C

A

5E C

A

5NLB- 31

5NLB- 31 5NLB- 33 5NLB- 33

5NLB- 335NLB- 33

5N L

B

5N L

B

5N L

B

5N L

B

5N L

B

5E C

A

5NLB- 33

5NLA- 24

5NLA- 24

5NLB- 14

5NLB- 14

5NLB- 12

5NLB- 14

5NLB- 14

5NLB- 12

5ECA- 28

5NLB- 35

5NLB- 355NLB- 37

5NLB- 37

5NLB- 13

5NLB- 37

5NLB- 10

5NLB- 10

5NLB- 6

5NLB- 10

5NLB- 10

5NLB- 6

5ECA- 265ECA- 24

5NLB- 6

5NLB- 8

5NLB- 8

5NLB- 8

5NLB- 8

5NLB- 6

5NLB- 39 5NLB- 35

5NLA- 24

5NLA- 24

5NLA- 24

5NLA- 24

5NLA- 20

5NLA- 20

5NLA- 20

5NLA- 20

5NLA- 22

5NLA- 22

5NLB- 19

5NLB- 19

5NLB- 21

5NLA- 22

5NLB- 17

5NLA- 26

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 12

5NLA- 26

5ECA- 7

5NLA- 12 5ECA- 9

5ECA- 9

5E C

A

5E C

A

5E

LA

5E

LA

5ELA- 4

5ECA- 13

5NLA- 12

5NLA- 24

5N L

B

5NLA- 22

5NLA- 22

5ECA- 20

5ECA- 20 5ECA- 20

5ECA- 7

5EHEA

5ELA

5ECA

5NLA

5NLB

5NHA

2 2

5NLA- 39

DEDUCT #1

7.6

9.4

H I K L

BATH

B6137A

BATH

B6135A

ELEC EQUIP

B6139

GROUP THERAPY

B6143

ONE BED

B6147

ONE BED

B6149

BATH

B6147A

BATH

B6149A

ONE BED

B6150

BATH

B6150A

TWO BED

B6208

QUIET

B6146

TWO BED

B6206

BATH

B6206A

BATH

B6208A

WASHER DRYER

B6205

NOURISH

KITCHEN

B6203

CLEAN UTILITY

B6201

CLEAN LINEN

B6199

OFFICE

B6140

TELE

B6142

RED BAG

STORAGE

B6138

SOILED UTILITY

B6136

LOCKER ROOM

B6195

TELE EQUIP

B6197

TWO BED

B6204

TWO BED

B6200

BATH

B6200A

BATH

B6204A

STAIR 2

BS2

TWO BED

B6194

BATH

B6192A

BATH

B6194A

CORRIDOR

B6C06

ONE BED

B6137

CORRIDOR

B6C03

CORRIDOR

B6C04

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA B

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:5

P

M

ED106B

ELECTRICAL PLAN - LEVEL 6 - AREA B -

DEMOLITION

654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F3

ELECTRICAL PLAN - LEVEL 6 - AREA B

- DEMOLITION

A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS

PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR

TO ROUGH-IN.

D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS

AND CEILINGS TO MAINTAIN FIRE RATING.

E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL

BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING

FACTOR FOR ROOF-MOUNTED CONDUITS.

G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES

AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE

INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.

I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE

INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN

ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN

BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND

CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.

COORDINATE WITH ARCHITECTURAL DETAILS.

L. EXIT SIGNS ARE TO BE TYPE "X1", UON.

M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN

THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF

ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR

TO INSTALLATION.

P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN

MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL

COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT

RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR

CLARITY.

1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH

PUSHBUTTON NURSE CALL STATION AT EACH LOCATION.

2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE

REMAINING EMERGNECY POWER OUTLET IN PATIENT ROOM AND ONE NORMAL POWER OUTLET PER

BED AND ONE OUTLET IN PATIENT TOILET ROOM WITH NURSE MANAGER.

E

E N

NNNNN

N

N

N

N

N

N

E N

E

N

E

N

E

N

E

N

E

N

E N

E N

E

N

E N

E

N

E N

J

J

J

J J

J

F

7.6

9.4

G4

RECEIVING

B6127

BATH

B6131A

BATH

B6127A

TWO BED

B6131

ONE BED

B6135

HAC

B6133

BATH

B6137A

BATH

B6135A

BATH

B6192A

BATH

B6194A

TWO BED

B6192

SUN DECK

B6188

SECLUSION

B6134A

ANTE RM

B6134

TOILET

B6134B

TOILET

B6193B

SECLUSION

B6193A ANTE RM

B6193

NURSE STATION

B6128

MEDICATION

B6128A

WORK RM HOUSE

STAFF

B6104

STAFF TOILET

B6125

COPY

B6124

HAC

B6184A

DAY RM

RECREATION

B6184

NON-FOOD STRG

5C139

TOILET

5C138

TOILET

5C137

GOLD ELEVATOR

SILVER

ELEVATOR

PSYCHIATRIST

OFFICE

5C144

HEAD NURSE

5C143

TELE

B6184C

ADL KITCHEN

5C133C

CORRIDOR

B6C06

ELEVATOR

LOBBY

B6EGD

CORRIDOR

B6C01

SOCIAL WORK

OFFICE

5C147

PSYCHIATRIST

OFFICE

5C146

NURSE CLINICIAN

PHYSICIAN

ASSISTANT

5C142

REHABILITATION

THERAPIST

OFFICE

5C141

DEMOSTRATION

CLASSROOM

5C158

CORRIDOR

5C-C11

CORRIDOR

5C-C9

HYDRO TANK

5C140

TRAY CART

STORAGE

5C133B

DINING

5C133A

BMS

5C159

CORRIDOR

B6C02

SALLY PORT

B6C02A

ANTE RM

B6134

ANTE RM

B6193

CORRIDOR

B6C05

33 3

5NLC- 42

5NLC- 42

5NLC- 405NLC- 40

5NLC- 40

5NLC- 40

5NLC- 42

5NLC- 42

5NLB- 36

5NLB- 1

5ECA- 16

5ECA- 16

5NLB- 32

5NLB- 32 5NLB- 34

5ECA- 40 5ECA- 42

5NLB- 41

5NLD- 8

5NLD- 12

5NLD- 12

5NLD- 12

5NLB- 4

5ECA- 22

5NLB- 4

5NLA- 26

5NLA- 26

5NLA- 8

5NLA- 8

5NLA- 8

5NLA- 175NLA- 17

5NLA- 6

5NLA- 6

5NLA- 6

5NLA- 8

5NLD- 65NLD- 6

5NLD- 6

5NLD- 6

5NLD- 6

5NLD- 8

5NLD- 6

5NLD- 6

5NLA- 10

5NLA- 26

5NLD- 8

5NLD- 8

5NLD- 8

5NLD- 14

5NLD- 16

5NLC

5NLC

5NLC- 3

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLD- 10

5NLD- 10

5NLD

5NLD

5NLD

5NLD- 10

5NLD- 10

5NLD

5NLD

5NLD

5ECA- 18

5ECA- 18

5ECA- 18

5NLD- 8

5NLD- 8

5NLB- 27

5NLC- 19

5NLC- 19

5NLD

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5NLC

5ECB

5NLC

5NLD

5EHEB

5NHB

5ELB

5NLA- 8

5NLA- 8

5NLA- 26

5NLD- 40

5ECA-15

5NLA-2

5NLA-2

5ECA-15

5ECA-15

5NLA-2

5NLA-2

ECA-14

ECA-14

ECA-14

ECA-14

5NLA-10

5NLA-10

5ECA-16

5ECA-16

5NLA-6

5NLA-6

5ECA-15

5E C

A -1

5E C

A -1

5N L

A -4

5N L

A -4

5E C

A -1

5E C

A -1

5N L

A -1

5E C

A -1

5E C

A -1

5N L

B -3

5N L

B -3

5N L

B -5

5N L

B -5

5N L

B -2

5N L

B -2

5NLA- 17

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA A

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:0

P

M

E-106A

ELECTRICAL PLAN - LEVEL 6 - AREA A - NEW 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F5

ELECTRICAL PLAN - LEVEL 6 - AREA A

- NEW

1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH

PUSHBUTTON NURSE CALL STATION AT EACH LOCATION

2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE

REMAINING EMERGENCY POWER OUTLET AND ONE NORMAL POWER OUTLET PER BED IN EACH

PATIENT ROOM AND PROVIDE ONE GFCI OUTLET IN PATIENT TOILET ROOM, COORDINATE ROUGH-IN

LOCATIONS WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED

ON/OFF CONTROL.

3. PROVIDE NEW ANTI-LIGATURE DOOR SENSOR ON BOTTOM OF DOOR. INTEGRATE WITH EXISTING

SENSOR LOCATED ON TOP OF DOOR. WIRE TO EXISTING POWER SUPPLY AND CONTROLS. MAIN

PANEL LOCATED IN THE NURSES STATION. SEE SPECIFICATION 08 71 00 FOR ADDITIONAL

REQUIRMENTS.

4. PROVIDE NEW POWER, DATA AND COAXIAL CONNECTIONS FOR NEW TV MONITOR AT 84" ABOVE

FINISHED FLOOR, COORDINATE ROUGH-IN LOCATIONS WITH NURSE MANAGER.

5. PROVIDE NEW POWER AND DATA AS SHOWN IN RENOVATED NURSES STATION.

6. PROVIDE NEW CAT 6A CABLING FOR ALL NEW DEVICES. PROVIDE NEW CAT 6A PATCH PANEL AND

LOCATE ON EXISTING RACK, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

7. PROVIDE NEW HARD-WIRED 120V/24V CONNECTION AND TRANSFORMER FOR INFRARED FLUSH

VALVE OPERATION.

8. TEMPORARY WALL OPENING FOR ACCESS TO MEDICAL ROOM DURING PHASING. CONTRACTOR

SHALL COORDINATE TEMPORARY RELOCATION OF ELECTRICAL UTILITIES AS NECESSARY. RETURN

TO EXISTING CONDITIONS AFTER INFILL.

9. RECONFIGURE RECEPTACLE LAYOUT IN MEDICATION ROOM. RELOCATE ONE NORMAL POWER

RECEPTACLE TO NORTH WALL AND ONE EMERGENCY POWER RECEPTACLE TO SOUTH WALL.

10. PROVIDE NEW ANTI-LIGATURE CAMERA (BASIS OF DESIGN AXIS Q92160-SLV)AND CONNECT TO EXISTING HEAD END EQUIPMENT. CONFIRM FINAL LOCATION WITH OWNER TO ENSURE ADQQUATE

COVERAGE.

A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS

PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR

TO ROUGH-IN.

D. PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR SLABS, WALLS

AND CEILINGS TO MAINTAIN FIRE RATING.

E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL

BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.

F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING

FACTOR FOR ROOF-MOUNTED CONDUITS.

G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES

AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE

INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.

I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE

INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN

ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME

AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

K. WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE EXIT SIGN

BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR FRAME AND

CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT.

COORDINATE WITH ARCHITECTURAL DETAILS.

L. EXIT SIGNS ARE TO BE TYPE "X1", UON.

M. PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

N. PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR GREATER THAN

THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

O. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF

ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR

TO INSTALLATION.

P. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN

MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

Q. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL

COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

R. WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY CONNECT

RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

S. THE OPENING IN CEILINGS ARE THE LOCATIONS OF THE HVAC AIR TERMINALS, NOT SHOWN FOR

CLARITY.

NNNN

N N N

N N

N

E N

E

N

E N

E N

E

N

E

N

E

N

E NE N

E

N

E N

E

N

E

N

E

N

E

N

E

N

E N

E

N

J J

J

J

J

J

J

J

J

J

J

J

7.6

9.4

H I K L

BATH

B6137A

BATH

B6135A

RED BAG

STORAGE

B6138

SOILED UTILITY

B6136

LOCKER ROOM

B6195

TWO BED

B6194

BATH

B6192A

BATH

B6194A

CORRIDOR

B6C06

ONE BED

B6137

CORRIDOR

B6C03

ELEC EQUIP

B6139

GROUP THERAPY

B6143

ONE BED

B6147

ONE BED

B6149

BATH

B6147A

BATH

B6149A

ONE BED

B6150

BATH

B6150A

TWO BED

B6208

QUIET

B6146

TWO BED

B6206

BATH

B6206A

BATH

B6208A

WASHER DRYER

B6205

NOURISH

KITCHEN

B6203

CLEAN UTILITY

B6201

CLEAN LINEN

B6199

OFFICE

B6140

TELE

B6142

TELE EQUIP

B6197

TWO BED

B6204

TWO BED

B6200

BATH

B6200A

BATH

B6204A

STAIR 2

BS2

CORRIDOR

B6C04

5ELA

5ECA

5NLA

5NLB

5NHA

5EHEA

5 5 5 5

5NLA- 85NLA- 8

5NLA- 8

5NLA- 26

5NLB- 28

5ECA- 38

5NLB- 7

5NLB- 5

5NLB- 26

5ECA- 36

5NLB- 26

5ECA- 36

5E C

A

5N L

B

5N L

B

5N L

B

5E C

A

5N L

B

5N L

B

5E C

A

305NLA- 24

5NLA- 24

5NLB- 14

5ECA- 28

5NLB- 14

5NLB- 10

5ECA- 26

5NLB- 10

5ECA- 24

5NLB- 8

5NLB- 8

5NLA- 24 5NLA- 24

5NLA- 24

5NLA- 24

5NLA- 20

5NLA- 20

5NLA- 20

5NLA- 20

5NLA- 22

5NLA- 22

5NLB- 19

5NLB- 19

5NLB- 21

5NLA- 22

5NLB- 17

5NLA- 26

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 14

5NLA- 12

5NLA- 26

5ECA- 7

5NLA- 12 5ECA- 9

5ECA- 9

5E C

A

5E C

A

5E

LA

5E

LA

5ELA- 4

5ECA- 13

5NLA- 12

5NLA- 24

5NLA- 22

5NLA- 22

5ECA- 20

5ECA- 20

5ECA- 20

5ECA- 7

2 2

1 1

5NLA- 39

5N L

B -5

5N L

B -2

5N L

B -2

5N L

B -2

5N L

B -1

5N L

B -1

5NLB-12

5NLB-13

5NLB-13

2 2

2 2

2 2

DEDUCT #1

5ECA- 38

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

AREA B

TRIPLE C - The A/E Group

1345 CAPITAL BLVD. SUITE A

RENO, NA 89502

MAT PERKINS

520-481-8548

/12

/20

B

IM

/6

-2

-1

I n p a ti e n t M e n ta l H e a lt h E

O C

C o m p lia n c e R e n o v a ti o n s /6

-2

-1

.1

.M

E P

F .r v t

/1

/2

:2

:1

P

M

E-106B

ELECTRICAL PLAN - LEVEL 6 - AREA B - NEW 654-20-117

02/12/2021 M. PERKINS G. WEAVER

BID DOCUMENT

SUBMITTAL

INPATIENT MENTAL HEALTH EOC

COMPLIANCE RENOVATIONS

975 KIRMAN AVENUE RENO, NV 89502-0993

SCALE: 1/4" = 1'-0"

F3

ELECTRICAL PLAN - LEVEL 6 - AREA B

- NEW

1. REMOVE EXISTING NURSE CALL PULL STRING IN SHOWER AND AT TOILET AND REPLACE WITH

PUSHBUTTON NURSE CALL STATION AT EACH LOCATION.

2. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT ALL PATIENT ROOMS. COORDINATE ONE

REMAINING EMERGENCY POWER OUTLET AND ONE NORMAL POWER OUTLET PER BED IN EACH

PATIENT ROOM AND PROVIDE ONE GFCI OUTLET IN PATIENT TOILET ROOM, COORDINATE ROUGH-IN

LOCATIONS WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED

ON/OFF CONTROL.

3. REMOVE CONVENIENCE OUTLETS, BLANK FACED JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) AT GROUP THERAPY ROOM. COORDINATE 1

REMAINING OUTLET FOR TV WITH NURSE MANAGER.

4. REMOVE CONVENIENCE OUTLETS, BLANK FACES JUNCTION BOXES, AND ASSOCIATED CONDUCTORS

(CONDUIT TO REMAIN AND ABANDONED IN PLACE) IN PROCEDURE ROOM AS NECESSARY.

COORDINATE WITH NURSE MANAGER OUTLETS TO REMAIN FOR EQUIPMENT.

5. PROVIDE NEW ANTI-LIGATURE DOOR SENSOR ON BOTTOM OF DOOR. INTEGRATE WITH EXISTING

SENSOR LOCATED ON TOP OF DOOR. WIRE TO EXISTING POWER SUPPLY AND CONTROLS. MAIN

PANEL LOCATED IN THE NURSES STATION. SEE SPECIFICATION 08 71 00 FOR ADDITIONAL

REQUIRMENTS.

6. PROVIDE NEW CAT 6A CABLING FOR ALL NEW DEVICES. PROVIDE NEW CAT 6A PATCH PANEL AND

LOCATE ON EXISTING RACK, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

7. PROVIDE NEW HARD-WIRED 120V/24V CONNECTION AND TRANSFORMER FOR INFRARED FLUSH

VALVE OPERATION.

8. NEW EMERGENCY POWER OUTLET WIRED TO PANEL AND CIRCUIT SHOWN, COORDINATE ROUGH-IN

LOCATION WITH NURSE MANAGER. PATIENT ROOM ELECTRICAL OUTLETS SHALL HAVE KEYED

ON/OFF CONTROL.

A.