Questions_Responses 20260123.pdf
PDF 430 KB Posted
- Attached to
- Replacement Transformer Enclosure
- Solicitation number
- 51291PR260000023
About this file
This is a Questions and Responses document for USCG Solicitation 51291PR260000023 regarding transformer enclosure replacement. The document does not address specific contract terms, pricing, or award details, but rather clarifies technical and procedural requirements based on twelve questions submitted by potential offerors.
The solicitation pertains to replacing a 750 KVA transformer enclosure (currently Type 3R) at a USCG facility. Key technical specifications include: 480V primary and 450V secondary voltage, existing transformer serial number 28367, and a requirement for twelve-inch minimum clearance from walls and obstructions at ventilation openings. The US Coast Guard will serve as the Authority Having Jurisdiction (AHJ). The USCG clarified that the requirement is open to any small business vendor capable of performing the work and is not sole-source; Amendment 1 removed references to any specific contractor. Contractors may fabricate and ship the replacement enclosure prior to installation, but remain responsible for onsite installation. Site visits are not currently scheduled, though additional photographs of the existing transformer and surrounding area have been provided. The only constraints on performance are the timeframes specified in the Statement of Work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Supplemental Photographs.pdf | ||
| Statement of Work Transformer Enclosure Final draft (1).pdf | ||
| WD AK20260001.pdf | ||
| Homer Transformer Photos (1).pdf | ||
| Statement of Work.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question or Comment Number Question/Comment USCG Response
1 What type of enclosure, as the photo does not show it? 3R is what is listed as the enclosure type on the nameplate.
2 Can a site visit be conducted? Nothing is scheduled at this time.
Can we get additional photos? Pan view of the inside, 360 of outside of the existing transformer and the surrounding area? Additional photographs provided.
Can you provide the manufacturer and serial number of the existing transformer? The nameplate states 28367.
5 What is the listed primary and secondary voltage? 480 Primary 450 Secondary
Will there be a requirement to provide field UL listing/certifications, such as UL 1561?
The nameplate says " twelve inch minimum clearance required from walls and obstructions at both incoming and outgoing ventilation openings."
7 Who is the AHJ? City, Local Utility or the Coast Guard? The US Coast Guard will be the authority having jurisdiction.
Can you provide detailed information regarding the 750 KVA transformer? See photographs of nameplate attached.
9 Please provide the dimensions of the existing enclosure.
The replacement transformer should be of sufficient size to accommodate a 750 KVA transformer.
Will it be acceptable to have the enclosure fabricated and shipped to the site prior to the transformer enclosure replacement?
Yes. However, clarifying that the contractor is responsible for the onsite installation of the replacement transformer enclosure.
11 Is this requirement intended to be sole source (or otherwise limited)?
Please see Amendment 1 to the solicitation. The SOW was replaced with a new version, removing any reference to a specific contractor to perform the work. This requirement is open to any small business vendor capable of performing the requirement.
Is there a current incumbent contractor or any constraints due to a prior contractor working on the transformer?
The only constraints are the timeframes identified to complete the work outlined in the Statement of Work.
Solicitation 51291PR260000023 Questions and Responses