This is an Evaluation Report prepared for Major's Metal Roofing & Custom Sheet Metal, Inc. regarding their 26-gauge 5V-Crimp metal roofing panel, with approval under Florida Building Code 8th Edition (2023) designation FL 16179.2-R5. The product consists of 24-inch wide coverage panels with five 1/2-inch high ribs, manufactured from minimum 26-gauge, 50 ksi steel available in galvanized, Galvalume, or painted finishes. The panels are designed for installation on minimum 19/32-inch thick APA-rated plywood or wood plank decking using 8d x 2-inch ring shank nails or #8 x 2-inch wood screws spaced at 6 inches on center. Installation requires a minimum roof slope of 1/2:12 or greater with underlayment meeting FBC 2023 Section 1507.4.5.1 specifications.

The evaluation report, prepared by Florida Professional Engineer Bala Sockalingam (PE #62240) and dated July 23, 2023, establishes design uplift pressure ratings of 109.3 psf at 12-inch fastener spacing and 159.3 psf at 6-inch fastener spacing, both with a safety factor of 2. Fastening utilizes #9 x 1.5-inch corrosion-resistant hex head wood screws with washers through panel ribs, with minimum 3/16-inch deck penetration. The report references compliance testing conducted per TAS 125-03 standards through Intertek Testing Services, with supporting test reports from 2006 and 2009. The product is not applicable for High Velocity Hurricane Zones, and fire classification ratings require separate documentation per ASTM E108/UL790 standards. A load span table provides uplift design loads for fastener spacing ranging from 6 to 12 inches on center, with loads varying from 159.3 psf to 109.3 psf respectively.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EVALUATION REPORT OF

MAJOR'S METAL ROOFING & CUSTOM SHEET METAL, INC.

‘26 GA. 5V-CRIMP PANEL’

FLORIDA BUILDING CODE 8TH EDITION (2023)

FLORIDA PRODUCT APPROVAL

FL 16179.2-R5

ROOFING

METAL ROOFING

Prepared For:

Major's Metal Roofing & Custom Sheet Metal, Inc.

406 NW 54th Street Miami, FL 33127

Telephone: (305) 757-9503 Fax: (305) 757-4031

Prepared By:

Bala Sockalingam, Ph.D., P.E.

Florida Professional Engineer #62240 1216 N Lansing Ave., Suite C

Tulsa, OK 74106 Telephone: (918) 492-5992

This report consists of Evaluation Report (3 Pages including cover)

Installation Details (1 Page) Load Span Table (1 Page)

Report No. C2697-2 Date: 7.23.2023

This item has been digitally signed and sealed by Bala Sockalingam, PE, on the date indicated.

Printed copies of this document are not considered signed and sealed and this signature must be verified on any electronic copies.

2023.07.23 12:01:13 -05'00'

Haven Burkee Textbox

V-CRIMP ROOFING PRODUCT APPROVAL

FL 16179.2-R5

C2697-2

7.23.2023

Manufacturer: Major's Metal Roofing & Custom Sheet Metal, Inc.

Product Name: 5V-Crimp

Panel Description: 24" wide coverage with (5) 1/2" high ribs

Materials: Min. 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or

Galvalume coated steel (ASTM A792) or painted steel (ASTM A755).

Corrosion resistant as per FBC 2023 Section 1507.4.3.

Deck Description: Min. 19/32" thick APA rated plywood or wood plank for new and existing constructions. Designed and installed as per FBC 2023.

Deck Attachment: 8d x 2" long ring shank nails or #8 x 2" long wood screws at 6" o.c. in the plywood field and edges

Underlayment: Minimum underlayment as per FBC 2023 Section 1507.4.5.1

Slope: 1/2:12 or greater in accordance with FBC 2023 Section 1507.4.2

Design Uplift Pressure: 109.3 psf at fastener spacing of 12" o.c.

(Factor of Safety = 2) 159.3 psf at fastener spacing of 6" o.c.

Fastener Type: #9 x 1.5" long hex head wood screws with washers through panel ribs spaced at 12" o.c. Fastener shall be of sufficient length to penetrate through deck a minimum of 3/16". Corrosion resistant as per FBC 2023 1507.4.4. At panel ends, the panel will be fastened to deck as per Major's Metal current installation procedure.

Test Standards: Roof assembly tested in accordance with TAS 125-03 ‘Standard

Requirements for Metal Roofing Systems’.

Code Compliance: The product described herein has demonstrated compliance with FBC

2023 Section 1507.4.

Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2023 Section 1609 or ASCE 7-22 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. The design pressure for reduced fastener spacing may be computed using rational analysis prepared by a Florida Professional Engineer or based on Major’s Metal load span table. This evaluation report is not applicable in High Velocity Hurricane Zone. Fire classification is not within the scope of this Evaluation Report. Refer to FBC 2023 Section 1505 and current approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product.

FL 16179.2-R5

C2697-2

7.23.2023

Supporting Documents: TAS 125-03 Test Reports Intertek Testing Services (Formerly Hurricane Test Laboratory, LLC) 0299-0507-06, Reporting Date 7/18/2006 0299-0308-09, Reporting Date 4/17/2009

MAJOR'S METAL ROOFING & CUSTOM SHEET METAL, INC.

5V-Crimp Panel Uplift Loads

(Min 26 ga.)

Description Fastener Spacing Uplift Design along panel length Load

(in) (psf)

Coverage width: 24" 6 159.3

7 150.9

8 142.6

9 134.3

10 125.9

11 117.6

12 109.3

Notes:

1. The bold numbers indicate design loads calculated from test data with safety factor of 2.

2. Panels must be installed as per Evaluation Report FL 16179.2 and Major's Metal current installation procedure.

3. Three or more spans condition.

Panel fasteners through ribs spaced at 12" o.c.

1216 N Lansing Ave., Suite C Tulsa, Ok 74106 918 492 5992

Bala Sockalingam, Ph.D., P.E.

FL 62240