This document comprises the approved construction plans and specifications for the Davis Technical College Electrical Transformer and Panel Replacement - Phase 1 project located at 550 E 300 S, Kaysville, Utah. The project, managed by the State of Utah's Division of Facilities Construction and Management (DFCM), involves the replacement and relocation of selected transformers and electrical panels throughout the main building. The construction scope includes demolition of existing electrical equipment, installation of new transformers (75 kVA to 300 kVA), and replacement of multiple electrical distribution panels located in various rooms (1018A, 1205A, 1408, 1405, 1006, and 1001F). The approved plans consist of detailed construction documents including electrical schedules, one-line diagrams, demolition and installation plans, typical labeling details, and panel schedules with load calculations. The plans were designed by LYNK Engineers, LLC (Project No. 26-00536) and reviewed for code compliance by the Division of Facilities Construction and Management on September 16, 2026. Two add alternates are included: ADD ALT 01 for demolishing and replacing existing "MDP-1" and ADD ALT 02 for demolishing and replacing existing "MDP-2."

The construction cost estimate for this Stage II invitation to bid is $300,000.00, with only prequalified contractors eligible to submit bids. The scope encompasses comprehensive work including existing circuit tracing and labeling, protection and reuse of existing branch circuits where possible, Shawmut terminations for splices, temporary cooling provisions during panel replacement, seismic bracing of all equipment, concrete housekeeping pads for equipment placement, and restoration of all finishes including flooring, carpet, walls, and ceilings. All work must comply with the National Electrical Code (NEC), International Building Code (IBC), NFPA standards, and International Fire Code (IFC), subject to on-site field inspection approval by the Authority Having Jurisdiction. Contractors are required to submit detailed submittals in electronic PDF format with indexed equipment sections, coordinate with architectural reflected ceiling plans, and assume approximately 15 circuits will require tracing with unknown loads to be documented and panel schedules updated accordingly.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 www.lynkengineers.com

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE STATE

O F

U

TA

H

State of Utah-Department of Administrative Services

DIVISION OF FACILITIES CONSTRUCTION

AND MANAGEMENT

4110 State Office Building/Salt Lake City, Utah 84114/538-3018

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

DFCM PROJECT #:DFCM PROJECT #:

LYNK PROJECT #: LYNK PROJECT #:

CONSTRUCTION DOCUMENTS: CONSTRUCTION DOCUMENTS:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:0

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

ELECTRICAL COVER

SHEET

E001

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

DAVIS TECHNICAL COLLEGE

ELECTRICAL TRANSFORMER AND

PANEL REPLACEMENT - PHASE 1

26-00536

550 E 300 S, Kaysville, UT 84037

AUG 7, 2026

27048220

27048220

Mark: Date: Description

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

THOMAS PETERSON

09/16/2026

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:0

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

ELECTRICAL

SYMBOLS & NOTES

E002

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

GENERAL ELECTRICAL NOTES

1. CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL FAMILIARIZE

THEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS,

MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED PRODUCTS,

CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN THE EQUIPMENT

SUPPLIED AND THE INTENT OR FUNCTION OF THE EQUIPMENT, ETC, SHALL BE

SUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING FOR CLARIFICATION PRIOR

TO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING OF THE PROJECT. WHERE

DISCREPANCIES OR MULTIPLE INTERPRETATIONS OCCUR, THE MOST STRINGENT

(WHICH IS GENERALLY RECOGNIZED AS THE MOST COSTLY) THAT MEETS THE

INTENT OF THE DOCUMENTS SHALL BE ENFORCED.

2. OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL AND

EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE INCORPORATED

INTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE INSTALLER AND COSTS

FOR RECEIVING, HANDLING, STORAGE, IF REQUIRED, AND INSTALLATION ARE

INCLUDED IN THE CONTRACT SUM.

A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLER

FURNISHED THE MATERIALS OR EQUIPMENT.

B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNER

FURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER WILL

INSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS ARE

DAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS WITH

THE TRANSPORT COMPANY AND THE OWNER WILL ARRANGE

FOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FOR

MANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OF

MANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.

C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATES

OF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING AND

HANDLING OWNER FURNISHED ITEMS AT THE SITE.THE INSTALLER IS

RESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROM

DAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, AND

TO REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF HIS

OPERATIONS.

DEFINITIONS

NOTE: ALL DEFINITIONS MAY NOT BE USED.

INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS,

NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR

SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE

CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED",

"SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE

THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.

DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED",

"SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY

THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.

APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE

ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND

REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS

STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.

FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO

THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY,

INSTALLATION, AND SIMILAR OPERATIONS."

INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT

SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION,

PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING,

CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS."

PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE

AND READY FOR THE INTENDED USE."

INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY

THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-

SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION

ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR

OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE

OPERATIONS THEY ARE ENGAGED TO PERFORM.

TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO

DESCRIBE ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS

"SPECIAL SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY

LIMITED TO ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS

SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY

SYSTEMS, VOICE AND DATA CABLING SYSTEMS, ETC...

ABBREVIATIONS

NOTE: ALL ABBREVIATIONS MAY NOT BE USED.

1P SINGLE POLE

1PH SINGLE-PHASE

1WAY ONE-WAY

2/C TWO-CONDUCTOR

2WAY TWO-WAY

3/C THREE-CONDUCTOR

3WAY THREE-WAY

4OUT QUADRUPLE RECEPTACLE

OUTLET

4PDT FOUR-POLE DOUBLE THROW

4PST FOUR-POLE SINGLE THROW

4W FOUR-WIRE

4WAY FOUR-WAY

A ABOVE COUNTER

AC ARMORED CABLE

ADA AMERICANS WITH DISABILITIES

ACT

ADJ ADJACENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING

CAPACITY

ALUM ALUMINUM

AMP AMPERE

ANN ANNUNCIATOR

AP ACCESS POINT (WIRELESS

DATA)

AR AS REQUIRED

ASC AMPS SHORT CIRCUIT

ATS AUTOMATIC TRANSFER

SWITCH

AV AUDIO VISUAL

AWG AMERICAN WIRE GAGE

BB

XFMR

BUCK-BOOST TRANSFORMER

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

C CEILING MOUNTED

CAT CATEGORY

CATV COMMUNITY ANTENNA

TELEVISION

CB CIRCUIT BREAKER

CCBA CUSTOM COLOR AS SELECTED

BY ARCHITECT

CCTV CLOSED CIRCUIT TELEVISION

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/

OWNER INSTALLED

CFBA CUSTOM FINISH AS SELECTED

BY ARCHITECT

CKT CIRCUIT

CM CONSTRUCTION MANAGER

CND CONDUIT

CO CONVENIENCE OUTLET

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTROL PANEL

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

dBA UNIT OF SOUND LEVEL

DPDT DOUBLE POLE, DOUBLE

THROW

DS DISCONNECT SWITCH

E ENHANCED

EA EACH

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENT ELECTRIC NONMETALLIC

TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ER EQUIPMENT ROOM

EX EXISTING

F FURNITURE MOUNTED

FA FIRE ALARM

FCP FIRE ALARM CONTROL PANEL

FLA FULL LOAD AMPS

FMC FLEXIBLE METAL CONDUIT

FOB FREIGHT ON BOARD

FPP FIBER PATCH PANEL

FVNR FULL VOLTAGE

NON-REVERSING

FVR FULL VOLTAGE REVERSING

GEN GENERATOR

GFCI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTION

GIG GIGA HERTZ

GND GROUND

HD HEAVY DUTY

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSE POWER

HPF HIGH POWER FACTOR

HPS HIGH PRESSURE SODIUM

HV HIGH VOLTAGE

HWM HORIZONTAL WIRE

MANAGEMENT

HZ HERTZ

I/O INPUT/ OUTPUT

IG ISOLATED GROUND

IMC INTERMEDIATE METAL

CONDUIT

IN/IS INSULATED/ ISOLATED

IR INFRARED

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE

REFERENCE AND LINE SYMBOLS

DETAIL INDICATOR: A5 INDICATES DETAIL NUMBER, E-501

INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.

A5 E-501

ELEVATION OR SECTION INDICATOR, EXTERIOR: A5 INDICATES

ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING

SHEET WHERE ELEVATION OR SECTION IS SHOWN.

A5 E-201

ELEVATION OR SECTION INDICATOR, INTERIOR: A5 INDICATES

ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING

SHEET WHERE ELEVATION OR SECTION IS SHOWN.

A5 E-201

ROOM IDENTIFIER WITH ROOM NAME AND NUMBER.

ROOM NAME

KEYNOTE INDICATOR.1

REVISION INDICATOR.1

CU-1 EQUIPMENT INDICATOR.

BREAK, STRAIGHT: TO BREAK PARTS OF DRAWING

BREAK, ROUND

MATCH LINE INDICATOR: CENTER, EXTRA WIDE LINE.MATCH LINE

SEE XX/X-XXX

NEW LINE: MEDIUM LINE.

EXISTING TO REMAIN LINE: THIN LINE.

DEMOLITION LINE: DASHED, MEDIUM LINE

ELECTRICAL EQUIPMENT INDICATOR. "XXX" INDICATES TYPE OF

EQUIPMENT OR EQUIPMENT ID. "EF-X" IDENTIFIES MECHANICAL

EQUIPMENT BEING SERVED. REFER TO EQUIPMENT SCHEDULE

FOR ADDITIONAL INFORMATION.

EF-X

XXX

EQUIPMENT INDICATOR. "X-X" INDICATES EQUIPMENT MARK

SHOWN ON EQUIPMENT SCHEDULE. "1LA-3" IDENTIFIES PANEL

EQUIPMENT IS CIRCUITED TO. REFER TO EQUIPMENT SCHEDULE

FOR ADDITIONAL INFORMATION.

1LA-3

X-X

MECHANICAL EQUIPMENT INDICATOR. "X-X" INDICATES

EQUIPMENT MARK SHOWN ON EQUIPMENT SCHEDULE. "XMDP"

IDENTIFIES PANEL EQUIPMENT IS CIRCUITED TO. REFER TO

EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.

XMDP

X-X

WIRING METHODS

SYMBOL DESCRIPTION

SYMBOLS LEGEND

WIRING.

BRANCH CIRCUIT HOME RUN TO PANELBOARD: NUMBER OF

ARROWS INDICATES NUMBER OF CIRCUITS. LETTER AND

NUMBER NOTATIONS IDENTIFY PANEL AND CIRCUIT NUMBERS.A-1,3,5

LOW VOLTAGE WIRING: DIVIDE, MEDIUM LINE.

CONDUIT STUB. DIMENSION RECORD DRAWINGS AND MARK.

CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR. REFER

TO ONE-LINE DIAGRAM.1

ADA ACCESS PUSH PLATEHC

JUNCTION BOX.J

JUNCTION BOX, SYSTEMS FURNITURE COMMUNICATION

CONNECTION.SCJ

JUNCTION BOX, SYSTEMS FURNITURE POWER CONNECTION.SPJ

PULL BOX.PB

CABLE TRAY ABOVE ACCESSIBLE CEILING.

"A" DENOTES CABLE TRAY WIDTH, "B" DENOTES CABLETRAY

DEPTH. +/-C'-D" DENOTES CABLE TRAY ELEVATION ABOVE OR

BELOW FINISHED SURFACE.

A"xB" +/-C'-D"

JUNCTION BOX, CEILING.CJ

LADDER RACK.

MECHANICAL EQUIPMENT CONNECTION. REFER TO EQUIPMENT

SCHEDULE FOR REQUIREMENTS.

SYMBOL DESCRIPTION

SYMBOLS LEGEND

SYMBOL DESCRIPTION

SYMBOLS LEGEND

ELECTRICAL POWER AND DISTRIBUTION

FUSE WITH RATING (ONE-LINE DIAGRAM).

DISCONNECT, FUSED (ONE-LINE DIAGRAM).

DISCONNECT, NONFUSED (ONE-LINE DIAGRAM).

DISCONNECT WITH FUSE AND MOTOR STARTER COMBINATION

(ONE-LINE DIAGRAM).

OVERLOAD RELAY (ONE-LINE DIAGRAM).

STARTER (ONE-LINE DIAGRAM).

CIRCUIT BREAKER, MOLDED CASE (ONE-LINE DIAGRAM).

CIRCUIT BREAKER, MOLDED CASE WITH SHUNT TRIP

(ONE-LINE DIAGRAM).

CIRCUIT BREAKER, MOTOR CIRCUIT PROTECTION

(ONE-LINE DIAGRAM).

MCP

CIRCUIT BREAKER, SOLID STATE (ONE-LINE DIAGRAM).

CIRCUIT BREAKER, SOLID STATE WITH GROUND FAULT

PROTECTION (ONE-LINE DIAGRAM).

GFP

MOTOR.

TRANSFORMER (ONE-LINE DIAGRAM).

TRANSFORMER, CURRENT (ONE-LINE DIAGRAM).

PANELBOARD (ONE-LINE DIAGRAM)."1H"

PANELBOARD WITH MAIN LUGS ONLY. BUS SIZE AND PHASE AS

SHOWN (ONE-LINE DIAGRAM).

225/3

"1H"

PANELBOARD WITH MAIN CIRCUIT BREAKER. SIZE AND PHASE AS

SHOWN (ONE-LINE DIAGRAM).

225/3

"1H"

PANELBOARD WITH MAIN AND SUB FEED CIRCUIT BREAKER

(ONE-LINE DIAGRAM).

60/3

225/3

"1H"

ELECTRICAL POWER AND DISTRIBUTION

PANELBOARD WITH SUB FEED LUGS (ONE-LINE DIAGRAM).

225/3 225/3 "1H" "1H"

PANELBOARD WITH CIRCUIT BREAKER AND SUB FEED LUGS

(ONE-LINE DIAGRAM).

225/3 "1H" "1H"

TRANSFER SWITCH (ONE-LINE DIAGRAM).

DIGITAL MULTIMETER (ONE-LINE DIAGRAM).DMM

SERVICE ENTRANCE SURGE PROTECTION (ONE-LINE DIAGRAM).

GENERATOR, ANNUNCIATOR (ONE-LINE DIAGRAM).ANN

GENERATOR, POWER (ONE-LINE DIAGRAM).G

DISCONNECT SWITCH, FUSED.

DISCONNECT SWITCH, UNFUSED.

STARTER, COMBINATION WITH DISCONNECT SWITCH.

STARTER OR MOTOR CONTROLLER.

PUSHBUTTON.

PUSHBUTTONS, MOTOR CONTROL.

PANELBOARD CABINET, FLUSH MOUNTED.

PANELBOARD CABINET, SURFACE MOUNTED, 1 SECTION.

PANELBOARD CABINET, SURFACE MOUNTED, 2 SECTION.

DP#__

DISTRIBUTION PANEL OR SWITCHBOARD.

LP

LIGHTING RELAY, CONTACTOR PANEL, OR DIMMING ENCLOSURE.

SWITCH, TOGGLE MOTOR STARTER WITH OVERLOAD

PROTECTION.ST

METER.M

EARTH GROUND (ONE-LINE DIAGRAM).

SINGLE BRANCH CIRCUIT HOME RUN TO PANELBOARD WITH

DEDICATED NEUTRAL CONDUCTOR. LETTER AND NUMBER

NOTATION IDENTIFY PANEL AND CIRCUIT NUMBER.A-1

PUSH BUTTON, REMOTE EMERGENCY STOP.EPO

KIRK-KEY MECHANICAL INTERLOCK (ONE-LINE DIAGRAM)K

DISTRIBUTION PANELBOARD, MOTOR CONTROL CENTER,

PLUG-IN BUSWAY, MEDIUM VOLTAGE SWITCHBOARD

(ONE-LINE DIAGRAM).

"1DPHA"

CIRCUIT BREAKER, ADJUSTABLE TRIP. "225AF" REPRESENTS

THE RATING AND "150AT" REPRESENTS THE TRIP SETTING.

(ONE-LINE DIAGRAM).

#AF

#AT

PANELBOARD WITH MAIN LUGS ONLY AND SURGE PROTECTION

WITH CIRCUIT BREAKER (ONE-LINE DIAGRAM).

25/3

225/3

"1H"

ARC ENERGY REDUCTION

3. EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL, AND

COMMUNICATION SPACES): INSTALL RACEWAYS BETWEEN DECK AND

STRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.

ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALL

CONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT COMPLY

WITH THESE REQUIREMENTS TO THE ARCHITECT.

4. SUBMITTALS: PROVIDE ORIGINAL ELECTRONIC PDF FORMAT, BOUND,

BOOKMARKED (EACH SECTION AND PRODUCT), AND HIGHLIGHTED. JOB NAME

AND SUBCONTRACTOR SHALL BE ON THE FRONT COVER. PREPARE INDEX OF

EQUIPMENT SUBMITTED IN EACH TAB.

5. REFLECTED CEILING PLANS: COORDINATE THE LOCATION OF LIGHT FIXTURES

WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. REFER ALL

DISCREPANCIES TO THE ARCHITECT AND ENGINEER.

6. ALL WORK SHALL BE DONE ACCORDING TO THE CURRENT NATIONAL ELECTRIC

CODE (NEC), IBC, NFPA, AND IFC. COMPLIANCE AND FINAL APPROVAL IS SUBJECT

TO THE ON SITE FIELD INSPECTION OF THE AHJ.

kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR

LED LIGHT EMITTING DIODE

LFMC LIQUID TIGHT FLEXIBLE METAL

CONDUIT

LFNC LIQUID TIGHT FLEXIBLE

NONMETALLIC CONDUIT

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTG LIGHTING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION

SYSTEM

MAX MAXIMUM

MC METAL CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTION

MDP MAIN DISTRIBUTION PANEL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT

PROTECTION

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFC NATIONAL FIRE CODE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OCP OVER CURRENT PROTECTION

OE OWNER ELECTRONICS

OF/CI OWNER FURNISHED/

CONTRACTOR INSTALLED

OF/OI OWNER FURNISHED/ OWNER

INSTALLED

OFP OBTAIN FROM PLANS

OH DR OVERHEAD (COILING) DOOR

OL OVERLOAD

PB PUSHBUTTON

PF POWER FACTOR

PH PHASE

PNL PANEL

PNM PLENUM

PR PAIR

PS POWER SUPPLY

PT POTENTIAL TRANSFORMER

PTZ PAN/TILT/ZOOM

QTY QUANTITY

R REMOVE

RCP REFLECTED CEILING PLAN

RMC RIGID METAL CONDUIT

RNC RIGID NONMETAL CONDUIT

RPM REVOLUTIONS PER MINUTE

RPP RISER PATCH PANEL

RR REMOVE AND RELOCATE

S/S START/STOP

SCA SHORT CIRCUIT AMPS

SCBA STANDARD COLOR AS

SELECTED BY ARCHITECT

SF SQUARE FOOT (FEET)

SFBA STANDARD FINISH AS

SELECTED BY ARCHITECT

SPD SURGE PROTECTIVE DEVICE

SPDT SINGLE POLE, DOUBLE THROW

SPEC SPECIFICATION

SPP STATION PATCH PANEL

SPST SINGLE POLE, SINGLE THROW

ST SINGLE THROW

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TL TWIST LOCK

TP TELEPHONE POLE

TP TWISTED PAIR

TR TELECOMMMUNICATIONS

ROOM

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE

SUPPRESSER

TYP TYPICAL

UF UNDERFLOOR

UGND UNDERGROUND

UPS UNINTERRUPTIBLE POWER

SUPPLY

V VOLTS

VA VOLT AMPERE

VFC/VF

D

VARIABLE FREQUENCY MOTOR

CONTROLLER

VWM VERTICAL WIRE MANAGEMENT

W/ WITH

W/O WITHOUT

WP WEATHERPROOF

WPP WIRELESS PATCH PANEL

XFMR TRANSFORMER

ELECTRICAL-SHEET INDEX

E001 ELECTRICAL COVER SHEET

E002 ELECTRICAL SYMBOLS & NOTES

E003 TYPICAL LABELING DETAILS

E004 TYPICAL LABELING DETAILS

E101 OVERALL LEVEL 1 ELECTRICAL PLAN

E301 ENLARGED DEMOLITION ROOM PLANS

E302 ENLARGED DEMOLITION INTERIOR PANELBOARDS

E303 ENLARGED ROOM PLANS

E601 ELECTRICAL SCHEDULES

E602 DEMOLITION ONE-LINE DIAGRAM - MAIN BUILDING - 1 OF 2

E603 DEMOLITION ONE-LINE DIAGRAM - MAIN BUILDING - 2 OF 2

E604 ONE-LINE DIAGRAM - MAIN BUILDING 1 OF 2

E605 ONE-LINE DIAGRAM - MAIN BUILDING - 2 OF 2

E611 PANEL SCHEDULES

E612 PANEL SCHEDULES

Mark: Date: Description

ADD ALTERNATES

PROVIDE THE FOLLOWING ADD ALTERNATES AS A SEPARATE BID. CONTRACTOR SHALL

BE RESPONSIBLE TO PROVIDE ALL SCOPE PER THE BID DOCUMENTS.

ADD ALT 01 - DEMOLISH AND REPLACE EXISTING "MDP-1", SEE 1-LINES AND PLAN VIEWS

FOR MORE SPECIFICS.

ADD ALT 02 - DEMOLISH AND REPLACE EXISTING "MDP-2", SEE 1-LINES AND PLAN VIEWS

FOR MORE SPECIFICS.

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

1LA1-1

1LA1-1

OFF

TYPICAL RECEPTACLE LABEL

LOCATION

TYPICAL LABELING FOR PANELBOARDS

IN NON-PUBLIC LOCATIONS

*LABEL TO BE CENTERED IN EQUIPMENT,

PREFERABLE ON FACE OF EQUIPMENT AND

TOWARDS THE TOP.

**REFER TO TYPICAL SWITCH/RECEPTACLE

LABELING DETAIL FOR LABEL

REQUIREMENTS.

TYPICAL SWITCH LABEL

LOCATION

***DISPOSE OF AN EXISTING PANELBOARD

NAME PLATES WHEN INSTALLING NEW NAME

PLATES.

CIRCUIT NUMBER

LABEL

CIRCUIT NUMBER

LABEL

PANELBOARD LABEL, LOCATED

INSIDE OF DOOR, HIDDEN FROM

PUBLIC

1LA1

1LA2

2LA1

2LA2

SPARE

1LB1

1LB2

2LB1

2LB2

SPARE

SWITCHBOARD LABEL

SWITCHBOARD LOAD

LABEL

TYPICAL LABELING FOR

SWITCHBOARDS

ARC FLASH LABEL LOCATED HERE

ON

OFF

DISCONNECT LABEL

ARC FLASH LABEL LOCATED HERE

TYPICAL LABELING FOR DISCONNECTS

ARC FLASH LABEL LOCATED HERE

1LA1,

208/120V, #PH, #W, 22KAIC,

FED FROM-1LDP1

ELEV-1

208/120V, 1PH, 3W

FED FROM MDP

1LDP1,

208/120V, #PH, #W, 22KAIC,

FED FROM-MDP1

SHADED AREAS TO BE ORANGE ALL OTHER TO BE

WHITE BACKGROUND

(TYP) DISTANCES IN INCHES

COORDINATE VOLTAGE VALUES WITH ONE-LINE

MATCH NAME OF EQUIPMENT WITH NAMES ON ONE-LINE

PROVIDE ADDRESS WHERE SKM ANALYTICS IS PERFORMED

PROVIDE JOB NUMBER "########", DATE OF ANALYSIS

AND ENGINEER WHO PERFORMED STUDY

*PROVIDE ARC FLASH LABEL FOR ALL

ELECTRICAL EQUIPMENT PER SPECIFICATIONS

AND REQUIRED BY NEC

X0 X0 X0

3 PHASE DRY TYPE STEP-DOWN TRANSFORMER

DELTA PRIMARY:WYE SECONDARY

1 N

G

FIRST DOWNSTREM

DISCONNECTING MEANS

SBJ3

SSBJ

GC

GC - GROUNDED CONDUCTOR (NEUTRAL)

SBJ - SYSTEM BONDING JUMPER

SSBJ - SUPPLY SIDE BONDING JUMPER

UC - UNGROUDNED (PHASE) CONDUCTOR

BCJ - BONDING CONDUCTOR/JUMPER

GEC - GROUNDING ELECTRODE CONDUCTOR

BCJ

GROUND BUS

UC

GEC

BCJ

TO NEAREST AVAILABLE BUILDING

GROUNDING ELECTRODE

PRIMARY FEEDER

1.

2.

NOTES:

MOUNT XFMR AT 2' ABOVE FINISHED FLOOR FOR ACCESS TO

ACCESSIBLE FLOOR BELOW

XFMR SUPPORTS SHALL COMPLY WITH SEISMIC REQUIREMENTS.

PROVIDE MANUFACTURER

RECOMMENDED MOUNT AND

ALL REQUIRED HARDWARE

RACEWAY

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:0

PM

Designer Checker

Author 26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

TYPICAL LABELING

DETAILS

E003

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

SCALE: NTSA3 TYPICAL SWITCH, RECEPTACLE AND PANELBOARD/SWITCHBOARD LABELING LOCATION DETAIL

SCALE: NTSA1 TYPICAL ARC FLASH LABEL

SCALE: NTSC3

TYPICAL INDOOR

STEP-DOWN TRANSFORMER SEPARATELY DERIVED SYSTEM GROUNDING AND BONDING DETAIL

Mark: Date: Description

SCALE: NTSC1 TRANSFORMER WALL MOUNTING

SHEET KEYNOTES

1 BOND METAL RACEWAY.

2 NO NEUTRAL TO GROUND BOND WITHIN GEAR, REMOVE NEUTRAL TO GROUND

BOND CONNECTION IF IT EXISTS.

3 SYSTEM BONDING JUMPER BONDING TRANSFORMER X0 TERMINAL TO

TRANSFORMER ENCLOSURE / GROUND BUS.

4 EQUIPMENT GROUND BOND TO ENCLOSURE.

5 BOND TO TRANSFORMER ENCLOSURE WITH #4/0 CU.

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MIN=WIDTH+2ED

M

IN

D

EP

TH

+2

ED

TH

IC

KN

ES

S t

ELECTRICAL/MECHANICAL

EQUIPMENT ATTACHED

TO HOUSEKEEPING SLAB,

SEE SCHEDULE

OUTLINE OF

ELECTRICAL/MECHANICAL

EQUIPMENT

WIDTH

D

EP

TH

ED

ED

ED

ED

PLAN VIEWSIDE VIEW

ISOMETRIC VIEW

EQUIPMENT

ANCHOR BOLT

DETAIL A

REINFORCING BAR

EACH WAY

CENTERED IN SLAB,

SEE SCHEDULE FOR

SIZE AND QUANTITY

OUTLINE OF

REINFORCED

CONCRETE

HOUSEKEEPING SLAB,

SEE SCHEDULE AND

NOTES

EXTERIOR

ANCHOR BOLT

CONNECTION

SEE DETAILS

INTERIOR

ANCHOR BOLT

CONNECTION,

SEE DETAILS

INTERIOR REINFORCED

HOUSEKEEPING SLAB,

SEE SCHEDULE FOR SIZE

AND REINFORCING

CONCRETE SLAB,

SEE STRUCTURAL

CONCRETE ANCHOR,

SEE SCHEDULE FOR

SIZE AND QUANTITY

ELECTRICAL EQUIPMENT,

SEE SCHEDULE

REINFORCED CONCRETE

HOUSEKEEPING SLAB ATTACHED TO

STRUCTURAL SLAB (NOT SHOWN), SEE

HOUSEKEEPING SLAB SCHEDULE

5" m in

HOUSEKEEPING SLAB SCHEDULE

LENGTH

(in)

THICKNESS

(in)

BAR SIZE (#) QUANTITY SPACING

(in o.c.)

COVER

(in)

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.

2.

3.

4.

5.

6.

7.

NOTE:

EDGE DISTANCE (ED) = 6" UNLESS NOTED OTHERWISE.

FOR REINFORCING IN THE WIDTH DIRECTION REFER TO SCHEDULE ABOVE AND SUBSTITUTE WIDTH

DIMENSION FOR THE LENGTH.

ALL REINFORCING IS TO BE TIED IN PLACE AND CHAIRED TO THE CORRECT HEIGHT (CENTER OF

SLAB) PRIOR TO PLACING CONCRETE.

ICC APPROVED WEDGE ANCHOR BOLTS SHALL BE EQUALLY SPACED AND EMBEDDED 3" MIN. INTO STRUCTURAL SLAB. BOLTS SHALL PROTRUDE FROM SLAB A MIN. OF 2" AND SHALL HAVE DOUBLE

NUT WITH FLAT WASHER BETWEEN. ALL ANCHORS BOLTS SHALL BE INSIDE THE PERIMETER

REINFORCING STEEL

THIS SCHEDULE OF FOR BIDDING PURPOSES ONLY! THE ACTUAL HOUSEKEEPING SLAB DESIGN AND

REINFORCING SHALL BE SUBMITTED VIA DEFERRED SUBMITTAL BY THE CONTRACTOR UNLESS

NOTED OTHERWISE.

3000 PSI CONCRETE STRENGTH AT 28 DAYS MIN UNLESS NOTED OTHERWISE

STRUCTURAL SLAB DESIGN PER OTHERS. DO NOT CUT OR DAMAGE POST TENSION CABLES OR SLAB

REINFORCING. VERIFY WITH STRUCTURAL ENGINEER

108 6 4 7 17 1.5

COVER

SLAB

ANCHOR

DIAMETER

3/8"

3/8"

3/8"

3/8"

1/2"

ANCHOR BOLT TO

STRUCTURAL SLAB DETAIL

B, SEE SCHEDULE

1/2"

1/2"

1/2"

ANCHOR

QTY (B) & #

ROWS (R)

2B, 2R

3B, 2R

3B, 3R

4B, 3R

5B, 3R

6B, 3R

6B, 4R

7B, 4R

3/ 4" m in

3" m in2" m in

DETAIL B

SLAB ANCHOR

DETAIL A

EQUIPMENT

ANCHOR

EQUIPMENT

HOUSEKEEPING

SLAB

STRUCUTRE

SLAB

REBAR

HOUSEKEEPING

SLAB

STRUCUTRE

SLAB

REBAR

RACEWAY .5" TO 6" (TYP)

ALL THREADED ROD -

SIZE AS REQUIRED

STRUCTURAL

BEAM, JOIST,

SLAB, ETC.

UNISTRUT CHANNEL - SIZE AS

REQUIRED BY WEIGHT SUPPORTED

CONDUIT CLAMP - .5" TO 1"

UNISTRUT 2 PIECE CHANNEL

PIPE STRAPS - 1.25" TO 6"

BEAM CLAMP, HANGER

CLAMP OR APPROVED

SUPPORT, AS REQUIRED BY

WEIGHT SUPPORTED

LABEL TO BE PROVIDED AT EACH SWITCHBOARD, PANELBOARD,

DISCONNECT/STARTER. LABEL IS TO BE 3" X REQUIRED LENGTH X 1/16"

LAMINATED 2-PLY PLASTIC LAMACOID. LETTERS SHALL BE FORMED BY

ENGRAVING OUTER WHITE PLY, EXPOSING BLACK PLY BENEATH.

LABEL IS TO BE MOUNTED USING DOUBLE SIDED ADHESIVE TAPE COVERING

THE BACK OF THE LABEL.

FIRST LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED AS

SHOWN. REPLACE THE LETTER/NUMBER WITH THOSE FOUND ON THE ONE-

LINE DIAGRAM.

SECOND LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED

AS SHOWN. THE FOLLOWING SHALL BE PROVIDED, VOLTAGE, PHASE,

NUMBER OF WIRES, AND AIC RATING OF DEVICE.

1 2

4 208/120V, #PH, #W, 22KAIC,

1LA1,

NOTE: EMERGENCY PANELS SHALL USE LAMACOID WITH RED OUTERPLY,

EXPOSING WHITE LETTERING BENEATH. CONTRACTOR TO USE SAME LABEL

SCHEME EXCEPT FIRST 'X' IS REPLACED WITH 'E' FOR EMERGENCY. SECOND 'X'

TO BE 'L' FOR LOW OR 'H' FOR HIGH VOLTAGE (480/277V). LAST '#' TO BE

REPLACED WITH LETTER INDICATING LOCATION OF PANEL.

FED FROM-MDP15

THIRD LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED AS

SHOWN. PROVIDE "FED FROM-" AND REPLACE MDP1 WITH THE DEVICES

NAME THAT FEEDS THE PANELBOARD.

LABEL TO BE PROVIDED THAT IS TO BE 4" X REQUIRED LENGTH X 1/16"

LAMINATED 2-PLY PLASTIC LAMACOID. LETTERS SHALL BE FORMED BY

ENGRAVING OUTER WHITE PLY, EXPOSING BLACK PLY BENEATH.

LABEL IS TO BE MOUNTED USING DOUBLE SIDED ADHESIVE TAPE COVERING

THE BACK OF THE LABEL.

FIRST LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, WITH THE EQUIPMENT

ID MATCHING PLANS.

SECOND LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED

AS SHOWN. THE FOLLOWING SHALL BE PROVIDED, VOLTAGE, PHASE,

NUMBER OF WIRES, AND AIC RATING OF GEAR.

1 2

4 480Y/277V, 3PH, 4W, 22KAIC,

MDP1,

THIRD & FOURTH LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND

FORMATTED AS SHOWN. LABEL WITH ACTUAL AVAILABLE FAULT CURRENT

AND ASSOCIATED CLEARING TIME.

AVAILABLE FAULT CURRENT -

XX,XXX A

MCB CLEARING TIME -

X.XX SECONDS

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:0

PM

Designer Checker

Author 26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

TYPICAL LABELING

DETAILS

E004

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

Mark: Date: Description

SCALE: NTSA3 TYPICAL CONCRETE HOUSEKEEPING PAD

SCALE: NTSC1 TYPICAL CONDUIT RACK DETAIL

SCALE: NTSA1 TYPICAL PANELBOARD/SWITCHBOARD/DISCONNECT/TRANSFORMER LABEL

SCALE: NTSB1 TYPICAL MAIN SERVICE EQUIPMENT/GEAR LABEL

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MB-20MB-19MB-18MB-17MB-16MB-15MB-14MB-13MB-12MB-11MB-10MB-9MB-8MB-7MB-6MB-5MB-4MB-3MB-2MB-1

MB-P

MB-N

MB-M

MB-L

MB-K

MB-J

MB-I

MB-H

MB-G

MB-F

MB-E

MB-D

MB-C

MB-B

MB-A

MB-AA

MB-AB

MB-AC

MB-AD

MB-AE

MB-AF

ELECTRICAL

ROOM

2006-G

E301 A1

E301 A2

E301 A4

E301 C1

E301 C2

E301 C4

E303 A1

E303 A2

E303 A4

E303 C2

E303 C4

E303 C1

(EX)

"TCN"

(EX)

"MDP2000"

(EX)

"LDP-D"

E301 D1

Room 1001F

(EX)

"T-MDP-2"

(EX)

"1A"

(EX)

"1HA"

"LCP"

"XFMR-TEQ6"

"XFMR-T1006"

"HB"

"LC"

"MDP-2"

"MDP-1"

"C"

"F" "D"

Room 1018A

Room

Room 1205A

Room

Room

(EX)

"MDP-3"

E301 D2

Room

VAULT

"LCP2"

SHEET KEYNOTES

1 CONTRACTOR TO PROVIDE NEW FUSE BUCKET IN EXISTING GEAR "EQDP" TO

FEED LOAD.

(EX)

"1QLA GEN"

(EX)

"1QLA UPS"

(EX)

"EQDP"

(EX)

"TRUEVARS" POWER

FACTOR FILTER"

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:0

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

OVERALL LEVEL 1

ELECTRICAL PLAN

E101

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

SCALE: 1" = 30'-0"A2 OVERALL LEVEL 1 ELECTRICAL PLAN NORTH

Mark: Date: Description

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MB-7

MB-F

(EX)

"MDP-1"

(EX)

"MDP-2"

(EX)

"T-MDP-2"

(EX)

"1HA"

(EX)

"1A"

Room 1205A

MB-14

MB-A

(EX)

"C"

Room

MB-14

MB-AB

(EX)

"D" (EX)

"F"

(EX)

"D SEC 2"

Room

MB-12

(EX)

"LCP"

(EX)

"LCP2"

4 4

Room 1018A

4 4

MB-11

(EX)

"LB"

Room 1001F

MB-12

MB-J

(EX)

"XFMR TB"

(EX)

"HB"

(EX)

"XFMR TCP (HB)"

(EX)

"LC"

Room

12 1214

(EX)

"TRUEVARS" POWER

FACTOR FILTER"

MB-12

MB-H

Room

5 (EX)

"XFMR-TEQ6 (CEILING)"

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:1

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

ENLARGED

DEMOLITION ROOM

PLANS

E301

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

SCALE: 1/4" = 1'-0"A1 ENLARGED DEMO PLAN - ROOM 1205A

SCALE: 1/4" = 1'-0"A2 ENLARGED DEMO PLAN - ROOM 1408

SCALE: 1/4" = 1'-0"A4 ENLARGED DEMO PLAN - ROOM 1405

SCALE: 1/4" = 1'-0"C1 ENLARGED DEMO PLAN - ROOM 1018-A

SCALE: 1/4" = 1'-0"C2 ENLARGED DEMO PLAN - ROOM 1001-F

SCALE: 1/4" = 1'-0"C4 ENLARGED DEMO PLAN - ROOM 1006 (BOILER ROOM)

GENERAL SHEET NOTES

SHEET KEYNOTES

1 REFER TO EP601 FOR FEEDER SCHEDULE.

2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE

REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL

WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.

3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC

CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR

REQUIREMENTS.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL

SCOPE OF WORK AS REQUIRED.

5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.

6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL

SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW

PANELBOARD LOCATION,

7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,

WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.

8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD

9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL

SCHEDULE TO REFLIECT ACTUAL LOAD DATA

Mark: Date: Description

1 PROTECT AND MAINTAIN ELECTRICAL EQUIPMENT

2 CONTRACTOR TO DEMOLISH EXISTING SURGE PROTECTION.

3 CONTRACTOR TO RELOCATE AS REQUIRED FOR NEW PANELBOARDS AND PATCH

AND REPAIR WALL TO MATCH EXISTING CONDITIONS.

4 CONTRACTOR TO DEMOLISH PANELBOARD COVER AND PANELBOARD INTERIOR.

PROTECT AND MAINTAIN EXISTING PANELBOARD CAN TO UTILIZE AS

PULLBOX/JUNCTION AND ALL CIRCUITS UNLESS NOTED OTHERWISE. TRACE

EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF POWER ON

RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO TRACE UNKNOWN

CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS WILL NEED TO BE

TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT LABELED DURING

THE CIRCUIT TRACING. DEMOLISH ALL ABANDONED CABLING AND CIRCUITS.

5 CONTRACTOR TO DEMOLISH EXISTING TRANSFORMER ABOVE CEILING AND

PROVIDE A NEW TRANSFORMER TO NEW LOCATION.

6 DEMOLISH EXISTING THERMOMETER. PROVIDE BLANK FACE PLATE TO COVER UP

JUNCTION BOX.

7 CONTRACTOR TO PROVIDE TEMPORARY COOLING THROUGHOUT PANEL

REPLACEMENT. FEED THE RTU FROM PANEL "1QLA GEN" AND SPLIT UNITS FROM

PANEL "1 QLA UPS". SO CORDS ALLOWED TO RUN ACROSS CEILING WHILE PANEL IS

DOWN.

8 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 01.

9 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 02.

10 REUSE EXISTING FEEDER, FIELD VERIFY WHERE FEEDER COMES INTO THE PANEL

BOARD AND PROCURE PANELBOARD WITH ABILITY TO LAND EXISTING CABLING ON

BOARD WITHOUT SPLICING CABLES.

11 OWNER TO MOVE DEVICE TO DIFFERENT LOCATION TO ALLOW FOR SURFACE

MOUNTED PANELBOARD.

12 DEMOLISH EXISTING TRANSFORMER AND ASSOCIATED GROUNDING.

13 DEMOLISH PANELBOARD INTERIOR. PROTECT AND MAINTAIN EXISTING

PANELBOARD CAN TO UTILIZE AS PULLBOX/JUNCTION AND ALL CIRCUITS UNLESS

NOTED OTHERWISE . LEAVE EXISTING COVER FOR ACCESS TO CABLING AND

REMOVE EXISTING PANELBOARD LABEL.

14 DEMOLISH EXISTING PANEL BOARD, PROTECT AND MAINTAIN EXISTING BRANCH

CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL BOARD.

TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF POWER

ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO TRACE

UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS WILL

NEED TO BE TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT

LABELED DURING THE CIRCUIT TRACING. DEMOLISH ALL CABLING AND ANY

CIRCUITS THAT HAVE BEEN ABANDONED.

15 DEMOLISH EXISTING PANEL BOARD, PROTECT AND MAINTAIN EXISTING BRANCH

CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL BOARD.

SCALE: NTSD1 IMAGE OF PANEL LCP AND LCP2

SCALE: 1/4" = 1'-0"D2 ENLARGED DEMO PLAN - ROOM 1018

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:1

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

ENLARGED

DEMOLITION

INTERIOR

PANELBOARDS

E302

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

GENERAL SHEET NOTES

1 REFER TO EP601 FOR FEEDER SCHEDULE.

2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE

REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL

WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.

3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC

CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR

REQUIREMENTS.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL

SCOPE OF WORK AS REQUIRED.

5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.

6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL

SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW

PANELBOARD LOCATION,

7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,

WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.

8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD

9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL

SCHEDULE TO REFLIECT ACTUAL LOAD DATA

Mark: Date: Description

SCALE: NTS

IMAGE OF PANEL LCP INTERIORA1 SCALE: NTS

IMAGE OF PANEL LCP2 INTERIORA2 SCALE: NTSA4 IMAGE OF PANEL LB INTERIOR

SCALE: NTSA5 IMAGE OF PANEL LC INTERIOR

SCALE: NTSC1 IMAGE OF PANEL HB INTERIOR

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

MB-7

MB-F

(EX)

"1A"

(EX)

"1HA"

(EX)

"T-MDP-2"

"MDP-2"

"MDP-1"

Room 1205A

MB-14

MB-A

"C"

Room

MB-14

MB-AB

"F""D SEC 2" "D"

Room

MB-11

Room 1001F 46

MB-12

MB-J

"XFMR-T1006"

"HB""LC"

Room

A3 E004

DS-LCP

(EX)

"TRUEVARS" POWER

FACTOR FILTER"

MB-12

"XFMR-TEQ6"

Room 1018A

"LCP"

C1 E003

"LCP2"

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:1

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

ENLARGED ROOM

PLANS

E303

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

SCALE: 1/4" = 1'-0"A1 ENLARGED PLAN - ROOM 1205A

SCALE: 1/4" = 1'-0"A2 ENLARGED PLAN - ROOM 1408

SCALE: 1/4" = 1'-0"A4 ENLARGED PLAN - ROOM 1405

SCALE: 1/4" = 1'-0"C2 ENLARGED PLAN - ROOM 1001-F

SCALE: 1/4" = 1'-0"C4 ENLARGED PLAN - ROOM 1006 (BOILER RM)

SCALE: 1/4" = 1'-0"C1 ENLARGED PLAN - ROOM 1018-A

GENERAL SHEET NOTES

SHEET KEYNOTES

1 REFER TO EP601 FOR FEEDER SCHEDULE.

2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE

REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL

WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.

3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC

CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR

REQUIREMENTS.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL

SCOPE OF WORK AS REQUIRED.

5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.

6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL

SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW

PANELBOARD LOCATION,

7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,

WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.

8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD

9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL

SCHEDULE TO REFLIECT ACTUAL LOAD DATA

Mark: Date: Description

1 INTERCEPT ALL EXISTING CIRCUITS FROM PANELBOARD LB AND EXTEND TO NEW

PANELBOARD LC. UTILIZE EXISTING PANELBOARD CAN AS PULLBOX/JUNCTION AND

LAND CIRCUITS ON NEW PANELBOARD. UTILIZE EXISTING COVER AS ACCESS TO

PULLBOX AND PROVIDE SHAWMUT TERMINATIONS OR EQUALS FOR SPLICING

CABLING.

2 CONTRACTOR TO INSTALL NEW TRANSFORMER AND REFEED ALL EXISTING

EQUIPMENT FROM TRANSFORMER "TB" AND "TCP (HB)" TO NEW TRANSFORMER.

PROVIDE NEW CONCRETE PAD FOR NEW GEAR.

3 ROUTE RACEWAY SURFACE MOUNTED IN THIS ROOM TO THE CEILING TO POWER

SOURCE AND BETWEEN TRANSFORMER AND PANELBOARD. ALL RACEWAYS

OUTSIDE OF THIS ROOM SHALL BE CONCEALED IN CEILINGS/WALLS.

4 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL

SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW

PANELBOARD LOCATION,

5 NO PIGTAIL SPLICING ALLOWED, EXTEND ALL CABLING TO NEW PANELBOARD

LOCATION.

6 CONTRACTOR TO PAINT SPACE AS REQUIRED FOR SPACE TO HAVE A CONTINUOUS

LOOK/FINISH.

7 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 01.

8 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 02.

9 CONTRACTOR TO INSTALL NEW PANELBOARD, PROTECT AND MAINTAIN EXISTING

BRANCH CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL

BOARD. TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF

POWER ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO

TRACE UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS

WILL NEED TO BE TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT

LABELED DURING THE CIRCUIT TRACING. DEMOLISH ALL CABLING AND ANY

CIRCUITS THAT HAVE BEEN ABANDONED.

10 CONTRACTOR TO INSTALL NEW TRANSFORMER IN NEW LOCATION. INTERCEPT AND

EXTEND ALL RACEWAY AND CABLING AS REQUIRED. REFEED EXISTING EQUIPMENT

FROM DEMOLISHED CEILING TRANSFORMER TO NEW GROUND TRANSFORMER.

PROVIDE WALL MOUNT RACK FOR TRANSFORMER AND LOCATE 2FT ABOVE

FINISHED FLOOR FOR ACCESSS TO ACCESSIBLE FLOOR BELOW.

11 WHERE REQUIRED FOR NEW EQUIPMENT PROVIDED BY CONTRACTOR

ADJUST/MOVE EXISTING RACEWAYS, DEVICES, ETC. THAT ARE IN CONFLICT WITH

THE NEW EQUIPMENT.

12 CONTRACTOR TO INSTALL NEW PANELBAORD INTERIOR AND COVER. UTILIZE

EXISTING PANELBOARD CAN AS PULLBOX/JUNCTION AND LAND CIRCUITS ON NEW

PANELBOARD.TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR

SOURCE OF POWER ON RECEPTACLES POWERED FROM PANELBOARD.

CONTRACTOR TO TRACE UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE.

ASSUME 15 CIRCUITS WILL NEED TO BE TRACED. ADD LABELS TO ALL

RECEPTACLES THAT WERE NOT LABELED DURING THE CIRCUIT TRACING.

DEMOLISH ALL CABLING AND ANY CIRCUITS THAT HAVE BEEN ABANDONED.

13 CONTRACTOR TO INSTALL NEW PANELBOARD, PROTECT AND MAINTAIN EXISTING

BRANCH CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL

BOARD. TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF

POWER ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO

TRACE UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS

WILL NEED TO BE TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT

LABELED DURING THE CIRCUIT TRACING. DEMOLISH ALL CABLING AND ANY

CIRCUITS THAT HAVE BEEN ABANDONED.

14 PROVIDE NEW BRANCH CIRCUIT TO FILTER.

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:1

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

ELECTRICAL

SCHEDULES

E601

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

Mark: Date: Description

SYM AMP

HH

AMPS

CONDUIT

SIZE

CONDUCTOR (NOTE 1)

IG/HH SE NOTESQTY SIZE G

1 20 - .75 2 12 12 12 8 2 2 20 - .75 3 12 12 12 8 2,3 3 20 24 .75 4 12 12 12 8 2,3 4 30 - .75 2 10 10 10 8 2 5 30 - .75 3 10 10 10 8 2 6 30 32 .75 4 10 10 10 8 2 7 40 - 1 2 8 10 8 6 2 8 40 - 1 3 8 10 8 6 2 9 40 44 1 4 8 10 8 6 2 10 55 - 1 2 6 10 8 4 2 11 55 - 1 3 6 10 8 4 2 12 55 60 1.25 4 6 10 8 4 2 13 70 - 1 2 4 8 4 2 2 14 70 - 1.25 3 4 8 4 2 2 15 70 76 1.25 4 4 8 4 2 2 16 85 - 1.25 2 3 8 3 2 2 17 85 - 1.25 3 3 8 3 2 2 18 85 92 1.25 4 3 8 3 2 2 19 95 - 1.25 3 2 8 2 2 2 20 95 104 1.50 4 2 8 2 2 2 21 130 - 1.50 3 1 6 2 2 2 22 130 116 1.50 4 1 6 2 2 2 23 150 - 2 3 1/0 6 2 1/0 2 24 150 136 2 4 1/0 6 2 1/0 2 25 175 - 2 3 2/0 6 2 2/0 2 26 175 156 2 4 2/0 6 2 2/0 2 27 200 - 2 3 3/0 6 2 2/0 2 28 200 180 2.50 4 3/0 6 2 2/0 2 29 230 - 2.50 3 4/0 4 2 2/0 2 30 230 208 2.50 4 4/0 4 2 2/0 2 31 255 - 2.50 3 250 4 1 2/0 2 32 255 232 2.50 4 250 4 1 2/0 2 33 310 - 3 3 350 3 1/0 3/0 2 34 310 280 3 4 350 3 1/0 3/0 2 35 380 - 3.50 3 500 3 3/0 3/0 2 36 380 344 4 4 500 3 3/0 3/0 2

37 400 - 2 EA 2 3 3/0 3 3/0 3/0 2

38 400 360 2 EA 2.50 4 3/0 3 3/0 3/0 2

39 510 - 2 EA 2.50 3 250 1 4/0 3/0 2

40 510 464 2 EA 3 4 250 1 4/0 3/0 2

41 620 - 2 EA 3 3 350 1/0 4/0 3/0 2,4

42 620 560 2 EA 3 4 350 1/0 4/0 3/0 2,4

43 760 - 2 EA 3.50 3 500 1/0 4/0 3/0 2,4

44 760 688 2 EA 4 4 500 1/0 4/0 3/0 2,4

45 855 - 3 EA 3 3 300 2/0 4/0 3/0 2,4

46 855 768 3 EA 3 4 300 2/0 4/0 3/0 2,4

47 1000 - 3 EA 3.50 3 400 2/0 4/0 3/0 4

48 1000 912 3 EA 3.50 4 400 2/0 4/0 3/0 4

49 1140 - 3 EA 4 3 500 3/0 4/0 3/0 4

50 1140 1032 3 EA 4 4 500 3/0 4/0 3/0 4

51 1240 - 4 EA 3 3 350 3/0 4/0 3/0 4

52 1240 1120 4 EA 3 4 350 3/0 4/0 3/0 4

53 1675 1520 5 EA 4 4 400 4/0 4/0 4/0 4

54 2010 1824 6 EA 4 4 400 250 250 250 4

55 2660 2408 7 EA 4 4 500 350 350 350 4

56 3040 2752 8 EA 4 4 500 500 500 500 4

57 4180 3784 11 EA 4 4 500 500 500 500 4

58 1200 - 5 EA 4 - - - - - 6

59 3000 - 10 EA 6 - - - - - 6

60 - - 10 EA 4 - - - - - 6

IG

(E.G.)

COPPER CONDUCTOR AND

CONDUIT SCHEDULE

SUBSCRIPT (NOTE 5)

SCHEDULE NUMBER

"2N": INCLUDE TWO NEUTRAL CONDUCTORS SIZED AS SCHEDULED FOR

PHASE AND NEUTRAL CONDUCTORS WHERE THE CONDUCTOR IS #1/0

OR LARGER. INCLUDE A SINGLE 200% RATED CONDUCTOR THAT IS

TWICE THE AMPACITY OF THE SCHEDULED PHASE AND NEUTRAL

CONDUCTOR WHERE THE CONDUCTOR IS BELOW #1/0 IN SIZE.

"CI": PROVIDE CIRCUIT INTEGRITY CABLE; TYPE TWO-HOUR FIRE

RESISTIVE CABLES IN CONDUIT OR PROVIDE FEEDER ENCASED IN

CONCRETE.

"FG" FULL SIZE GROUND, SIZE EQUIPMENT GROUNDING CONDUCTOR TO

BE SAME SIZE AS THE PHASE CONDUCTORS.

"HH": NEUTRAL CURRENTS EXIST DUE TO HIGH HARMONIC "NONLINEAR"

LOADS. CURRENT CARRYING CONDUCTORS DERATED

ACCORDINGLY. PROVIDE THE IG/HH SIZE FOR THE EQUIPMENT

GROUNDING CONDUCTOR.

"IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)

SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND

CONDUCTOR.

"MC": PROVIDE FEEDER IN METAL-CLAD CABLE; TYPE MC IN PLACE OF

SINGLE CONDUCTORS IN CONDUIT.

"SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN, WHICH

IS SIZED FOR THE GROUNDING OF THE SECONDARY OF THE

SEPARATELY DERIVED SYSTEM.

"SER": PROVIDE SERVICE-ENTRANCE CABLE; TYPE SE OR SER IN PLACE OF

SINGLE CONDUCTORS IN CONDUIT.

CONDUCTOR AND CONDUIT SCHEDULE NOTES

CIRCUIT

AMPACITY/VOLTAGE

CIRCUIT

LENGTH

CONDUCTOR SIZE

(PHASE, NEUTRAL AND GR) CONDUIT SIZE

20A/120V 0' - 60' #12 AWG 0.75" Ø

20A/120V 60' - 95' #10 AWG 0.75" Ø

20A/120V 95' - 150' #8 AWG 1" Ø

20A/120V 150' - 240' #6 AWG 1.25" Ø

20A/277V 0' - 140' #12 AWG 0.75" Ø

20A/277V 140' - 220' #10 AWG 0.75" Ø

20A/277V 220' - 350' #8 AWG 1" Ø

20A/277V 350' - 550' #6 AWG 1.25" Ø

1.

2.

3.

NOTES:

WIRE SIZING IS BASED ON COPPER CONDUCTORS SUPPLYING A 20A,

120V CIRCUIT AT THE INDICATED VOLTAGE, ASSUMED TO BE 80%

LOADED (16A), WITH MAXIMUM VOLTAGE DROP OF 3% AT THE LOAD.

DOWN-SIZED WIRE AT DEVICE/LOAD AS REQUIRED AND TERMINATE

CONDUCTORS IN A SAFE AND CODE COMPLIANT MANNER.

CONDUIT SIZE IS BASED ON A MAXIMUM OF 3 CIRCUITS PER CONDUIT,

EACH WITH A SEPARATE NEUTRAL CONDUCTOR.

BRANCH CIRCUIT CONDUCTOR

AND CONDUIT SIZING TABLE

1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH MODIFICATIONS

AS NOTED IN NOTE 5. ALL CONDUCTORS SHOWN ARE THWN UNLESS

OTHERWISE NOTED.

2. PROVIDE EQUIPMENT GROUND CONDUCTORS PER TABLE 250-122 WHEN

CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING SHOWN IN

TABLE.

3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING

COMPUTERS.

4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE

CONDUCTORS.

5. SYMBOL SUBSCRIPTS:

6. RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.

8/7/2026

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

SPD GFI

1600/ 3

SECT

400/3 "1K" "1K"

400/3

800/ 3

100/3

EX

100/3

"1HA"

100/3

EX

100/3

"1HB"

100/3

EX

100/3

"2HA"

150/3

EX

150/3

"MP1"

200/3

EX

200/3

"MP2"

800/ 3

100/3

EX

100/3

"1A"

150/3

EX

150/3

"1B"

200/3

EX

200/3

"1C"

100/3

"1D"

100/3

EX

100/3

"1E"

100/3

EX

100/3

"1H"

100/3

EX

100/3

"1I"

100/3

EX

100/3

"2A"

GROUND

PER NEC

XFMR "TLGN"

150kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

#4/0 CU

100/3

100/3

"LF"

225/3

"LG"

SPD

600/ 3

100/3

"L"

100/3

"EM"

GROUND

PER NEC

XFMR "T1"

225kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

#4/0 CU

600/ 3

400/3

400/3

"WSC"

400/3

400/3

"WSA"

400/3

400/3

"WSD"

250/3

250/3

"HD"

600/3

600/3

"3HA"

250/3

250/3

"HKP"

400/3

400/3

"WSB"

225/3

225/3

"E"

600/3

600/3

"1CSL"

80/3

"2D"

SECT

200/3 "K2" "K2"

200/3

100/3

EX

100/3

"1-P"

200/3

EX

200/3

"2B.1"

ARCH/ENG

CLASS

100/3

EX

100/3

"2B.2"

COSMO

100/3

EX

100/3

"2F"

225/3

GROUND

PER NEC

XFMR "TCN"

300kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

#4/0 CU

GROUND

PER NEC

(EX) "XFMR"

75kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

#4/0 CU

100/3

"LA-2"

50/3

"LD"

50/3

"LW"

125/3

175/3

GROUND

PER NEC

"XFMR-TCP (HB)"

112.5kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

#4/0 CU

GROUND

PER NEC

"XFMR-TB"

75kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

225/3

225/3

"G"

225/3

225/3

"I"

225/3

225/3

"A"

SECT

225/3 "B" "B"

225/3

SECT

400/3 "D" "D"

400/3

SECT

400/3 "C" "C"

400/3

225/3

"LB"

400/3

"LC"

225/3

"HB"

250/3

"LCP"

SPD

GROUND

PER NEC

(EX) "XFMR"

75kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

#4/0 CU

100/3

"SP"

GROUND

PER NEC

"XFMR-T1"

75kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

100/3

"P"

GROUND

PER NEC

"XFMR-T2"

75kVA 480-208Y/120V 3Ø, 4W

DELTA/ WYE

200/3

400/3

"2"

22/3

400/3

"N"

125/3

400/3

"WSC"

400/3

400/3

"L"

50/3

EX

50/3

"1G"

80/3

EX

80/3

"2E"

COSMO

12470-480Y/277V 3Ø, 4W

FROM KCP

SECTIONALIZER

"MDP2000"

EXISTING MAIN SWITCH BOARD

2000A 480/277 3⌀, 4W, 65,000AIC

SE

400/3

FRS-R-225

IG

400/3

LPJ-400

IG

EXISTING "MDP-1"

800A 480/277 3⌀, 4W, 30,000 AIC

350/3SPACE SPACE

(EX) "T-MDP-2"

225 KVA

480-208/120V 3⌀, 4W

EXISTING "MDP-2"

800A 208/120 3⌀, 4W, 30,000 AIC

EX

EX

MAU-1MAU-1

800/3

400/3 250/3

300/3

NEXT TO RM 1053

400/3

SPARE

200KVAR, 8 STEP

AUTO POWER

FACTOR

CORRECTION

CAPACITOR

CABINET

PROVIDE

CAPACITOR

SYSTEMS TO

ACHEIVE 95%

POWER FACTOR

400/3

SPARE

100/3

SPARE

"XFMR - APP"

12470-480Y/277V 3Ø, 4W

FROM KCP

SCETIONALIZER

EX

EX

20/1 X13

SPARE

60/3

TO

RTU

60/3

TO

RTU

50/3

TO

UNKNOWN

EXISTING

LOAD

100/3

100/3 15/3

TO TOOL

GRINDER

20/3

TO

EDM

20/3

TO

LATHE

"HDP-A"

EXISTING DISTRIBUTION SWITCH BOARD

600A 480/277 3⌀, 4W, 65,000AIC

350/3

20/3 X6

SPARE

20/3

TO BROWN

& SHARPE

GRINDER

225/3

SPARE

400/3

SPARE

150/3

SPARE

150/3

SPARE

80/3

TO

MAZAK

VTC 16

50/3

TO AIR

COMP

20/3

TO

BAND

SAW

20/1 X3

SPARE

400/3

SPARE

20/3

TO

GROB

BAND

SAW

100/3

TO

SHIZOKA

20/1

TO

POWERMATIC

GRINDER

20/2

TO DO

ALL

GRINDER

50/1

SPARE

GROUND BUS

NEUTRAL BUS

TO EXISTING

GROUNDING

SYSTEM

GROUND BUS

NEUTRAL BUS

TO EXISTING

GROUNDING

SYSTEM

SEC 01 SEC 03

EXISTING PANEL "LDP-D"

208/120V, 3PH, 4W

600A MCB, 10,000AIC

IG

200/3

LPJ-400

IG

EX

400/3 700/3

400/3

350/3 125/3

SPARE

800/3

100/3 50/3

50/3 350/3

SE

SE

800/3

400/3 400/3

SE

225/3

225/3225/3 225/3

400/3

400/3

125/3 400/3

800/3

ELEV1ELEV1

150A

SEC 02

600/3400/3

SPARE

250/3 X4

SPARE

250/3 X4

SPARE

60/3TVSS

50/3200/3150/3100/3100/3100/3 225/3 350/3

200/3100/3 100/3 100/3 100/3 100/3 100/3 100/3 100/3 80/3 100/380/3200/3150/3

EXISTING PANEL "F"

208/120V, 3PH, 4W

800A MCB, 20,000AIC

"H" 277/480V

3PH, 4W, 400A

"LDP" 277/480V

3PH, 4W, 800A

"HA" 277/480V

3PH, 4W, 400A

"LA-1 SEC.1"

120/208V

3PH, 4W, 800A

8 8 8 8 8

8 8 8 8 8 8

8 8 8 8 8 8 8 8 8 8 8 8 8

JUNCTION BOX

OUTSIDE OF SHOP

EX 8

8EX

200/3

SLOT

200/3

SLOT

M 12

324 S. State St., Suite 400 Salt Lake City, UT 84111

800-678-7077 801-328-5151 www.lynkengineers.com

Kobayashi

5497590-2202 Christopher Kelly

L

IC

EN

S E

D

PROF E S S I ONA L

ENG

I NEER

S T A T E O F U T A H

No.

IND

USTRY

TH

E

G R E A T

SE

AL

OF THE

STATE

O F

U

TA

H

C

A

B

2 3

D

E

1 2 3

C

4 5

2026 LYNK ENGINEERS, LLC.

SHEET TITLE

PROJECT NO:

DRAWN BY:

CHECKED BY:

SIGNATURE:

RECORD DRAWING DATE:

DESIGNED BY:

A

ISSUE:

DATE:

B

4 5

D

E

DFCM APPROVAL STAMP

4110 STATE OFFICE BLDG

SALT LAKE CITY, UT 84112

DFCM

7/31/2026

DFCM PROJECT NO:

Au to de sk

D oc s:

//2

6-

- D av is T ec h

- P an el

T ra ns fo rm er

R ep la ce m en t/2 6-

- E le cC en tra l.r vt

8/

/2

6:

:1

PM

KAK

LSK

KAK

26-00536

AUG 7, 2026

CONSTRUCTION

DOCUMENTS

DEMOLITION

ONE-LINE DIAGRAM -

MAIN BUILDING - 1 OF

E602

DAVIS

TECHNICAL

COLLEGE

ELECTRICAL

TRANSFORMER

AND PANEL

REPLACEMENT

- PHASE 1

550 E 300 S, Kaysville, UT 84037

27048220

GENERAL SHEET NOTES

1 REFER TO EP601 FOR FEEDER SCHEDULE.

2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE

REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL

WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.

3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC

CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR

REQUIREMENTS.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL

SCOPE OF WORK AS REQUIRED.

5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.

6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL

SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW

PANELBOARD LOCATION,

7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,

WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.

8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD

9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL

SCHEDULE TO REFLIECT ACTUAL LOAD DATA

SHEET KEYNOTES

1 DEMOLISH EXISTING PANEL BOARD, PROTECT AND MAINTAIN EXISTING BRANCH

CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL BOARD.

TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF POWER

ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO TRACE

UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS WILL

NEED TO BE TRACED. ADD LABELS TO ALL…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .