5-2-CS27019-27048220-Approved Plans.pdf
PDF 10 MB Posted
- Solicitation number
- CS27019
- Issued by
- Utah
About this file
Summary
This document comprises the approved construction plans and specifications for the Davis Technical College Electrical Transformer and Panel Replacement - Phase 1 project located at 550 E 300 S, Kaysville, Utah. The project, managed by the State of Utah's Division of Facilities Construction and Management (DFCM), involves the replacement and relocation of selected transformers and electrical panels throughout the main building. The construction scope includes demolition of existing electrical equipment, installation of new transformers (75 kVA to 300 kVA), and replacement of multiple electrical distribution panels located in various rooms (1018A, 1205A, 1408, 1405, 1006, and 1001F). The approved plans consist of detailed construction documents including electrical schedules, one-line diagrams, demolition and installation plans, typical labeling details, and panel schedules with load calculations. The plans were designed by LYNK Engineers, LLC (Project No. 26-00536) and reviewed for code compliance by the Division of Facilities Construction and Management on September 16, 2026. Two add alternates are included: ADD ALT 01 for demolishing and replacing existing "MDP-1" and ADD ALT 02 for demolishing and replacing existing "MDP-2."
The construction cost estimate for this Stage II invitation to bid is $300,000.00, with only prequalified contractors eligible to submit bids. The scope encompasses comprehensive work including existing circuit tracing and labeling, protection and reuse of existing branch circuits where possible, Shawmut terminations for splices, temporary cooling provisions during panel replacement, seismic bracing of all equipment, concrete housekeeping pads for equipment placement, and restoration of all finishes including flooring, carpet, walls, and ceilings. All work must comply with the National Electrical Code (NEC), International Building Code (IBC), NFPA standards, and International Fire Code (IFC), subject to on-site field inspection approval by the Authority Having Jurisdiction. Contractors are required to submit detailed submittals in electronic PDF format with indexed equipment sections, coordinate with architectural reflected ceiling plans, and assume approximately 15 circuits will require tracing with unknown loads to be documented and panel schedules updated accordingly.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE STATE
O F
U
TA
H
State of Utah-Department of Administrative Services
DIVISION OF FACILITIES CONSTRUCTION
AND MANAGEMENT
4110 State Office Building/Salt Lake City, Utah 84114/538-3018
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
DFCM PROJECT #:DFCM PROJECT #:
LYNK PROJECT #: LYNK PROJECT #:
CONSTRUCTION DOCUMENTS: CONSTRUCTION DOCUMENTS:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:0
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
ELECTRICAL COVER
SHEET
E001
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
DAVIS TECHNICAL COLLEGE
ELECTRICAL TRANSFORMER AND
PANEL REPLACEMENT - PHASE 1
26-00536
550 E 300 S, Kaysville, UT 84037
AUG 7, 2026
27048220
27048220
Mark: Date: Description
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
09/16/2026
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:0
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
ELECTRICAL
SYMBOLS & NOTES
E002
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
GENERAL ELECTRICAL NOTES
1. CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL FAMILIARIZE
THEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS,
MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED PRODUCTS,
CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN THE EQUIPMENT
SUPPLIED AND THE INTENT OR FUNCTION OF THE EQUIPMENT, ETC, SHALL BE
SUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING FOR CLARIFICATION PRIOR
TO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING OF THE PROJECT. WHERE
DISCREPANCIES OR MULTIPLE INTERPRETATIONS OCCUR, THE MOST STRINGENT
(WHICH IS GENERALLY RECOGNIZED AS THE MOST COSTLY) THAT MEETS THE
INTENT OF THE DOCUMENTS SHALL BE ENFORCED.
2. OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL AND
EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE INCORPORATED
INTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE INSTALLER AND COSTS
FOR RECEIVING, HANDLING, STORAGE, IF REQUIRED, AND INSTALLATION ARE
INCLUDED IN THE CONTRACT SUM.
A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLER
FURNISHED THE MATERIALS OR EQUIPMENT.
B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNER
FURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER WILL
INSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS ARE
DAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS WITH
THE TRANSPORT COMPANY AND THE OWNER WILL ARRANGE
FOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FOR
MANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OF
MANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.
C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATES
OF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING AND
HANDLING OWNER FURNISHED ITEMS AT THE SITE.THE INSTALLER IS
RESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROM
DAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, AND
TO REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF HIS
OPERATIONS.
DEFINITIONS
NOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS,
NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR
SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE
CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED",
"SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE
THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED",
"SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY
THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE
ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND
REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS
STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO
THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY,
INSTALLATION, AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT
SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION,
PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING,
CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE
AND READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY
THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-
SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION
ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR
OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE
OPERATIONS THEY ARE ENGAGED TO PERFORM.
TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO
DESCRIBE ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS
"SPECIAL SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY
LIMITED TO ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS
SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY
SYSTEMS, VOICE AND DATA CABLING SYSTEMS, ETC...
ABBREVIATIONS
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
1P SINGLE POLE
1PH SINGLE-PHASE
1WAY ONE-WAY
2/C TWO-CONDUCTOR
2WAY TWO-WAY
3/C THREE-CONDUCTOR
3WAY THREE-WAY
4OUT QUADRUPLE RECEPTACLE
OUTLET
4PDT FOUR-POLE DOUBLE THROW
4PST FOUR-POLE SINGLE THROW
4W FOUR-WIRE
4WAY FOUR-WAY
A ABOVE COUNTER
AC ARMORED CABLE
ADA AMERICANS WITH DISABILITIES
ACT
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING
CAPACITY
ALUM ALUMINUM
AMP AMPERE
ANN ANNUNCIATOR
AP ACCESS POINT (WIRELESS
DATA)
AR AS REQUIRED
ASC AMPS SHORT CIRCUIT
ATS AUTOMATIC TRANSFER
SWITCH
AV AUDIO VISUAL
AWG AMERICAN WIRE GAGE
BB
XFMR
BUCK-BOOST TRANSFORMER
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
C CEILING MOUNTED
CAT CATEGORY
CATV COMMUNITY ANTENNA
TELEVISION
CB CIRCUIT BREAKER
CCBA CUSTOM COLOR AS SELECTED
BY ARCHITECT
CCTV CLOSED CIRCUIT TELEVISION
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFBA CUSTOM FINISH AS SELECTED
BY ARCHITECT
CKT CIRCUIT
CM CONSTRUCTION MANAGER
CND CONDUIT
CO CONVENIENCE OUTLET
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CONTROL PANEL
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
dBA UNIT OF SOUND LEVEL
DPDT DOUBLE POLE, DOUBLE
THROW
DS DISCONNECT SWITCH
E ENHANCED
EA EACH
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRIC NONMETALLIC
TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ER EQUIPMENT ROOM
EX EXISTING
F FURNITURE MOUNTED
FA FIRE ALARM
FCP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METAL CONDUIT
FOB FREIGHT ON BOARD
FPP FIBER PATCH PANEL
FVNR FULL VOLTAGE
NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEN GENERATOR
GFCI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GIG GIGA HERTZ
GND GROUND
HD HEAVY DUTY
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
HV HIGH VOLTAGE
HWM HORIZONTAL WIRE
MANAGEMENT
HZ HERTZ
I/O INPUT/ OUTPUT
IG ISOLATED GROUND
IMC INTERMEDIATE METAL
CONDUIT
IN/IS INSULATED/ ISOLATED
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE
REFERENCE AND LINE SYMBOLS
DETAIL INDICATOR: A5 INDICATES DETAIL NUMBER, E-501
INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.
A5 E-501
ELEVATION OR SECTION INDICATOR, EXTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ELEVATION OR SECTION INDICATOR, INTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ROOM IDENTIFIER WITH ROOM NAME AND NUMBER.
ROOM NAME
KEYNOTE INDICATOR.1
REVISION INDICATOR.1
CU-1 EQUIPMENT INDICATOR.
BREAK, STRAIGHT: TO BREAK PARTS OF DRAWING
BREAK, ROUND
MATCH LINE INDICATOR: CENTER, EXTRA WIDE LINE.MATCH LINE
SEE XX/X-XXX
NEW LINE: MEDIUM LINE.
EXISTING TO REMAIN LINE: THIN LINE.
DEMOLITION LINE: DASHED, MEDIUM LINE
ELECTRICAL EQUIPMENT INDICATOR. "XXX" INDICATES TYPE OF
EQUIPMENT OR EQUIPMENT ID. "EF-X" IDENTIFIES MECHANICAL
EQUIPMENT BEING SERVED. REFER TO EQUIPMENT SCHEDULE
FOR ADDITIONAL INFORMATION.
EF-X
XXX
EQUIPMENT INDICATOR. "X-X" INDICATES EQUIPMENT MARK
SHOWN ON EQUIPMENT SCHEDULE. "1LA-3" IDENTIFIES PANEL
EQUIPMENT IS CIRCUITED TO. REFER TO EQUIPMENT SCHEDULE
FOR ADDITIONAL INFORMATION.
1LA-3
X-X
MECHANICAL EQUIPMENT INDICATOR. "X-X" INDICATES
EQUIPMENT MARK SHOWN ON EQUIPMENT SCHEDULE. "XMDP"
IDENTIFIES PANEL EQUIPMENT IS CIRCUITED TO. REFER TO
EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.
XMDP
X-X
WIRING METHODS
SYMBOL DESCRIPTION
SYMBOLS LEGEND
WIRING.
BRANCH CIRCUIT HOME RUN TO PANELBOARD: NUMBER OF
ARROWS INDICATES NUMBER OF CIRCUITS. LETTER AND
NUMBER NOTATIONS IDENTIFY PANEL AND CIRCUIT NUMBERS.A-1,3,5
LOW VOLTAGE WIRING: DIVIDE, MEDIUM LINE.
CONDUIT STUB. DIMENSION RECORD DRAWINGS AND MARK.
CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR. REFER
TO ONE-LINE DIAGRAM.1
ADA ACCESS PUSH PLATEHC
JUNCTION BOX.J
JUNCTION BOX, SYSTEMS FURNITURE COMMUNICATION
CONNECTION.SCJ
JUNCTION BOX, SYSTEMS FURNITURE POWER CONNECTION.SPJ
PULL BOX.PB
CABLE TRAY ABOVE ACCESSIBLE CEILING.
"A" DENOTES CABLE TRAY WIDTH, "B" DENOTES CABLETRAY
DEPTH. +/-C'-D" DENOTES CABLE TRAY ELEVATION ABOVE OR
BELOW FINISHED SURFACE.
A"xB" +/-C'-D"
JUNCTION BOX, CEILING.CJ
LADDER RACK.
MECHANICAL EQUIPMENT CONNECTION. REFER TO EQUIPMENT
SCHEDULE FOR REQUIREMENTS.
SYMBOL DESCRIPTION
SYMBOLS LEGEND
SYMBOL DESCRIPTION
SYMBOLS LEGEND
ELECTRICAL POWER AND DISTRIBUTION
FUSE WITH RATING (ONE-LINE DIAGRAM).
DISCONNECT, FUSED (ONE-LINE DIAGRAM).
DISCONNECT, NONFUSED (ONE-LINE DIAGRAM).
DISCONNECT WITH FUSE AND MOTOR STARTER COMBINATION
(ONE-LINE DIAGRAM).
OVERLOAD RELAY (ONE-LINE DIAGRAM).
STARTER (ONE-LINE DIAGRAM).
CIRCUIT BREAKER, MOLDED CASE (ONE-LINE DIAGRAM).
CIRCUIT BREAKER, MOLDED CASE WITH SHUNT TRIP
(ONE-LINE DIAGRAM).
CIRCUIT BREAKER, MOTOR CIRCUIT PROTECTION
(ONE-LINE DIAGRAM).
MCP
CIRCUIT BREAKER, SOLID STATE (ONE-LINE DIAGRAM).
CIRCUIT BREAKER, SOLID STATE WITH GROUND FAULT
PROTECTION (ONE-LINE DIAGRAM).
GFP
MOTOR.
TRANSFORMER (ONE-LINE DIAGRAM).
TRANSFORMER, CURRENT (ONE-LINE DIAGRAM).
PANELBOARD (ONE-LINE DIAGRAM)."1H"
PANELBOARD WITH MAIN LUGS ONLY. BUS SIZE AND PHASE AS
SHOWN (ONE-LINE DIAGRAM).
225/3
"1H"
PANELBOARD WITH MAIN CIRCUIT BREAKER. SIZE AND PHASE AS
SHOWN (ONE-LINE DIAGRAM).
225/3
"1H"
PANELBOARD WITH MAIN AND SUB FEED CIRCUIT BREAKER
(ONE-LINE DIAGRAM).
60/3
225/3
"1H"
ELECTRICAL POWER AND DISTRIBUTION
PANELBOARD WITH SUB FEED LUGS (ONE-LINE DIAGRAM).
225/3 225/3 "1H" "1H"
PANELBOARD WITH CIRCUIT BREAKER AND SUB FEED LUGS
(ONE-LINE DIAGRAM).
225/3 "1H" "1H"
TRANSFER SWITCH (ONE-LINE DIAGRAM).
DIGITAL MULTIMETER (ONE-LINE DIAGRAM).DMM
SERVICE ENTRANCE SURGE PROTECTION (ONE-LINE DIAGRAM).
GENERATOR, ANNUNCIATOR (ONE-LINE DIAGRAM).ANN
GENERATOR, POWER (ONE-LINE DIAGRAM).G
DISCONNECT SWITCH, FUSED.
DISCONNECT SWITCH, UNFUSED.
STARTER, COMBINATION WITH DISCONNECT SWITCH.
STARTER OR MOTOR CONTROLLER.
PUSHBUTTON.
PUSHBUTTONS, MOTOR CONTROL.
PANELBOARD CABINET, FLUSH MOUNTED.
PANELBOARD CABINET, SURFACE MOUNTED, 1 SECTION.
PANELBOARD CABINET, SURFACE MOUNTED, 2 SECTION.
DP#__
DISTRIBUTION PANEL OR SWITCHBOARD.
LP
LIGHTING RELAY, CONTACTOR PANEL, OR DIMMING ENCLOSURE.
SWITCH, TOGGLE MOTOR STARTER WITH OVERLOAD
PROTECTION.ST
METER.M
EARTH GROUND (ONE-LINE DIAGRAM).
SINGLE BRANCH CIRCUIT HOME RUN TO PANELBOARD WITH
DEDICATED NEUTRAL CONDUCTOR. LETTER AND NUMBER
NOTATION IDENTIFY PANEL AND CIRCUIT NUMBER.A-1
PUSH BUTTON, REMOTE EMERGENCY STOP.EPO
KIRK-KEY MECHANICAL INTERLOCK (ONE-LINE DIAGRAM)K
DISTRIBUTION PANELBOARD, MOTOR CONTROL CENTER,
PLUG-IN BUSWAY, MEDIUM VOLTAGE SWITCHBOARD
(ONE-LINE DIAGRAM).
"1DPHA"
CIRCUIT BREAKER, ADJUSTABLE TRIP. "225AF" REPRESENTS
THE RATING AND "150AT" REPRESENTS THE TRIP SETTING.
(ONE-LINE DIAGRAM).
#AF
#AT
PANELBOARD WITH MAIN LUGS ONLY AND SURGE PROTECTION
WITH CIRCUIT BREAKER (ONE-LINE DIAGRAM).
25/3
225/3
"1H"
ARC ENERGY REDUCTION
3. EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL, AND
COMMUNICATION SPACES): INSTALL RACEWAYS BETWEEN DECK AND
STRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.
ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALL
CONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT COMPLY
WITH THESE REQUIREMENTS TO THE ARCHITECT.
4. SUBMITTALS: PROVIDE ORIGINAL ELECTRONIC PDF FORMAT, BOUND,
BOOKMARKED (EACH SECTION AND PRODUCT), AND HIGHLIGHTED. JOB NAME
AND SUBCONTRACTOR SHALL BE ON THE FRONT COVER. PREPARE INDEX OF
EQUIPMENT SUBMITTED IN EACH TAB.
5. REFLECTED CEILING PLANS: COORDINATE THE LOCATION OF LIGHT FIXTURES
WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. REFER ALL
DISCREPANCIES TO THE ARCHITECT AND ENGINEER.
6. ALL WORK SHALL BE DONE ACCORDING TO THE CURRENT NATIONAL ELECTRIC
CODE (NEC), IBC, NFPA, AND IFC. COMPLIANCE AND FINAL APPROVAL IS SUBJECT
TO THE ON SITE FIELD INSPECTION OF THE AHJ.
kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR
LED LIGHT EMITTING DIODE
LFMC LIQUID TIGHT FLEXIBLE METAL
CONDUIT
LFNC LIQUID TIGHT FLEXIBLE
NONMETALLIC CONDUIT
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION
SYSTEM
MAX MAXIMUM
MC METAL CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTION
MDP MAIN DISTRIBUTION PANEL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OCP OVER CURRENT PROTECTION
OE OWNER ELECTRONICS
OF/CI OWNER FURNISHED/
CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/ OWNER
INSTALLED
OFP OBTAIN FROM PLANS
OH DR OVERHEAD (COILING) DOOR
OL OVERLOAD
PB PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PNM PLENUM
PR PAIR
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PTZ PAN/TILT/ZOOM
QTY QUANTITY
R REMOVE
RCP REFLECTED CEILING PLAN
RMC RIGID METAL CONDUIT
RNC RIGID NONMETAL CONDUIT
RPM REVOLUTIONS PER MINUTE
RPP RISER PATCH PANEL
RR REMOVE AND RELOCATE
S/S START/STOP
SCA SHORT CIRCUIT AMPS
SCBA STANDARD COLOR AS
SELECTED BY ARCHITECT
SF SQUARE FOOT (FEET)
SFBA STANDARD FINISH AS
SELECTED BY ARCHITECT
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE THROW
SPEC SPECIFICATION
SPP STATION PATCH PANEL
SPST SINGLE POLE, SINGLE THROW
ST SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TL TWIST LOCK
TP TELEPHONE POLE
TP TWISTED PAIR
TR TELECOMMMUNICATIONS
ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSER
TYP TYPICAL
UF UNDERFLOOR
UGND UNDERGROUND
UPS UNINTERRUPTIBLE POWER
SUPPLY
V VOLTS
VA VOLT AMPERE
VFC/VF
D
VARIABLE FREQUENCY MOTOR
CONTROLLER
VWM VERTICAL WIRE MANAGEMENT
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WPP WIRELESS PATCH PANEL
XFMR TRANSFORMER
ELECTRICAL-SHEET INDEX
E001 ELECTRICAL COVER SHEET
E002 ELECTRICAL SYMBOLS & NOTES
E003 TYPICAL LABELING DETAILS
E004 TYPICAL LABELING DETAILS
E101 OVERALL LEVEL 1 ELECTRICAL PLAN
E301 ENLARGED DEMOLITION ROOM PLANS
E302 ENLARGED DEMOLITION INTERIOR PANELBOARDS
E303 ENLARGED ROOM PLANS
E601 ELECTRICAL SCHEDULES
E602 DEMOLITION ONE-LINE DIAGRAM - MAIN BUILDING - 1 OF 2
E603 DEMOLITION ONE-LINE DIAGRAM - MAIN BUILDING - 2 OF 2
E604 ONE-LINE DIAGRAM - MAIN BUILDING 1 OF 2
E605 ONE-LINE DIAGRAM - MAIN BUILDING - 2 OF 2
E611 PANEL SCHEDULES
E612 PANEL SCHEDULES
Mark: Date: Description
ADD ALTERNATES
PROVIDE THE FOLLOWING ADD ALTERNATES AS A SEPARATE BID. CONTRACTOR SHALL
BE RESPONSIBLE TO PROVIDE ALL SCOPE PER THE BID DOCUMENTS.
ADD ALT 01 - DEMOLISH AND REPLACE EXISTING "MDP-1", SEE 1-LINES AND PLAN VIEWS
FOR MORE SPECIFICS.
ADD ALT 02 - DEMOLISH AND REPLACE EXISTING "MDP-2", SEE 1-LINES AND PLAN VIEWS
FOR MORE SPECIFICS.
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
1LA1-1
1LA1-1
OFF
TYPICAL RECEPTACLE LABEL
LOCATION
TYPICAL LABELING FOR PANELBOARDS
IN NON-PUBLIC LOCATIONS
*LABEL TO BE CENTERED IN EQUIPMENT,
PREFERABLE ON FACE OF EQUIPMENT AND
TOWARDS THE TOP.
**REFER TO TYPICAL SWITCH/RECEPTACLE
LABELING DETAIL FOR LABEL
REQUIREMENTS.
TYPICAL SWITCH LABEL
LOCATION
***DISPOSE OF AN EXISTING PANELBOARD
NAME PLATES WHEN INSTALLING NEW NAME
PLATES.
CIRCUIT NUMBER
LABEL
CIRCUIT NUMBER
LABEL
PANELBOARD LABEL, LOCATED
INSIDE OF DOOR, HIDDEN FROM
PUBLIC
1LA1
1LA2
2LA1
2LA2
SPARE
1LB1
1LB2
2LB1
2LB2
SPARE
SWITCHBOARD LABEL
SWITCHBOARD LOAD
LABEL
TYPICAL LABELING FOR
SWITCHBOARDS
ARC FLASH LABEL LOCATED HERE
ON
OFF
DISCONNECT LABEL
ARC FLASH LABEL LOCATED HERE
TYPICAL LABELING FOR DISCONNECTS
ARC FLASH LABEL LOCATED HERE
1LA1,
208/120V, #PH, #W, 22KAIC,
FED FROM-1LDP1
ELEV-1
208/120V, 1PH, 3W
FED FROM MDP
1LDP1,
208/120V, #PH, #W, 22KAIC,
FED FROM-MDP1
SHADED AREAS TO BE ORANGE ALL OTHER TO BE
WHITE BACKGROUND
(TYP) DISTANCES IN INCHES
COORDINATE VOLTAGE VALUES WITH ONE-LINE
MATCH NAME OF EQUIPMENT WITH NAMES ON ONE-LINE
PROVIDE ADDRESS WHERE SKM ANALYTICS IS PERFORMED
PROVIDE JOB NUMBER "########", DATE OF ANALYSIS
AND ENGINEER WHO PERFORMED STUDY
*PROVIDE ARC FLASH LABEL FOR ALL
ELECTRICAL EQUIPMENT PER SPECIFICATIONS
AND REQUIRED BY NEC
X0 X0 X0
3 PHASE DRY TYPE STEP-DOWN TRANSFORMER
DELTA PRIMARY:WYE SECONDARY
1 N
G
FIRST DOWNSTREM
DISCONNECTING MEANS
SBJ3
SSBJ
GC
GC - GROUNDED CONDUCTOR (NEUTRAL)
SBJ - SYSTEM BONDING JUMPER
SSBJ - SUPPLY SIDE BONDING JUMPER
UC - UNGROUDNED (PHASE) CONDUCTOR
BCJ - BONDING CONDUCTOR/JUMPER
GEC - GROUNDING ELECTRODE CONDUCTOR
BCJ
GROUND BUS
UC
GEC
BCJ
TO NEAREST AVAILABLE BUILDING
GROUNDING ELECTRODE
PRIMARY FEEDER
1.
2.
NOTES:
MOUNT XFMR AT 2' ABOVE FINISHED FLOOR FOR ACCESS TO
ACCESSIBLE FLOOR BELOW
XFMR SUPPORTS SHALL COMPLY WITH SEISMIC REQUIREMENTS.
PROVIDE MANUFACTURER
RECOMMENDED MOUNT AND
ALL REQUIRED HARDWARE
RACEWAY
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:0
PM
Designer Checker
Author 26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
TYPICAL LABELING
DETAILS
E003
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
SCALE: NTSA3 TYPICAL SWITCH, RECEPTACLE AND PANELBOARD/SWITCHBOARD LABELING LOCATION DETAIL
SCALE: NTSA1 TYPICAL ARC FLASH LABEL
SCALE: NTSC3
TYPICAL INDOOR
STEP-DOWN TRANSFORMER SEPARATELY DERIVED SYSTEM GROUNDING AND BONDING DETAIL
Mark: Date: Description
SCALE: NTSC1 TRANSFORMER WALL MOUNTING
SHEET KEYNOTES
1 BOND METAL RACEWAY.
2 NO NEUTRAL TO GROUND BOND WITHIN GEAR, REMOVE NEUTRAL TO GROUND
BOND CONNECTION IF IT EXISTS.
3 SYSTEM BONDING JUMPER BONDING TRANSFORMER X0 TERMINAL TO
TRANSFORMER ENCLOSURE / GROUND BUS.
4 EQUIPMENT GROUND BOND TO ENCLOSURE.
5 BOND TO TRANSFORMER ENCLOSURE WITH #4/0 CU.
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MIN=WIDTH+2ED
M
IN
D
EP
TH
+2
ED
TH
IC
KN
ES
S t
ELECTRICAL/MECHANICAL
EQUIPMENT ATTACHED
TO HOUSEKEEPING SLAB,
SEE SCHEDULE
OUTLINE OF
ELECTRICAL/MECHANICAL
EQUIPMENT
WIDTH
D
EP
TH
ED
ED
ED
ED
PLAN VIEWSIDE VIEW
ISOMETRIC VIEW
EQUIPMENT
ANCHOR BOLT
DETAIL A
REINFORCING BAR
EACH WAY
CENTERED IN SLAB,
SEE SCHEDULE FOR
SIZE AND QUANTITY
OUTLINE OF
REINFORCED
CONCRETE
HOUSEKEEPING SLAB,
SEE SCHEDULE AND
NOTES
EXTERIOR
ANCHOR BOLT
CONNECTION
SEE DETAILS
INTERIOR
ANCHOR BOLT
CONNECTION,
SEE DETAILS
INTERIOR REINFORCED
HOUSEKEEPING SLAB,
SEE SCHEDULE FOR SIZE
AND REINFORCING
CONCRETE SLAB,
SEE STRUCTURAL
CONCRETE ANCHOR,
SEE SCHEDULE FOR
SIZE AND QUANTITY
ELECTRICAL EQUIPMENT,
SEE SCHEDULE
REINFORCED CONCRETE
HOUSEKEEPING SLAB ATTACHED TO
STRUCTURAL SLAB (NOT SHOWN), SEE
HOUSEKEEPING SLAB SCHEDULE
5" m in
HOUSEKEEPING SLAB SCHEDULE
LENGTH
(in)
THICKNESS
(in)
BAR SIZE (#) QUANTITY SPACING
(in o.c.)
COVER
(in)
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.
2.
3.
4.
5.
6.
7.
NOTE:
EDGE DISTANCE (ED) = 6" UNLESS NOTED OTHERWISE.
FOR REINFORCING IN THE WIDTH DIRECTION REFER TO SCHEDULE ABOVE AND SUBSTITUTE WIDTH
DIMENSION FOR THE LENGTH.
ALL REINFORCING IS TO BE TIED IN PLACE AND CHAIRED TO THE CORRECT HEIGHT (CENTER OF
SLAB) PRIOR TO PLACING CONCRETE.
ICC APPROVED WEDGE ANCHOR BOLTS SHALL BE EQUALLY SPACED AND EMBEDDED 3" MIN. INTO STRUCTURAL SLAB. BOLTS SHALL PROTRUDE FROM SLAB A MIN. OF 2" AND SHALL HAVE DOUBLE
NUT WITH FLAT WASHER BETWEEN. ALL ANCHORS BOLTS SHALL BE INSIDE THE PERIMETER
REINFORCING STEEL
THIS SCHEDULE OF FOR BIDDING PURPOSES ONLY! THE ACTUAL HOUSEKEEPING SLAB DESIGN AND
REINFORCING SHALL BE SUBMITTED VIA DEFERRED SUBMITTAL BY THE CONTRACTOR UNLESS
NOTED OTHERWISE.
3000 PSI CONCRETE STRENGTH AT 28 DAYS MIN UNLESS NOTED OTHERWISE
STRUCTURAL SLAB DESIGN PER OTHERS. DO NOT CUT OR DAMAGE POST TENSION CABLES OR SLAB
REINFORCING. VERIFY WITH STRUCTURAL ENGINEER
108 6 4 7 17 1.5
COVER
SLAB
ANCHOR
DIAMETER
3/8"
3/8"
3/8"
3/8"
1/2"
ANCHOR BOLT TO
STRUCTURAL SLAB DETAIL
B, SEE SCHEDULE
1/2"
1/2"
1/2"
ANCHOR
QTY (B) & #
ROWS (R)
2B, 2R
3B, 2R
3B, 3R
4B, 3R
5B, 3R
6B, 3R
6B, 4R
7B, 4R
3/ 4" m in
3" m in2" m in
DETAIL B
SLAB ANCHOR
DETAIL A
EQUIPMENT
ANCHOR
EQUIPMENT
HOUSEKEEPING
SLAB
STRUCUTRE
SLAB
REBAR
HOUSEKEEPING
SLAB
STRUCUTRE
SLAB
REBAR
RACEWAY .5" TO 6" (TYP)
ALL THREADED ROD -
SIZE AS REQUIRED
STRUCTURAL
BEAM, JOIST,
SLAB, ETC.
UNISTRUT CHANNEL - SIZE AS
REQUIRED BY WEIGHT SUPPORTED
CONDUIT CLAMP - .5" TO 1"
UNISTRUT 2 PIECE CHANNEL
PIPE STRAPS - 1.25" TO 6"
BEAM CLAMP, HANGER
CLAMP OR APPROVED
SUPPORT, AS REQUIRED BY
WEIGHT SUPPORTED
LABEL TO BE PROVIDED AT EACH SWITCHBOARD, PANELBOARD,
DISCONNECT/STARTER. LABEL IS TO BE 3" X REQUIRED LENGTH X 1/16"
LAMINATED 2-PLY PLASTIC LAMACOID. LETTERS SHALL BE FORMED BY
ENGRAVING OUTER WHITE PLY, EXPOSING BLACK PLY BENEATH.
LABEL IS TO BE MOUNTED USING DOUBLE SIDED ADHESIVE TAPE COVERING
THE BACK OF THE LABEL.
FIRST LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED AS
SHOWN. REPLACE THE LETTER/NUMBER WITH THOSE FOUND ON THE ONE-
LINE DIAGRAM.
SECOND LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED
AS SHOWN. THE FOLLOWING SHALL BE PROVIDED, VOLTAGE, PHASE,
NUMBER OF WIRES, AND AIC RATING OF DEVICE.
1 2
4 208/120V, #PH, #W, 22KAIC,
1LA1,
NOTE: EMERGENCY PANELS SHALL USE LAMACOID WITH RED OUTERPLY,
EXPOSING WHITE LETTERING BENEATH. CONTRACTOR TO USE SAME LABEL
SCHEME EXCEPT FIRST 'X' IS REPLACED WITH 'E' FOR EMERGENCY. SECOND 'X'
TO BE 'L' FOR LOW OR 'H' FOR HIGH VOLTAGE (480/277V). LAST '#' TO BE
REPLACED WITH LETTER INDICATING LOCATION OF PANEL.
FED FROM-MDP15
THIRD LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED AS
SHOWN. PROVIDE "FED FROM-" AND REPLACE MDP1 WITH THE DEVICES
NAME THAT FEEDS THE PANELBOARD.
LABEL TO BE PROVIDED THAT IS TO BE 4" X REQUIRED LENGTH X 1/16"
LAMINATED 2-PLY PLASTIC LAMACOID. LETTERS SHALL BE FORMED BY
ENGRAVING OUTER WHITE PLY, EXPOSING BLACK PLY BENEATH.
LABEL IS TO BE MOUNTED USING DOUBLE SIDED ADHESIVE TAPE COVERING
THE BACK OF THE LABEL.
FIRST LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, WITH THE EQUIPMENT
ID MATCHING PLANS.
SECOND LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND FORMATTED
AS SHOWN. THE FOLLOWING SHALL BE PROVIDED, VOLTAGE, PHASE,
NUMBER OF WIRES, AND AIC RATING OF GEAR.
1 2
4 480Y/277V, 3PH, 4W, 22KAIC,
MDP1,
THIRD & FOURTH LINE: LETTERING IS TO BE 3/8" HIGH, CENTERED, AND
FORMATTED AS SHOWN. LABEL WITH ACTUAL AVAILABLE FAULT CURRENT
AND ASSOCIATED CLEARING TIME.
AVAILABLE FAULT CURRENT -
XX,XXX A
MCB CLEARING TIME -
X.XX SECONDS
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:0
PM
Designer Checker
Author 26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
TYPICAL LABELING
DETAILS
E004
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
Mark: Date: Description
SCALE: NTSA3 TYPICAL CONCRETE HOUSEKEEPING PAD
SCALE: NTSC1 TYPICAL CONDUIT RACK DETAIL
SCALE: NTSA1 TYPICAL PANELBOARD/SWITCHBOARD/DISCONNECT/TRANSFORMER LABEL
SCALE: NTSB1 TYPICAL MAIN SERVICE EQUIPMENT/GEAR LABEL
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MB-20MB-19MB-18MB-17MB-16MB-15MB-14MB-13MB-12MB-11MB-10MB-9MB-8MB-7MB-6MB-5MB-4MB-3MB-2MB-1
MB-P
MB-N
MB-M
MB-L
MB-K
MB-J
MB-I
MB-H
MB-G
MB-F
MB-E
MB-D
MB-C
MB-B
MB-A
MB-AA
MB-AB
MB-AC
MB-AD
MB-AE
MB-AF
ELECTRICAL
ROOM
2006-G
E301 A1
E301 A2
E301 A4
E301 C1
E301 C2
E301 C4
E303 A1
E303 A2
E303 A4
E303 C2
E303 C4
E303 C1
(EX)
"TCN"
(EX)
"MDP2000"
(EX)
"LDP-D"
E301 D1
Room 1001F
(EX)
"T-MDP-2"
(EX)
"1A"
(EX)
"1HA"
"LCP"
"XFMR-TEQ6"
"XFMR-T1006"
"HB"
"LC"
"MDP-2"
"MDP-1"
"C"
"F" "D"
Room 1018A
Room
Room 1205A
Room
Room
(EX)
"MDP-3"
E301 D2
Room
VAULT
"LCP2"
SHEET KEYNOTES
1 CONTRACTOR TO PROVIDE NEW FUSE BUCKET IN EXISTING GEAR "EQDP" TO
FEED LOAD.
(EX)
"1QLA GEN"
(EX)
"1QLA UPS"
(EX)
"EQDP"
(EX)
"TRUEVARS" POWER
FACTOR FILTER"
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:0
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
OVERALL LEVEL 1
ELECTRICAL PLAN
E101
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
SCALE: 1" = 30'-0"A2 OVERALL LEVEL 1 ELECTRICAL PLAN NORTH
Mark: Date: Description
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MB-7
MB-F
(EX)
"MDP-1"
(EX)
"MDP-2"
(EX)
"T-MDP-2"
(EX)
"1HA"
(EX)
"1A"
Room 1205A
MB-14
MB-A
(EX)
"C"
Room
MB-14
MB-AB
(EX)
"D" (EX)
"F"
(EX)
"D SEC 2"
Room
MB-12
(EX)
"LCP"
(EX)
"LCP2"
4 4
Room 1018A
4 4
MB-11
(EX)
"LB"
Room 1001F
MB-12
MB-J
(EX)
"XFMR TB"
(EX)
"HB"
(EX)
"XFMR TCP (HB)"
(EX)
"LC"
Room
12 1214
(EX)
"TRUEVARS" POWER
FACTOR FILTER"
MB-12
MB-H
Room
5 (EX)
"XFMR-TEQ6 (CEILING)"
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:1
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
ENLARGED
DEMOLITION ROOM
PLANS
E301
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
SCALE: 1/4" = 1'-0"A1 ENLARGED DEMO PLAN - ROOM 1205A
SCALE: 1/4" = 1'-0"A2 ENLARGED DEMO PLAN - ROOM 1408
SCALE: 1/4" = 1'-0"A4 ENLARGED DEMO PLAN - ROOM 1405
SCALE: 1/4" = 1'-0"C1 ENLARGED DEMO PLAN - ROOM 1018-A
SCALE: 1/4" = 1'-0"C2 ENLARGED DEMO PLAN - ROOM 1001-F
SCALE: 1/4" = 1'-0"C4 ENLARGED DEMO PLAN - ROOM 1006 (BOILER ROOM)
GENERAL SHEET NOTES
SHEET KEYNOTES
1 REFER TO EP601 FOR FEEDER SCHEDULE.
2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC
CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL
SCOPE OF WORK AS REQUIRED.
5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.
6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL
SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW
PANELBOARD LOCATION,
7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,
WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.
8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD
9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL
SCHEDULE TO REFLIECT ACTUAL LOAD DATA
Mark: Date: Description
1 PROTECT AND MAINTAIN ELECTRICAL EQUIPMENT
2 CONTRACTOR TO DEMOLISH EXISTING SURGE PROTECTION.
3 CONTRACTOR TO RELOCATE AS REQUIRED FOR NEW PANELBOARDS AND PATCH
AND REPAIR WALL TO MATCH EXISTING CONDITIONS.
4 CONTRACTOR TO DEMOLISH PANELBOARD COVER AND PANELBOARD INTERIOR.
PROTECT AND MAINTAIN EXISTING PANELBOARD CAN TO UTILIZE AS
PULLBOX/JUNCTION AND ALL CIRCUITS UNLESS NOTED OTHERWISE. TRACE
EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF POWER ON
RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO TRACE UNKNOWN
CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS WILL NEED TO BE
TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT LABELED DURING
THE CIRCUIT TRACING. DEMOLISH ALL ABANDONED CABLING AND CIRCUITS.
5 CONTRACTOR TO DEMOLISH EXISTING TRANSFORMER ABOVE CEILING AND
PROVIDE A NEW TRANSFORMER TO NEW LOCATION.
6 DEMOLISH EXISTING THERMOMETER. PROVIDE BLANK FACE PLATE TO COVER UP
JUNCTION BOX.
7 CONTRACTOR TO PROVIDE TEMPORARY COOLING THROUGHOUT PANEL
REPLACEMENT. FEED THE RTU FROM PANEL "1QLA GEN" AND SPLIT UNITS FROM
PANEL "1 QLA UPS". SO CORDS ALLOWED TO RUN ACROSS CEILING WHILE PANEL IS
DOWN.
8 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 01.
9 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 02.
10 REUSE EXISTING FEEDER, FIELD VERIFY WHERE FEEDER COMES INTO THE PANEL
BOARD AND PROCURE PANELBOARD WITH ABILITY TO LAND EXISTING CABLING ON
BOARD WITHOUT SPLICING CABLES.
11 OWNER TO MOVE DEVICE TO DIFFERENT LOCATION TO ALLOW FOR SURFACE
MOUNTED PANELBOARD.
12 DEMOLISH EXISTING TRANSFORMER AND ASSOCIATED GROUNDING.
13 DEMOLISH PANELBOARD INTERIOR. PROTECT AND MAINTAIN EXISTING
PANELBOARD CAN TO UTILIZE AS PULLBOX/JUNCTION AND ALL CIRCUITS UNLESS
NOTED OTHERWISE . LEAVE EXISTING COVER FOR ACCESS TO CABLING AND
REMOVE EXISTING PANELBOARD LABEL.
14 DEMOLISH EXISTING PANEL BOARD, PROTECT AND MAINTAIN EXISTING BRANCH
CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL BOARD.
TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF POWER
ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO TRACE
UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS WILL
NEED TO BE TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT
LABELED DURING THE CIRCUIT TRACING. DEMOLISH ALL CABLING AND ANY
CIRCUITS THAT HAVE BEEN ABANDONED.
15 DEMOLISH EXISTING PANEL BOARD, PROTECT AND MAINTAIN EXISTING BRANCH
CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL BOARD.
SCALE: NTSD1 IMAGE OF PANEL LCP AND LCP2
SCALE: 1/4" = 1'-0"D2 ENLARGED DEMO PLAN - ROOM 1018
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:1
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
ENLARGED
DEMOLITION
INTERIOR
PANELBOARDS
E302
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
GENERAL SHEET NOTES
1 REFER TO EP601 FOR FEEDER SCHEDULE.
2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC
CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL
SCOPE OF WORK AS REQUIRED.
5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.
6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL
SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW
PANELBOARD LOCATION,
7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,
WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.
8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD
9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL
SCHEDULE TO REFLIECT ACTUAL LOAD DATA
Mark: Date: Description
SCALE: NTS
IMAGE OF PANEL LCP INTERIORA1 SCALE: NTS
IMAGE OF PANEL LCP2 INTERIORA2 SCALE: NTSA4 IMAGE OF PANEL LB INTERIOR
SCALE: NTSA5 IMAGE OF PANEL LC INTERIOR
SCALE: NTSC1 IMAGE OF PANEL HB INTERIOR
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
MB-7
MB-F
(EX)
"1A"
(EX)
"1HA"
(EX)
"T-MDP-2"
"MDP-2"
"MDP-1"
Room 1205A
MB-14
MB-A
"C"
Room
MB-14
MB-AB
"F""D SEC 2" "D"
Room
MB-11
Room 1001F 46
MB-12
MB-J
"XFMR-T1006"
"HB""LC"
Room
A3 E004
DS-LCP
(EX)
"TRUEVARS" POWER
FACTOR FILTER"
MB-12
"XFMR-TEQ6"
Room 1018A
"LCP"
C1 E003
"LCP2"
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:1
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
ENLARGED ROOM
PLANS
E303
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
SCALE: 1/4" = 1'-0"A1 ENLARGED PLAN - ROOM 1205A
SCALE: 1/4" = 1'-0"A2 ENLARGED PLAN - ROOM 1408
SCALE: 1/4" = 1'-0"A4 ENLARGED PLAN - ROOM 1405
SCALE: 1/4" = 1'-0"C2 ENLARGED PLAN - ROOM 1001-F
SCALE: 1/4" = 1'-0"C4 ENLARGED PLAN - ROOM 1006 (BOILER RM)
SCALE: 1/4" = 1'-0"C1 ENLARGED PLAN - ROOM 1018-A
GENERAL SHEET NOTES
SHEET KEYNOTES
1 REFER TO EP601 FOR FEEDER SCHEDULE.
2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC
CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL
SCOPE OF WORK AS REQUIRED.
5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.
6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL
SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW
PANELBOARD LOCATION,
7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,
WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.
8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD
9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL
SCHEDULE TO REFLIECT ACTUAL LOAD DATA
Mark: Date: Description
1 INTERCEPT ALL EXISTING CIRCUITS FROM PANELBOARD LB AND EXTEND TO NEW
PANELBOARD LC. UTILIZE EXISTING PANELBOARD CAN AS PULLBOX/JUNCTION AND
LAND CIRCUITS ON NEW PANELBOARD. UTILIZE EXISTING COVER AS ACCESS TO
PULLBOX AND PROVIDE SHAWMUT TERMINATIONS OR EQUALS FOR SPLICING
CABLING.
2 CONTRACTOR TO INSTALL NEW TRANSFORMER AND REFEED ALL EXISTING
EQUIPMENT FROM TRANSFORMER "TB" AND "TCP (HB)" TO NEW TRANSFORMER.
PROVIDE NEW CONCRETE PAD FOR NEW GEAR.
3 ROUTE RACEWAY SURFACE MOUNTED IN THIS ROOM TO THE CEILING TO POWER
SOURCE AND BETWEEN TRANSFORMER AND PANELBOARD. ALL RACEWAYS
OUTSIDE OF THIS ROOM SHALL BE CONCEALED IN CEILINGS/WALLS.
4 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL
SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW
PANELBOARD LOCATION,
5 NO PIGTAIL SPLICING ALLOWED, EXTEND ALL CABLING TO NEW PANELBOARD
LOCATION.
6 CONTRACTOR TO PAINT SPACE AS REQUIRED FOR SPACE TO HAVE A CONTINUOUS
LOOK/FINISH.
7 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 01.
8 PROVIDE ALL SCOPE ASSOCIATED WITH GEAR IN ADD ALTERNATE 02.
9 CONTRACTOR TO INSTALL NEW PANELBOARD, PROTECT AND MAINTAIN EXISTING
BRANCH CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL
BOARD. TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF
POWER ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO
TRACE UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS
WILL NEED TO BE TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT
LABELED DURING THE CIRCUIT TRACING. DEMOLISH ALL CABLING AND ANY
CIRCUITS THAT HAVE BEEN ABANDONED.
10 CONTRACTOR TO INSTALL NEW TRANSFORMER IN NEW LOCATION. INTERCEPT AND
EXTEND ALL RACEWAY AND CABLING AS REQUIRED. REFEED EXISTING EQUIPMENT
FROM DEMOLISHED CEILING TRANSFORMER TO NEW GROUND TRANSFORMER.
PROVIDE WALL MOUNT RACK FOR TRANSFORMER AND LOCATE 2FT ABOVE
FINISHED FLOOR FOR ACCESSS TO ACCESSIBLE FLOOR BELOW.
11 WHERE REQUIRED FOR NEW EQUIPMENT PROVIDED BY CONTRACTOR
ADJUST/MOVE EXISTING RACEWAYS, DEVICES, ETC. THAT ARE IN CONFLICT WITH
THE NEW EQUIPMENT.
12 CONTRACTOR TO INSTALL NEW PANELBAORD INTERIOR AND COVER. UTILIZE
EXISTING PANELBOARD CAN AS PULLBOX/JUNCTION AND LAND CIRCUITS ON NEW
PANELBOARD.TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR
SOURCE OF POWER ON RECEPTACLES POWERED FROM PANELBOARD.
CONTRACTOR TO TRACE UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE.
ASSUME 15 CIRCUITS WILL NEED TO BE TRACED. ADD LABELS TO ALL
RECEPTACLES THAT WERE NOT LABELED DURING THE CIRCUIT TRACING.
DEMOLISH ALL CABLING AND ANY CIRCUITS THAT HAVE BEEN ABANDONED.
13 CONTRACTOR TO INSTALL NEW PANELBOARD, PROTECT AND MAINTAIN EXISTING
BRANCH CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL
BOARD. TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF
POWER ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO
TRACE UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS
WILL NEED TO BE TRACED. ADD LABELS TO ALL RECEPTACLES THAT WERE NOT
LABELED DURING THE CIRCUIT TRACING. DEMOLISH ALL CABLING AND ANY
CIRCUITS THAT HAVE BEEN ABANDONED.
14 PROVIDE NEW BRANCH CIRCUIT TO FILTER.
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:1
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
ELECTRICAL
SCHEDULES
E601
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
Mark: Date: Description
SYM AMP
HH
AMPS
CONDUIT
SIZE
CONDUCTOR (NOTE 1)
IG/HH SE NOTESQTY SIZE G
1 20 - .75 2 12 12 12 8 2 2 20 - .75 3 12 12 12 8 2,3 3 20 24 .75 4 12 12 12 8 2,3 4 30 - .75 2 10 10 10 8 2 5 30 - .75 3 10 10 10 8 2 6 30 32 .75 4 10 10 10 8 2 7 40 - 1 2 8 10 8 6 2 8 40 - 1 3 8 10 8 6 2 9 40 44 1 4 8 10 8 6 2 10 55 - 1 2 6 10 8 4 2 11 55 - 1 3 6 10 8 4 2 12 55 60 1.25 4 6 10 8 4 2 13 70 - 1 2 4 8 4 2 2 14 70 - 1.25 3 4 8 4 2 2 15 70 76 1.25 4 4 8 4 2 2 16 85 - 1.25 2 3 8 3 2 2 17 85 - 1.25 3 3 8 3 2 2 18 85 92 1.25 4 3 8 3 2 2 19 95 - 1.25 3 2 8 2 2 2 20 95 104 1.50 4 2 8 2 2 2 21 130 - 1.50 3 1 6 2 2 2 22 130 116 1.50 4 1 6 2 2 2 23 150 - 2 3 1/0 6 2 1/0 2 24 150 136 2 4 1/0 6 2 1/0 2 25 175 - 2 3 2/0 6 2 2/0 2 26 175 156 2 4 2/0 6 2 2/0 2 27 200 - 2 3 3/0 6 2 2/0 2 28 200 180 2.50 4 3/0 6 2 2/0 2 29 230 - 2.50 3 4/0 4 2 2/0 2 30 230 208 2.50 4 4/0 4 2 2/0 2 31 255 - 2.50 3 250 4 1 2/0 2 32 255 232 2.50 4 250 4 1 2/0 2 33 310 - 3 3 350 3 1/0 3/0 2 34 310 280 3 4 350 3 1/0 3/0 2 35 380 - 3.50 3 500 3 3/0 3/0 2 36 380 344 4 4 500 3 3/0 3/0 2
37 400 - 2 EA 2 3 3/0 3 3/0 3/0 2
38 400 360 2 EA 2.50 4 3/0 3 3/0 3/0 2
39 510 - 2 EA 2.50 3 250 1 4/0 3/0 2
40 510 464 2 EA 3 4 250 1 4/0 3/0 2
41 620 - 2 EA 3 3 350 1/0 4/0 3/0 2,4
42 620 560 2 EA 3 4 350 1/0 4/0 3/0 2,4
43 760 - 2 EA 3.50 3 500 1/0 4/0 3/0 2,4
44 760 688 2 EA 4 4 500 1/0 4/0 3/0 2,4
45 855 - 3 EA 3 3 300 2/0 4/0 3/0 2,4
46 855 768 3 EA 3 4 300 2/0 4/0 3/0 2,4
47 1000 - 3 EA 3.50 3 400 2/0 4/0 3/0 4
48 1000 912 3 EA 3.50 4 400 2/0 4/0 3/0 4
49 1140 - 3 EA 4 3 500 3/0 4/0 3/0 4
50 1140 1032 3 EA 4 4 500 3/0 4/0 3/0 4
51 1240 - 4 EA 3 3 350 3/0 4/0 3/0 4
52 1240 1120 4 EA 3 4 350 3/0 4/0 3/0 4
53 1675 1520 5 EA 4 4 400 4/0 4/0 4/0 4
54 2010 1824 6 EA 4 4 400 250 250 250 4
55 2660 2408 7 EA 4 4 500 350 350 350 4
56 3040 2752 8 EA 4 4 500 500 500 500 4
57 4180 3784 11 EA 4 4 500 500 500 500 4
58 1200 - 5 EA 4 - - - - - 6
59 3000 - 10 EA 6 - - - - - 6
60 - - 10 EA 4 - - - - - 6
IG
(E.G.)
COPPER CONDUCTOR AND
CONDUIT SCHEDULE
SUBSCRIPT (NOTE 5)
SCHEDULE NUMBER
"2N": INCLUDE TWO NEUTRAL CONDUCTORS SIZED AS SCHEDULED FOR
PHASE AND NEUTRAL CONDUCTORS WHERE THE CONDUCTOR IS #1/0
OR LARGER. INCLUDE A SINGLE 200% RATED CONDUCTOR THAT IS
TWICE THE AMPACITY OF THE SCHEDULED PHASE AND NEUTRAL
CONDUCTOR WHERE THE CONDUCTOR IS BELOW #1/0 IN SIZE.
"CI": PROVIDE CIRCUIT INTEGRITY CABLE; TYPE TWO-HOUR FIRE
RESISTIVE CABLES IN CONDUIT OR PROVIDE FEEDER ENCASED IN
CONCRETE.
"FG" FULL SIZE GROUND, SIZE EQUIPMENT GROUNDING CONDUCTOR TO
BE SAME SIZE AS THE PHASE CONDUCTORS.
"HH": NEUTRAL CURRENTS EXIST DUE TO HIGH HARMONIC "NONLINEAR"
LOADS. CURRENT CARRYING CONDUCTORS DERATED
ACCORDINGLY. PROVIDE THE IG/HH SIZE FOR THE EQUIPMENT
GROUNDING CONDUCTOR.
"IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)
SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND
CONDUCTOR.
"MC": PROVIDE FEEDER IN METAL-CLAD CABLE; TYPE MC IN PLACE OF
SINGLE CONDUCTORS IN CONDUIT.
"SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN, WHICH
IS SIZED FOR THE GROUNDING OF THE SECONDARY OF THE
SEPARATELY DERIVED SYSTEM.
"SER": PROVIDE SERVICE-ENTRANCE CABLE; TYPE SE OR SER IN PLACE OF
SINGLE CONDUCTORS IN CONDUIT.
CONDUCTOR AND CONDUIT SCHEDULE NOTES
CIRCUIT
AMPACITY/VOLTAGE
CIRCUIT
LENGTH
CONDUCTOR SIZE
(PHASE, NEUTRAL AND GR) CONDUIT SIZE
20A/120V 0' - 60' #12 AWG 0.75" Ø
20A/120V 60' - 95' #10 AWG 0.75" Ø
20A/120V 95' - 150' #8 AWG 1" Ø
20A/120V 150' - 240' #6 AWG 1.25" Ø
20A/277V 0' - 140' #12 AWG 0.75" Ø
20A/277V 140' - 220' #10 AWG 0.75" Ø
20A/277V 220' - 350' #8 AWG 1" Ø
20A/277V 350' - 550' #6 AWG 1.25" Ø
1.
2.
3.
NOTES:
WIRE SIZING IS BASED ON COPPER CONDUCTORS SUPPLYING A 20A,
120V CIRCUIT AT THE INDICATED VOLTAGE, ASSUMED TO BE 80%
LOADED (16A), WITH MAXIMUM VOLTAGE DROP OF 3% AT THE LOAD.
DOWN-SIZED WIRE AT DEVICE/LOAD AS REQUIRED AND TERMINATE
CONDUCTORS IN A SAFE AND CODE COMPLIANT MANNER.
CONDUIT SIZE IS BASED ON A MAXIMUM OF 3 CIRCUITS PER CONDUIT,
EACH WITH A SEPARATE NEUTRAL CONDUCTOR.
BRANCH CIRCUIT CONDUCTOR
AND CONDUIT SIZING TABLE
1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH MODIFICATIONS
AS NOTED IN NOTE 5. ALL CONDUCTORS SHOWN ARE THWN UNLESS
OTHERWISE NOTED.
2. PROVIDE EQUIPMENT GROUND CONDUCTORS PER TABLE 250-122 WHEN
CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING SHOWN IN
TABLE.
3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING
COMPUTERS.
4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE
CONDUCTORS.
5. SYMBOL SUBSCRIPTS:
6. RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.
8/7/2026
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
SPD GFI
1600/ 3
SECT
400/3 "1K" "1K"
400/3
800/ 3
100/3
EX
100/3
"1HA"
100/3
EX
100/3
"1HB"
100/3
EX
100/3
"2HA"
150/3
EX
150/3
"MP1"
200/3
EX
200/3
"MP2"
800/ 3
100/3
EX
100/3
"1A"
150/3
EX
150/3
"1B"
200/3
EX
200/3
"1C"
100/3
"1D"
100/3
EX
100/3
"1E"
100/3
EX
100/3
"1H"
100/3
EX
100/3
"1I"
100/3
EX
100/3
"2A"
GROUND
PER NEC
XFMR "TLGN"
150kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
#4/0 CU
100/3
100/3
"LF"
225/3
"LG"
SPD
600/ 3
100/3
"L"
100/3
"EM"
GROUND
PER NEC
XFMR "T1"
225kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
#4/0 CU
600/ 3
400/3
400/3
"WSC"
400/3
400/3
"WSA"
400/3
400/3
"WSD"
250/3
250/3
"HD"
600/3
600/3
"3HA"
250/3
250/3
"HKP"
400/3
400/3
"WSB"
225/3
225/3
"E"
600/3
600/3
"1CSL"
80/3
"2D"
SECT
200/3 "K2" "K2"
200/3
100/3
EX
100/3
"1-P"
200/3
EX
200/3
"2B.1"
ARCH/ENG
CLASS
100/3
EX
100/3
"2B.2"
COSMO
100/3
EX
100/3
"2F"
225/3
GROUND
PER NEC
XFMR "TCN"
300kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
#4/0 CU
GROUND
PER NEC
(EX) "XFMR"
75kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
#4/0 CU
100/3
"LA-2"
50/3
"LD"
50/3
"LW"
125/3
175/3
GROUND
PER NEC
"XFMR-TCP (HB)"
112.5kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
#4/0 CU
GROUND
PER NEC
"XFMR-TB"
75kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
225/3
225/3
"G"
225/3
225/3
"I"
225/3
225/3
"A"
SECT
225/3 "B" "B"
225/3
SECT
400/3 "D" "D"
400/3
SECT
400/3 "C" "C"
400/3
225/3
"LB"
400/3
"LC"
225/3
"HB"
250/3
"LCP"
SPD
GROUND
PER NEC
(EX) "XFMR"
75kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
#4/0 CU
100/3
"SP"
GROUND
PER NEC
"XFMR-T1"
75kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
100/3
"P"
GROUND
PER NEC
"XFMR-T2"
75kVA 480-208Y/120V 3Ø, 4W
DELTA/ WYE
200/3
400/3
"2"
22/3
400/3
"N"
125/3
400/3
"WSC"
400/3
400/3
"L"
50/3
EX
50/3
"1G"
80/3
EX
80/3
"2E"
COSMO
12470-480Y/277V 3Ø, 4W
FROM KCP
SECTIONALIZER
"MDP2000"
EXISTING MAIN SWITCH BOARD
2000A 480/277 3⌀, 4W, 65,000AIC
SE
400/3
FRS-R-225
IG
400/3
LPJ-400
IG
EXISTING "MDP-1"
800A 480/277 3⌀, 4W, 30,000 AIC
350/3SPACE SPACE
(EX) "T-MDP-2"
225 KVA
480-208/120V 3⌀, 4W
EXISTING "MDP-2"
800A 208/120 3⌀, 4W, 30,000 AIC
EX
EX
MAU-1MAU-1
800/3
400/3 250/3
300/3
NEXT TO RM 1053
400/3
SPARE
200KVAR, 8 STEP
AUTO POWER
FACTOR
CORRECTION
CAPACITOR
CABINET
PROVIDE
CAPACITOR
SYSTEMS TO
ACHEIVE 95%
POWER FACTOR
400/3
SPARE
100/3
SPARE
"XFMR - APP"
12470-480Y/277V 3Ø, 4W
FROM KCP
SCETIONALIZER
EX
EX
20/1 X13
SPARE
60/3
TO
RTU
60/3
TO
RTU
50/3
TO
UNKNOWN
EXISTING
LOAD
100/3
100/3 15/3
TO TOOL
GRINDER
20/3
TO
EDM
20/3
TO
LATHE
"HDP-A"
EXISTING DISTRIBUTION SWITCH BOARD
600A 480/277 3⌀, 4W, 65,000AIC
350/3
20/3 X6
SPARE
20/3
TO BROWN
& SHARPE
GRINDER
225/3
SPARE
400/3
SPARE
150/3
SPARE
150/3
SPARE
80/3
TO
MAZAK
VTC 16
50/3
TO AIR
COMP
20/3
TO
BAND
SAW
20/1 X3
SPARE
400/3
SPARE
20/3
TO
GROB
BAND
SAW
100/3
TO
SHIZOKA
20/1
TO
POWERMATIC
GRINDER
20/2
TO DO
ALL
GRINDER
50/1
SPARE
GROUND BUS
NEUTRAL BUS
TO EXISTING
GROUNDING
SYSTEM
GROUND BUS
NEUTRAL BUS
TO EXISTING
GROUNDING
SYSTEM
SEC 01 SEC 03
EXISTING PANEL "LDP-D"
208/120V, 3PH, 4W
600A MCB, 10,000AIC
IG
200/3
LPJ-400
IG
EX
400/3 700/3
400/3
350/3 125/3
SPARE
800/3
100/3 50/3
50/3 350/3
SE
SE
800/3
400/3 400/3
SE
225/3
225/3225/3 225/3
400/3
400/3
125/3 400/3
800/3
ELEV1ELEV1
150A
SEC 02
600/3400/3
SPARE
250/3 X4
SPARE
250/3 X4
SPARE
60/3TVSS
50/3200/3150/3100/3100/3100/3 225/3 350/3
200/3100/3 100/3 100/3 100/3 100/3 100/3 100/3 100/3 80/3 100/380/3200/3150/3
EXISTING PANEL "F"
208/120V, 3PH, 4W
800A MCB, 20,000AIC
"H" 277/480V
3PH, 4W, 400A
"LDP" 277/480V
3PH, 4W, 800A
"HA" 277/480V
3PH, 4W, 400A
"LA-1 SEC.1"
120/208V
3PH, 4W, 800A
8 8 8 8 8
8 8 8 8 8 8
8 8 8 8 8 8 8 8 8 8 8 8 8
JUNCTION BOX
OUTSIDE OF SHOP
EX 8
8EX
200/3
SLOT
200/3
SLOT
M 12
324 S. State St., Suite 400 Salt Lake City, UT 84111
800-678-7077 801-328-5151 www.lynkengineers.com
Kobayashi
5497590-2202 Christopher Kelly
L
IC
EN
S E
D
PROF E S S I ONA L
ENG
I NEER
S T A T E O F U T A H
No.
IND
USTRY
TH
E
G R E A T
SE
AL
OF THE
STATE
O F
U
TA
H
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 LYNK ENGINEERS, LLC.
SHEET TITLE
PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
DFCM APPROVAL STAMP
4110 STATE OFFICE BLDG
SALT LAKE CITY, UT 84112
DFCM
7/31/2026
DFCM PROJECT NO:
Au to de sk
D oc s:
//2
6-
- D av is T ec h
- P an el
T ra ns fo rm er
R ep la ce m en t/2 6-
- E le cC en tra l.r vt
8/
/2
6:
:1
PM
KAK
LSK
KAK
26-00536
AUG 7, 2026
CONSTRUCTION
DOCUMENTS
DEMOLITION
ONE-LINE DIAGRAM -
MAIN BUILDING - 1 OF
E602
DAVIS
TECHNICAL
COLLEGE
ELECTRICAL
TRANSFORMER
AND PANEL
REPLACEMENT
- PHASE 1
550 E 300 S, Kaysville, UT 84037
27048220
GENERAL SHEET NOTES
1 REFER TO EP601 FOR FEEDER SCHEDULE.
2 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
3 ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC
CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND PROVIDE FULL
SCOPE OF WORK AS REQUIRED.
5 PROTECT AND MAINTAIN ALL EXISTING EQUIPMENT UNLESS NOTED OTHERWISE.
6 NO PIGTAIL SPLICING ALLOWED, PROVIDE SHAWMUT TERMINATIONS FOR ALL
SPLICES BETWEEN NEW AND EXISTING CABLING. EXTEND ALL CABLING TO NEW
PANELBOARD LOCATION,
7 CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND REPAIR FLOOR, CARPET,
WALLS, CEILINGS AND FINISHES BACK TO EXISTING CONDITIONS.
8 DEMOLISH ALL ABANDONED CABLING BETWEEN SOURCE AND LOAD
9 TRACE OUT ALL EXISTING LOADS THAT ARE UNKNOWN AND UPDATE PANEL
SCHEDULE TO REFLIECT ACTUAL LOAD DATA
SHEET KEYNOTES
1 DEMOLISH EXISTING PANEL BOARD, PROTECT AND MAINTAIN EXISTING BRANCH
CIRCUITS, BRANCH CIRCUITS TO BE RE-TERMINATED ON NEW PANEL BOARD.
TRACE EXISTING BRANCH CIRCUITS AND PROVIDE LABEL FOR SOURCE OF POWER
ON RECEPTACLES POWERED FROM PANELBOARD. CONTRACTOR TO TRACE
UNKNOWN CIRCUITS AND UPDATE PANEL SCHEDULE. ASSUME 15 CIRCUITS WILL
NEED TO BE TRACED. ADD LABELS TO ALL…