H1-Final_Construction_Documents_-_Plans_USMS_Sec_Barrier.pdf
PDF 8 MB Posted
- Attached to
- USMS Security Barrier Replacement Federal contract opportunity
- Solicitation number
- 47PF0019R0010
About this file
USMS Security Barrier Project-Plans
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_3-Updated_SF1442-14b.pdf | ||
| Amendment_03-Updated_Snow_Melt_Dwgs_and_Cost_Breakdown.pdf | ||
| Attachment_1-ESL_Snow_Melt_Dwg_Add._2_Final_3.14.19_(1).pdf | ||
| Attachment_2-Revise_Contract_Price_Form.docx | DOCX document | |
| Amendment_02-ESL_USMS_Security_Barrier.pdf | ||
| Amendment_01-USMS_Security_Barrier_Replacement-GC-1.pdf | ||
| Attachment_3-Final_ESL_Snow_Melt_Dwg_2.27.18.pdf | ||
| Attachment_2-GSA_Security_Barrier_Replacement_Div_22_&_23_Specs.pdf | ||
| Attachment_1-GSA_Security_Barrier_Upgrade_Rev._1_Construction_Documents_-_Plans.pdf | ||
| RFP_47PF00-19R-0010.pdf | ||
| H2-Final_Construction_Documents_-_Specifications_USMS_Sec_Barrier.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
GI001
MELVIN PRICE FEDERAL COURTHOUSE
USMS SECURITY
BARRIER REPLACEMENT
FINAL CONSTRUCTION DOCUMENTS
Contact: Contact:
MELVIN PRICE FEDERAL
COURTHOUSE
Brett Etling Project COR
508 South Eighth Street.
East St. Louis, IL 62201 p: 217.801.9743 e: brett.etling@gsa.gov
OWNER
GUIDON DESIGN
INC.
Stacey Paul Project Engineer Project PM
905 North Capitol Avenue Suite 100 Indianapolis, IN 46204 p: 317.800.6388 x 104 e: spaul@guidondesign.com
CIVIL ENGINEER
VICINITY MAP
LOCATION MAP
N
PROJECT LOCATION
N
MECHANICAL &
ELECTRICAL
BCCLT, CONSULTING
ENGINEERS
James E. Meadows Senior Electrical Engineer
9100 Marksfield Rd.
#200 Louisville, KY 40222 p: 812.423.4407 e: meadows@bcclt.com
Contact:
U.S. COURTHOUSE
SHEET LIST
SHEET NUMBER SHEET NAME
MELVIN PRICE FEDERAL BUILDING
PROJECT LOCATION
GENERAL
GI001 COVER SHEET
GI002 GENERAL NOTES
GI003 PHASING PLAN
CIVIL
CD101 DEMOLITION PLAN
CS101 SITE PLAN - NEW WORK
CS102 LOOP DETECTOR LAYOUT PLAN - NEW WORK
CS501 SITE DETAILS
CS502 RAM-PROOF BARRIER GATE DETAILS - NEW WORK
CG101 GRADING PLAN - NEW WORK
EP101 ELECTRICAL LEGEND & DEMOLITION PLAN
EP102 ELECTRICAL POWER PLAN - NEW WORK
EP103 ELECTRICAL DETAILS
GREAT LAKES REGION 5
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
CONTRACTOR
STAGING/STORAGE
AREA
GENERAL NOTES
GI002
GREAT LAKES REGION 5
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
GREAT LAKES REGION 5
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
0 2010
N
GI003
PHASING PLAN
0 2010
N
DEMOLITION PLAN
CD101
GREAT LAKES REGION 5
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
0 2010
N
CS101
SITE PLAN - NEW WORK
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
0 2010
N
CS102
LOOP DETECTOR LAYOUT PLAN - NEW WORK
LOOP DETECTOR LAYOUT PLAN - NEW WORK
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
SITE DETAILS
CS501
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
CS502
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
GSA SECURITY UPGRADE
750 MISSOURI AVENUE
MELVIN-PRICE FEDERAL BUILDING
DSM
BRETT ETLING
10-10-2018
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
CIVIL
EAST SAINT LOUIS IL 62201
30" X 42"
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
0 2010
N
CG101
GRADING PLAN - NEW WORK
GRADING PLAN - NEW WORK
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BYDATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N
TR
A C
TO
R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
MELVIN-PRICE FEDERAL BUILDING
BRETT ETLING
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
750 EAST MISSOURI AVE.
EAST SAINT LOUIS
GSA SECURITY UPGRADE
10-10-2018
30x42
IL 62201
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
ELECTRICAL LEGEND & DEMOLITION PLAN
JEM
L1 ELEC
EP101
S
TAT E OF I L L I N
O I S
A E
S E EAOS
EISTEE
OFESSIONAL
ENINEE
OF
AutoCAD SHX Text
NOTE 1
AutoCAD SHX Text
NOTE 1
AutoCAD SHX Text
CAMERA
AutoCAD SHX Text
CAMERA
AutoCAD SHX Text
HYDRAULIC
AutoCAD SHX Text
PUMP, NOTE 5
AutoCAD SHX Text
%%UGARAGE
AutoCAD SHX Text
%%UPARKING
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
INTERCOM RACEWAY
AutoCAD SHX Text
AND CABLING TO
AutoCAD SHX Text
REMAIN FOR REUSE.
AutoCAD SHX Text
%%UDRIVE
AutoCAD SHX Text
%%USTREET
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text
SUMP PUMP, NOTE 3
AutoCAD SHX Text C
AutoCAD SHX Text
EP101
AutoCAD SHX Text
INTERCOM PEDESTAL NOTE 6
AutoCAD SHX Text S
AutoCAD SHX Text
SECURITY BOLLARD REMOTE CONTROL, NOTE 9
AutoCAD SHX Text
SWITCH FOR BOLLARD HEAT TAPE; NOTE 8
AutoCAD SHX Text EXIST. PANEL `RBL-1Bb'
AutoCAD SHX Text
OVERHEAD DOOR CONTROLLER
AutoCAD SHX Text
HYDRAULIC LINE & POWER JUNCTION BOX, NOTE 4
AutoCAD SHX Text
INTERCOM & CARD READER PEDESTAL, NOTE 6
AutoCAD SHX Text
POST MOUNTED WARNING LIGHT, NOTE 5
AutoCAD SHX Text
POST MOUNTED WARNING LIGHT, NOTE 5
AutoCAD SHX Text
OVERHEAD DOOR
AutoCAD SHX Text
UNDERGROUND CONDUITS, NOTE 2
AutoCAD SHX Text
GUARD SHACK
AutoCAD SHX Text
HYDRAULIC BOLLARDS, TYP.
AutoCAD SHX Text
EP101
AutoCAD SHX Text
EP101
AutoCAD SHX Text
GUARD SHACK FLOOD LIGHT, NOTE 10
AutoCAD SHX Text
GUARD SHACK FLOOD LIGHT, NOTE 10
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
%%UELECTRICAL DEMOLITION PLAN
AutoCAD SHX Text A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE BUILDING AND SITE THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE BUILDING AND SITE TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS, VERIFY SIZE, LOCATION, AND USAGE OF UTILITIES AND EQUIPMENT PRIOR TO CONSTRUCTION. B. ALL EQUIPMENT REMOVED FOR RELOCATION SHALL BE REMOVED IN SUCH A ALL EQUIPMENT REMOVED FOR RELOCATION SHALL BE REMOVED IN SUCH A MANNER THAT REUSE IS POSSIBLE. C. PATCH ALL OPENINGS IN WALLS, FLOORS, AND CEILINGS WHERE REMOVAL OF PATCH ALL OPENINGS IN WALLS, FLOORS, AND CEILINGS WHERE REMOVAL OF EQUIPMENT OR DEVICES CREATES SUCH OPENINGS. PATCH OPENINGS TO MATCH EXISTING. D. IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN MUST BE RELOCATED IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN MUST BE RELOCATED OR REMOVED DUE TO INTERFERENCE WITH NEW EQUIPMENT INSTALLATION, THE CIRCUITS SHALL BE MODIFIED IN SUCH A MANNER WHICH WILL ENSURE THE PROPER OPERATION OF THE EQUIPMENT AFTER CONSTRUCTION IS COMPLETE, USE THE SAME TYPE OF CONDUCTOR AND SAME CONDUIT SIZE AS EXISTING TO MAKE ALL REQUIRED MODIFICATIONS. E. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS REQUIRED FOR THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS REQUIRED FOR THE INSTALLATION OF NEW WORK, WHETHER OR NOT IT IS SPECIFICALLY INDICATED OR NOTED IN THESE DOCUMENTS. F. ALL CONDUIT RUNS TO REMOVED EQUIPMENT OR DEVICES SHALL BE COMPLETELY ALL CONDUIT RUNS TO REMOVED EQUIPMENT OR DEVICES SHALL BE COMPLETELY REMOVED BACK TO SOURCE, INCLUDING ALL HANGERS, BEAM CLAMPS, MISCELLANEOUS SUPPORTS, AND WIRING. G. COORDINATE CONDUIT ROUTING WITH EXISTING EQUIPMENT TO AVOID CONFLICTS COORDINATE CONDUIT ROUTING WITH EXISTING EQUIPMENT TO AVOID CONFLICTS WITH EQUIPMENT AND EQUIPMENT CLEARANCE. H. SEAL AROUND ALL WALL PENETRATIONS WITH FIRE STOPPING. SEAL AROUND ALL WALL PENETRATIONS WITH FIRE STOPPING. I. BRANCH CIRCUIT NEUTRAL CONDUCTORS SHALL NOT BE SHARED WITH ANOTHER BRANCH CIRCUIT NEUTRAL CONDUCTORS SHALL NOT BE SHARED WITH ANOTHER CIRCUIT. J. EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH A GREEN EQUIPMENT EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH A GREEN EQUIPMENT GROUNDING CONDUCTOR.
AutoCAD SHX Text
1. DISCONNECT AND REMOVE POWER TO GATE ARM DISCONNECT AND REMOVE POWER TO GATE ARM EQUIPMENT. 2. EXISTING CONDUITS FOR POWER AND COMMUNICATIONS TO EXISTING CONDUITS FOR POWER AND COMMUNICATIONS TO GUARD SHACK; (1) 2"C FOR POWER AND (2) 2"C FOR COMMUNICATIONS. DO NOT DISTURB CONDUITS. 3. DISCONNECT AND REMOVE POWER SERVING SUMP PUMP. DISCONNECT AND REMOVE POWER SERVING SUMP PUMP. 4. REMOVE PULL BOX AND ASSOCIATED CONDUIT AND WIRING. REMOVE PULL BOX AND ASSOCIATED CONDUIT AND WIRING. 5. DISCONNECT AND REMOVE POWER TO EQUIPMENT. DISCONNECT AND REMOVE POWER TO EQUIPMENT. 6. DISCONNECT POWER FROM PEDESTAL. DISCONNECTION AND DISCONNECT POWER FROM PEDESTAL. DISCONNECTION AND REMOVAL OF SECURITY SYSTEM DEVICES AND CABLING SHALL BE BY GOVERNMENT SECURITY VENDOR. 7. REMOVE PEDESTAL AFTER GOVERNMENT VENDOR REMOVES REMOVE PEDESTAL AFTER GOVERNMENT VENDOR REMOVES SECURITY DEVICES AND CABLING. 8. DISCONNECT AND REMOVE SWITCH AND ASSOCIATED WIRING DISCONNECT AND REMOVE SWITCH AND ASSOCIATED WIRING AND RACEWAYS FOR BOLLARD HEAT TAPE. 9. DISCONNECT AND REMOVE HYDRAULIC BOLLARD REMOTE DISCONNECT AND REMOVE HYDRAULIC BOLLARD REMOTE CONTROL STATION AND ASSOCIATED WIRING AND RACEWAYS AT THIS LOCATION AND IN THE SECURITY CONTROL ROOM. 10. REMOVE GUARD SHACK FLOOD LIGHTING FIXTURE FOR REMOVE GUARD SHACK FLOOD LIGHTING FIXTURE FOR REPLACEMENT. CIRCUIT TO REMAIN FOR REUSE. SEE EP102 FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
%%UGENERAL ELECTRICAL NOTES:
AutoCAD SHX Text
%%UDEMOLITION NOTES:
AutoCAD SHX Text
ELECTRICAL LEGEND
AutoCAD SHX Text
WORKING CLEARANCE
AutoCAD SHX Text
NP-1,3,5
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CONDUCTORS
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
INDICATE NUMBER OF CONDUCTORS REQUIRED. CONDUIT
AutoCAD SHX Text
CIRCUIT CONCEALED IN CEILING OR WALL. CROSSBARS
AutoCAD SHX Text
HOMERUN TO PANELBOARD INDICATED. NUMBER OF
AutoCAD SHX Text
ARROWHEADS INDICATES NUMBER OF CIRCUITS. NUMBER
AutoCAD SHX Text
NOT SIZED IS Ô", CONDUCTORS NOT SIZED ARE #12 AWG.
AutoCAD SHX Text
INDICATES CIRCUIT NUMBERS. PREFIX INDICATES PANEL
AutoCAD SHX Text
SURFACE MOUNTED PANELBOARD.
AutoCAD SHX Text
TRANSFORMER.
AutoCAD SHX Text
SOLIDLY GROUNDED WYE CONNECTION.
AutoCAD SHX Text
DELTA CONNECTION.
AutoCAD SHX Text
CIRCUIT BREAKER.
AutoCAD SHX Text
SWITCH AND FUSE UNIT.
AutoCAD SHX Text
SWITCH.
AutoCAD SHX Text
FUSE.
AutoCAD SHX Text
POINT OF CONNECTION NEW TO EXISTING.
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
NUMBER.
AutoCAD SHX Text
FUSIBLE DISCONNECT SWITCH. MOUNT 4'-6" A.F.F. TO CENTER, UNLESS NOTED
AutoCAD SHX Text
OTHERWISE.
AutoCAD SHX Text
FUSE.
AutoCAD SHX Text
CONDUIT EXPOSED.
AutoCAD SHX Text
CONDUIT CONCEALED BENEATH GROUND.
AutoCAD SHX Text
WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE. MOUNT AT 16" A.F.F. TO BOTTOM,
AutoCAD SHX Text
UNLESS NOTED OTHERWISE. 'GFI' SUBSCRIPT INDICATES GROUND FAULT CURRENT
AutoCAD SHX Text
INTERRUPTER.
AutoCAD SHX Text
SINGLE POLE 20A SPECIFICATION GRADE TOGGLE SWITCH. MOUNT 44" A.F.F. TO
AutoCAD SHX Text
BOTTOM, NOTED OTHERWISE.
AutoCAD SHX Text S
AutoCAD SHX Text
NUMBER AT OUTLET INDICATES CIRCUIT ARRANGEMENT.
AutoCAD SHX Text "1,2,3"
AutoCAD SHX Text
LOWER CASE LETTERS AT OUTLETS INDICATE SWITCHING ARRANGEMENTS.
AutoCAD SHX Text a,b,c
AutoCAD SHX Text
E-XXX
AutoCAD SHX Text
AutoCAD SHX Text
PHOTOGRAPH VIEW. # INDICATES PHOTOGRAPH NUMBER. EXXX INDICATES
AutoCAD SHX Text
PHOTOGRAPH SHEET/DRAWING REFERENCE.
AutoCAD SHX Text
GFI
AutoCAD SHX Text
INDICATES GROUND FAULT CIRCUIT INTERRUPTER.
AutoCAD SHX Text
EX
AutoCAD SHX Text
INDICATES EXISTING WHEN SHOWN NEXT TO DEVICE.
AutoCAD SHX Text A.F.F.
AutoCAD SHX Text
ABOVE FINISHED FLOOR.
AutoCAD SHX Text
%%USYMBOL
AutoCAD SHX Text
%%UDESCRIPTION
AutoCAD SHX Text
%%USYMBOL
AutoCAD SHX Text
%%UDESCRIPTION
AutoCAD SHX Text
SECURITY SYSTEM CAMERA. CAMERA AND ASSOCIATED WIRING IS BY GOVERNMENT.
AutoCAD SHX Text
WALL MOUNTED JUNCTION BOX, MOUNT 16" A.F.F. TO BOTTOM,
AutoCAD SHX Text
UNLESS NOTED OTHERWISE.
AutoCAD SHX Text J
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text A
AutoCAD SHX Text
%%UPHOTO
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text B
AutoCAD SHX Text
%%UPHOTO
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text C
AutoCAD SHX Text
%%UPHOTO
AutoCAD SHX Text
OVERHEAD DOOR CONTROLLER
AutoCAD SHX Text
HYDRAULIC PUMP
AutoCAD SHX Text
HYDRAULIC LINE & POWER JUNCTION BOX
AutoCAD SHX Text
HYDRAULIC LINE & POWER JUNCTION BOX
AutoCAD SHX Text
SECURITY BOLLARD REMOTE CONTROL
AutoCAD SHX Text
SWITCH FOR BOLLARD HEAT TAPE
AutoCAD SHX Text
INTERCOM PEDESTAL
AutoCAD SHX Text PANEL RBL-1Bb
AutoCAD SHX Text A
AutoCAD SHX Text
LIGHTING FIXTURE TYPE.
AutoCAD SHX Text
POLE LIGHT COMPLETE WITH POLE, BRACKETS REQUIRED NUMBER OF LIGHTING FIXTURES,
AutoCAD SHX Text
REINFORCED CONCRETE FOUNDATION, AND ALL ACCESSORIES AS SCHEDULED.
AutoCAD SHX Text
PTZ SUBSCRIPT INDICATES PAN-TILT-ZOOM TYPE.
AutoCAD SHX Text 10-10-2018
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BYDATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N
TR
A C
TO
R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
MELVIN-PRICE FEDERAL BUILDING
BRETT ETLING
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
750 EAST MISSOURI AVE.
EAST SAINT LOUIS
GSA SECURITY UPGRADE
10-10-2018
30x42
IL 62201
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
ELECTRICAL POWER PLAN - NEW WORK
JEM
L1 ELEC
EP102
S
TA T E OF I L L I N
OFESSIONAL
ENINEE
OF
AutoCAD SHX Text
CAMERA
AutoCAD SHX Text
CAMERA
AutoCAD SHX Text
EXISTING UG CONDUITS
AutoCAD SHX Text
FOR GUARD SHACK
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
POWER & COMMUNICATIONS.
AutoCAD SHX Text
PANEL
AutoCAD SHX Text RBL-1Bb
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text J
AutoCAD SHX Text +96"
AutoCAD SHX Text +96"
AutoCAD SHX Text
MONITOR
AutoCAD SHX Text
EXISTING CONDUITS FOR
AutoCAD SHX Text
GUARD SHACK POWER
AutoCAD SHX Text
AND COMMUNICATIONS
AutoCAD SHX Text
NOTE 6
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text
COMMUNICATIONS
AutoCAD SHX Text
(2) 2"C FOR
AutoCAD SHX Text
POWER CIRCUIT
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
1"C BACK TO
AutoCAD SHX Text
SECURITY OFFICE
AutoCAD SHX Text
NOTE 3
AutoCAD SHX Text
NOTE 7
AutoCAD SHX Text J
AutoCAD SHX Text RBL-1Bb-19
AutoCAD SHX Text J
AutoCAD SHX Text 8"x8"J-BOX
AutoCAD SHX Text
EXISTING OVERHEAD DOOR
AutoCAD SHX Text
2"C. TO SECURITY OFFICE, NOTE 12
AutoCAD SHX Text
JUNCTION BOX FOR VIDEO MONITOR
AutoCAD SHX Text RBL-1Bb-14
AutoCAD SHX Text
NOTE 11
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
NOTE 10
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text 3#10,1#10G 3/4"C
AutoCAD SHX Text RBL-1Bb-2, 3#10,1#10G 3/4"C
AutoCAD SHX Text RBL-1Bb-8, 3#10,1#10G 3/4"C
AutoCAD SHX Text
EXISTING OVERHEAD DOOR CONTROLLER
AutoCAD SHX Text
SECURITY GATE BACK-UP POWER INVERTER
AutoCAD SHX Text POWER HANDHOLE 11"Wx18L"x12"D, NOTE 15
AutoCAD SHX Text COMMUNICATION HANDHOLE 24"Wx18L"x12"D, NOTE 15
AutoCAD SHX Text
SECURITY BARRIER PIVOT POST, NOTE 4
AutoCAD SHX Text
COMM/SECURITY SYSTEM CONDUIT, 1"C
AutoCAD SHX Text RBL-1Bb-19, 3#10,1#10G,3/4"C
AutoCAD SHX Text RBL-1Bb-8, 3#10,1#10G,1"C RBL-1Bb-19
AutoCAD SHX Text
NOTE 5
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text
NOTE 9
AutoCAD SHX Text
NOTE 8
AutoCAD SHX Text
COMM/SECURITY SYSTEM CONDUIT, 2"C
AutoCAD SHX Text
NOTE 9
AutoCAD SHX Text
NOTE 8
AutoCAD SHX Text
NOTE 5
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text
SECURITY BARRIER PIVOT POST, NOTE 4
AutoCAD SHX Text RBL-1Bb-2, 3#10, 1#10G, 1"C
AutoCAD SHX Text
CATCH BLOCK
AutoCAD SHX Text
ACCESS CONTROL PEDESTAL, NOTES 1,2
AutoCAD SHX Text
LOOP DETECTOR, TYP.
AutoCAD SHX Text
GUARD SHACK PANEL
AutoCAD SHX Text
ACCESS CONTROL PEDESTAL; NOTES 1,2
AutoCAD SHX Text C1
AutoCAD SHX Text C2
AutoCAD SHX Text C3
AutoCAD SHX Text C4
AutoCAD SHX Text
C5 PTZ
AutoCAD SHX Text B
AutoCAD SHX Text
PS
AutoCAD SHX Text B
AutoCAD SHX Text
PS
AutoCAD SHX Text
EX
AutoCAD SHX Text H
AutoCAD SHX Text
GUARD SHACK
AutoCAD SHX Text A
AutoCAD SHX Text HANDHOLE 11"Wx11L"x12"D, NOTES 15,16
AutoCAD SHX Text
EXIST SITE LTG CIRCUIT, NOTE 18
AutoCAD SHX Text
NOTE 17
AutoCAD SHX Text
RELACE WIRING AS REQUIRED
AutoCAD SHX Text
CCTV SYSTEM CONDUIT, 1"C
AutoCAD SHX Text H
AutoCAD SHX Text HANDHOLE 11"Wx11L"x12"D, NOTES 15,16
AutoCAD SHX Text
1"C TO SECURITY OFFICE; NOTE 12
AutoCAD SHX Text
LOOP DETECTOR, TYP.
AutoCAD SHX Text
NOTE 20
AutoCAD SHX Text
EXIST J-BOX
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
LOOP WIRES
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
C6 PTZ
AutoCAD SHX Text
NEW CAMERA. CENTER ABOVE DOOR
AutoCAD SHX Text J
AutoCAD SHX Text
NEW CAMERA
AutoCAD SHX Text
NEW CAMERA
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text
NOTE 23
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text
NOTE 24
AutoCAD SHX Text
NOTE 24
AutoCAD SHX Text
NOTE 24
AutoCAD SHX Text H
AutoCAD SHX Text
NOTE 24
AutoCAD SHX Text H
AutoCAD SHX Text
NOTE 24
AutoCAD SHX Text H
AutoCAD SHX Text
NOTE 24
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text
NOTE 13
AutoCAD SHX Text H
AutoCAD SHX Text
NOTE 25
AutoCAD SHX Text H
AutoCAD SHX Text
NOTE 25
AutoCAD SHX Text RBL-1Bb-19
AutoCAD SHX Text RBL-1Bb-19
AutoCAD SHX Text C
AutoCAD SHX Text
NOTE 23
AutoCAD SHX Text
PANEL
AutoCAD SHX Text RBL-1Bb
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
SHACK
AutoCAD SHX Text
GUARD
AutoCAD SHX Text
READER PEDESTAL
AutoCAD SHX Text
INTERCOM/CARD
AutoCAD SHX Text
BARRIER
AutoCAD SHX Text
SECURITY
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
SECURITY
AutoCAD SHX Text
JUNCTION
AutoCAD SHX Text
BOX
AutoCAD SHX Text
UP
AutoCAD SHX Text 253.00'(R)
AutoCAD SHX Text
BARRIER
AutoCAD SHX Text
SECURITY
AutoCAD SHX Text
INTERCOM/ CARD READER PEDESTAL
AutoCAD SHX Text
CONDUIT FOR PEDESTAL AND MONITOR COMM/LV CONDUCTORS, NOTE 12
AutoCAD SHX Text
EXIST. GUARD SHACK POWER CONDUIT
AutoCAD SHX Text
EXIST. GUARD SHACK COMM. CONDUITS
AutoCAD SHX Text
CONDUIT SECURITY GATE COMM/LV CONDUCTORS, NOTE 12
AutoCAD SHX Text
ELECT. RM.
AutoCAD SHX Text
NOTE 21
AutoCAD SHX Text
NOTE 22
AutoCAD SHX Text
EXISTING GUARD SHACK POWER AND COMM CONDUITS
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
%%UELECTRICAL POWER PLAN - NEW WORK
AutoCAD SHX Text A. REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR ADDITIONAL DETAILS AND REQUIREMENTS. B. ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE PER GOVERNMENT STANDARD. PROVIDE PULL STRING IN CONDUIT.
AutoCAD SHX Text
1. CARD READER STATION, INTERCOM STATION, AND DURESS ALARM STATION CARD READER STATION, INTERCOM STATION, AND DURESS ALARM STATION ON PEDESTAL. DEVICES AND CABLING SHALL BE PROVIDED BY GOVERNMENT SECURITY VENDOR. 2. PROVIDE (1) TYPE B LIGHTING FIXTURE AND ASSOCIATED STEP DOWN PROVIDE (1) TYPE B LIGHTING FIXTURE AND ASSOCIATED STEP DOWN TRANSFORMER FOR ACCESS CONTROL STAND LIGHTING. MOUNT TO UNDERSIDE OF TOP LIP OF WEATHERSHIELD FACING PEDESTAL FRONT. 3. PROVIDE (1) 1" CONDUIT WITH PULL STRING TO SECURITY OFFICE. CONDUIT PROVIDE (1) 1" CONDUIT WITH PULL STRING TO SECURITY OFFICE. CONDUIT FOR CARD READER CABLING. 4. WIRE SECURITY GATE EQUIPMENT PER MANUFACTURER'S SPECIFICATIONS. WIRE SECURITY GATE EQUIPMENT PER MANUFACTURER'S SPECIFICATIONS. PROVIDE ALL REQUIRED RACEWAYS AND CABLING. 5. PROVIDE 5/8"x 8"L GROUND ROD PER MANUFACTURER'S SPECIFICATIONS. PROVIDE 5/8"x 8"L GROUND ROD PER MANUFACTURER'S SPECIFICATIONS. CONNECT TO PIVOT POST GROUND ROD CONNECTOR WITH 1#6 GROUND. WIRE LENGTH SHALL NOT EXCEED 3 FEET. COORDINATE LOCATION WITH PIVOT POST FOOTING. 6. PROVIDE 12 FOOT HIGH POLE AND ASSOCIATED REINFORCED CONCRETE BASE PROVIDE 12 FOOT HIGH POLE AND ASSOCIATED REINFORCED CONCRETE BASE TO MOUNT SECURITY CAMERAS. MOUNT CCTV C4 AT 10 FOOT ABOVE FINISHED GRADE AND CCTV C5 AT 11 FOOT ABOVE FINISHED GRADE. 7. MODIFY/ EXTEND EXISTING INTERCOM RACEWAY AS REQUIRED. MODIFY/ EXTEND EXISTING INTERCOM RACEWAY AS REQUIRED. 8. PROVIDE CONDUIT FOR CATCH POST HEATER. REFER TO SECURITY GATE PROVIDE CONDUIT FOR CATCH POST HEATER. REFER TO SECURITY GATE GATE DETAIL `3' ON EP103. 9. PROVIDE CONDUIT FOR CATCH POST AUXILIARY DEVICES. REFER TO SECURITY PROVIDE CONDUIT FOR CATCH POST AUXILIARY DEVICES. REFER TO SECURITY GATE DETAIL '3' ON EP103. 10. RBL-1Bb-2: 3#10, 1#10G (GATE) RBL-1Bb-2: 3#10, 1#10G (GATE) RBL-1Bb-8: 3#10, 1#10G (GATE) RBL-1Bb-19: 2#10, 1#10G (PEDESTAL) 11. PROVIDE CONDUIT FITTING AND ROUTE DOWN FACE OF EXTERIOR WALL. SEAL PROVIDE CONDUIT FITTING AND ROUTE DOWN FACE OF EXTERIOR WALL. SEAL PENETRATION WATERTIGHT. EXISTING PENETRATIONS THROUGH WALL FOR REMOVED EQUIPMENT MAY BE USED TO THE EXTENT POSSIBLE. 12. SECURITY COMMUNICATIONS/LV CONDUCTORS SHALL BE PROVIDED BY SECURITY COMMUNICATIONS/LV CONDUCTORS SHALL BE PROVIDED BY GOVERNMENT SECURITY VENDOR. COORDINATE REQUIREMENTS WITH VENDOR. REQUIREMENTS WITH VENDOR. PROVIDE ALL REQUIRED CONDUIT. 13. PROVIDE (1) 1" CONDUIT FOR EACH VEHICLE LOOP WIRE. PROVIDE (1) 1" CONDUIT FOR EACH VEHICLE LOOP WIRE. 14. PROVIDE (1) 3/4" CONDUIT WITH PULL STRING FOR SECURITY PROVIDE (1) 3/4" CONDUIT WITH PULL STRING FOR SECURITY INTERCONNECTION TO OVERHEAD DOOR CONTROLLER. COORDINATE REQUIREMENTS WITH SECURITY VENDOR. 15. REFER TO HANDHOLE DETAILS `1' AND `2' ON EP103. REFER TO HANDHOLE DETAILS `1' AND `2' ON EP103. 16. INTERCEPT EXISTING SITE LIGHTING CIRCUIT AND EXTEND TO TYPE A POLE INTERCEPT EXISTING SITE LIGHTING CIRCUIT AND EXTEND TO TYPE A POLE LIGHT. PROVIDE HANDHOLE. MODIFY/EXTEND EXISTING CIRCUIT AS REQUIRED. WIRING CONNECTIONS WITHIN HANHOLE SHALL BE EPOXY FILLED FOR WATER TIGHT CONNECTIONS. 17. REFER TO DETAIL 4 POLE BASE DETAIL ON EP103. REFER TO DETAIL 4 POLE BASE DETAIL ON EP103. 18. VERIFY LOCATION OF EXISTING UNDERGROUND LIGHTING CIRCUIT. VERIFY LOCATION OF EXISTING UNDERGROUND LIGHTING CIRCUIT. 19. PROVIDE POWER SUPPLY FOR TYPE B LIGHTING FIXTURE. MOUNT TO PROVIDE POWER SUPPLY FOR TYPE B LIGHTING FIXTURE. MOUNT TO PEDESTAL BASE. ROUTE LOW VOLTAGE WIRING WITHIN PEDESTAL. 20. PROVIDE 1 INCH CONDUIT SLEEVE THROUGH WALL FOR PASSAGE OF TRAFFIC PROVIDE 1 INCH CONDUIT SLEEVE THROUGH WALL FOR PASSAGE OF TRAFFIC LOOP WIRES. COORDINATE REQUIREMENTS WITH LOOP WIRE PROVIDER. 21. ROUTE CONDUITS WITH PULL STRING CONCEALED ABOVE CEILING TO ABOVE ROUTE CONDUITS WITH PULL STRING CONCEALED ABOVE CEILING TO ABOVE EXISTING SECURITY FLOOR MOUNTED CABINETS. BUSH END OF CONDUITS. 22. ROUTE CONDUITS EXPOSED IN INMATE CORRIDOR. COORDINATE ROUTE WITH ROUTE CONDUITS EXPOSED IN INMATE CORRIDOR. COORDINATE ROUTE WITH EXISTING CONDUITS IN CORRIDOR. 23. MOUNT LIGHTING FIXTURE TO UNDERSIDE OF THE GUARD SHACK ROOF MOUNT LIGHTING FIXTURE TO UNDERSIDE OF THE GUARD SHACK ROOF OVERHANG AT LOCATIONS OF PREVIOUS FLOOD LIGHT FIXTURE. CONNECT TO EXISTING FLOOD LIGHT CIRCUIT. MODIFY/EXTEND WIRING AND RACEWAYS AS REQUIRED. 24. PROVIDE 12"X12" HANDHOLE AT EACH LOOP WIRE JUNCTION. REFER TO PROVIDE 12"X12" HANDHOLE AT EACH LOOP WIRE JUNCTION. REFER TO HANDHOLE DETAILS '1' AND '2' ON EP103. HANDHOLE SHALL BE TRAFFIC RATED TIER 22. 25. PROVIDE HORN/STROBE WARNING SIGNAL FOR EACH BARRIER ARM SYSTEM. PROVIDE HORN/STROBE WARNING SIGNAL FOR EACH BARRIER ARM SYSTEM. SIGNAL SHALL BE EXTERIOR RATED, 120V. PROVIDE ALL REQUIRED RELAYS, WIRING, RACEWAYS, AND INTERCONNECT TO SECURITY GATE AND SECURITY SYSTEM TO ALARM WHEN GATE IS OPENING & CLOSING. COORDINATE REQUIREMENTS WITH GATE PROVIDER AND SECURITY VENDOR. MOUNT TO GATE HOUSING. HORN/STROBE SHALL BE MAXI-SIGNAL 120-31T-STROBE OR APPROVED EQUAL.
AutoCAD SHX Text
GENERAL ELECTRICAL NOTES:
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
SCALE: 1/16" = 1'-0"
AutoCAD SHX Text
%%UBASEMENT RACEWAY PLAN
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BYDATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N
TR
A C
TO
R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
MELVIN-PRICE FEDERAL BUILDING
BRETT ETLING
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
750 EAST MISSOURI AVE.
EAST SAINT LOUIS
GSA SECURITY UPGRADE
10-10-2018
30x42
IL 62201
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
ELECTRICAL DETAILS
JEM
L1 ELEC
EP103
S
TA T E OF I L L I N
OFESSIONAL
ENINEE
OF
AutoCAD SHX Text 5'-0"
AutoCAD SHX Text
24" DIA.
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text 6"
AutoCAD SHX Text
FINAL GRADE
AutoCAD SHX Text
CONDUIT
AutoCAD SHX Text
3" CLEAR
AutoCAD SHX Text
HIGH QUALITY GROUTED
AutoCAD SHX Text
FINISH ON BASE
AutoCAD SHX Text
SIX (6) #5 BARS
AutoCAD SHX Text
EQUALLY SPACED
AutoCAD SHX Text
#4 HOOP, TIE
AutoCAD SHX Text @ 12 C-C
AutoCAD SHX Text
CONCRETE BASE
AutoCAD SHX Text
POLE
AutoCAD SHX Text
HAND HOLE
AutoCAD SHX Text
REMOVABLE BASE
AutoCAD SHX Text
ANCHOR BOLTS
AutoCAD SHX Text
1" CHAMFER
AutoCAD SHX Text
GROUT UNDER
AutoCAD SHX Text
ENTIRE BASE
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text 1/2"x8'-0"
AutoCAD SHX Text
#4 BARE STRANDED COPPER
AutoCAD SHX Text
GROUND CABLE. BOND TO
AutoCAD SHX Text
CONDUITS, ANCHOR BOLTS,
AutoCAD SHX Text
STEEL REINFORCEMENT, AND
AutoCAD SHX Text
LIGHTING POLE
AutoCAD SHX Text
LIGHTING FIXTURE
AutoCAD SHX Text
AS INDICATED
AutoCAD SHX Text POLE FOR SECURITY CAMERA SHALL MATCH LIGHTING POLE, EXCEPT FOR HEIGHT. COORDINATE REQUIREMENTS WITH GOVERNMENT'S SECURITY VENDOR.
AutoCAD SHX Text
%%UELECTRIC HANDHOLE DETAIL
AutoCAD SHX Text
%%U INSTALLATION IN TURF AREAS
AutoCAD SHX Text 6"
AutoCAD SHX Text
VARIES
AutoCAD SHX Text
CLEAN Ô"
AutoCAD SHX Text
CRUSHED ROCK
AutoCAD SHX Text
HANDHOLE
AutoCAD SHX Text A. REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR ADDITIONAL DETAILS AND REQUIREMENTS. B. ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE PER GOVERNMENT STANDARD.
AutoCAD SHX Text
GENERAL ELECTRICAL NOTES:
AutoCAD SHX Text
%%U SECURITY GATE DIAGRAM
AutoCAD SHX Text
CONDUIT(S) WITH BELL ENDS (TYP). SIZE, QUANTITY AND WIRING AS INDICATED ON PLANS
AutoCAD SHX Text
1" CONDUIT FOR POWER INFEED
AutoCAD SHX Text
1" CONDUIT FOR LV COMMUNICATIONS
AutoCAD SHX Text 5/8" x 8'-0" GROUND ROD
AutoCAD SHX Text 1" CONDUIT FOR VEHICLE LOOP WIRES. PROVIDE INDIVIDUAL CONDUIT PER LOOP.ENTIRE LOOP WIRE SHALL BE INSTALLED WITHIN CONDUIT. PROVIDE JUNCTION BOX IN PAVEMENT AT EACH LOOP JUNCTION. LOCATE AS DIRECTED BY MANUFACTURER.
AutoCAD SHX Text
3/4" CONDUIT FOR CATCH POST AUXILIARY DEVICES
AutoCAD SHX Text
3/4" CONDUIT FOR CATCH POST HEATER
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
PIVOT POST
AutoCAD SHX Text
CATCH POST
AutoCAD SHX Text
MAIN BREAKER
AutoCAD SHX Text 100A/3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text %%UEXIST. PANEL RBL-1Bb
AutoCAD SHX Text
%%UBUSSING DIAGRAM
AutoCAD SHX Text 20A/2
AutoCAD SHX Text 20A/2
AutoCAD SHX Text 30A/3
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/3
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/3
AutoCAD SHX Text
GARAGE DOOR
AutoCAD SHX Text
HVAC TRANS.
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
NORTH SECURITY GATE, NOTE 1
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
PARKING LOT VEHICLE GATE
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
SOUTH SECURITY GATE, NOTE 1
AutoCAD SHX Text
ACCESS CONTROL PEDESTAL, NOTE 2
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
RECEPT. - GARAGE, SEC. MONITOR, NOTE 2
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text GRADE. FEATHER AND TAMP BACKFILL TO CREATE FLUSH INSTALLATION AND POSITIVE DRAINAGE AWAY FROM BOX
AutoCAD SHX Text
3/4" CONDUIT FOR EARTH GROUND
AutoCAD SHX Text
100A, MAIN BREAKER 208Y/120V 3 , 4W, 30 CKT.GENERAL ELECTRIC A SERIES, II PANEL
AutoCAD SHX Text
1. PROVIDE BREAKER. PROVIDE BREAKER. 2. UTILIZE EXISTING BREAKER.UTILIZE EXISTING BREAKER.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text W
AutoCAD SHX Text D
AutoCAD SHX Text
SKID RESISTANT
AutoCAD SHX Text
SURFACE
AutoCAD SHX Text L
AutoCAD SHX Text
ELECTRIC
AutoCAD SHX Text
%%UBOX
AutoCAD SHX Text
%%UCOVER
AutoCAD SHX Text
POLYMER CONCRETE COVER.
AutoCAD SHX Text
1/2" X 2 1/2" " X 2 1/2" " PULL SLOT
AutoCAD SHX Text
LOGO AS SPECIFIED.
AutoCAD SHX Text
PROVIDE GASKET BETWEEN COVER AND BOX
AutoCAD SHX Text
DIMENSIONS AS INDICATED
AutoCAD SHX Text
POLYMER CONCRETE SIDES WITH NO BASE
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
%%U ELECTRIC HANDHOLE DETAIL
AutoCAD SHX Text
STAINLESS STEEL HEAVY DUTY BOLT AND WASHER, WITH STAINLESS STEEL INSERTS, TYP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
LIGHTING FIXTURE SCHEDULE
AutoCAD SHX Text
POLE: DB9 4F14-188 14'
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
FIXTURE SERIES
AutoCAD SHX Text
METAL
AutoCAD SHX Text
LAMP
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
BALLAST
AutoCAD SHX Text
FACTOR
AutoCAD SHX Text
HIGH POWER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
FIXTURE
AutoCAD SHX Text
VOLTAGE
AutoCAD SHX Text
POLE
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
LIGHT: PRM3 V5 250PSMH AGN SLA7-2
AutoCAD SHX Text
TRANSFORMER: 9075-TRN-SS
AutoCAD SHX Text
LED
AutoCAD SHX Text
FACTOR
AutoCAD SHX Text
HIGH POWER
AutoCAD SHX Text 1.4
AutoCAD SHX Text
AutoCAD SHX Text
SURFACE
AutoCAD SHX Text
LIGHT: 7031 30 GH
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text DECORATIVE SITE LIGHTING POLE WITH (2) LIGHTING FIXTURES SIMILAR TO THE EXISTING SITE POLE FIXTURES. LIGHTING FIXTURE SHALL BE ROUND, 18" DIA, WITH SAG LENS, TYPE V CUTOFF LIGHT DISTRIBUTION, CAST ALUMINUM CONSTRUCTION, STAINLESS STEEL HARDWARE. COLOR SHALL MATCH EXISTING FIXTURES. PROVIDE COMPLETE WITH FIXTURES, POLE, REINFORCED CONCRETE BASE, AND ALL REQUIRED MOUNTING ACCESSORIES. POLE SHALL BE ROUND WITH FLUTED DECORATIVE BASE. POLE HEIGHT SHALL MATCH HEIGHT OF EXISTING SITE POLE LIGHTING.
AutoCAD SHX Text 3"L LED HARDSCAPE LIGHTING FIXTURE (OVERALL 4.5"L x 3"W x 1"D) WITH TRANSLUCENT DIFFUSER, STAINLESS STEEL TAMPER RESISTANT SCREWS, IP66 RATED, AND ALUMINUM HOUSING WITH GRAPHITE COLOR. PROVIDE WITH ASSOCIATED STEP DOWN TRANSFORMER. TRANSFORMER SHALL BE IP65 RATED FOR OUTDOOR MOUNTING AND INTEGRAL ELECTRONIC TIMER. TRANSFORMER SHALL BE HARDWIRED.
AutoCAD SHX Text
HALIDE
AutoCAD SHX Text 3000K
AutoCAD SHX Text
ARCHITECTURAL AREA LIGHTING
AutoCAD SHX Text
120/208 (MATCH EXISTING CIRCUIT VOLTAGE)
AutoCAD SHX Text
WAC LIGHTING
AutoCAD SHX Text
AutoCAD SHX Text
%%UPOLE BASE DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LED
AutoCAD SHX Text
FACTOR
AutoCAD SHX Text
HIGH POWER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SURFACE
AutoCAD SHX Text
DSXF1 LED P1 40K MFL VG
AutoCAD SHX Text C
AutoCAD SHX Text 9"W x 7.75"H x 3"D LED FLOOD LIGHT WITH DIE-CAST ALUMINUM BLACK HOUSING, MEDIUM FLOOD LIGHT DISTRIBUTION, ADJUSTABLE KNUCKLE FOR AIMING, CLEAR TEMPERED GLASS LENS, AND VANDAL GUARD.
AutoCAD SHX Text 4000K
AutoCAD SHX Text
LITHONIA
AutoCAD SHX Text
AutoCAD SHX Text
PROVIDE WITH MOGUL BASE TO MATCH BASE
AutoCAD SHX Text
OF PROVIDED LED RETROFIT LAMP
AutoCAD SHX Text PROVIDE LED RETROFIT LAMP. LAMP SHALL BE 45 WATTS, 5800 LUMENS, WESTINGHOUSE T30 HIGH LUMEN LED LAMP. VERIFY PHYSICAL DIMENSIONS OF LAMP AND FIXTURE. LAMP SHALL FIT WITHIN FIXTURE HOUSING. MODIFY THE FIXTURE TO ACCEPT LED REPLACEMENT LAMP.
| Sheets and Views |
| GI001 COVER SHEET |
| GI002 GENERAL NOTES |
| GI003 PHASING PLAN |
| CD101 DEMOLITION PLAN |
| CS101 SITE PLAN - NEW WORK |
| CS102 LOOP DETECTOR LAYOUT PLAN - NEW WORK |
| CS501 SITE DETAILS |
| CS502 RAM-PROOF BARRIER GATE DETAILS - NEW WORK |
| CG101 GRADING PLAN - NEW WORK |
File details come from the government source that posted it.