H1-Final_Construction_Documents_-_Plans_USMS_Sec_Barrier.pdf

PDF 8 MB Posted

Attached to
USMS Security Barrier Replacement Federal contract opportunity
Solicitation number
47PF0019R0010
Issued by
General Services Administration Public Buildings Service Region 5

About this file

USMS Security Barrier Project-Plans

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COVER SHEET

GI001

MELVIN PRICE FEDERAL COURTHOUSE

USMS SECURITY

BARRIER REPLACEMENT

FINAL CONSTRUCTION DOCUMENTS

Contact: Contact:

MELVIN PRICE FEDERAL

COURTHOUSE

Brett Etling Project COR

508 South Eighth Street.

East St. Louis, IL 62201 p: 217.801.9743 e: brett.etling@gsa.gov

OWNER

GUIDON DESIGN

INC.

Stacey Paul Project Engineer Project PM

905 North Capitol Avenue Suite 100 Indianapolis, IN 46204 p: 317.800.6388 x 104 e: spaul@guidondesign.com

CIVIL ENGINEER

VICINITY MAP

LOCATION MAP

N

PROJECT LOCATION

N

MECHANICAL &

ELECTRICAL

BCCLT, CONSULTING

ENGINEERS

James E. Meadows Senior Electrical Engineer

9100 Marksfield Rd.

#200 Louisville, KY 40222 p: 812.423.4407 e: meadows@bcclt.com

Contact:

U.S. COURTHOUSE

SHEET LIST

SHEET NUMBER SHEET NAME

MELVIN PRICE FEDERAL BUILDING

PROJECT LOCATION

GENERAL

GI001 COVER SHEET

GI002 GENERAL NOTES

GI003 PHASING PLAN

CIVIL

CD101 DEMOLITION PLAN

CS101 SITE PLAN - NEW WORK

CS102 LOOP DETECTOR LAYOUT PLAN - NEW WORK

CS501 SITE DETAILS

CS502 RAM-PROOF BARRIER GATE DETAILS - NEW WORK

CG101 GRADING PLAN - NEW WORK

EP101 ELECTRICAL LEGEND & DEMOLITION PLAN

EP102 ELECTRICAL POWER PLAN - NEW WORK

EP103 ELECTRICAL DETAILS

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

CONTRACTOR

STAGING/STORAGE

AREA

GENERAL NOTES

GI002

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

0 2010

N

GI003

PHASING PLAN

0 2010

N

DEMOLITION PLAN

CD101

GREAT LAKES REGION 5

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

0 2010

N

CS101

SITE PLAN - NEW WORK

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

0 2010

N

CS102

LOOP DETECTOR LAYOUT PLAN - NEW WORK

LOOP DETECTOR LAYOUT PLAN - NEW WORK

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

SITE DETAILS

CS501

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

CS502

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BY

DATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N T R A C T O R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

GSA SECURITY UPGRADE

750 MISSOURI AVENUE

MELVIN-PRICE FEDERAL BUILDING

DSM

BRETT ETLING

10-10-2018

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

CIVIL

EAST SAINT LOUIS IL 62201

30" X 42"

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

0 2010

N

CG101

GRADING PLAN - NEW WORK

GRADING PLAN - NEW WORK

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BYDATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N

TR

A C

TO

R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

MELVIN-PRICE FEDERAL BUILDING

BRETT ETLING

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

750 EAST MISSOURI AVE.

EAST SAINT LOUIS

GSA SECURITY UPGRADE

10-10-2018

30x42

IL 62201

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

ELECTRICAL LEGEND & DEMOLITION PLAN

JEM

L1 ELEC

EP101

S

TAT E OF I L L I N

O I S

A E

S E EAOS

EISTEE

OFESSIONAL

ENINEE

OF

AutoCAD SHX Text

NOTE 1

AutoCAD SHX Text

NOTE 1

AutoCAD SHX Text

CAMERA

AutoCAD SHX Text

CAMERA

AutoCAD SHX Text

HYDRAULIC

AutoCAD SHX Text

PUMP, NOTE 5

AutoCAD SHX Text

%%UGARAGE

AutoCAD SHX Text

%%UPARKING

AutoCAD SHX Text J

AutoCAD SHX Text J

AutoCAD SHX Text

INTERCOM RACEWAY

AutoCAD SHX Text

AND CABLING TO

AutoCAD SHX Text

REMAIN FOR REUSE.

AutoCAD SHX Text

%%UDRIVE

AutoCAD SHX Text

%%USTREET

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

SUMP PUMP, NOTE 3

AutoCAD SHX Text C

AutoCAD SHX Text

EP101

AutoCAD SHX Text

INTERCOM PEDESTAL NOTE 6

AutoCAD SHX Text S

AutoCAD SHX Text

SECURITY BOLLARD REMOTE CONTROL, NOTE 9

AutoCAD SHX Text

SWITCH FOR BOLLARD HEAT TAPE; NOTE 8

AutoCAD SHX Text EXIST. PANEL `RBL-1Bb'

AutoCAD SHX Text

OVERHEAD DOOR CONTROLLER

AutoCAD SHX Text

HYDRAULIC LINE & POWER JUNCTION BOX, NOTE 4

AutoCAD SHX Text

INTERCOM & CARD READER PEDESTAL, NOTE 6

AutoCAD SHX Text

POST MOUNTED WARNING LIGHT, NOTE 5

AutoCAD SHX Text

POST MOUNTED WARNING LIGHT, NOTE 5

AutoCAD SHX Text

OVERHEAD DOOR

AutoCAD SHX Text

UNDERGROUND CONDUITS, NOTE 2

AutoCAD SHX Text

GUARD SHACK

AutoCAD SHX Text

HYDRAULIC BOLLARDS, TYP.

AutoCAD SHX Text

EP101

AutoCAD SHX Text

EP101

AutoCAD SHX Text

GUARD SHACK FLOOD LIGHT, NOTE 10

AutoCAD SHX Text

GUARD SHACK FLOOD LIGHT, NOTE 10

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text

%%UELECTRICAL DEMOLITION PLAN

AutoCAD SHX Text A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE BUILDING AND SITE THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE BUILDING AND SITE TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS, VERIFY SIZE, LOCATION, AND USAGE OF UTILITIES AND EQUIPMENT PRIOR TO CONSTRUCTION. B. ALL EQUIPMENT REMOVED FOR RELOCATION SHALL BE REMOVED IN SUCH A ALL EQUIPMENT REMOVED FOR RELOCATION SHALL BE REMOVED IN SUCH A MANNER THAT REUSE IS POSSIBLE. C. PATCH ALL OPENINGS IN WALLS, FLOORS, AND CEILINGS WHERE REMOVAL OF PATCH ALL OPENINGS IN WALLS, FLOORS, AND CEILINGS WHERE REMOVAL OF EQUIPMENT OR DEVICES CREATES SUCH OPENINGS. PATCH OPENINGS TO MATCH EXISTING. D. IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN MUST BE RELOCATED IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN MUST BE RELOCATED OR REMOVED DUE TO INTERFERENCE WITH NEW EQUIPMENT INSTALLATION, THE CIRCUITS SHALL BE MODIFIED IN SUCH A MANNER WHICH WILL ENSURE THE PROPER OPERATION OF THE EQUIPMENT AFTER CONSTRUCTION IS COMPLETE, USE THE SAME TYPE OF CONDUCTOR AND SAME CONDUIT SIZE AS EXISTING TO MAKE ALL REQUIRED MODIFICATIONS. E. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS REQUIRED FOR THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS REQUIRED FOR THE INSTALLATION OF NEW WORK, WHETHER OR NOT IT IS SPECIFICALLY INDICATED OR NOTED IN THESE DOCUMENTS. F. ALL CONDUIT RUNS TO REMOVED EQUIPMENT OR DEVICES SHALL BE COMPLETELY ALL CONDUIT RUNS TO REMOVED EQUIPMENT OR DEVICES SHALL BE COMPLETELY REMOVED BACK TO SOURCE, INCLUDING ALL HANGERS, BEAM CLAMPS, MISCELLANEOUS SUPPORTS, AND WIRING. G. COORDINATE CONDUIT ROUTING WITH EXISTING EQUIPMENT TO AVOID CONFLICTS COORDINATE CONDUIT ROUTING WITH EXISTING EQUIPMENT TO AVOID CONFLICTS WITH EQUIPMENT AND EQUIPMENT CLEARANCE. H. SEAL AROUND ALL WALL PENETRATIONS WITH FIRE STOPPING. SEAL AROUND ALL WALL PENETRATIONS WITH FIRE STOPPING. I. BRANCH CIRCUIT NEUTRAL CONDUCTORS SHALL NOT BE SHARED WITH ANOTHER BRANCH CIRCUIT NEUTRAL CONDUCTORS SHALL NOT BE SHARED WITH ANOTHER CIRCUIT. J. EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH A GREEN EQUIPMENT EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH A GREEN EQUIPMENT GROUNDING CONDUCTOR.

AutoCAD SHX Text

1. DISCONNECT AND REMOVE POWER TO GATE ARM DISCONNECT AND REMOVE POWER TO GATE ARM EQUIPMENT. 2. EXISTING CONDUITS FOR POWER AND COMMUNICATIONS TO EXISTING CONDUITS FOR POWER AND COMMUNICATIONS TO GUARD SHACK; (1) 2"C FOR POWER AND (2) 2"C FOR COMMUNICATIONS. DO NOT DISTURB CONDUITS. 3. DISCONNECT AND REMOVE POWER SERVING SUMP PUMP. DISCONNECT AND REMOVE POWER SERVING SUMP PUMP. 4. REMOVE PULL BOX AND ASSOCIATED CONDUIT AND WIRING. REMOVE PULL BOX AND ASSOCIATED CONDUIT AND WIRING. 5. DISCONNECT AND REMOVE POWER TO EQUIPMENT. DISCONNECT AND REMOVE POWER TO EQUIPMENT. 6. DISCONNECT POWER FROM PEDESTAL. DISCONNECTION AND DISCONNECT POWER FROM PEDESTAL. DISCONNECTION AND REMOVAL OF SECURITY SYSTEM DEVICES AND CABLING SHALL BE BY GOVERNMENT SECURITY VENDOR. 7. REMOVE PEDESTAL AFTER GOVERNMENT VENDOR REMOVES REMOVE PEDESTAL AFTER GOVERNMENT VENDOR REMOVES SECURITY DEVICES AND CABLING. 8. DISCONNECT AND REMOVE SWITCH AND ASSOCIATED WIRING DISCONNECT AND REMOVE SWITCH AND ASSOCIATED WIRING AND RACEWAYS FOR BOLLARD HEAT TAPE. 9. DISCONNECT AND REMOVE HYDRAULIC BOLLARD REMOTE DISCONNECT AND REMOVE HYDRAULIC BOLLARD REMOTE CONTROL STATION AND ASSOCIATED WIRING AND RACEWAYS AT THIS LOCATION AND IN THE SECURITY CONTROL ROOM. 10. REMOVE GUARD SHACK FLOOD LIGHTING FIXTURE FOR REMOVE GUARD SHACK FLOOD LIGHTING FIXTURE FOR REPLACEMENT. CIRCUIT TO REMAIN FOR REUSE. SEE EP102 FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

%%UGENERAL ELECTRICAL NOTES:

AutoCAD SHX Text

%%UDEMOLITION NOTES:

AutoCAD SHX Text

ELECTRICAL LEGEND

AutoCAD SHX Text

WORKING CLEARANCE

AutoCAD SHX Text

NP-1,3,5

AutoCAD SHX Text

PHASE

AutoCAD SHX Text

NEUTRAL

AutoCAD SHX Text

CONDUCTORS

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

INDICATE NUMBER OF CONDUCTORS REQUIRED. CONDUIT

AutoCAD SHX Text

CIRCUIT CONCEALED IN CEILING OR WALL. CROSSBARS

AutoCAD SHX Text

HOMERUN TO PANELBOARD INDICATED. NUMBER OF

AutoCAD SHX Text

ARROWHEADS INDICATES NUMBER OF CIRCUITS. NUMBER

AutoCAD SHX Text

NOT SIZED IS Ô", CONDUCTORS NOT SIZED ARE #12 AWG.

AutoCAD SHX Text

INDICATES CIRCUIT NUMBERS. PREFIX INDICATES PANEL

AutoCAD SHX Text

SURFACE MOUNTED PANELBOARD.

AutoCAD SHX Text

TRANSFORMER.

AutoCAD SHX Text

SOLIDLY GROUNDED WYE CONNECTION.

AutoCAD SHX Text

DELTA CONNECTION.

AutoCAD SHX Text

CIRCUIT BREAKER.

AutoCAD SHX Text

SWITCH AND FUSE UNIT.

AutoCAD SHX Text

SWITCH.

AutoCAD SHX Text

FUSE.

AutoCAD SHX Text

POINT OF CONNECTION NEW TO EXISTING.

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

NUMBER.

AutoCAD SHX Text

FUSIBLE DISCONNECT SWITCH. MOUNT 4'-6" A.F.F. TO CENTER, UNLESS NOTED

AutoCAD SHX Text

OTHERWISE.

AutoCAD SHX Text

FUSE.

AutoCAD SHX Text

CONDUIT EXPOSED.

AutoCAD SHX Text

CONDUIT CONCEALED BENEATH GROUND.

AutoCAD SHX Text

WALL OUTLET WITH 20A, 125V DUPLEX RECEPTACLE. MOUNT AT 16" A.F.F. TO BOTTOM,

AutoCAD SHX Text

UNLESS NOTED OTHERWISE. 'GFI' SUBSCRIPT INDICATES GROUND FAULT CURRENT

AutoCAD SHX Text

INTERRUPTER.

AutoCAD SHX Text

SINGLE POLE 20A SPECIFICATION GRADE TOGGLE SWITCH. MOUNT 44" A.F.F. TO

AutoCAD SHX Text

BOTTOM, NOTED OTHERWISE.

AutoCAD SHX Text S

AutoCAD SHX Text

NUMBER AT OUTLET INDICATES CIRCUIT ARRANGEMENT.

AutoCAD SHX Text "1,2,3"

AutoCAD SHX Text

LOWER CASE LETTERS AT OUTLETS INDICATE SWITCHING ARRANGEMENTS.

AutoCAD SHX Text a,b,c

AutoCAD SHX Text

E-XXX

AutoCAD SHX Text

AutoCAD SHX Text

PHOTOGRAPH VIEW. # INDICATES PHOTOGRAPH NUMBER. EXXX INDICATES

AutoCAD SHX Text

PHOTOGRAPH SHEET/DRAWING REFERENCE.

AutoCAD SHX Text

GFI

AutoCAD SHX Text

INDICATES GROUND FAULT CIRCUIT INTERRUPTER.

AutoCAD SHX Text

EX

AutoCAD SHX Text

INDICATES EXISTING WHEN SHOWN NEXT TO DEVICE.

AutoCAD SHX Text A.F.F.

AutoCAD SHX Text

ABOVE FINISHED FLOOR.

AutoCAD SHX Text

%%USYMBOL

AutoCAD SHX Text

%%UDESCRIPTION

AutoCAD SHX Text

%%USYMBOL

AutoCAD SHX Text

%%UDESCRIPTION

AutoCAD SHX Text

SECURITY SYSTEM CAMERA. CAMERA AND ASSOCIATED WIRING IS BY GOVERNMENT.

AutoCAD SHX Text

WALL MOUNTED JUNCTION BOX, MOUNT 16" A.F.F. TO BOTTOM,

AutoCAD SHX Text

UNLESS NOTED OTHERWISE.

AutoCAD SHX Text J

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text A

AutoCAD SHX Text

%%UPHOTO

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text B

AutoCAD SHX Text

%%UPHOTO

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text C

AutoCAD SHX Text

%%UPHOTO

AutoCAD SHX Text

OVERHEAD DOOR CONTROLLER

AutoCAD SHX Text

HYDRAULIC PUMP

AutoCAD SHX Text

HYDRAULIC LINE & POWER JUNCTION BOX

AutoCAD SHX Text

HYDRAULIC LINE & POWER JUNCTION BOX

AutoCAD SHX Text

SECURITY BOLLARD REMOTE CONTROL

AutoCAD SHX Text

SWITCH FOR BOLLARD HEAT TAPE

AutoCAD SHX Text

INTERCOM PEDESTAL

AutoCAD SHX Text PANEL RBL-1Bb

AutoCAD SHX Text A

AutoCAD SHX Text

LIGHTING FIXTURE TYPE.

AutoCAD SHX Text

POLE LIGHT COMPLETE WITH POLE, BRACKETS REQUIRED NUMBER OF LIGHTING FIXTURES,

AutoCAD SHX Text

REINFORCED CONCRETE FOUNDATION, AND ALL ACCESSORIES AS SCHEDULED.

AutoCAD SHX Text

PTZ SUBSCRIPT INDICATES PAN-TILT-ZOOM TYPE.

AutoCAD SHX Text 10-10-2018

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BYDATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N

TR

A C

TO

R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

MELVIN-PRICE FEDERAL BUILDING

BRETT ETLING

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

750 EAST MISSOURI AVE.

EAST SAINT LOUIS

GSA SECURITY UPGRADE

10-10-2018

30x42

IL 62201

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

ELECTRICAL POWER PLAN - NEW WORK

JEM

L1 ELEC

EP102

S

TA T E OF I L L I N

OFESSIONAL

ENINEE

OF

AutoCAD SHX Text

CAMERA

AutoCAD SHX Text

CAMERA

AutoCAD SHX Text

EXISTING UG CONDUITS

AutoCAD SHX Text

FOR GUARD SHACK

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

POWER & COMMUNICATIONS.

AutoCAD SHX Text

PANEL

AutoCAD SHX Text RBL-1Bb

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text J

AutoCAD SHX Text +96"

AutoCAD SHX Text +96"

AutoCAD SHX Text

MONITOR

AutoCAD SHX Text

EXISTING CONDUITS FOR

AutoCAD SHX Text

GUARD SHACK POWER

AutoCAD SHX Text

AND COMMUNICATIONS

AutoCAD SHX Text

NOTE 6

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text

COMMUNICATIONS

AutoCAD SHX Text

(2) 2"C FOR

AutoCAD SHX Text

POWER CIRCUIT

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

1"C BACK TO

AutoCAD SHX Text

SECURITY OFFICE

AutoCAD SHX Text

NOTE 3

AutoCAD SHX Text

NOTE 7

AutoCAD SHX Text J

AutoCAD SHX Text RBL-1Bb-19

AutoCAD SHX Text J

AutoCAD SHX Text 8"x8"J-BOX

AutoCAD SHX Text

EXISTING OVERHEAD DOOR

AutoCAD SHX Text

2"C. TO SECURITY OFFICE, NOTE 12

AutoCAD SHX Text

JUNCTION BOX FOR VIDEO MONITOR

AutoCAD SHX Text RBL-1Bb-14

AutoCAD SHX Text

NOTE 11

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

NOTE 10

AutoCAD SHX Text

JUNCTION BOX

AutoCAD SHX Text 3#10,1#10G 3/4"C

AutoCAD SHX Text RBL-1Bb-2, 3#10,1#10G 3/4"C

AutoCAD SHX Text RBL-1Bb-8, 3#10,1#10G 3/4"C

AutoCAD SHX Text

EXISTING OVERHEAD DOOR CONTROLLER

AutoCAD SHX Text

SECURITY GATE BACK-UP POWER INVERTER

AutoCAD SHX Text POWER HANDHOLE 11"Wx18L"x12"D, NOTE 15

AutoCAD SHX Text COMMUNICATION HANDHOLE 24"Wx18L"x12"D, NOTE 15

AutoCAD SHX Text

SECURITY BARRIER PIVOT POST, NOTE 4

AutoCAD SHX Text

COMM/SECURITY SYSTEM CONDUIT, 1"C

AutoCAD SHX Text RBL-1Bb-19, 3#10,1#10G,3/4"C

AutoCAD SHX Text RBL-1Bb-8, 3#10,1#10G,1"C RBL-1Bb-19

AutoCAD SHX Text

NOTE 5

AutoCAD SHX Text

GROUND ROD

AutoCAD SHX Text

NOTE 9

AutoCAD SHX Text

NOTE 8

AutoCAD SHX Text

COMM/SECURITY SYSTEM CONDUIT, 2"C

AutoCAD SHX Text

NOTE 9

AutoCAD SHX Text

NOTE 8

AutoCAD SHX Text

NOTE 5

AutoCAD SHX Text

GROUND ROD

AutoCAD SHX Text

SECURITY BARRIER PIVOT POST, NOTE 4

AutoCAD SHX Text RBL-1Bb-2, 3#10, 1#10G, 1"C

AutoCAD SHX Text

CATCH BLOCK

AutoCAD SHX Text

ACCESS CONTROL PEDESTAL, NOTES 1,2

AutoCAD SHX Text

LOOP DETECTOR, TYP.

AutoCAD SHX Text

GUARD SHACK PANEL

AutoCAD SHX Text

ACCESS CONTROL PEDESTAL; NOTES 1,2

AutoCAD SHX Text C1

AutoCAD SHX Text C2

AutoCAD SHX Text C3

AutoCAD SHX Text C4

AutoCAD SHX Text

C5 PTZ

AutoCAD SHX Text B

AutoCAD SHX Text

PS

AutoCAD SHX Text B

AutoCAD SHX Text

PS

AutoCAD SHX Text

EX

AutoCAD SHX Text H

AutoCAD SHX Text

GUARD SHACK

AutoCAD SHX Text A

AutoCAD SHX Text HANDHOLE 11"Wx11L"x12"D, NOTES 15,16

AutoCAD SHX Text

EXIST SITE LTG CIRCUIT, NOTE 18

AutoCAD SHX Text

NOTE 17

AutoCAD SHX Text

RELACE WIRING AS REQUIRED

AutoCAD SHX Text

CCTV SYSTEM CONDUIT, 1"C

AutoCAD SHX Text H

AutoCAD SHX Text HANDHOLE 11"Wx11L"x12"D, NOTES 15,16

AutoCAD SHX Text

1"C TO SECURITY OFFICE; NOTE 12

AutoCAD SHX Text

LOOP DETECTOR, TYP.

AutoCAD SHX Text

NOTE 20

AutoCAD SHX Text

EXIST J-BOX

AutoCAD SHX Text J

AutoCAD SHX Text J

AutoCAD SHX Text

LOOP WIRES

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

C6 PTZ

AutoCAD SHX Text

NEW CAMERA. CENTER ABOVE DOOR

AutoCAD SHX Text J

AutoCAD SHX Text

NEW CAMERA

AutoCAD SHX Text

NEW CAMERA

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text

NOTE 23

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text

NOTE 24

AutoCAD SHX Text

NOTE 24

AutoCAD SHX Text

NOTE 24

AutoCAD SHX Text H

AutoCAD SHX Text

NOTE 24

AutoCAD SHX Text H

AutoCAD SHX Text

NOTE 24

AutoCAD SHX Text H

AutoCAD SHX Text

NOTE 24

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text

NOTE 13

AutoCAD SHX Text H

AutoCAD SHX Text

NOTE 25

AutoCAD SHX Text H

AutoCAD SHX Text

NOTE 25

AutoCAD SHX Text RBL-1Bb-19

AutoCAD SHX Text RBL-1Bb-19

AutoCAD SHX Text C

AutoCAD SHX Text

NOTE 23

AutoCAD SHX Text

PANEL

AutoCAD SHX Text RBL-1Bb

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

SHACK

AutoCAD SHX Text

GUARD

AutoCAD SHX Text

READER PEDESTAL

AutoCAD SHX Text

INTERCOM/CARD

AutoCAD SHX Text

BARRIER

AutoCAD SHX Text

SECURITY

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

SECURITY

AutoCAD SHX Text

JUNCTION

AutoCAD SHX Text

BOX

AutoCAD SHX Text

UP

AutoCAD SHX Text 253.00'(R)

AutoCAD SHX Text

BARRIER

AutoCAD SHX Text

SECURITY

AutoCAD SHX Text

INTERCOM/ CARD READER PEDESTAL

AutoCAD SHX Text

CONDUIT FOR PEDESTAL AND MONITOR COMM/LV CONDUCTORS, NOTE 12

AutoCAD SHX Text

EXIST. GUARD SHACK POWER CONDUIT

AutoCAD SHX Text

EXIST. GUARD SHACK COMM. CONDUITS

AutoCAD SHX Text

CONDUIT SECURITY GATE COMM/LV CONDUCTORS, NOTE 12

AutoCAD SHX Text

ELECT. RM.

AutoCAD SHX Text

NOTE 21

AutoCAD SHX Text

NOTE 22

AutoCAD SHX Text

EXISTING GUARD SHACK POWER AND COMM CONDUITS

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text

%%UELECTRICAL POWER PLAN - NEW WORK

AutoCAD SHX Text A. REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR ADDITIONAL DETAILS AND REQUIREMENTS. B. ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE PER GOVERNMENT STANDARD. PROVIDE PULL STRING IN CONDUIT.

AutoCAD SHX Text

1. CARD READER STATION, INTERCOM STATION, AND DURESS ALARM STATION CARD READER STATION, INTERCOM STATION, AND DURESS ALARM STATION ON PEDESTAL. DEVICES AND CABLING SHALL BE PROVIDED BY GOVERNMENT SECURITY VENDOR. 2. PROVIDE (1) TYPE B LIGHTING FIXTURE AND ASSOCIATED STEP DOWN PROVIDE (1) TYPE B LIGHTING FIXTURE AND ASSOCIATED STEP DOWN TRANSFORMER FOR ACCESS CONTROL STAND LIGHTING. MOUNT TO UNDERSIDE OF TOP LIP OF WEATHERSHIELD FACING PEDESTAL FRONT. 3. PROVIDE (1) 1" CONDUIT WITH PULL STRING TO SECURITY OFFICE. CONDUIT PROVIDE (1) 1" CONDUIT WITH PULL STRING TO SECURITY OFFICE. CONDUIT FOR CARD READER CABLING. 4. WIRE SECURITY GATE EQUIPMENT PER MANUFACTURER'S SPECIFICATIONS. WIRE SECURITY GATE EQUIPMENT PER MANUFACTURER'S SPECIFICATIONS. PROVIDE ALL REQUIRED RACEWAYS AND CABLING. 5. PROVIDE 5/8"x 8"L GROUND ROD PER MANUFACTURER'S SPECIFICATIONS. PROVIDE 5/8"x 8"L GROUND ROD PER MANUFACTURER'S SPECIFICATIONS. CONNECT TO PIVOT POST GROUND ROD CONNECTOR WITH 1#6 GROUND. WIRE LENGTH SHALL NOT EXCEED 3 FEET. COORDINATE LOCATION WITH PIVOT POST FOOTING. 6. PROVIDE 12 FOOT HIGH POLE AND ASSOCIATED REINFORCED CONCRETE BASE PROVIDE 12 FOOT HIGH POLE AND ASSOCIATED REINFORCED CONCRETE BASE TO MOUNT SECURITY CAMERAS. MOUNT CCTV C4 AT 10 FOOT ABOVE FINISHED GRADE AND CCTV C5 AT 11 FOOT ABOVE FINISHED GRADE. 7. MODIFY/ EXTEND EXISTING INTERCOM RACEWAY AS REQUIRED. MODIFY/ EXTEND EXISTING INTERCOM RACEWAY AS REQUIRED. 8. PROVIDE CONDUIT FOR CATCH POST HEATER. REFER TO SECURITY GATE PROVIDE CONDUIT FOR CATCH POST HEATER. REFER TO SECURITY GATE GATE DETAIL `3' ON EP103. 9. PROVIDE CONDUIT FOR CATCH POST AUXILIARY DEVICES. REFER TO SECURITY PROVIDE CONDUIT FOR CATCH POST AUXILIARY DEVICES. REFER TO SECURITY GATE DETAIL '3' ON EP103. 10. RBL-1Bb-2: 3#10, 1#10G (GATE) RBL-1Bb-2: 3#10, 1#10G (GATE) RBL-1Bb-8: 3#10, 1#10G (GATE) RBL-1Bb-19: 2#10, 1#10G (PEDESTAL) 11. PROVIDE CONDUIT FITTING AND ROUTE DOWN FACE OF EXTERIOR WALL. SEAL PROVIDE CONDUIT FITTING AND ROUTE DOWN FACE OF EXTERIOR WALL. SEAL PENETRATION WATERTIGHT. EXISTING PENETRATIONS THROUGH WALL FOR REMOVED EQUIPMENT MAY BE USED TO THE EXTENT POSSIBLE. 12. SECURITY COMMUNICATIONS/LV CONDUCTORS SHALL BE PROVIDED BY SECURITY COMMUNICATIONS/LV CONDUCTORS SHALL BE PROVIDED BY GOVERNMENT SECURITY VENDOR. COORDINATE REQUIREMENTS WITH VENDOR. REQUIREMENTS WITH VENDOR. PROVIDE ALL REQUIRED CONDUIT. 13. PROVIDE (1) 1" CONDUIT FOR EACH VEHICLE LOOP WIRE. PROVIDE (1) 1" CONDUIT FOR EACH VEHICLE LOOP WIRE. 14. PROVIDE (1) 3/4" CONDUIT WITH PULL STRING FOR SECURITY PROVIDE (1) 3/4" CONDUIT WITH PULL STRING FOR SECURITY INTERCONNECTION TO OVERHEAD DOOR CONTROLLER. COORDINATE REQUIREMENTS WITH SECURITY VENDOR. 15. REFER TO HANDHOLE DETAILS `1' AND `2' ON EP103. REFER TO HANDHOLE DETAILS `1' AND `2' ON EP103. 16. INTERCEPT EXISTING SITE LIGHTING CIRCUIT AND EXTEND TO TYPE A POLE INTERCEPT EXISTING SITE LIGHTING CIRCUIT AND EXTEND TO TYPE A POLE LIGHT. PROVIDE HANDHOLE. MODIFY/EXTEND EXISTING CIRCUIT AS REQUIRED. WIRING CONNECTIONS WITHIN HANHOLE SHALL BE EPOXY FILLED FOR WATER TIGHT CONNECTIONS. 17. REFER TO DETAIL 4 POLE BASE DETAIL ON EP103. REFER TO DETAIL 4 POLE BASE DETAIL ON EP103. 18. VERIFY LOCATION OF EXISTING UNDERGROUND LIGHTING CIRCUIT. VERIFY LOCATION OF EXISTING UNDERGROUND LIGHTING CIRCUIT. 19. PROVIDE POWER SUPPLY FOR TYPE B LIGHTING FIXTURE. MOUNT TO PROVIDE POWER SUPPLY FOR TYPE B LIGHTING FIXTURE. MOUNT TO PEDESTAL BASE. ROUTE LOW VOLTAGE WIRING WITHIN PEDESTAL. 20. PROVIDE 1 INCH CONDUIT SLEEVE THROUGH WALL FOR PASSAGE OF TRAFFIC PROVIDE 1 INCH CONDUIT SLEEVE THROUGH WALL FOR PASSAGE OF TRAFFIC LOOP WIRES. COORDINATE REQUIREMENTS WITH LOOP WIRE PROVIDER. 21. ROUTE CONDUITS WITH PULL STRING CONCEALED ABOVE CEILING TO ABOVE ROUTE CONDUITS WITH PULL STRING CONCEALED ABOVE CEILING TO ABOVE EXISTING SECURITY FLOOR MOUNTED CABINETS. BUSH END OF CONDUITS. 22. ROUTE CONDUITS EXPOSED IN INMATE CORRIDOR. COORDINATE ROUTE WITH ROUTE CONDUITS EXPOSED IN INMATE CORRIDOR. COORDINATE ROUTE WITH EXISTING CONDUITS IN CORRIDOR. 23. MOUNT LIGHTING FIXTURE TO UNDERSIDE OF THE GUARD SHACK ROOF MOUNT LIGHTING FIXTURE TO UNDERSIDE OF THE GUARD SHACK ROOF OVERHANG AT LOCATIONS OF PREVIOUS FLOOD LIGHT FIXTURE. CONNECT TO EXISTING FLOOD LIGHT CIRCUIT. MODIFY/EXTEND WIRING AND RACEWAYS AS REQUIRED. 24. PROVIDE 12"X12" HANDHOLE AT EACH LOOP WIRE JUNCTION. REFER TO PROVIDE 12"X12" HANDHOLE AT EACH LOOP WIRE JUNCTION. REFER TO HANDHOLE DETAILS '1' AND '2' ON EP103. HANDHOLE SHALL BE TRAFFIC RATED TIER 22. 25. PROVIDE HORN/STROBE WARNING SIGNAL FOR EACH BARRIER ARM SYSTEM. PROVIDE HORN/STROBE WARNING SIGNAL FOR EACH BARRIER ARM SYSTEM. SIGNAL SHALL BE EXTERIOR RATED, 120V. PROVIDE ALL REQUIRED RELAYS, WIRING, RACEWAYS, AND INTERCONNECT TO SECURITY GATE AND SECURITY SYSTEM TO ALARM WHEN GATE IS OPENING & CLOSING. COORDINATE REQUIREMENTS WITH GATE PROVIDER AND SECURITY VENDOR. MOUNT TO GATE HOUSING. HORN/STROBE SHALL BE MAXI-SIGNAL 120-31T-STROBE OR APPROVED EQUAL.

AutoCAD SHX Text

GENERAL ELECTRICAL NOTES:

AutoCAD SHX Text

NOTES:

AutoCAD SHX Text

SCALE: 1/16" = 1'-0"

AutoCAD SHX Text

%%UBASEMENT RACEWAY PLAN

PROPERTY OF THE

UNITED STATES GOVERNMENT

FOR OFFICIAL USE ONLY

SHEET OF

DISCIPLINE

DRAWING NO.

DRAWN BYDATE

PCN NO.

GSA PM

PROJ. DESC.

BLDG NO.

CITY/ST./ZIP

STREET

BLDG NAME

MARK

FLOOR NO.

DATEDESCRIPTION

REVISION

TITLE

GENERAL SERVICES ADMINISTRATION

SHEET DESIGNATOR

SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.

SHEET SIZE

SUB A/E

PRIME A/E

CONS. CONTR.

A/E CON. NO.

C O N

TR

A C

TO

R S

CONSTR. CON.

A/E TASK NO.

CONS. WORK

CONTRACTOR INFO

MELVIN-PRICE FEDERAL BUILDING

BRETT ETLING

905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com

IL0301ES

750 EAST MISSOURI AVE.

EAST SAINT LOUIS

GSA SECURITY UPGRADE

10-10-2018

30x42

IL 62201

GS-05-P-17-SC-D-0001

47PF-0018F-0230

GUIDON BCCLT JV LLC

ELECTRICAL DETAILS

JEM

L1 ELEC

EP103

S

TA T E OF I L L I N

OFESSIONAL

ENINEE

OF

AutoCAD SHX Text 5'-0"

AutoCAD SHX Text

24" DIA.

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text 6"

AutoCAD SHX Text

FINAL GRADE

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text

3" CLEAR

AutoCAD SHX Text

HIGH QUALITY GROUTED

AutoCAD SHX Text

FINISH ON BASE

AutoCAD SHX Text

SIX (6) #5 BARS

AutoCAD SHX Text

EQUALLY SPACED

AutoCAD SHX Text

#4 HOOP, TIE

AutoCAD SHX Text @ 12 C-C

AutoCAD SHX Text

CONCRETE BASE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

HAND HOLE

AutoCAD SHX Text

REMOVABLE BASE

AutoCAD SHX Text

ANCHOR BOLTS

AutoCAD SHX Text

1" CHAMFER

AutoCAD SHX Text

GROUT UNDER

AutoCAD SHX Text

ENTIRE BASE

AutoCAD SHX Text

GROUND ROD

AutoCAD SHX Text 1/2"x8'-0"

AutoCAD SHX Text

#4 BARE STRANDED COPPER

AutoCAD SHX Text

GROUND CABLE. BOND TO

AutoCAD SHX Text

CONDUITS, ANCHOR BOLTS,

AutoCAD SHX Text

STEEL REINFORCEMENT, AND

AutoCAD SHX Text

LIGHTING POLE

AutoCAD SHX Text

LIGHTING FIXTURE

AutoCAD SHX Text

AS INDICATED

AutoCAD SHX Text POLE FOR SECURITY CAMERA SHALL MATCH LIGHTING POLE, EXCEPT FOR HEIGHT. COORDINATE REQUIREMENTS WITH GOVERNMENT'S SECURITY VENDOR.

AutoCAD SHX Text

%%UELECTRIC HANDHOLE DETAIL

AutoCAD SHX Text

%%U INSTALLATION IN TURF AREAS

AutoCAD SHX Text 6"

AutoCAD SHX Text

VARIES

AutoCAD SHX Text

CLEAN Ô"

AutoCAD SHX Text

CRUSHED ROCK

AutoCAD SHX Text

HANDHOLE

AutoCAD SHX Text A. REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR REFER TO GENERAL ELECTRICAL NOTES ON SHEET EP101 FOR ADDITIONAL DETAILS AND REQUIREMENTS. B. ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE ALL CONDUITS FOR SECURITY CABLING SHALL BE PAINTED BLUE PER GOVERNMENT STANDARD.

AutoCAD SHX Text

GENERAL ELECTRICAL NOTES:

AutoCAD SHX Text

%%U SECURITY GATE DIAGRAM

AutoCAD SHX Text

CONDUIT(S) WITH BELL ENDS (TYP). SIZE, QUANTITY AND WIRING AS INDICATED ON PLANS

AutoCAD SHX Text

1" CONDUIT FOR POWER INFEED

AutoCAD SHX Text

1" CONDUIT FOR LV COMMUNICATIONS

AutoCAD SHX Text 5/8" x 8'-0" GROUND ROD

AutoCAD SHX Text 1" CONDUIT FOR VEHICLE LOOP WIRES. PROVIDE INDIVIDUAL CONDUIT PER LOOP.ENTIRE LOOP WIRE SHALL BE INSTALLED WITHIN CONDUIT. PROVIDE JUNCTION BOX IN PAVEMENT AT EACH LOOP JUNCTION. LOCATE AS DIRECTED BY MANUFACTURER.

AutoCAD SHX Text

3/4" CONDUIT FOR CATCH POST AUXILIARY DEVICES

AutoCAD SHX Text

3/4" CONDUIT FOR CATCH POST HEATER

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

PIVOT POST

AutoCAD SHX Text

CATCH POST

AutoCAD SHX Text

MAIN BREAKER

AutoCAD SHX Text 100A/3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text %%UEXIST. PANEL RBL-1Bb

AutoCAD SHX Text

%%UBUSSING DIAGRAM

AutoCAD SHX Text 20A/2

AutoCAD SHX Text 20A/2

AutoCAD SHX Text 30A/3

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/3

AutoCAD SHX Text 20A/1

AutoCAD SHX Text 20A/3

AutoCAD SHX Text

GARAGE DOOR

AutoCAD SHX Text

HVAC TRANS.

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

SPACE

AutoCAD SHX Text

NORTH SECURITY GATE, NOTE 1

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

PARKING LOT VEHICLE GATE

AutoCAD SHX Text

EXISTING LOAD

AutoCAD SHX Text

SOUTH SECURITY GATE, NOTE 1

AutoCAD SHX Text

ACCESS CONTROL PEDESTAL, NOTE 2

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

RECEPT. - GARAGE, SEC. MONITOR, NOTE 2

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

SPARE

AutoCAD SHX Text GRADE. FEATHER AND TAMP BACKFILL TO CREATE FLUSH INSTALLATION AND POSITIVE DRAINAGE AWAY FROM BOX

AutoCAD SHX Text

3/4" CONDUIT FOR EARTH GROUND

AutoCAD SHX Text

100A, MAIN BREAKER 208Y/120V 3 , 4W, 30 CKT.GENERAL ELECTRIC A SERIES, II PANEL

AutoCAD SHX Text

1. PROVIDE BREAKER. PROVIDE BREAKER. 2. UTILIZE EXISTING BREAKER.UTILIZE EXISTING BREAKER.

AutoCAD SHX Text

NOTES:

AutoCAD SHX Text W

AutoCAD SHX Text D

AutoCAD SHX Text

SKID RESISTANT

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text L

AutoCAD SHX Text

ELECTRIC

AutoCAD SHX Text

%%UBOX

AutoCAD SHX Text

%%UCOVER

AutoCAD SHX Text

POLYMER CONCRETE COVER.

AutoCAD SHX Text

1/2" X 2 1/2" " X 2 1/2" " PULL SLOT

AutoCAD SHX Text

LOGO AS SPECIFIED.

AutoCAD SHX Text

PROVIDE GASKET BETWEEN COVER AND BOX

AutoCAD SHX Text

DIMENSIONS AS INDICATED

AutoCAD SHX Text

POLYMER CONCRETE SIDES WITH NO BASE

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

%%U ELECTRIC HANDHOLE DETAIL

AutoCAD SHX Text

STAINLESS STEEL HEAVY DUTY BOLT AND WASHER, WITH STAINLESS STEEL INSERTS, TYP.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

LIGHTING FIXTURE SCHEDULE

AutoCAD SHX Text

POLE: DB9 4F14-188 14'

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

FIXTURE SERIES

AutoCAD SHX Text

METAL

AutoCAD SHX Text

LAMP

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

BALLAST

AutoCAD SHX Text

FACTOR

AutoCAD SHX Text

HIGH POWER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WATTS

AutoCAD SHX Text

NO.

AutoCAD SHX Text

FIXTURE

AutoCAD SHX Text

VOLTAGE

AutoCAD SHX Text

POLE

AutoCAD SHX Text

MOUNTING

AutoCAD SHX Text

LIGHT: PRM3 V5 250PSMH AGN SLA7-2

AutoCAD SHX Text

TRANSFORMER: 9075-TRN-SS

AutoCAD SHX Text

LED

AutoCAD SHX Text

FACTOR

AutoCAD SHX Text

HIGH POWER

AutoCAD SHX Text 1.4

AutoCAD SHX Text

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

LIGHT: 7031 30 GH

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text DECORATIVE SITE LIGHTING POLE WITH (2) LIGHTING FIXTURES SIMILAR TO THE EXISTING SITE POLE FIXTURES. LIGHTING FIXTURE SHALL BE ROUND, 18" DIA, WITH SAG LENS, TYPE V CUTOFF LIGHT DISTRIBUTION, CAST ALUMINUM CONSTRUCTION, STAINLESS STEEL HARDWARE. COLOR SHALL MATCH EXISTING FIXTURES. PROVIDE COMPLETE WITH FIXTURES, POLE, REINFORCED CONCRETE BASE, AND ALL REQUIRED MOUNTING ACCESSORIES. POLE SHALL BE ROUND WITH FLUTED DECORATIVE BASE. POLE HEIGHT SHALL MATCH HEIGHT OF EXISTING SITE POLE LIGHTING.

AutoCAD SHX Text 3"L LED HARDSCAPE LIGHTING FIXTURE (OVERALL 4.5"L x 3"W x 1"D) WITH TRANSLUCENT DIFFUSER, STAINLESS STEEL TAMPER RESISTANT SCREWS, IP66 RATED, AND ALUMINUM HOUSING WITH GRAPHITE COLOR. PROVIDE WITH ASSOCIATED STEP DOWN TRANSFORMER. TRANSFORMER SHALL BE IP65 RATED FOR OUTDOOR MOUNTING AND INTEGRAL ELECTRONIC TIMER. TRANSFORMER SHALL BE HARDWIRED.

AutoCAD SHX Text

HALIDE

AutoCAD SHX Text 3000K

AutoCAD SHX Text

ARCHITECTURAL AREA LIGHTING

AutoCAD SHX Text

120/208 (MATCH EXISTING CIRCUIT VOLTAGE)

AutoCAD SHX Text

WAC LIGHTING

AutoCAD SHX Text

AutoCAD SHX Text

%%UPOLE BASE DETAIL

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LED

AutoCAD SHX Text

FACTOR

AutoCAD SHX Text

HIGH POWER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text

DSXF1 LED P1 40K MFL VG

AutoCAD SHX Text C

AutoCAD SHX Text 9"W x 7.75"H x 3"D LED FLOOD LIGHT WITH DIE-CAST ALUMINUM BLACK HOUSING, MEDIUM FLOOD LIGHT DISTRIBUTION, ADJUSTABLE KNUCKLE FOR AIMING, CLEAR TEMPERED GLASS LENS, AND VANDAL GUARD.

AutoCAD SHX Text 4000K

AutoCAD SHX Text

LITHONIA

AutoCAD SHX Text

AutoCAD SHX Text

PROVIDE WITH MOGUL BASE TO MATCH BASE

AutoCAD SHX Text

OF PROVIDED LED RETROFIT LAMP

AutoCAD SHX Text PROVIDE LED RETROFIT LAMP. LAMP SHALL BE 45 WATTS, 5800 LUMENS, WESTINGHOUSE T30 HIGH LUMEN LED LAMP. VERIFY PHYSICAL DIMENSIONS OF LAMP AND FIXTURE. LAMP SHALL FIT WITHIN FIXTURE HOUSING. MODIFY THE FIXTURE TO ACCEPT LED REPLACEMENT LAMP.

Sheets and Views
GI001 COVER SHEET
GI002 GENERAL NOTES
GI003 PHASING PLAN
CD101 DEMOLITION PLAN
CS101 SITE PLAN - NEW WORK
CS102 LOOP DETECTOR LAYOUT PLAN - NEW WORK
CS501 SITE DETAILS
CS502 RAM-PROOF BARRIER GATE DETAILS - NEW WORK
CG101 GRADING PLAN - NEW WORK