Attachment_3-Final_ESL_Snow_Melt_Dwg_2.27.18.pdf
PDF 3 MB Posted
- Attached to
- USMS Security Barrier Replacement Federal contract opportunity
- Solicitation number
- 47PF0019R0010
About this file
Attachment 3-Amendment 01-Snow Melt DWGS
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_3-Updated_SF1442-14b.pdf | ||
| Amendment_03-Updated_Snow_Melt_Dwgs_and_Cost_Breakdown.pdf | ||
| Attachment_1-ESL_Snow_Melt_Dwg_Add._2_Final_3.14.19_(1).pdf | ||
| Attachment_2-Revise_Contract_Price_Form.docx | DOCX document | |
| Amendment_02-ESL_USMS_Security_Barrier.pdf | ||
| Amendment_01-USMS_Security_Barrier_Replacement-GC-1.pdf | ||
| Attachment_2-GSA_Security_Barrier_Replacement_Div_22_&_23_Specs.pdf | ||
| Attachment_1-GSA_Security_Barrier_Upgrade_Rev._1_Construction_Documents_-_Plans.pdf | ||
| H1-Final_Construction_Documents_-_Plans_USMS_Sec_Barrier.pdf | ||
| RFP_47PF00-19R-0010.pdf | ||
| H2-Final_Construction_Documents_-_Specifications_USMS_Sec_Barrier.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCHEDULE OF PLUMBING FIXTURES AND CONNECTIONSRDL
GREAT LAKES REGION 5
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BYDATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N
TR
A C
TO
R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
MELVIN-PRICE FEDERAL BUILDING
BRETT ETLING
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
750 EAST MISSOURI AVE.
EAST SAINT LOUIS
GSA SECURITY UPGRADE
02-27-2019
30x42
IL 62201
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
RIL11680
P-1-01
WI
LL
IAM J. HOSMON
STATE OF ILLINO
IS
62-57780 registered professional engineer of
02-27-19
AutoCAD SHX Text
UP
AutoCAD SHX Text 253.00'(R)
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text G
AutoCAD SHX Text G
AutoCAD SHX Text
EX. 4"
AutoCAD SHX Text G
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text PIPING TO BE INSTALLED ABOVE LAY-IN CEILING. CONTRACTOR SHALL REMOVE AND REINSTALL CEILING TILES AS NECESSARY FOR INSTALLATION OF PIPES, ANY DAMAGED CEILING TILES SHALL BE REPLACED.
AutoCAD SHX Text
CW
AutoCAD SHX Text
CW
AutoCAD SHX Text G
AutoCAD SHX Text PIPING TO BE INSTALLED ABOVE GYP. BOARD CEILING. CONTRACTOR SHALL REMOVE AND REPLACE (FIRE RATED) CEILING INCLUDING FINISHING, PRIMING, AND PAINTING TO MATCH AS NECESSARY FOR INSTALLATION OF PIPES.
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text 2"
AutoCAD SHX Text
%%UHB1
AutoCAD SHX Text 34" CW-DN TO HOSE BIB. PROVIDE CHEMELEX 5BTV-1-CT OR EQUAL 120V, 5W/FT HEAT TRACING (SELF-REGULATING) ON EXPOSED PIPE BETWEEN THE CEILING AND THE HOSE BIB. HEAT TRACING TO INCLUDE JUNCTION BO, AMBIENT TEMPERATURE SENSOR, AND SEAL, AND INSULATION INSTALLED TO MANUFACTURER'S RECOMMENDATIONS. PROVIDE CURRENT SENSOR FOR MONITORING OF HEAT TRACE OPERATION MONITORING AT FRONT END BMS.
AutoCAD SHX Text
EX. 3"
AutoCAD SHX Text
EX. 2"
AutoCAD SHX Text
EX. 2"
AutoCAD SHX Text
EX. 2"
AutoCAD SHX Text
EX. 3"
AutoCAD SHX Text
GAS VENT TERMINATION (SEE DETAIL)
AutoCAD SHX Text
34" G-DN TO BOILER
AutoCAD SHX Text
BOILER
AutoCAD SHX Text
EXPANSION TANK
AutoCAD SHX Text
HYDRONIC PUMPS
AutoCAD SHX Text
AIR SEPARATOR
AutoCAD SHX Text
GLYCOL FEEDER
AutoCAD SHX Text
GAS PRV. SEE DETAIL
AutoCAD SHX Text
GV
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 34"
AutoCAD SHX Text 34"
AutoCAD SHX Text 34"
AutoCAD SHX Text 34"
AutoCAD SHX Text 12"
AutoCAD SHX Text
EX. 1 "12"
AutoCAD SHX Text
FAUCET / VALVE
AutoCAD SHX Text
DRAIN
AutoCAD SHX Text
DOMESTIC
AutoCAD SHX Text
CW
AutoCAD SHX Text
DOMESTIC
AutoCAD SHX Text
HW
AutoCAD SHX Text
SANITARY
AutoCAD SHX Text
WASTE
AutoCAD SHX Text
SANITARY
AutoCAD SHX Text
VENT
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
SUPPLY STOPS
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
AND MODEL
AutoCAD SHX Text
DOMESTIC
AutoCAD SHX Text
TW
AutoCAD SHX Text
MARK
AutoCAD SHX Text
TAILPIECE
AutoCAD SHX Text
P-TRAP
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
CENTERS
AutoCAD SHX Text
HANDLES
AutoCAD SHX Text
SPOUT
AutoCAD SHX Text
MARK
AutoCAD SHX Text
FIXTURE
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MODEL NO.
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
STYLE
AutoCAD SHX Text
MANUFACTURER & MODEL
AutoCAD SHX Text
HB1
AutoCAD SHX Text
HOSE BIBB
AutoCAD SHX Text
WALL MOUNT
AutoCAD SHX Text
CHROME PLATED SOLID BRASS
AutoCAD SHX Text
LOOSE KEY
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text CERAMIC 1/4 TURN OPERATING CARTRIDGE. PROVIDE VACUUM BREAKER. MOUNT 18" ABOVE FINISHED FLOOR.
AutoCAD SHX Text
HB1
AutoCAD SHX Text 34"
AutoCAD SHX Text
ZURN
AutoCAD SHX Text Z875L7
AutoCAD SHX Text
PLUMBING_PLAN_NEW_WORK
AutoCAD SHX Text
TRC
AutoCAD SHX Text L1
AutoCAD SHX Text
MECH
AutoCAD SHX Text P101
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: Ê" = 1'-0"
AutoCAD SHX Text
%%UPLUMBING PLAN
AutoCAD SHX Text
SECURITY GATE BACK-UP POWER INVERTER
AutoCAD SHX Text
EX. DOOR CONTROLS
AutoCAD SHX Text
CONNECTION POINT-
AutoCAD SHX Text
END CAP
AutoCAD SHX Text
NEW TO EXISTING
AutoCAD SHX Text
BRANCH CONNECTION
AutoCAD SHX Text
VALVE IN VERTICAL
AutoCAD SHX Text
RISER DOWN
AutoCAD SHX Text
RISER UP
AutoCAD SHX Text
RISER OR DROP
AutoCAD SHX Text
FLOW-IN DIRECTION
AutoCAD SHX Text
OF ARROW
AutoCAD SHX Text
UNION
AutoCAD SHX Text
SHUT-OFF VALVE
AutoCAD SHX Text
%%USYMBOLS
AutoCAD SHX Text
CW
AutoCAD SHX Text G
AutoCAD SHX Text
DOMESTIC COLD WATER
AutoCAD SHX Text
NATURAL GAS
AutoCAD SHX Text
WATER HAMMER ARRESTOR
AutoCAD SHX Text A
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
AutoCAD SHX Text
KEY NOTE
AutoCAD SHX Text
%%UABBREVIATION
AutoCAD SHX Text
%%UPLUMBING LEGEND
AutoCAD SHX Text
DOMESTIC COLD WATER
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
NATURAL GAS
AutoCAD SHX Text
CW
AutoCAD SHX Text
EX
AutoCAD SHX Text G
AutoCAD SHX Text
RELIEF VENT
AutoCAD SHX Text
RV
AutoCAD SHX Text
REDUCED PRESSURE BACKFLOW
AutoCAD SHX Text
RPBP
AutoCAD SHX Text
PREVENTER
AutoCAD SHX Text
VENT
AutoCAD SHX Text
HOSE BIBB
AutoCAD SHX Text
HOSE BIBB
AutoCAD SHX Text
HB
AutoCAD SHX Text
%%UPIPE SLEEVE DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
%%UEXTERIOR WALL
AutoCAD SHX Text
CORE DRILL
AutoCAD SHX Text
WALL
AutoCAD SHX Text A
AutoCAD SHX Text
PROVIDE ACCESS PANEL FOR WATER HAMMER ARRESTOR.
AutoCAD SHX Text
*ZURN MODELS ARE FOR MINIMUM QUALITY.
AutoCAD SHX Text
WATER HAMMER ARRESTER SCHEDULE
AutoCAD SHX Text
AutoCAD SHX Text 155-330
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text 114-154
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text 61-113
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text 33-60
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text 12-32
AutoCAD SHX Text B
AutoCAD SHX Text 1-11
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
IDENTIFICATION
AutoCAD SHX Text
SERIES Z-1700
AutoCAD SHX Text
*ZURN MODEL
AutoCAD SHX Text
FIXTURE UNITS
AutoCAD SHX Text
ARRESTER
AutoCAD SHX Text
WATER HAMMER
AutoCAD SHX Text
%%UGAS VENT TERMINATION DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
TURN PIPING DOWN TOWARDS GROUND
AutoCAD SHX Text
GAS VENT FROM PRV OR GAS TRAIN
AutoCAD SHX Text
SEE EXTERIOR WALL PIPE SLEEVE DETAIL.
AutoCAD SHX Text
WALL
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
INDOOR INSTALLATION
AutoCAD SHX Text
%%UGAS PRV INSTALLATION DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text NPS 2 AND SMALLER: GAS BALL VALVE, NPS 2 AND LARGER: 12 AND LARGER: GAS PLUG VALVE
AutoCAD SHX Text
Y-STRAINER
AutoCAD SHX Text
BUILDING ENVELOP
AutoCAD SHX Text
VENT TERMINATION (SEE GAS VENT TERMINATION DETAIL)
AutoCAD SHX Text
VENT PRV TO THE OUTSIDE, WHERE APPLICABLE
AutoCAD SHX Text
38" NIPPLE AND GAS BALL VALVE WITH CAP FOR PRESSURE GAGE ATTACHMENT (TYP)
AutoCAD SHX Text
REFERENCE FLOOR PLANS FOR PIPE SIZE
AutoCAD SHX Text
REDUCED PRESSURE
AutoCAD SHX Text
SUPPLY PRESSURE
AutoCAD SHX Text
BRASS BUG SCREEN SECURED WITH STAINLESS STEEL CLAMP
AutoCAD SHX Text
STRAINER
AutoCAD SHX Text
NATURAL GAS VENT
AutoCAD SHX Text
GV
AutoCAD SHX Text
GAS COCK
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
STAINLESS STEEL ESCUTCHEON.
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BYDATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N
TR
A C
TO
R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
MELVIN-PRICE FEDERAL BUILDING
BRETT ETLING
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
750 EAST MISSOURI AVE.
EAST SAINT LOUIS
GSA SECURITY UPGRADE
02-27-2019
30x42
IL 62201
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
RIL11680
WI
LL
IAM J. HOSMON
STATE OF ILLINO
IS
62-57780
02-27-19 registered professional engineer of
AutoCAD SHX Text
UP
AutoCAD SHX Text
8TH STREET
AutoCAD SHX Text
PWP
AutoCAD SHX Text
DN.
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text ALERTON CONTROL FOR AHU-6LL. CONNECT SNOW MELT CONTROL PANEL VIA BACNET MSTP TO AHU-6LL ALTERON CONTROL FOR CONNECTION TO EXISTING FRONT END BMS JACE LOCATED IN THE TOP FLOOR ATRIUM.
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text M
AutoCAD SHX Text
PARKING GARAGE
AutoCAD SHX Text T
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text M
AutoCAD SHX Text
PARKING GARAGE
AutoCAD SHX Text
GUARD
AutoCAD SHX Text
SHACK
AutoCAD SHX Text T
AutoCAD SHX Text
MECHANICAL_DETAILS_NEW_WORK
AutoCAD SHX Text
TRC
AutoCAD SHX Text L1
AutoCAD SHX Text
MECH
AutoCAD SHX Text M101
AutoCAD SHX Text
AutoCAD SHX Text
%%UB-1
AutoCAD SHX Text
%%UP-2
AutoCAD SHX Text
%%UET-1
AutoCAD SHX Text
%%UP-1
AutoCAD SHX Text
SEE PIPING DIAGRAM FOR CONTINUATION
AutoCAD SHX Text
%%UGF-1
AutoCAD SHX Text
SNOW MELT CONTROL PANEL
AutoCAD SHX Text 1 " STAINLESS STEEL MANIFOLD PROVIDED WITH SNOW 12" STAINLESS STEEL MANIFOLD PROVIDED WITH SNOW MELT SYSTEM CONTRACTOR TO PROVIDE 31"x27"x5" NEMA 4 WEATHER RESISTANT ENCLOSURE. CONCEAL TUBES WITH LINE SET COVERS FROM THE ENCLOSURE TO GRADE.
AutoCAD SHX Text
1Ð"HWS&R
AutoCAD SHX Text SNOW MELT SYSTEM " RADIANTPEX+ BARRIER TUBING SPACED 34" RADIANTPEX+ BARRIER TUBING SPACED AT 12" O.C. PROVIDED WITH 1 " STAINLESS STEEL MANIFOLD. 12" STAINLESS STEEL MANIFOLD. COORDINATE TUBING WITH SENSOR LOOP WIRE JUNCTION BOXES WITH ELECTRICAL CONTRACTOR PRIOR TO TUBING ROUGH-IN. FLEX TUBING AROUND JUNCTION BOXES AS REQUIRED. DETAILS OF SNOW MELT SYSTEM SHALL CONFORM TO MANUFACTURER'S REQUIREMENTS.
AutoCAD SHX Text PHASE INSTALLATION SO ONE LANE IS ALWAYS OPEN. WHEN INSTALLING THE FIRST LANE, LEAVE 18" WIDE OPENING IN BETWEEN LANES FOR COILS TO EXIT. STORE COILS HERE UNTIL THE SECOND LANE DEMO IS COMPLETE.
AutoCAD SHX Text
SCALE: Ê" = 1'-0"
AutoCAD SHX Text
%%UHVAC PIPING PLAN
AutoCAD SHX Text
%%UAS-1
AutoCAD SHX Text ROUTE " RADIANTPEX+ BARRIER TUBING FROM 34" RADIANTPEX+ BARRIER TUBING FROM DRIVEWAY LOOPS TO MANIFOLD (TYP.OF 12). COORDINATE BURIED TUBING WITH POWER CONDUIT AND COMMUNICATION CONDUITS. REFERENCE ELECTRICAL DRAWINGS
AutoCAD SHX Text
MOISTURE SENSOR
AutoCAD SHX Text
SEE ENLARGED PLAN ON THIS SHEET
AutoCAD SHX Text
SCALE: Ì" = 1'-0"
AutoCAD SHX Text
%%UHVAC ENLARGED PLAN
AutoCAD SHX Text
3" AIR INTAKE AND VENT TO FLUSH MOUNT VENT KIT
AutoCAD SHX Text
SECURITY BARRIER
AutoCAD SHX Text
VEHICLE DETECTION LOOP, TYP.
AutoCAD SHX Text
BOLLARD, TYP.
AutoCAD SHX Text
REFER TO CIVIL PLANS FOR ADDITIONAL INFORMATION ON SLAB CONSTRUCTION
AutoCAD SHX Text
SECURITY BARRIER
AutoCAD SHX Text
OUTDOOR TEMPERATURE SENSOR
AutoCAD SHX Text
SECURITY GATE BACK-UP POWER INVERTER
AutoCAD SHX Text
EX. DOOR CONTROLS
AutoCAD SHX Text
TRENCH DRAIN
AutoCAD SHX Text
ELECTRICAL JUNCTION BOX (TYP.)
AutoCAD SHX Text
%%UUNDERSLAB AND EDGE INSULATION DETIAL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
GRADE
AutoCAD SHX Text
COMPACTED GRADE - SEE
AutoCAD SHX Text
CONCRETE SLAB - SEE ARCHITECTURAL
AutoCAD SHX Text
ARCHITECTURAL DRAWINGS
AutoCAD SHX Text
1" THICK EDGE
AutoCAD SHX Text
ARCHITECTURAL DRAWINGS FOR DETAILS.
AutoCAD SHX Text
1" THICK UNDER-
AutoCAD SHX Text
SLAB INSULATION
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
PEX TUBING
AutoCAD SHX Text
FOAM BOARD STAPLES
AutoCAD SHX Text
SPACE 18" ON CENTER
AutoCAD SHX Text
%%UEXPANSION JOINT DETAIL
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
COMPACTED GRADE - SEE
AutoCAD SHX Text
12" PIPE WRAP SLEEVE
AutoCAD SHX Text
ARCHITECTURAL DRAWINGS FOR DETAILS.
AutoCAD SHX Text
1" THICK RIGID UNDER-
AutoCAD SHX Text
SLAB INSULATION
AutoCAD SHX Text
PEX TUBING
AutoCAD SHX Text
FOAM BOARD STAPLES
AutoCAD SHX Text
SPACE 18" ON CENTER
AutoCAD SHX Text
CONCRETE SLAB - SEE
AutoCAD SHX Text
ARCHITECTURAL DRAWINGS
AutoCAD SHX Text
FOR DETAILS.
AutoCAD SHX Text
EXPANSION JOINT - SEE ARCHITECTURAL
AutoCAD SHX Text
1/2" SEALANT
DRAWINGS FOR DETAILS.
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BYDATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N
TR
A C
TO
R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
MELVIN-PRICE FEDERAL BUILDING
BRETT ETLING
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
750 EAST MISSOURI AVE.
EAST SAINT LOUIS
GSA SECURITY UPGRADE
02-27-2019
30x42
IL 62201
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
RIL11680
WI
LL
IAM J. HOSMON
STATE OF ILLINO
IS
62-57780 registered professional engineer of
02-27-19
AutoCAD SHX Text
SCHEDULE OF BOILER
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
HEATING MBH CAPACITY INPUT
AutoCAD SHX Text
HEATING MBH CAPACITY OUTPUT
AutoCAD SHX Text
ELECTRICAL CHARACTERISTICS
AutoCAD SHX Text
NOTES
AutoCAD SHX Text B-1
AutoCAD SHX Text
LAARS
AutoCAD SHX Text
NEOTHERM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 120/1
AutoCAD SHX Text 1,2,3
AutoCAD SHX Text NOTES: 1. PROVIDE WITH SINGLE POINT POWER CONNECTION. 2. PROVIDE WITH FLUSH MOUNT VENT KIT. 3. PROVIDE WITH FACTORY MOUNTED BACNET CONTROLS.
AutoCAD SHX Text
SCHEDULE OF EXPANSION TANK
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
USAGE
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
ACCEPTANCE VOLUME
AutoCAD SHX Text
TOTAL VOLUME
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
ET-1
AutoCAD SHX Text
HOT WATER
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
ETSX-30
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1,2,3
AutoCAD SHX Text NOTES: 1. CHARGE TO 12 PSI. 2. TANK SHALL BE ASME DIAPHRAM TANK. 3. MAXIMUM PRESSURE: 75 PSI @ 220° F.
AutoCAD SHX Text
SCHEDULE OF GLYCOL FEED SYSTEM
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
TANK GALLONS
AutoCAD SHX Text
ELECTRICAL CHARACTERISTICS
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
GF-1
AutoCAD SHX Text
WESSELS
AutoCAD SHX Text G-Series
AutoCAD SHX Text
AutoCAD SHX Text 110V
AutoCAD SHX Text 1,2,3,4
AutoCAD SHX Text NOTES: 1. PROVIDE ALARM KIT WITH GLYCOL FEED PANEL, FLOAT AND ALARM CONTACT CLOSURE FOR USE WITH REMOTE ALARM TO BMS SYSTEM. 2. PROVIDE WITH WALL MOUNTING SHELF 3. PANEL SHALL BE FACTORY MOUNTED TO STORAGE TANK. ALL INTERCONNECTING CONTROLS, CONDUITS AND OTHER REQUIRED COMPONENTS SHALL BE PROVIDED FOR A COMPLETE OPERABLE SYSTEM. 4. GLYCOL FEED SYSTEM SHALL MAINTAIN 40% GLYCOL SOLUTION.
AutoCAD SHX Text
SCHEDULE OF PUMPS
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
SERIES
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
GPM
AutoCAD SHX Text
HEAD/FOOT
AutoCAD SHX Text
MOTOR W
AutoCAD SHX Text
ELECTRICAL CHARACTERISTICS
AutoCAD SHX Text
SHAFT SEALS
AutoCAD SHX Text
NOTES
AutoCAD SHX Text P-1
AutoCAD SHX Text
ARMSTRONG
AutoCAD SHX Text
ASTRO 2
AutoCAD SHX Text
268 CI
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 115/1
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
AutoCAD SHX Text P-2
AutoCAD SHX Text
ARMSTRONG
AutoCAD SHX Text
ASTRO 2
AutoCAD SHX Text
268 CI
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 115/1
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
AutoCAD SHX Text
SCHEDULE OF AIR SEPERATOR
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
USAGE
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MODEL
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
AS-1
AutoCAD SHX Text
HOT WATER
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
AS-MB
AutoCAD SHX Text 1.25
AutoCAD SHX Text 23.1
AutoCAD SHX Text
AutoCAD SHX Text T/P
AutoCAD SHX Text
DRAIN VALVE
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
%%UHOT WATER FLOW DIAGRAM & CONTROLS
AutoCAD SHX Text
%%UP-1
AutoCAD SHX Text
%%UP-2
AutoCAD SHX Text
%%UET-1
AutoCAD SHX Text
%%UB-1
AutoCAD SHX Text
CONTROL PANEL CONNECT TO WALL RECEPTICLE
AutoCAD SHX Text
FS
AutoCAD SHX Text
VALVE (TYP.)
AutoCAD SHX Text ONE (1) GAS HOT WATER BOILER (1) SAFETY RELIEF VALVE AT 100 PSI. (1) WATER LEVEL. PROBE-TYPE AUXILIARY LOW WATER CUT-OFF WITH MANUAL RESET. (1) AQUASTATL, 120°F TO 240°F, HIGH LIMIT, AUTO RE-SET.(1) AQUASTATL, 110°F TO 290°F, HIGH LIMIT, MANUAL RE-SET.(1) FIELD PROVIDED WATTS-RADIANT CONTROLLER. ADDITIONAL FEATURES (1) INTERLOCKING FLOW SWITCH, SHIPPED LOOSE PROVIDE THE FOLLOWING INFORMATION THROUGH A MODBUS CONNECTION: TO EXISTING BMS SYSTEM INLET AND OUTLET WATER TEMPERATURE STACK TEMPERATURE STATUS OF SENSORS FAN SPEED SET POINTS BURNER STATUS LOCKOUT CODES ALARM REASONS SYSTEM PUMP STATUS BOILER PUMP STATUS LOW GLYCOL HEAT TRACE STATUS
AutoCAD SHX Text
HOT WATER BOILER
AutoCAD SHX Text
RELIEF VALVE
AutoCAD SHX Text
OUTDOOR SENSOR
AutoCAD SHX Text
SNOW MELT CONTROL PANEL
AutoCAD SHX Text
RELAY
AutoCAD SHX Text
RELAY
AutoCAD SHX Text
MOISTURE SENSOR IN SLAB OF DRIVE
AutoCAD SHX Text
%%UAS-1
AutoCAD SHX Text NOTE: : 1. INITIAL FILL WITH PROPYLENE GLYCOL FOR 40% SOLUTION. INITIAL FILL WITH PROPYLENE GLYCOL FOR 40% SOLUTION. 2. CONTROLS TO BE FIELD INSTALLED BY DIV. 23 CONTRACTOR. CONTROLS TO BE FIELD INSTALLED BY DIV. 23 CONTRACTOR. 3. DIVISION 23, SPEC SECTION 230900, PROVIDER SHALL INCLUDE ALL FIELD DIVISION 23, SPEC SECTION 230900, PROVIDER SHALL INCLUDE ALL FIELD WIRING, ENGINEERING, AND PROGRAMMING FOR FULL INTEGRATION AND CONTROL OF SNOW MELT SYSTEM AT FRONT END BMS (NIAGRA M4) COMPUTER. GRAPHICS TO INCLUDE MAPPING OF HYDRONIC SYSTEM AND BOILER.
AutoCAD SHX Text
%%UGF-1
AutoCAD SHX Text
SNOW MELT SYSTEM LOOPS
AutoCAD SHX Text
34" RELIEF VALVE SET FOR 125 PSI
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
120V POWER BY DIV. 26
AutoCAD SHX Text
MECHANICAL_DETAILS_NEW_WORK
AutoCAD SHX Text
TRC
AutoCAD SHX Text L1
AutoCAD SHX Text
MECH
AutoCAD SHX Text M102
AutoCAD SHX Text
AutoCAD SHX Text BACNET MSTP TO AHU-6LL ALTERON CONTROL. COMMUNICATION WITH EXISTING FRONT END BMS JACE TO BE VIA AHU-6LL CONTROL PANEL.
AutoCAD SHX Text PROVIDE WATTS RADIANT, OR APPROVED EQUAL SNOW MELTING SYSTEM AS INDICATED. TOTAL CIRCUITS OF 6, TOTAL MANIFOLDS OF 1, AND TOTAL SNOW MELT LOAD OF 233,161 BTUH. PROVIDE HARDWIRED, OPENLY PROGRAMMABLE BACNET CONTROLLER FULLY INTEGRATED INTO BUILDINGS BMS. INCLUDED SHALL BE: : - " RADIANT PEX+ COILS 34" RADIANT PEX+ COILS -1 " SS ACCESSORIES KIT W/ 1 " FNPT ISOLATION BALL VALVES, 1 PAIR 12" SS ACCESSORIES KIT W/ 1 " FNPT ISOLATION BALL VALVES, 1 PAIR 12" FNPT ISOLATION BALL VALVES, 1 PAIR -1 " HI-FLOW FLOWMETER MANIFOLD, SS, M-6, 1 PAIR 12" HI-FLOW FLOWMETER MANIFOLD, SS, M-6, 1 PAIR 1 PAIR - " SS-T20F PEX COMPRESSION FITTINGS 34" SS-T20F PEX COMPRESSION FITTINGS -1 " SS MANIFOLD ELBOW 12" SS MANIFOLD ELBOW -1 " SS MANIFOLD PRESSURE TEST KIT 12" SS MANIFOLD PRESSURE TEST KIT -PACK OF CABLE TIES (1000) -PROFESSIONAL TUBING CUTTER -PEX UNWINDER - " PEX TERMINAL BEND SUPPORTS (2 PACK OF 10) 34" PEX TERMINAL BEND SUPPORTS (2 PACK OF 10) -PS HYDRAULIC SEPERATOR 22PGM W/TAILPIECE -1 " FNPT NA TAILPIECE SET (2) 14" FNPT NA TAILPIECE SET (2) -ARMSTRONG PUMPS AS SCHEDULED -ARMSTRONG FF150T 1 " FPTFLEX FLANGE KIT 12" FPTFLEX FLANGE KIT -WATTS AIR SEPARATOR AS SCHEDULED -WATTS EXPANSION TANK AS SCHEDULED -WATTS RBFFRESIDENTIAL BOILER FILL FITTING -WATTS LF009M2-QT RPZBACKFLOW PREVENTOR W/0881380 909-ELC -TEKMAR SNOW MELTING CONTROL, TEKMARNET, ELECTRIC OR HYDRONIC MIXING -(2) TEKMAR RELAY 24V (AC) COIL -TEKMAR 24V(AC) TRANSFORMER, 40 VA W/ MOUNTING BOX -TEKMAR SNOW/ICE SENSOR IN-SLAB W/ WIRE, LENGTH AS REQUIRED -TEKMAR SNOW/ICE SENSOR SOCKET -WESSELS GLYCOL MAKEUP UNIT AS SCHEDULED -(8) NOBLE NOBURST, 40% RTU PREMIXED PROPYLEN GLYCOL ANTI-FREESE, 5 GALLON BUCKETNOBLE NOBURST, 40% RTU PREMIXED PROPYLEN GLYCOL ANTI-FREESE, 5 GALLON BUCKET
AutoCAD SHX Text
SNOW MELT SYSTEM
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
SHT.
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
FLOW - IN DIRECTION
AutoCAD SHX Text
BALL VALVE
AutoCAD SHX Text
RISER DOWN (ELBOW)
AutoCAD SHX Text
RISER UP (ELBOW)
AutoCAD SHX Text
RISE OR DROP
AutoCAD SHX Text
MANUAL AIR VENT
AutoCAD SHX Text
TEST PLUG
AutoCAD SHX Text
PRESSURE & TEMPERATURE
AutoCAD SHX Text
PRESSURE RELIEF VALVE
AutoCAD SHX Text
OF ARROW
AutoCAD SHX Text
PRESS.
AutoCAD SHX Text O.A.
AutoCAD SHX Text
MECH.
AutoCAD SHX Text
GPM
AutoCAD SHX Text
OUTSIDE AIR
AutoCAD SHX Text
PRESSURE
AutoCAD SHX Text
GALLONS PER MINUTE
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
EXH.
AutoCAD SHX Text
EXHAUST
AutoCAD SHX Text
%%UHVAC SYMBOLS AND ABBREVIATIONS LEGEND
AutoCAD SHX Text
CAP.
AutoCAD SHX Text
BTUH
AutoCAD SHX Text
CAPACITY
AutoCAD SHX Text
BTU/HR
AutoCAD SHX Text
NOTE: NOT ALL SYMBOLS MAY BE USED.
AutoCAD SHX Text
HOT WATER SUPPLY PIPING
AutoCAD SHX Text
HOT WATER RETURN PIPING
AutoCAD SHX Text
TEMP & PRESSURE GAUGE
AutoCAD SHX Text T/P
AutoCAD SHX Text
HWR
AutoCAD SHX Text
HWS
AutoCAD SHX Text
BHP
AutoCAD SHX Text
BRAKE HORSEPOWER
AutoCAD SHX Text
MAX.
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
PSI
AutoCAD SHX Text
POUNDS PER SQUARE INCH
AutoCAD SHX Text
%%UGENERAL NOTES:
AutoCAD SHX Text A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE AREA TO BECOME FAMILIAR WITH THE EXISTING THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE AREA TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS. VERIFY SIZE, LOCATION, AND USAGE OF EXISTING UTILITIES PRIOR TO REMOVAL. FOR FURTHER INFORMATION WITH REGARD TO THE EXTENT OF REMOVALS, SEE THE CONSTRUCTION DRAWINGS AND THE ARCHITECTURAL DRAWINGS WHICH SHOW WORK TO BE PERFORMED. B. IF EQUIPMENT TO REMAIN MUST BE REMOVED DUE TO REMOVAL OR CONSTRUCTION, THE EQUIPMENT SHALL IF EQUIPMENT TO REMAIN MUST BE REMOVED DUE TO REMOVAL OR CONSTRUCTION, THE EQUIPMENT SHALL BE RELOCATED IN A MANNER THAT IS ACCEPTABLE BY THE ARCHITECT/ENGINEER. C. PROPER CONNECTIONS, MATERIALS, AND SIZES OF DUCTWORK SHALL BE MAINTAINED TO ENSURE EQUIPMENT PROPER CONNECTIONS, MATERIALS, AND SIZES OF DUCTWORK SHALL BE MAINTAINED TO ENSURE EQUIPMENT IS MADE FULLY OPERATIONAL. D. FOR ALL RATED WALLS THAT ARE EXTENDED TO STRUCTURE PROVIDE SLEEVES FOR NEW AND EXISTING PIPING FOR ALL RATED WALLS THAT ARE EXTENDED TO STRUCTURE PROVIDE SLEEVES FOR NEW AND EXISTING PIPING AND DUCTWORK PENETRATING WALLS PER SPECS. REFER TO LIFE SAFETY PLANS. E. DRAWING IS DIAGRAMMATIC, PROVIDE ADDITIONAL OFFSETS, TRANSITIONS, ETC. AS REQUIRED TO AVOID DRAWING IS DIAGRAMMATIC, PROVIDE ADDITIONAL OFFSETS, TRANSITIONS, ETC. AS REQUIRED TO AVOID INTERFERENCE'S ENCOUNTERED. RELOCATION OF EXISTING DUCT AND EQUIPMENT HANGERS REQUIRED FOR INSTALLATION WORK SHALL BE CONSIDERED PART OF THIS CONTRACT. F. CONTRACTOR SHALL PROVIDE MANUFACTURER'S RECOMMENDED ACCESS TO ALL EQUIPMENT AND VALVES. CONTRACTOR SHALL PROVIDE MANUFACTURER'S RECOMMENDED ACCESS TO ALL EQUIPMENT AND VALVES. ACCESS SHALL BE REMOVABLE BY CEILING TILES AND CEILING ACCESS PANELS. COORDINATE LOCATION OF MECHANICAL EQUIPMENT WITH OTHER TRADES TO AVOID CONFLICT. G. CEILING CAVITY SPACE IS VERY LIMITED WHERE EQUIPMENT, DUCTWORK AND PIPING IS TO BE INSTALLED. CEILING CAVITY SPACE IS VERY LIMITED WHERE EQUIPMENT, DUCTWORK AND PIPING IS TO BE INSTALLED. COORDINATE ALL SPRINKLER PIPING, ELECTRICAL CONDUIT AND OTHER UTILITIES WHERE REQUIRED FOR NEW INSTALLATION. THE CONTRACTOR SHALL BE RESPONSIBLE TO VISIT EACH AREA OF WORK TO IDENTIFY ANY UTILITIES THAT MUST BE RELOCATED. NOTIFY ENGINEER AND OWNER OF UTILITIES TO BE RELOCATED AND COORDINATE SCHEDULE OF THE ASSOCIATED DOWNTIME WITH THE OWNER. H. CONTRACTOR SHALL PROVIDE FIELD WIRING, ENGINEERING, AND PROGRAMMING FOR FULL INTEGRATION WITH CONTRACTOR SHALL PROVIDE FIELD WIRING, ENGINEERING, AND PROGRAMMING FOR FULL INTEGRATION WITH BUILDING'S BMS (NIAGRA M4). GRAPHICS TO INCLUDE MAPPING OF HYDRONIC SYSTEM AND BOILER. I. CONTRACTOR SHALL SIMULATE TEMPERATURE AND MOISTURE TO PROVE SNOW MELT SYSTEM OPERATION.CONTRACTOR SHALL SIMULATE TEMPERATURE AND MOISTURE TO PROVE SNOW MELT SYSTEM OPERATION.
AutoCAD SHX Text
%%USNOW MELT SEQUENCE OF OPERATION:
IF MOISTURE IS DETECTED WHILE THE OUTDOOR TEMPERATURE IS BETWEEN WARM WEATHER SHUT DOWN AND COLD WEATHER CUT OFF, THE CONTROL SHALL ENTER THE "MELTING" STATE. IN THIS STATE THE CONTROL SHALL DETERMINE A SLAB TARGET TEMPERATURE, BASED ON THE MELTING SETPOINT AND THE CURRENT OUTDOOR TEMPERATURE, AND REGULATE THE HEAT SOURCE TO MAINTAIN THIS TARGET. IT SHALL REMAIN IN THIS STATE UNTIL MOISTURE IS NO LONGER DETECTED AND ANY ADDITIONAL MELT TIME (AS PROGRAMMED) HAS EXPIRED. DURING OPERATION, SHOULD THE OUTDOOR TEMPERATURE DROP BELOW THE COLD WEATHER CUT OFF SETPOINT, THE CONTROL SHALL SHUT DOWN THE HEATING SYSTEM TO CONSERVE ENERGY; THE CONTROLS SHALL ENTER A 'MELT PENDING' STATE AND WILL RESUME MELTING WHEN THE OUTDOOR TEMPERATURE RISES ABOVE THE COLD WEATHER CUT OFF SET POINT. IF AN IDLE SETPOINT HAS BEEN CONFIGURED, THE CONTROL SHALL MAINTAIN THE DESIRED SLAB TEMPERATURE WHILE THE OUTDOOR TEMPERATURE IS BETWEEN WARM WEATHER SHUT DOWN AND COLD WEATHER CUT OFF. WARM WEATHER SHUT DOWN SETPOINT: THE CONTROL SHALL INCORPORATE AN ADJUSTABLE WARM WEATHER SHUT DOWN SETPOINT. WHEN THE OUTDOOR TEMPERATURE RISES ABOVE THE WWSD, THE CONTROL WILL DEACTIVATE THE SNOW MELTING SYSTEM, THEREBY CONSERVING ENERGY. COLD WEATHER CUT OFF SETPOINT: THE CONTROL SHALL INCORPORATE AN ADJUSTABLE COLD WEATHER CUT OFF SETPOINT. WHEN THE OUTDOOR TEMPERATURE FALLS BELOW THIS SETTING, THE CONTROL WILL DEACTIVATE THE SYSTEM, THEREBY CONSERVING ENERGY. IF A MELT IS IN PROGRESS WHEN THE TEMPERATURE FALLS BELOW THIS SETPOINT, THE CONTROL SHALL ENTER A PENDING STATE UNTIL THE OUTDOOR TEMPERATURE RISES ABOVE THE COLD WEATHER CUT OFF. THE CONTROL WILL RESUME MELTING UNTIL MOISTURE IS NO LONGER DETECTED. MELTING SETPOINT: THE CONTROL SHALL INCORPORATE AN ADJUSTABLE MELTING SETPOINT. THE CONTROL WILL MAINTAIN THE SLAB SURFACE AT THE MELTING SETPOINT BY ACCOUNTING FOR OUTDOOR TEMPERATURE WHILE THE CONTROL IS IN THE MELT STATE. IDLING SETPOINT: THE CONTROL SHALL INCORPORATE AN ADJUSTABLE IDLE SETPOINT. THE CONTROL WILL MAINTAIN THE SLAB SURFACE AT THE IDLE SETPOINT IF ONE IS CONFIGURED; OTHERWISE, THE IDLE FEATURE SHALL BE OFF. STORM SETPOINT: THE CONTROL SHALL INCORPORATE AN ADJUSTABLE STORM SETPOINT. WHEN A STORM IS EXPECTED, THE CONTROL MAY ENTER THE TEMPORARY IDLE, OR STORM, STATE. THE CONTROL WILL MAINTAIN THE SLAB SURFACE AT THE STORM SETPOINT FOR A TIME FRAME UP TO 24:00 HOURS. THE STORM OPERATION CAN ONLY BE ACTIVATED BY A USER SWITCH OR GATEWAY. SLAB OUTDOOR RESET: THE CONTROL SHALL MAINTAIN A SETPOINT SLAB SURFACE TEMPERATURE BY ADJUSTING TARGET WATER TEMPERATURES IN PROPORTION TO THE CURRENT OUTDOOR TEMPERATURE. EFFICIENCY IS MAXIMIZED BY ACCOUNTING FOR CHANGES IN HEAT LOSS THAT RESULT WITH CHANGES IN OUTDOOR TEMPERATURE. SLAB PROTECTION: THE CONTROL SHALL PROVIDE OPTIONAL SLAB PROTECTION. ONCE ENABLED, SLAB PROTECTION SHALL LIMIT THE TEMPERATURE OF THE SUPPLY WATER TO HELP PROTECT THE SLAB AGAINST THERMAL STRESSES. EXERCISING: THE CONTROL SHALL BE ABLE TO OPERATE THE PUMPS EVERY THREE DAYS TO PREVENT PUMP SEIZURE. MEMORY: THE CONTROL SHALL STORE ALL CONFIGURATION AND SETTINGS IN NON-VOLATILE MEMORY. IN CASE OF POWER FAILURE THE CONTROL SHOULD BE ABLE TO RETRIEVE ALL OF ITS LATEST SETTINGS. DISPLAY: THE CONTROL SHALL HAVE A TOUCHSCREEN DISPLAY TO CLEARLY DISPLAY THE CURRENT SYSTEM OPERATION WITH AN ILLUMINATED STATUS MESSAGE.
SNOW MELT POWER PLAN - NEW WORK
KA
L1 ELEC
EP104
GREAT LAKES REGION 5
PROPERTY OF THE
UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
SHEET OF
DISCIPLINE
DRAWING NO.
DRAWN BY
DATE
PCN NO.
GSA PM
PROJ. DESC.
BLDG NO.
CITY/ST./ZIP
STREET
BLDG NAME
MARK
FLOOR NO.
DATEDESCRIPTION
REVISION
TITLE
GENERAL SERVICES ADMINISTRATION
SHEET DESIGNATOR
SENSITIVE BUT UNCLASSIFIED (SBU) - PROPERTY OF THE UNITED STATES GOVERNMENT. COPYING, DISSEMINATION, OR DISTRIBUTION OF THESE DRAWINGS, PLANS, OR SPECIFICATIONS TO UNAUTHORIZED PERSONS IS PROHIBITED. Do not remove this notice. Properly destroy documents when no longer needed.
SHEET SIZE
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
C O N T R A C T O R S
CONSTR. CON.
A/E TASK NO.
CONS. WORK
CONTRACTOR INFO
MELVIN-PRICE FEDERAL BUILDING
BRETT ETLING
905 North Capital Avenue, Suite 100 Indianapolis, IN 46204 www.guidondesign.com
IL0301ES
750 EAST MISSOURI AVE.
EAST SAINT LOUIS
GSA SECURITY UPGRADE
02-27-2019
30x42
IL 62201
GS-05-P-17-SC-D-0001
47PF-0018F-0230
GUIDON BCCLT JV LLC
RIL11680
S
TAT E OF I L L I N
O I S
A E
S E EAOS
EISTEE
OFESSIONAL
ENINEE
OF
AutoCAD SHX Text
EXISTING CONDUITS FOR
AutoCAD SHX Text
GUARD SHACK POWER
AutoCAD SHX Text
AND COMMUNICATIONS
AutoCAD SHX Text
EXIST. OVERHEAD DOOR CONTROLLER
AutoCAD SHX Text
EXIST SECURITY GATE BACK-UP POWER INVERTER
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text EXIST. PANEL RBL-1Bb
AutoCAD SHX Text
SNOW MELT CONTROL PANEL, 120V,1
AutoCAD SHX Text
GF-1 120V,1
AutoCAD SHX Text P-1 370W, 120V,1
AutoCAD SHX Text P-2 370W, 120V,1
AutoCAD SHX Text RBL-1Bb-16, NOTE 2
AutoCAD SHX Text RBL-1Bb-18, NOTE 2
AutoCAD SHX Text B-1, 2A,120V,1
AutoCAD SHX Text S
AutoCAD SHX Text
NOTE 1
AutoCAD SHX Text J
AutoCAD SHX Text
NOTE 3
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
%%UELECTRICAL POWER PLAN
AutoCAD SHX Text A. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE BUILDING AND SITE THE CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE BUILDING AND SITE TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS, VERIFY SIZE, LOCATION, AND USAGE OF UTILITIES AND EQUIPMENT PRIOR TO CONSTRUCTION. B. ALL EQUIPMENT REMOVED FOR RELOCATION SHALL BE REMOVED IN SUCH A ALL EQUIPMENT REMOVED FOR RELOCATION SHALL BE REMOVED IN SUCH A MANNER THAT REUSE IS POSSIBLE. C. PATCH ALL OPENINGS IN WALLS, FLOORS, AND CEILINGS WHERE REMOVAL OF PATCH ALL OPENINGS IN WALLS, FLOORS, AND CEILINGS WHERE REMOVAL OF EQUIPMENT OR DEVICES CREATES SUCH OPENINGS. PATCH OPENINGS TO MATCH EXISTING. D. IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN MUST BE RELOCATED IF PORTIONS OF CIRCUITS SERVING EQUIPMENT TO REMAIN MUST BE RELOCATED OR REMOVED DUE TO INTERFERENCE WITH NEW EQUIPMENT INSTALLATION, THE CIRCUITS SHALL BE MODIFIED IN SUCH A MANNER WHICH WILL ENSURE THE PROPER OPERATION OF THE EQUIPMENT AFTER CONSTRUCTION IS COMPLETE, USE THE SAME TYPE OF CONDUCTOR AND SAME CONDUIT SIZE AS EXISTING TO MAKE ALL REQUIRED MODIFICATIONS. E. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS REQUIRED FOR THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REMOVALS REQUIRED FOR THE INSTALLATION OF NEW WORK, WHETHER OR NOT IT IS SPECIFICALLY INDICATED OR NOTED IN THESE DOCUMENTS. F. ALL CONDUIT RUNS TO REMOVED EQUIPMENT OR DEVICES SHALL BE COMPLETELY ALL CONDUIT RUNS TO REMOVED EQUIPMENT OR DEVICES SHALL BE COMPLETELY REMOVED BACK TO SOURCE, INCLUDING ALL HANGERS, BEAM CLAMPS, MISCELLANEOUS SUPPORTS, AND WIRING. G. COORDINATE CONDUIT ROUTING WITH EXISTING EQUIPMENT TO AVOID CONFLICTS COORDINATE CONDUIT ROUTING WITH EXISTING EQUIPMENT TO AVOID CONFLICTS WITH EQUIPMENT AND EQUIPMENT CLEARANCE. H. SEAL AROUND ALL WALL PENETRATIONS WITH FIRE STOPPING. SEAL AROUND ALL WALL PENETRATIONS WITH FIRE STOPPING. I. BRANCH CIRCUIT NEUTRAL CONDUCTORS SHALL NOT BE SHARED WITH ANOTHER BRANCH CIRCUIT NEUTRAL CONDUCTORS SHALL NOT BE SHARED WITH ANOTHER CIRCUIT. J. EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH A GREEN EQUIPMENT EACH BRANCH CIRCUIT SHALL BE EQUIPPED WITH A GREEN EQUIPMENT GROUNDING CONDUCTOR.
AutoCAD SHX Text
%%UGENERAL ELECTRICAL NOTES:
AutoCAD SHX Text
ELECTRICAL LEGEND
AutoCAD SHX Text
WORKING CLEARANCE
AutoCAD SHX Text
NP-1,3,5
AutoCAD SHX Text
PHASE
AutoCAD SHX Text
NEUTRAL
AutoCAD SHX Text
CONDUCTORS
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
INDICATE NUMBER OF CONDUCTORS REQUIRED. CONDUIT
AutoCAD SHX Text
CIRCUIT CONCEALED IN CEILING OR WALL. CROSSBARS
AutoCAD SHX Text
HOMERUN TO PANELBOARD INDICATED. NUMBER OF
AutoCAD SHX Text
ARROWHEADS INDICATES NUMBER OF CIRCUITS. NUMBER
AutoCAD SHX Text
NOT SIZED IS Ô", CONDUCTORS NOT SIZED ARE #12 AWG.
AutoCAD SHX Text
INDICATES CIRCUIT NUMBERS. PREFIX INDICATES PANEL
AutoCAD SHX Text
SURFACE MOUNTED PANELBOARD.
AutoCAD SHX Text
CIRCUIT BREAKER.
AutoCAD SHX Text
NUMBER.
AutoCAD SHX Text
CONDUIT EXPOSED.
AutoCAD SHX Text
CONDUIT CONCEALED BENEATH GROUND.
AutoCAD SHX Text
%%USYMBOL
AutoCAD SHX Text
%%UDESCRIPTION
AutoCAD SHX Text 120V
AutoCAD SHX Text
%%UPUMPS P-1 & P-2
AutoCAD SHX Text
SCALE: NONE
AutoCAD SHX Text
OL
AutoCAD SHX Text
INTERLOCK
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
OFF
AutoCAD SHX Text
HAND
AutoCAD SHX Text
AUTO
AutoCAD SHX Text R
AutoCAD SHX Text M
AutoCAD SHX Text
MOTOR RUN
AutoCAD SHX Text
PILOT LIGHT
AutoCAD SHX Text
STARTER
AutoCAD SHX Text %%C
AutoCAD SHX Text N
AutoCAD SHX Text
AUX. STARTER
AutoCAD SHX Text
CONTACT
AutoCAD SHX Text M
AutoCAD SHX Text
MAIN BREAKER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text %%UEXIST. PANEL RBL-1Bb
AutoCAD SHX Text
%%UBUSSING DIAGRAM
AutoCAD SHX Text 20A/2
AutoCAD SHX Text 20A/2
AutoCAD SHX Text 30A/3
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/3
AutoCAD SHX Text 20A/1
AutoCAD SHX Text 20A/3
AutoCAD SHX Text
GARAGE DOOR
AutoCAD SHX Text
HVAC TRANS.
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
NORTH SECURITY GATE
AutoCAD SHX Text
SNOW MELT PUMPS, P-1 & P-2
AutoCAD SHX Text
SNOW MELT C. PNL., BOILER, GF-1, HEAT TRACE
AutoCAD SHX Text
PARKING LOT VEHICLE GATE
AutoCAD SHX Text
EXISTING LOAD
AutoCAD SHX Text
SOUTH SECURITY GATE
AutoCAD SHX Text
ACCESS CONTROL PEDESTAL
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
RECEPT. - GARAGE, SEC. MONITOR
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
SPARE
AutoCAD SHX Text
100A, MAIN BREAKER 208Y/120V 3 , 4W, 30 CKT.GENERAL ELECTRIC A SERIES, II PANEL
AutoCAD SHX Text
1. PROVIDE NEMA SIZE 0 FULL VOLTAGE NON-REVERSING STARTER FOR PUMPS PROVIDE NEMA SIZE 0 FULL VOLTAGE NON-REVERSING STARTER FOR PUMPS `P-1' & `P-2'. PROVIDE WITH HAND-OFF-AUTO SELECTOR SWITCH AND PILOT LIGHT IN STARTER COVER. REFER TO P-1 AND P-2 CONTROL WIRING DIAGRAM. 2. PROVIDE CIRCUIT TO PANEL. UTILIZE SPARE 20A/1 CIRCUIT BREAKER IN PANEL. PROVIDE CIRCUIT TO PANEL. UTILIZE SPARE 20A/1 CIRCUIT BREAKER IN PANEL. 3. PROVIDE POWER TO WATER LINE FREEZE PROTECTION HEATING PROVIDE POWER TO WATER LINE FREEZE PROTECTION HEATING CABLE SYSTEM. SEE MECHANICAL DRAWINGS.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text 100A/3
AutoCAD SHX Text S
AutoCAD SHX Text
MOTOR.
AutoCAD SHX Text COMBINATION MAGNETIC MOTOR CONTROLLER TO SUIT MOTOR. MOUNT 4'-6" A.F.F. TO CENTER, UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
NOTE 2
AutoCAD SHX Text
%%UCONTROL WIRING DIAGRAM
AutoCAD SHX Text 20A, 125V DUPLEX RECEPTACLE. MOUNT 18 INCHES ABOVE FINISHED FLOOR TO BOTTOM, UNLESS NOTED OTHERWISE.
AutoCAD SHX Text SINGLE POLE 20A SPECIFICATION GRADE TOGGLE SWITCH. MOUNT 44" A.F.F. TO BOTTOM, NOTED OTHERWISE.
2-27-2019
| EP104 |
| Sheets and Views |
| EP104 |
| M101 |
| Sheets and Views |
| M101 |
| M102 |
| Sheets and Views |
| M102 |
| P101 |
| Sheets and Views |
| P101 |
File details come from the government source that posted it.