Answers to questions
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF_1442.pdf | ||
| SF_30.pdf | ||
| Solicitation_Amendment_47PC1118B0002_0002.pdf | ||
| 10_-_Jackson_Pre_Bid_Agenda__11-7-17.pdf | ||
| 10_-_SF_30.pdf | ||
| 10_-_addendum_1.pdf | ||
| 10_-_site_visit_sign_in.pdf | ||
| Solicitation_Document.pdf | ||
| https://www.fbo.gov/index?s=opportunity&mode=form&id=63d4c16b720feb3c07b1a836d0a05c82&tab=core&_cview=1 | — | |
| Solicitation_Agreement.pdf | ||
| SF_1442.pdf | ||
| Document_Security_Notice.pdf | ||
| GSA_527.pdf | ||
| Reps_and_Certs.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NKB#12245.33: Jackson USBC Build-Out Pre-Bid RFIs – Batch #1
1) On SHT. A-002, what are the Floor Slab to Bottom of the Deck Dimensions? There are two (2)
Wall Types 920a. Which is correct?
Answer: Floor Slab to Bottom of Deck dimensions are as follows:
Basement to 1st floor = 15’-11”
1st floor to 2nd floor =15’-9”
3rd floor to 4th floor =14’-1 ¼”
4th floor to 5th floor =13’-7 3/8”
5th floor to 6th floor =20’-10”
Contractor should verify these dimensions in the field
Answer: Please see the wall tags that identify 920a and 920e. This is a typographical error
2) Please clearly identify base bid work and options.
Answer: Refer to Specifications 011000-2 SUMMARY OF WORK 1.1C
3) The Room Finish Schedule on SHT. AE603 lists a room EX303 that is to be painted. Where does this room show up in the plans?
Answer: This seems to be a typographical error. This is the corridor next to Open Station 232. See Sheet
AE422
4) Who is the existing Fire Alarm System Manufacturer/Provider/Vendor?
Answer: Service and testing of the existing system has been by Buffalo Security Fire CompanySiemens model XLS Fire Finder
5) Who is the existing Access Control System Manufacturer/Provider/Vendor?
Answer: Tyco, GC is only responsible for infrastructure.
6) There are two (2) existing electrical panels on the 2nd floor being renovated to match existing. I need to know the Manufacturer/Panel Info for existing panels LLA-2 and LL1-2 located in 2nd floor Electric Closet (Reference Detail 2/E-423 for location).
Answer:
LL-A-2: Eaton Type PRL1A, 208Y/120V, 3 Phase, 4 wire with 150A Main CB
LL-A1-2: Eaton Type PRL1A, 208Y/120V, 3 Phase, 4 wire with 150A Main CB