36E77618R0092-006.pdf

PDF 11 MB Posted

Attached to
Construct Community Living Center Cottage Minor - Des Moines
Solicitation number
36E77618R0092
Issued by

About this file

36E77618R0092 ATTACHMENT 5 - Construct CLC Cottage Final Drawings Part 2.pdf

View the file

Other files

File Type Posted
36E77618C0031-000.docx DOCX document
36E77618R0092-0005003.pdf PDF
36E77618R0092-0005002.docx DOCX document
36E77618R0092-0004001.pdf PDF
36E77618R0092-0004003.pdf PDF
36E77618R0092-0004000.docx DOCX document
36E77618R0092-0004002.pdf PDF
36E77618R0092-0003001.pdf PDF
36E77618R0092-0003002.pdf PDF
36E77618R0092-0003000.docx DOCX document
36E77618R0092-0002001.pdf PDF
36E77618R0092-0002000.docx DOCX document
36E77618R0092-0002002.pdf PDF
36E77618R0092-001.docx DOCX document
36E77618R0092-002.pdf PDF
36E77618R0092-004.pdf PDF
36E77618R0092-009.docx DOCX document
36E77618R0092-010.pdf PDF
36E77618R0092-008.docx DOCX document
36E77618R0092-003.pdf PDF
36E77618R0092-005.pdf PDF
36E77618R0092-007.pdf PDF
36E77618R0092-000.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE

OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD

VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM

THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR

SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW

ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO

REMAIN. FULL-TONE LINES INDICATED NEW OR RELOCATED

CONSTRUCTION.

E. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE

ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE REFERENCES

MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON BOTH SIDES OF THE

MATCH LINE

F. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL PIPING WITH

STRUCTURE, CEILING, LIGHTING, AND DUCTWORK.

G. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

H. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.

MAINTAIN ALL CODE REQUIRED CLEARANCES.

J. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL

REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY

OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED

HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE

AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT

THEREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE

OWNER AND CONTRACTOR.

K. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND GENERAL

CONTRACTOR.

A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL

DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION.

DIMENSIONS AND EXISTING CONDITIONS ARE APPROXIMATE. CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE INTENDED

TO BE REMOVED, RELOCATED, OR SALVAGED ARE SHOWN AS SOLID, FULL-

TONE LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND

ARE SHOWN AS HALF-TONE.

B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED

BELOW OR HERE-IN. THE CONTRACTOR SHALL COORDINATE ALL

REQUIRED RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING

BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION REQUIRED

AND AS LISTED BELOW.

C. THE REMOVAL OF HVAC AND PLUMBING EQUIPMENT FROM FINISHED AREAS

AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED WITH

ARCHITECTURAL PLANS AND DETAILS AS WELL AS NOTES ON THE

MECHANICAL DRAWING TO ENSURE PROPER PATCHING AND REPAIR IS

MADE TO THE BUILDING.

D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND

REMOVAL OF ALL EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND

APPURTENANCES AS REQUIRED TO BUILD, ERECT, INSTALL, OR

ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER HAVING FIRST

RIGHT OF REFUSAL ON ALL ITEMS.

E. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE

CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND

STORED OR REINSTALLED ON THE SITE AS DIRECTED. REMOVED OR

SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE OWNER.

F. COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND

CONTROLS WITH ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL

REMOVALS.

G. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL

REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY

OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED

HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE

AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT

THEREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE

OWNER AND ARCHITECT.

H. ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION

SHALL BE COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

MECHANICAL INFO SHEET

TMJ AJP

BGJ

M000

58 97

06054.032

TRUE

NORTH

PLAN

NORTH

NORTH

NORTH

ARROW

SYMBOL LEGEND ABBREVIATIONS

MATCHLINE

AREA A

AREA B

EXISTING

COLUMN

NEW

COLUMN

X

X

X

SIM

X

XX-XX

XXXX

DX

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

150 SF

ROOM / SPACE

NUMBER

LETTER INDICATES

NEW COLUMN LINE

LETTER INDICATES

EXISTING COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

ROOM AREA DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION DESIGNATION

GRAPHIC AREA FOR DRAWING

TITLE

SCALE OF THE DRAWING

18 Ø

18x10

18/10

PIPE GUIDE

HOSE BIBB

THERMOMETER

PIPE ANCHOR

HB

STEAM TRAP

PH

WH

YH

SIGHT GLASS-REFRIGERANT

POST HYDRANT

YARD HYDRANT

WALL HYDRANT

PRESSURE GAUGE

ROUND DUCT

CA

PN

VD

FLAT OVAL DUCT-1ST FIG IS SIDE SHOWN

FLEXIBLE DUCTWORK CONNECTION

RECT DUCT-1ST FIG IS SIDE SHOWN

ACOUSTICAL DUCT LINER

VOLUME DAMPER

CONTROL AIR SUPPLY

NEW TO EXISTING CONNECTION

PNEUMATIC TUBE

FIRE WATER (BURIED)

SPRINKLER DRAIN

FIRE SPRINKLER MAIN

BALL VALVE

TAMPER SWITCH

BUTTERFLY VALVE

MANUAL BALANCING VALVE

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

GAS COCK OR VALVE

CONTROL VALVE (3 WAY)

CONTROL VALVE (2 WAY)

PLUG VALVE

GLOBE VALVE

HOSE END DRAIN VALVE

ANGLE VALVE

PRESSURE REDUCING VALVE

AUTO FLOW CONTROL VALVE

GATE VALVE OR GEN SHUT-OFF VALVE

CHECK VALVE

HVAC DUCTWORK AND SPECIALTIES

PIPING SPECIALTIES AND FITTINGS (CONT)

MISCELLANEOUS SYMBOLS

EXTRACTOR

SIZE/TYPE

RETURN OR EXHAUST DUCT DOWN

RETURN OR EXHAUST REGISTER OR

GRILLE (VERTICAL MOUNTING)

SUPPLY REGISTER OR GRILLE

ROUND DUCT UP / DOUBLE LINE PIPE

ROUND DUCT DOWN / DOUBLE LINE PIPE

RETURN OR EXHAUST DUCT UP

(R OR G) (VERTICAL MOUNTING)

TURNING VANES

SUPPLY AND FRESH AIR DUCT DOWN

SUPPLY AND FRESH AIR DUCT

SIZE/TYPE

SIZE/TYPE

FLOW

FLOW

SIZE/TYPE

FLOW

FLOW

S

S

SMOKE DAMPER-HORIZ FIRE SEPARATION

SMOKE DAMPER-VERT FIRE SEPARATION

FIRE DAMPER-VERT FIRE SEPARATION

FIRE DAMPER-HORIZ FIRE SEPARATION

MOTORIZED DAMPER-OPPOSED BLADE

MOTORIZED DAMPER-PARALLEL BLADE

ROUND CEILING SUPPLY DIFFUSER

(HORIZONTAL MOUNTING)

GRAVITY DAMPER

(OR) SAFETY VALVE-STEAM

TEMP & PRESS RELIEF

FLOOR SINK

AREA DRAIN

FLOOR DRAIN

GRADE CLEANOUT

THERMO EXPANSION VALVE-REFRIGERANT

PLUMBING VENT THRU ROOF

CLEANOUT / WALL CLEANOUT

THERMOSTATIC MIXING VALVE

VALVE IN VERTICAL PIPE-TYPE SHOWN

M

M

MANHOLE

TRENCH DRAIN

OVERFLOW ROOF DRAIN

RUNNING TRAP

OXYGEN OUTLET

PIPE CAP

ELBOW UP

AIR OUTLET

TEE

ELBOW DOWN

VACUUM OUTLET

RUNNING TRAP WITH CLEANOUTS

ROOF DRAIN

SIZE/TYPE

FLOW

HUMIDISTAT

THERMOSTAT

FLEXIBLE DUCT

S

H

T

FS

FS

TEMPERATURE SENSOR

UNION

TEE DOWN

STRAINER

DIELECTRIC UNION

THERMOMETER WELL

CONCENTRIC REDUCER

EXPANSION JOINT

FLEXIBLE PIPE CONNECTION

ECCENTRIC REDUCER

AIR VENT (MANUAL UNLESS NOTED)

PITCH PIPE DOWN IN DIR OF ARROW

TEE UP

FIRE/SMOKE DAMPER-HORIZ FIRE SEPARATION

FIRE/SMOKE DAMPER-VERT FIRE SEPARATION

RECTANGULAR RETURN REG OR GRILLE

(HORIZONTAL MOUNTING)

RECTANGULAR SUPPLY DIFF, REG OR GRILLE

(HORIZONTAL MOUNTING)

SOLENOID VALVE

SM

FW

D

TS

VALVES

FS

M

M

S

LPC

HPS

MPC

MPS

LPS

HVAC PIPING

GHWR

GHWS

HWR

HWS

PC

HPC

ES

BBD BOILER BLOW DOWN

EXHAUST STEAM

PUMPED CONDENSATE

HIGH PRESSURE CONDENSATE

HIGH PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE

MEDIUM PRESSURE STEAM

LOW PRESSURE CONDENSATE

LOW PRESSURE STEAM

GLYCOL HOT WATER RETURN

GLYCOL HOT WATER SUPPLY

HOT WATER RETURN

HOT WATER SUPPLY

_"FS-_

_"AD-_

_"FD-_

CO

VTR

GCO

_"OD-_

MH

X

A

V

_"RD-_

PIPING SPECIALTIES AND FITTINGS

WCO

FIRE PROTECTION

XXX

PLUMBING

FIXTURES

PLUMBING FIXTURE

DESIGNATION

X"

PIPE

SIZE PIPE SIZE (DIAMETER)

X"/X"

DUCT

SIZE

WIDTH / HEIGHT

SIZE/TYPE

FLOW

RECTANGULAR EXHAUST REG OR GRILLE

(HORIZONTAL MOUNTING)

REF. DEMO NOTES ( )GENERAL NOTES MXMDXGENERAL DEMOLITION NOTES

CWS

GCWS

CWR

GCS

CR

CS

RL

RD

RS

GCWR

GLYCOL CONDENSER WATER SUPPLY

GLYCOL CHILLED WATER RETURN

GLYCOL CHILLED WATER SUPPLY

REFRIGERANT LIQUID LINE

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION LINE

GHCS

GHCR

CD

HCS

HCR

GCR

HOT/CHILLED WATER SUPPLY

HOT/CHILLED WATER RETURN

GLYCOL CONDENSER WATER RETURN

GLYCOL HOT/CHILLED WATER RETURN

GLYCOL HOT/CHILLED WATER SUPPLY

CONDENSATE DRAIN

REF. NOTES ( )

RECIRCULATING DOMESTIC HOT WATER (RDHW)

DOMESTIC COLD WATER (DCW)

DOMESTIC HOT WATER (DHW)

RD

SAN

SAN

PLUMBING PIPING

ACID VENT

TW

AV

AW

W

DS

LS

SCW

RTW

SHW

V SANITARY VENT

BURIED EXTERIOR WATER

RECIRCULATING TEMPERED WATER

TEMPERED WATER

DISTILLED WATER

LAWN SPRINKLER

SOFTENED HOT WATER

SOFTENED COLD WATER

ACID WASTE

SUBSOIL OR FOUNDATION DRAIN

STORM DRAIN (BELOW FLOOR)

STORM DRAIN (ABOVE FLOOR)

SANITARY DRAIN (BELOW FLOOR)

SANITARY DRAIN (ABOVE FLOOR)

OXYGEN

GASOLINE

VACUUM

OX

GS

G

VAC

RO

A

FOF

FOG

LPG

FOV

FOR

FOS

FUEL OIL RETURN

FUEL OIL SUPPLY

FUEL OIL GAGE

FUEL OIL FILL

FUEL OIL VENT

REVERSE OSMOSIS PROCESSED WATER

COMPRESSED AIR

NATURAL GAS

LIQUEFIED PETROLEUM GAS

DEIONIZED WATERDI

XX-XX

MECHANICAL SHEET LIST

SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.

L LAVATORY

LAT LEAVING AIR TEMPERATURE

LH LAB HOOD

LPC LOW PRESSURE CONDENSATE

LPG LIQUIFIED PETROLEUM GAS

LPS LOW PRESSURE STEAM

LRA LOCKED ROTOR AMPS

LS LAUNDRY SINK

LSS LAWN SPRINKLER DESIGN

LV LOUVER

LWT LEAVING WATER TEMPERATURE

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MB MACHINE BOLT

MBH 1000 BTUH

MCA MINIMUM CIRCUIT AMPS

MD MOTORIZED DAMPER

MG GAS: MEDIUM-PRESSURE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT

PROTECTION

MPC MEDIUM PRESSURE

CONDENSATE

MPS MEDIUM PRESSURE STEAM

MS MOP SINK

N NITROGEN

NC NORMALLY CLOSED

NG NATURAL GAS

NO NORMALLY OPEN

NPCW NONPOTABLE COLD WATER

NPHW NONPOTABLE HOT WATER

NPHWR NONPOTABLE HOT WATER

RETURN

OA OUTSIDE AIR

OD OVERFLOW ROOF DRAIN

OX OXYGEN

P PUMP

PC POINT OF CURVATURE

PHC PREHEAT COIL

PIV POST INDICATING VALVE

PRV PRESSURE REGULATING VALVE

PS PLASTER SINKS

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH,

ABSOLUTE

PSIG POUNDS PER SQUARE INCH,

GAUGE

PTAC PACKAGED TERMINAL AIR

CONDITIONER

RA RETURN AIR

RCP RADIANT CEILING PANELS

RD ROOF AREA DRAINS

RDL REFRIGERANT DISCHARGE LINE

RF RETURN FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RL REFRIGERANT LIQUID LINE

RLA RELIEF AIR

RLF RELIEF FAN

RO REVERSE OSMOSIS WATER

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION LINE

RTU ROOF TOP UNIT

RV RELIEF VALVE

S SINKS

SA SUPPLY AIR

SAN SANITARY SEWER

SB SITZ BATH

SD SMOKE DAMPER

SF SUPPLY FAN

SFU SANITARY FIXTURE UNITS

SH SHOWERS

SHB SHAMPOO BOWLS

SP STATIC PRESSURE

SS SERVICE SINK

SSCU DUSTLESS SPLIT SYSTEM

CONDENSING UNIT

SSFC DUCTLESS SPLIT SYSTEM

SSS SURGEON SCRUB SINKS

ST STORAGE TANK

SUP SUMP PUMP

SW STORM WATER

TD TRENCH DRAIN

TMV THERMOSTATIC MIXING VALVES

TONS TONS OF REFRIGERATION

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TWU TROUGH WALL AIR CONDITIONER

UH UNIT HEATER

UR URINAL

US UTILITY SINK

V VENT

VAC VACUUM

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

WB WET BULB

WC WATER CLOSETS

WCO WALL CLEANOUT

WF WASH FOUNTAINS

WFU WATER FIXTURE UNITS

WH WALL HYDRANT

WPD WATER PRESSURE DROP

WS WATER SOFTENER

WSHP WATER SOURCE HEAT PUMP

WWHP WATER TO WATER HEAT PUMP

YH YARD HYDRANT

A COMPRESSED AIR

AC AIR COMPRESSOR

AD AIR DOOR

AFCV AUTO FLOW CONTROL VALVE

AHU AIR HANDLING UNIT

AMP AMPERE

APD AIR PRESSURE DROP

ARD AIR PRESSURE DROP

AS AIR SEPARATOR

AV ACID VENT

AW ACID WASTE

AW AREA DRAIN

B BOILER

BC BLOWER COIL

BD BIDET

BF BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BHP BREAK HORSEPOWER

BLKG BLOCKING

BLV BALANCING VALVE

BT BATHTUBS

BV BALL VALVE

BW BEDPAN WASHERS

C CHILLER

CC COOLING COIL

CD CONDENSATE DRAIN

CF CEILING FANS

CFM CUBIC FEET PER MINUTE

CHIU CABINET HEATER

CHV CHECK VALVE

CI CAST IRON

CMU COMBINATION UNITS

CR CONDENSER WATER RETURN

CRAC COMPUTER ROOM AIR

CONDITIONER

CS CONDENSER WATER SUPPLY

CSS CLINICAL SERVICE SINKS

CT COOLING TOWER

CU AIR COOLED CONDENSING UNIT

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

D DIFFUSER

DB DRY-BULB TEMPERATURE

DCW DOMESTIC COLD WATER

DEG DEGREE

DF DRINKING FOUNTAIN

DGCO DOUBLE GRADE CLEANOUT

DH EMERGENCY DRENCH HOSES

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RECIRC

DI DEIONIZED WATER

DOA DEDICATED OUTDOOR AIR UNIT

DP DOMESTIC PUMP

DS DISTILLED WATER

DSA DUCT SOUND ATTENUATORS

DSCW DOMESTIC SOF COLD WATER

DSHW DOMESTIC SOFT HOT WATER

DSHWRDOMESTIC SOFT HOT WATER

RETURN

DST DOMESTIC STORAGE TANK

DTW DOMESTIC TEMPERED WATER

DTWR DOMESTIC TEMPERED WATER

RETURN

DXT DOMESTIC EXPANSION TANK

EA EACH

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDH ELECTRIC DUCT HEATER

EEW EMERGENCY EYE WASH

EEWS EMERGENCY EYE

WASH/SHOWERS

EF EXHAUST FAN

EFF EFFICIENCY

EFW EMERGENCY FACE WASH

EH EXHAUST HOOD

ERV ENERGY RECOVERY

VENTILATOR

ES EMERGENCY SHOWER

ESP EXTERNAL STATIC PRESSURE

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER

TEMPERATURE

EX EXPANSION TANK

F FIRE PROTECTION WATER

SUPPLY

F FURNACE

FCO FOOT CANDLE

FCT FLUID COOLER TOWERS

FCU FAN COIL UNIT

FD FIRE DAMPER

FLA FULL LOAD AMPS

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FLOOR SINKS

FSD FIRE/SMOKE DAMPER

FTR FINNED TUBE RADIATION

G GAS: LOW-PRESSURE

GCR GLYCOL CONDENSER

WATER RETURN

GCS GLYCOL CONDENSER

WATER SUPPLY

GCWR GLYCOL CHILLED

WATER RETURN

GCWS GLYCOL CHILLED

WATER SUPPLY

GD GARBAGE DISPOSAL

GD GRAVITY DAMPER

GDH GAS DUCT HEATER

GHCR GLYCOL HOT/COLD

WATER RETURN

GHCS GLYCOL HOT/COLD

WATER SUPPLY

GHWR GLYCOL HOT WATER RETURN

GHWS GLYCOL HOT WATER SUPPLY

GI GREASE INTERCEPTOR

GIV GRAVITY INTAKE VENTILATOR

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRV GRAVITY RELIEF VENTILATOR

GV GAS VENT

GWH GAS WATER HEATER

H HYDRANTS

HB HOSE BIBB

HC HEATING COIL

HCR HOT/COLD WATER RETURN

HCS HOT/COLD WATER SUPPLY

HG GAS: HIGH-PRESSURE

HP HEAT PUMP (AIR SOURCE)

IH INTAKE HOOD

IRH INFRARED RADIANT HEATER

KDH KITCHEN DISHWASHING HOOD

KH KITCHEN HOOD

KW KILOWATT

KWH KILOWATT HOURS

HP HORSEPOWER

HPC HIGH PRESSURE CONDENSTATE

HPS HIGH PRESURE STEAM

HRC HEAT RECOVERY COIL

HU HUMIDIFIER

HWR HOT WATER RETURN (HEATING)

HWS HOT WATER SUPPLY (HEATING)

HX HEAT EXCHANGER

M000 MECHANICAL INFO SHEET

MH101 FIRST FLOOR PLAN-HVAC

MH102 ATTIC FLOOR PLAN - HVAC

MP100 MECHANICAL SITE PLAN

MP101 FIRST FLOOR HVAC PIPING PLAN

MP102 ATTIC FLOOR PLAN - HVAC PIPING

M301 MECHANICAL CONTROL SEQUENCE

M302 MECHANICAL FLOW DIAGRAMS

M401 MECHANICAL DETAILS

M402 MECHANICAL DETAILS

M403 MECHANICAL DETAILS

M501 MECHANICAL SCHEDULES

M502 MECHANICAL SCHEDULES

T

T

T

T

T

T T T T

T

T

T

T

T

T T

T

T

T

T

T T

FS

T

T T

MEN

WOMEN

NURSE ADMIN.

LOUNGE

CORRIDOR

CORRIDOR

SOILED UTILITY

STORAGE

RESIDENT

LAUNDRY

SPA

ELECT.

HSKPG

GROUP ROOM

CLEAN LINEN

DEN

SERVERY

BATHROOM

2525A

BATHROOM

2527A

BATHROOM

2529A

BATHROOM

2523A

BATHROOM

2521A

BATHROOM

2519A

RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

(BARIATRIC)

MED. STO.

BATHROOM

2505A RESIDENT

RESIDENT

BATHROOM

2507A

BATHROOM

2509A

RESIDENT

RESIDENT

BATHROOM

2513A

RESIDENT

BATHROOM

2515A

RESIDENT

(BARIATRIC)

CORRIDOR

SRVC CORR.

FAMILY

FOYER

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

STAIR 1

FIRE/WATER

SRVC

CLEAN EQUIP.

CLEAN UTILITY

CORRIDOR

HOME OFFICE

2508A

PRODUCTION

KITCHEN

LIVING ROOM

VAV-2545

VAV-2528

VAV-2507

VAV-2505

VAV-2511

VAV-2509

VAV-2519

VAV-2521

VAV-2529

VAV-2527

VAV-2525

VAV-2523

IT

STAFF REPORT

ROOM

9" Ø LS-1

250 CFM

9" Ø LS-1

250 CFM

(TYP. 12)

(TYP. 12)

12x12 E-2

110 CFM

12x12 R-2

390 CFM

12x12 E-2

110 CFM

(TYP. 4)

8" Ø S-1

350 CFM

22x22 R-1

350 CFM

12x12 E-2

110 CFM

12x12 E-2

110 CFM

22x22 R-1

720 CFM

8" Ø S-1

280 CFM

12x12 R-1

380 CFM

6" Ø S-1

100 CFM

12x12 E-1

200 CFM

12x12 E-1

290 CFM

8" Ø S-1

260 CFM

6" Ø S-1

200 CFM

6" Ø S-1

50 CFM

6" Ø S-1

200 CFM

12x12 R-1

400 CFM

6" Ø S-1

200 CFM

12x12 R-1

130 CFM

6" Ø S-1

200 CFM

12x12 E-1

100 CFM

8" Ø S-1

180 CFM

8" Ø S-1

180 CFM

6" Ø S-1

180 CFM

12x12 R-1

175 CFM

12x12 R-1

225 CFM

6" Ø S-1

230 CFM

6x6 R-1

100 CFM

6" Ø S-1

150 CFM

12x12 R-2

390 CFM

22x22 R-1

630 CFM

10x6 S-2

180 CFM

8" Ø S-1

225 CFM

12x12 R-1

330 CFM

6" Ø S-1

140 CFM

6" Ø S-1

140 CFM

8" Ø S-1

350 CFM

8" Ø S-1

350 CFM

8" Ø S-1

350 CFM

8" Ø S-1

295 CFM

22x22 R-1

1890 CFM

22x22 R-1

300 CFM

8" Ø S-1

250 CFM

6" Ø S-1

180 CFM

12x12 R-2

125 CFM

6" Ø S-1

180 CFM

22x22 R-1

880 CFM

6" Ø S-1

95 CFM

8" Ø S-1

250 CFM

8" Ø S-1

160 CFM

22x22 R-1

160 CFM

12x12 R-1

1710 CFM

8" Ø S-1

275 CFM

12x12 E-1

200 CFM

6" Ø S-1

225 CFM 12x12 E-1

110 CFM

12x12 R-2

390 CFM

16x12 RA x

R

A x

R

A

R

Q

P

L

M

K

J

H

G

F

E

D

B

A

1 2 3 5 6 7 9 12 13 14 158

C

N

N.1

D.4

S

VAV-2539

VAV-2531

12x10 SA

10x10 SA

12x10 SA (TYP. 6)

(TYP. 6)

(TYP. 6)

(TYP. 6)

(TYP. 6)

6x6 EA

8x8 EA

8x8 RA 6x6 RA 6x6 RA

10x10 RA

10x8 SA

6" Ø SA

VAV-2510

14x14 SA

12x10 SA

14x12 EA

8" Ø SA

16x16 SA

VAV-2506

8x6 EA

8x8 EA 6" Ø SA

12x8 SA

8x8 RA

VAV-2526

4" Ø EA

SS-1

DBF-1

16x14 SA

22x12 RA

10x10 RA10x10 RA

14x12 RA 16x16 RA

12x8 SA

10x10 SA

9" Ø LS-1

250 CFM

10x8 SA

8x6 RA

10x8 RA

12x6 RA

12x12 RA

(TYP. 5)

10x8 SA

6" Ø SA

12x10 SA

14x14 SA

16x12 RA20x20 RA24x20 RA x

S

A

30x20 RA

12" Ø SA

20x12 RA16x10 RA

10x6 SA

30x22 RA

10" Ø SA

14x12 SA

10x8 SA x

R

A

8x10 SA

(TYP. 3)

(TYP. 4)

8" Ø S-1

180 CFM

22x12 SA

26x18 RA

12" Ø SA

7" Ø SA

12x12 RA

7" Ø SA 7" Ø SA

7" Ø SA7" Ø SA

6" Ø SA

VAV-2517

VAV-2504

VAV-2515

VAV-2513

VAV-2501

1 (TYP.)6x6 EA6x6 EA

8x8 EA

(TYP. 8)

20x12

TRANSFER

DUCT

12x12 E-2

110 CFM

(TYP. 6)

6" Ø EA

6"Ø UP TO EF-2

KH-1

KH-2

VAV-2562

14x14 SA

6" Ø SA

8" Ø S-1

290 CFM

(TYP. 4)

16x16 RA

VAV-2512

8" Ø S-1

225 CFM

8" Ø S-1

225 CFM

8" Ø S-1

225 CFM

16x8 SA

12x8 SA

8" Ø SA

FCU-2

16x8 SA

12x8 SA

8" Ø S-1

225 CFM

AREA A

AREA B

FCU-3

8" Ø S-1

225 CFM

20x20 R-1

20x8 RA

20x8 RA

20x20 R-1

8" Ø S-1

225 CFM

8" Ø S-1

225 CFM

8" Ø SA

6" Ø LS-2

180 CFM

6" Ø LS-3

110 CFM

VAV-2514

CLEAN LINEN

DEN

SERVERY

DINING

RESIDENT

BATHROOM

2507A

BATHROOM

2509A

RESIDENT

RESIDENT

BATHROOM

2511A

BATHROOM

2513A

RESIDENT

FAMILY

FOYER

CORRIDOR

LIVING ROOM

(TYP. 4)

8" Ø S-1

295 CFM

x

R

A

(TYP. 3)

(TYP. 4)

12x12 RA

(TYP.)

(TYP. 8)

12x12 EA

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE

OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD

VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM

THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR

SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW

ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE

ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE REFERENCES

MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON BOTH SIDES OF THE

MATCH LINE

E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK WITH

STRUCTURE, CEILING, LIGHTING, AND PIPING.

F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

G. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.

MAINTAIN ALL CODE REQUIRED CLEARANCES.

H. ANY UTILITY OR SYSTEM DISRUPTION OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND GENERAL

CONNTRACTOR

I. SEE PHASING PLANS ON SHEET G102. COORDINATE WORK WITH PHASING

PLANS.

9 121110

T

U

V

W

8.6 11.3

Y

12.3

CORRIDOR

FCU-1

UH-1

STAIR 4

S4

PASSAGE

C1-3E

8" Ø S-1

225 CFM

8" Ø S-1

225 CFM

8" Ø S-1

225 CFM

VESTIBULE

CORRIDOR

AREA A

AREA B

12x8 SA

16x8 SA

8" Ø SA

10x6 S-2

250 CFM

20x20 R-1

670 CFM

20x8 RA

8" Ø SA

16x16 R-1

500 CFM

16x8 RA 10x6 SA

8" Ø SA

10x10 SA

8" Ø S-1

250 CFM

RESIDENT

ROOM

C119

13 14

T

U

V

12.3

RESIDENT

ROOM

C119

TOILET

C119A

STAIR 4

S4

PASSAGE

C1-3E

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

FIRST FLOOR PLAN-HVAC

TMJ AJP

BGJ

MH101

59 97

06054.032

1 ALL RESIDENT ROOM TEMPERATURE CONTROLS TO BE VIA

PROGRAMMABLE WALL THERMOSTAT.

2 DUCTWORK OFFSET DUE TO STRUCTURE.

3 SUPPLY, RETURN, AND EXHAUST MAINS RUN IN TRUSSES ABOVE

BOTTOM CHORD OF TRUSSES.

4 VAV/CAV BOXES AND TERMINAL AIR DISTRIBUTION DUCTWORK IN

INTERSTITIAL CEILING SPACE.

5 FIRE DAMPERS AT FLOOR PENETRATION TO MECHANICAL ROOM ABOVE.

6 THREE-SLOT LINEAR DIFFUSER AT 9'-6" A.F.F.

7 PAINT DRYER VENT CAP TO MATCH WALL.

8 SEE KITCHEN HOOD SCHEDULE FOR FIRE SUPPRESSION SYSTEMS

PROVIDED WITH HOODS.

9 MEASURE POSITIVE PRESSURE RELATIVE TO CORRIDOR DURING TAB

WITH CFM SHOWN ON THIS PLAN.

10 SEAL DUCT AT ALL VERTICAL SMOKE SEPARATION PENETRATIONS. SEE

CODE SUMMARY PLAN FOR ADDITIONAL INFORMATION.

11 FIRE/SMOKE DAMPER IN CORRIDOR WALL IN TRANSFER DUCT. (DAMPER

I.D. 25.FS.R.1.2510.4)

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - HVAC

GENERAL HVAC NOTES:

REF. NOTES ( ):X

NORTHKEY PLAN

E X

IS

S

E

A M

U N

N E

L

EXIS

T C

HIL

LER T

UNNEL

1W

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - HVAC AREA B

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - DEMO HVAC

REF. DEMO NOTES ( ):X

1 EXISTING FAN COIL UNITS TO BE REMOVED FROM BUILDING 12 STAIR AND

PASSAGE.

MECHANICAL

ELEC.

STAIR 1

F

E

D

B

2 3 5 6 7 98

C

D.4

SSU-1

SSU-2

SS-2

34x22 L-2 34x22 L-2 34x22 L-2

34x22 L-1 34x22 L-1 34x22 L-1 34x22 L-1

RF-1 36x24 RA36x24 RA

EF-2

EF-1

VFD

TEMPERATURE

CONTROL PANEL

VFD

10x6 G-4

200 CFM

x

R

A

18x16 EA x

E

A

EF-3

AHU-12

MH102

PLATFORM FOR SERVICING

GREASE FAN AT KITCHEN HOOD -

SEE ARCH. PLANS AND DETAILS

36x24 RA

36x24 EA

60x22 OA

34x22 OA

VFD

36x24 EA

PLENUM

VAV-2552

10x8 E-1

400 CFM

10x6 S-2

250 CFM

10x6 S-2

300 CFM

10x10 SA10x6 SA

6 7 8

F F

F

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE

OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD

VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM

THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR

SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW

ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE

ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE REFERENCES

MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON BOTH SIDES OF THE

MATCH LINE

E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK WITH

STRUCTURE, CEILING, LIGHTING, AND PIPING.

F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

G. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.

MAINTAIN ALL CODE REQUIRED CLEARANCES.

H. ANY UTILITY OR SYSTEM DISRUPTION OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND GENERAL

CONNTRACTOR

I. SEE PHASING PLANS ON SHEET G102. COORDINATE WORK WITH PHASING

PLANS.

35679 810

CLERESTORY ROOF BEARING

128' - 4"

M

32x100 OA

22x60 OA 22x34 OA

32x98 RA x

R

A

AHU-1

x

R

A

18x16 EA

EF-3

10" Ø EA

10" Ø EA

x

S

A

7" Ø SA

10x6 S-2

300 CFM

6x10 SA10x10 SA

VAV-2552

10x6 S-2

250 CFM

x

E

A

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

ATTIC FLOOR PLAN - HVAC

TMJ AJP

BGJ

MH102

60 97

06054.032

SCALE: 1/4" = 1'-0"

SECOND FLOOR PLAN - HVAC

GENERAL MECHANICAL NOTES:

REF. NOTES ( ):X

1 4" CONCRETE HOUSEKEEPING PAD. EXTEND 6" BEYOND EQUIPMENT EACH

DIRECTION (TYPICAL).

2 TWO TRANSFER GRILLES, ONE EACH SIDE OF WALL CONNECTED BY

EQUAL SIZE TRANSFER DUCT THROUGH WALL.

3 WALL MOUNTED VFD'S FOR EF-1 AND RF-1.

4 WALL CAP EXHAUST PROVIDED WITH EF-3 SYSTEM.

5 PROVIDE DUCT DETECTOR IN SUPPLY AIR. COORDINATE WITH FIRE

ALARM COORDINATOR.

6 EXHAUST AIR FIRE DAMPER AT FLOOR. (DAMPER I.D. 25.FD.E.2.2552.3)

7 RETURN AIR FIRE DAMPER AT FLOOR. (DAMPER I.D. 25.FD.R.2.2552.2)

8 SUPPLY AIR FIRE DAMPER AT FLOOR. (DAMPER I.D. 25.FD.S.2.2552.1)

SCALE: 1/4" = 1'-0"

HVAC SECTION - MECH 2552

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HIL

LER T

UNNEL

1W

DN

UP

DNDN

UP

SEE 2/MP100 FOR CONTINUATION.

MP102

CWP-2

CRV-3

5 6

SP-1 8

MP102

MP102

SEE 1/MP100 FOR

CONTINUATION.

4" CWS/R TO

EXISTING CHILLER

TUNNEL

3" PC & 3" HPS

IN EXISTING

STEAM TUNNEL

5 6

MP102

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE

OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD

VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM

THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR

SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW

ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO

REMAIN. FULL-TONE LINES INDICATED NEW OR RELOCATED

CONSTRUCTION.

E. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE

ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE REFERENCES

MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON BOTH SIDES OF THE

MATCH LINE

F. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL PIPING WITH

STRUCTURE, CEILING, LIGHTING, AND DUCTWORK.

G. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

H. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.

MAINTAIN ALL CODE REQUIRED CLEARANCES.

J. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL

REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY

OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED

HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE

AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT

THEREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE

OWNER AND CONTRACTOR.

K. ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND GENERAL

CONTRACTOR.

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

MECHANICAL SITE PLAN

TMJ AJP

BGJ

MP100

61 97

06054.032

SCALE: 1/16" = 1'-0"

SUB GRADE BUILDING & TUNNEL

SCALE: 1/16" = 1'-0"

SUB-GRADE TUNNEL

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HIL

LER T

UNNEL

1W

GENERAL HVAC PIPING NOTES:

REF. NOTES ( ):X

1 4" CWS, 4" CWR, 3" HPS, AND 3" LPR FROM THIS POINT. PROVIDE STEAM

TRAP AND BEGIN 2" HPR DRIP LEG FROM THIS POINT SOUTH TO

CONNECTION AT EXISTING TUNNEL EXPANSION LOOP.

2 LOCATE GUIDES NO CLOSER THAN 20'-0" FROM EXPANSION LOOP.

LOCATE SLIDES NEAR EXPANSION LOOP.

3 NEW PIPE RACK CONNECTED TO EXISTING CHILLED WATER PIPE RACK

TOP SUPPORT STRUT (TYPICAL AT EXISTING RACK LOCATIONS).

4 PROVIDE KEFLEX F040KFCSUWE40 EXPANSION LOOP ON CHILLED WATER

SUPPLY AND RETURN.

5 SEE SHEET CS102 FOR PROFILE VIEW OF UTILITY TRENCH.

6 SEE 2/MP102 FOR INFORMATION ON PRECAST UTILITY TRENCH BASIS OF

DESIGN.

7 ANCHOR POINT.

8 SUMP PUMP DISCHARGE TO BE PIPED TO STORM DRAIN. 2" PIPED STORM

FROM BELOW GRADE STRUCTURE TO STORM SEWER STRUCTURE

CALLED OUT IN REFERENCE NOTE 6 ON SHEET CG101.

9 PRECAST UTILITY TRENCH, ALSO REFERRED TO AS A DUCT BANK TO BE

COORDINATED WITH MECHANICAL PIPING, ELECTRICAL, AND EXCAVATION

SUB CONTRACTORS.

SCALE: 1/16" = 1'-0"

SUB-GRADE PLAN - DEMO HVAC PIPING

REF. DEMO NOTES ( ):X

1 INACTIVE ABANDONED STEAM AND CONDENSATE IN THIS LOCATION TO

BE DEMOLISHED.

T

T T

R

Q

P

L

M

K

J

H

G

F

E

D

B

A

1 2 3 5 6 7 9 12 13 14 158

C

N

N.1

D.4

SERVERY

2508PRODUCTION

KITCHEN

SPA

HOME OFFICE

2508A

FIRE/WATER

SRVC

CLEAN EQUIP.

CLEAN UTILITY

RESIDENT

(BARIATRIC)

RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

2519 MED. STO.

BATHROOM

2519A

BATHROOM

2521A

BATHROOM

2523A

BATHROOM

2525A

BATHROOM

2527A

BATHROOM

2529A

STAIR 1

IT

NURSE ADMIN.

LOUNGE

MEN

WOMEN

CORRIDOR

CORRIDOR

SOILED UTILITY

RESIDENT

LAUNDRY

ELECT.

HSKPG

CLEAN LINEN

2528GROUP ROOM

STAFF REPORT

ROOM

CORRIDOR

CORRIDOR

BATHROOM

2515A

BATHROOM

2513A

BATHROOM

2511A

BATHROOM

2509A

BATHROOM

2507A

BATHROOM

2505A

RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

RESIDENT

(BARIATRIC)

FAMILY

SRVC CORR.

CORRIDOR

FOYER

LIVING ROOM

CORRIDOR

CORRIDOR

DEN

DINING

CORRIDOR

S

3/4"3/4"

3/4"3/4"

1/2"1/2"

3/4"3/4"

3/4"3/4" 3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"3/4"3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"3/4"

1/2"1/2"

1/2"1/2"

1/2"1/2" 1/2"1/2"

1/2"1/2"

1/2"1/2"

3/4"3/4"

3/4"3/4"3/4"3/4"

1/2"1/2"

1/2"1/2"

2"

RCP-2527A RCP-2525A RCP-2523A RCP-2521ARCP-2529A

VAV-2545

RCP-2543A

RCP-2541A

VAV-2528

VAV-2510

VAV-2512

VAV-2527

VAV-2523

VAV-2521 VAV-2519

RCP-2515A

RCP-2513A

VAV-2511

RCP-2511A

VAV-2509

RCP-2509A

VAV-2507

RCP-2507A

VAV-2505

RCP-2505A

RCP-2519A

VAV-2506

VAV-2539

VAV-2526

VAV-2531

VAV-2529

VAV-2525

1/2"1/2"

1/2"1/2" 1/2"1/2"

1/2"1/2"

1/2"1/2"

1/2"1/2"

3/4"3/4"

1/2"1/2"

1 1/2"

1 1/4"

1/2"1/2"

3/4"3/4"

1 1/2"

1/2" 2"

1" 2"

H W

R H W

S C W

R C W

S

2"

3/4"

3/4"3/4"

3/4"3/4"

1 1/2"

1"

SS-1

AREA A

AREA B

FCU-2

FCU-3

VAV-2517

VAV-2513

VAV-2515

VAV-2504

1/2"1/2"

3/4"3/4"

2" 1 1/4" 1/2"1/2"

1/2"

VAV-2501

RL

RS

3/4"3/4"

3/4"3/4"

VAV-2562

1"1"

1"1"

3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"

3/4" 3/4"

3/4"

RCP-2512

3/4"

1 1/2"

RCP-S1

3/4"3/4"

1"1/2"

1/2"1/2"

3/4"3/4"

9 121110

T

U

V

W

8.6 11.3

Y

12.3

CORRIDOR

AREA A

AREA B

FCU-1

UH-1

STAIR 4

S4

PASSAGE

C1-3E

3/4"3/4"

HWR

HWS

RESIDENT

ROOM

C119

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE

OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD

VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM

THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR

SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW

ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE

ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE REFERENCES

MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON BOTH SIDES OF THE

MATCH LINE

E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL PIPING WITH

STRUCTURE, CEILING, LIGHTING, AND DUCTWORK.

F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

G. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.

MAINTAIN ALL CODE REQUIRED CLEARANCES.

H. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL

REASONABLE BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY

OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED

HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE

AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT

THREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE

OWNER AND CONTRACTOR.

I. ANY UTILITY OR SYSTEM DISRUPTION OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND GENERAL

CONNTRACTOR

J. SEE PHASING PLANS ON SHEET G102. COORDINATE WORK WITH PHASING

PLANS.

13 14

T

U

V

W

12.3

HWR

HWS

RESIDENT

ROOM

C119

PASSAGE

C1-3E

STAIR 4

S41

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

FIRST FLOOR HVAC PIPING PLAN

TMJ AJP

BGJ

MP101

62 97

06054.032

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - HVAC PIPING AREA A

GENERAL HVAC PIPING NOTES:

REF. NOTES ( ):X

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HIL

LER T

UNNEL

1W

1 2" HWS AND HWR FROM ABOVE. SEE MP102 FOR CONTINUATION.

2 1" CWS AND CWR FROM ABOVE. SEE MP102 FOR CONTINUATION.

3 DIFFERENTIAL PRESSURE SENSOR LOCATION. SEE 3/M302.

4 RADIANT HEATING PANEL MOUNTED ON BOTTOM OF STAIR LANDING.

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - HVAC PIPING AREA B

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - DEMO HVAC PIPING

REF. DEMO NOTES ( ):X

1 EXISTING FAN COIL UNITS TO BE REMOVED INCLUDING ASSOCIATED

PIPING BACK TO MAIN AND ALL CONTROLS.

D.4

EX. STEAM P2 TOP

90' - 0"

EX. STEAM P3 FLOOR

87' - 8"

EX. STEAM P3 TOP

94' - 0"

CWP-2

CWP-1

CRV-3

3/4" LPC3/4" LPC

4" CWS

3" LPC

3" HPS

4" CWR

F

E

D

B

2 3 5 6 7 9 128

C

D.4

SSU-1

SSU-2

SS-2

RS

RL

RL

HX-2

CRV-1

HWP-1

HX-1

RS

HWP-2

ET-1

3" LPC

4" CWR

4" CWS

STEAM PRV

3" MPS

2" HWR

2" HWS

CRV-2

AHU-1

AS-1

3" HPS

6'-3 7/64"

G

R O

U N

D C

O V

E R

M

IN

WATER

TIGHT

GROUTE

REMOVABLE

COVER

TYPE 39 SADDLE

PROVIDE CENTER

BOLT FOR SPANS

GREATER THAN 24"

4" 5.4#

SECTION THRU TRENCH

1. PRECAST COVER WEIGHT:2255 LBS

2. PRECAST TRENCH WEIGHT: 2950 LBS

FOR ONE 10'-0" SECTION

3. FORTERRA PRECAST UTILITY TRENCH

BASIS OF DESIGN.

4" CWS

4" CWR

3" HPS

3" LPR

ELECTRICAL CONDUIT

(SEE ELECTRICAL PLANS)

PRECAST COVER

HS-20 DESIGN

TONGUE AND

GROOVE TYPE JOINTS

3" HAUNCH EACH

SIDE CONTINUOUS

PRECAST

TRENCH

SECTION

GROUTE

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE

OWNER AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD

VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM

THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR

SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW

ENTIRE SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. IN VIEWING THESE DRAWINGS, THE CONTRACTOR SHALL PAY CLOSE

ATTENTION TO THE MATCH LINES. SOME WORK AND NOTE REFERENCES

MAY BE REPEATED, BUT DO NOT ALWAYS SHOW ON BOTH SIDES OF THE

MATCH LINE

E. CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK WITH

STRUCTURE, CEILING, LIGHTING, AND PIPING.

F. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL

EQUIPMENT TO ALLOW FOR MAINTENANCE ACCESS.

G. DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS.

MAINTAIN ALL CODE REQUIRED CLEARANCES.

H. ANY UTILITY OR SYSTEM DISRUPTION OR OUTAGES DURING

CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER AND GENERAL

CONNTRACTOR

I. SEE PHASING PLANS ON SHEET G102. COORDINATE WORK WITH PHASING

PLANS.

6'-3 7/64"

G

R O

U N

D C

O V

E R

M

IN

WATER

TIGHT

GROUTE

REMOVABLE

COVER

TYPE 39 SADDLE

PROVIDE CENTER

BOLT FOR SPANS

GREATER THAN 24"

4" 5.4#

SECTION THRU TRENCH

4" CWS

4" CWR

ELECTRICAL CONDUIT

(SEE ELECTRICAL PLANS)

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

ATTIC FLOOR PLAN - HVAC PIPING

TMJ AJP

BGJ

MP102

63 97

06054.032

SCALE: 3/8" = 1'-0"

TUNNEL DETAIL 3

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - HVAC PIPING

SCALE: 1/2" = 1'-0"

PRECAST UTILITY TRENCH DETAIL

1 SEE STEAM AND CHILLED WATER PIPING CONTINUATION ON SHEET

MP100.

2 HIGH PRESSURE CONDENSATE RETURN FROM DRIP LEGS TO

CONDENSATE PUMP RECEIVER.

3 4" CONCRETE HOUSEKEEPING PAD. EXTEND 6" BEYOND EQUIPMENT EACH

DIRECTION (TYPICAL).

4 PROVIDE FITTINGS AND VALVES IN THE MECHANICAL ROOM TO

FACILITATE HYPER CHLORINATION OF THE BUILDING DOMESTIC WATER

SYSTEM BY VA STAFF IN THE FUTURE.

GENERAL HVAC NOTES:

REF. NOTES ( ):X

NORTHKEY PLAN

E X

E

N

N E

L

EXIS

T C

HIL

LER T

UNNEL

1W

SCALE: 1/2" = 1'-0"

PRECAST UTILITY TRENCH DETAIL

ROOM THERMOSTAT/SENSOR

WALL MOUNTED

48" [1200mm] AFF.

VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM

TU

RHCHWS

HWR

V-1

REHEAT

COIL

AIR TERMINAL

UNIT

AIR

FLOW

TE

ATU

CONTROLLER

PC

TE

A

IR

F L O

W (C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

SP

VAV BOX CONTROL SEQUENCE

W/DEADBAND

100%

V A V A

IR

F

LO

WR

E H

E A T F

LO

W

A. SET POINTS SHALL BE SET AS FOLLOWS:

COOLING 75°F (ADJ)

HEATING 70°F(ADJ)

DEADBAND OF 5° F BETWEEN HEATING AND

COOLING SET POINTS WILL BE MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE

VAV DAMPER WILL MODULATE TO MINIMUM

POSITION.

C. UPON FURTHER DROP IN SPACE

TEMPERATURE VALVE V-1 WILL MODULATE

TO MAINTAIN SET POINT + .5° F. THE

ADJUSTABLE TOLERANCE OF + .5° F HAS

BEEN SELECTED TO PREVENT VALVE

HUNTING

D. THE REVERSE SHALL OCCUR ON THE RISE

IN SPACE TEMPERATURE.

FE

ALARM

PROCESSING

D U

T Y

C Y C

L E

F U

N C

T

IO

N

S C

H E

D U

LE

S

T A

R T /S

T O

P

HUMIDITY HIGH LIMIT

RETURN FAN VSMC ALARM

SUPPLY FAN VSMC ALARM

RETURN FAN STATUS

STATIC PRESSURE HIGH LIMIT

SUPPLY AIR FLOW (CFM)

RETURN LOW PRESSURE

S T A

T U

S

SYSTEM

A

LA

R M

P R

IO

R

IT

Y

/A D

D -A

LT

E

R N

A T E

N O

E

LE

C T R

IC

D

E V

IC

E

S P

E E

D C

O M

M A

N D

P O

IN

T

ID

DISCHARGE STATIC PRESSURE

DISCHARGE AIR HUMIDITY

DISCHARGE AIR TEMPERATURE

PRE-HEAT TEMPERATURE

MIXED AIR TEMPERATURE

COOLING COIL TEMPERATURE

SYSTEM COMPONENT:

RETURN AIR FLOW (CFM)

RETURN AIR TEMPERATURE

-- O P

E N

/C

LO

S E

S T A

R T /S

T O

P -- V

A

LV

E P

O S

IT

IO

N

D A

M P

E R

P O

S

IT

IO

N

JOB: 0555.09

VAV AIR HANDLER

VA SAMPLE POINTS LIST

SYSTEM:

BUILDING:

LEGEND

POINT

BINARY

T E

M P

E R

A T U

R E

T I)

L oc a l A la rm

P a ne l

M as te r A la rm

P a ne l

A re a A la rm

P an el

H

IG

H S

T A

T

IC

P R

E S

S U

R E

H

IG

H H

U M

ID

IT

Y

P R

E S

S U

R E

--L O

W T

E M

P E

R A

T U

R E

P E

R C

E N

T

P R

E S

S U

R E

P O

S

IT

IO

N

F

LO

W

H

IG

H L

IM

IT

L O

W L

IM

IT

SYSTEM INPUTS

ANA- BINARY ANALOG

S P

A C

E T

E M

P . C

O N

T R

O L

--S T A

T

IC

P R

E S

S U

R E

R E

S E

T

--D E

M A

N D

L

IM

IT

IN

G

T E

M P

E R

A T U

R E

R E

S E

T

T E

M P

E R

A T U

R E

O V

E R

R

ID

E

E N

T H

A

LP

Y E

C O

N O

M

IZ

E R

T E

M P

E R

A T U

R E

E C

O N

O M

IZ

E

R

F A

IL

U

R E

M O

D E

P R

E S

S U

R E

/V O

LU

M

E C

O N

T R

O L

REMARKS

F U

LL

C

O M

M U

N

IC

A T

IO

N

SYSTEM SOFTWARE/CONTROL

APPLICATION/FUNCTION

PAGE:

RETURN AIR HUMIDITY

SUPPLY FAN STATUS

MIXED AIR LOW LIMIT

RETURN AIR DAMPER

RETURN FAN START/STOP

STEAM HUMIDIFIER VALVE V-4

COILING VALVE V-1

PRE-HEAT VALVE V-2

EXHAUST AIR DAMPER

MINIMUM OUTSIDE AIR DAMPER

SUPPLY FAN VSMC

OUTSIDE AIR DAMPER

RETURN FAN VSMC

S T A

T

IC

P R

E S

S U

R E

C A

R B

O N

M O

N O

X

ID

E

H U

M

ID

IT

Y

V A

C U

U M

STEAM ISOLATION VALVE V-3

SUPPLY FAN START/STOP

AI-1

AI-2

AI-3

AI-4

AI-5

AI-6

AI-7

AI-8

AI-9

AI-10

T R

E N

D

IN

G

OUTSIDE AIR TEMPERATURE AI-11

BI-1

BI-2

BI-3

BI-4

BI-5

BI-6

BI-7

BI-8

AO-1

AO-2

AO-3

AO-4

AO-5

AO-7

AO-8

AO-9

AO-10

BO-1

BO-2

BO-3

FULL COMMUNICATION

FULL COMMUNICATION

A B

B R

E V

IA

T

IO

N

RAT

RAH

RAF

MAT

PHT

CCT

DAT

DASP

DAH

SAF

OAT

RLP

RF-STS

SF-STS

TSL-1

SPS-2

HHL

SF-ALA

RF-ALA

RF-SPD

SF-SPD

OAD

RAD

EAD

MIN-OAD

PHT-V1

CLG-V1

HUM-V4

RF-SST

SF-SST

HUM-ISO-V3

WITH MINIMUM OUTSIDE AIR

POINTS LIST FOR VAV AIR HANDLING UNIT

OUTPUTS

LOG

SCALE: NOT TO SCALE

VARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR CONTROL DIAGRAM

EXHAUST AIR

D-3

D-2

P R

E

F

IL

T E

R

OUTSIDE AIR

D-1

C O

IL

P

R E

H E

A T

C O

IL

C

O O

L

IN

G

LOCATE SENSOR

OUTSIDE UNDER

SHIELD

MPS

V-2

V-1

CHR

CHS

RETURN FAN

SUPPLY FAN

A F

M D

RETURN

AIR

F

IN

A L F

IL

T

E R

A F

M D

TT

TT

TT TT FT

A F

T E

R

F

IL

T E

R

TT HT

D-4

A F

M D

MINIMUM

OUTSIDE

AIR

HS

CS

VFD

HSVFD

FT

T-5

T-2

T-3 T-6

H-1

IT

SD

ONLY WHERE

REQUIRED

HOT GLYCOL

WATER, HOT

WATER OR

ELECTRIC

COILS ARE

PERMISSIBLE

SUBSTITUTES

CURRENT

TRANSMITTER

FOR FAN

STATUS ,TYP.

PSH

SMOKE

DETECTOR

VARIABLE

FREQUENCY DRIVE,

TYP.

DISCHARGE

PLENUM

ZC

ZC

ZC

ZC

FT DPS DPS

TT

T-1

SST

SPD

DPS

PSL

CS

T4

SST

SPD

AIA

COMM SD

TSL

TSL-1

1. GENERAL

1.1 UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE.

WHEN THE UNIT IS "OFF" D-1, D-3, SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" D-1, SD-1 AND

SD-2 SHALL BE FULLY OPEN. D-2 AND D-3 SHALL MODULATE IN ACCORDANCE WITH THE FOLLOWING

SEQUENCE:

2. TEMPERATURE CONTROL

2.1

2.2

2.3

2.4

3. AIR FLOW CONTROL

3.1

3.2

3.3

4. HUMIDITY CONTROL

4.1

4.2

5. FREEZE PROTECTION

5.1

6. AUTOMATIC SHUTDOWN/RESTART

6.1

6.2

7. EMERGENCY CONSTANT SPEED OPERATION

7.1

SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT VIA DIGITAL

CONTROL PANEL BY MODULATING V-1 OR D-2 AND D-3 OR V-2 IN SEQUENCE.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS ABOVE 75°F (ADJ) [23.8°C], THE DIGITAL CONTROL PANEL SHALL PREVENT THE MODULATION OF D-2 AND D-3 AND SHALL ASSUME THE MINIMUM OUTSIDE AIR POSITION (D-2 FULLY OPENED AND D-3 FULLY CLOSED). THE DIGITAL

CONTROL PANEL SHALL MODULATE V-1 TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY

TT-1.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS BETWEEN 65°F [18.3°C] AND THE SUPPLY AIR TEMPERATURE SENSED BY TT-1, DAMPER D-2 SHALL FULLY CLOSE AND D1 AND D3 SHALL BE FULLY OPEN (MAXIMUM OUTSIDE AIR POSITION). THE DIGITAL CONTROL PANEL SHALL

MODULATE V-1 TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1.

WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS BELOW THE SUPPLY AIR

TEMPERATURE, SENSED BY TT-1, DAMPERS D1, D-2 AND D-3 SHALL MODULATE TO MAINTAIN THE SCHEDULED SUPPLY AIR TEMPERATURE. IF D-2 IS OPEN AND D-3 IS CLOSED TO MINIMUM OUTSIDE AIR, V-2 SHALL MODULATE OPEN TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1.

THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING THE

SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" [25mm] OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-1. RESET STATIC PRESSURE BASED ON ACTUAL

BUILDING LOAD BY POLLING ALL ATU

THE DIGITAL CONTROL PANEL, USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS, SHALL

RESET THE RETURN AIR FAN VSMC TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE BETWEEN

THE SUPPLY AIR AND THE RETURN AIR EQUAL TO MINIMUM OUTSIDE AIR.

USING HIGH PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT

THE SUPPLY FAN FROM DEVELOPING OVER 3" [75mm] OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 DOES EXCEED 3" [75mm] THE SUPPLY AIR FAN SHALL STOP. SPS-2 SHALL BE HARDWIRED TO THE SUPPLY FAN VSMC AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO

OR BYPASS MODE. SPS-2 WILL REQUIRE MANUAL RESET AT THE DEVICE.

UPON FAILURE OF THE VSMC, THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED

MANUALLY AT THE DIGITAL CONTROL PANEL OR THE ECC THROUGH THE BY-PASS STARTER. FANS

SHALL THEN BE OPERATED AT CONSTANT SPEED.

IF THE AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F [7°C], AN ALARM SIGNAL SHALL INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F [4.4°C], AS SENSED BY

THE TSL THE SUPPLY AND RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM SHALL

INDICATE AT THE DIGITAL CONTROL PANEL AND ECC. TSL SHALL BE HARDWIRED TO THE SUPPLY

FAN UFD AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. TSL WILL REQUIRE

MANUAL RESET AT THE DEVICE.

WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY AND RETURN FANS

SHALL SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM.

ALL SMOKE DAMPERS IN THE SUPPLY AND RETURN DUCTS SHALL CLOSE.

EXHAUST FANS SERVING AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. SUPPLY AND

RETURN FANS SHALL RESTART AND SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT IS

RESET.

WHEN THE DIGITAL CONTROL PANEL IS NOT CALLING FOR HUMIDITY, SENSED BY RETURN AIR

HUMIDITY H-1, 2-WAY "ON-OFF" CONTROL VALVE V-3 SHALL REMAIN CLOSED. WHEN THE DIGITAL

CONTROL PANEL IS CALLING FOR HUMIDITY, V-3 SHALL REMAIN OPEN.

RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT OF 35% RH (ADJ) VIA DIGITAL CONTROL PANEL BY MODULATING CONTROL VALVE V-4 TO MAINTAIN THE DESIRED HUMIDITY. THE DCP SHALL

OVERRIDE THIS CONTROL TO MAINTAIN HUMIDITY OF 80% AS SENSED BY H-2. DCP SHALL CLOSE

VALVE V-3 WHENEVER THE SUPPLY FAN IS OFF. VALVE V-4 SHALL BE INTERLOCKED WITH A

TEMPERATURE SWITCH TO KEEP THE HUMIDIFIER OFF UNTIL CONDENSATE TEMPERATURE

APPROACHES STEAM TEMPERATURE.

SEQUENCE OF OPERATION FOR VARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR

8. ECONOMIZER

8.1

8.2

THE ECONOMIZER SHALL BE ENABLED WHENEVER THE OUTSIDE AIR TEMPERATURE SENSED BY

TT-2 IS LESS THAN 65°F (ADJ.) AND THE OUTSIDE AIR TEMPERATURE SENSED BY TT-2 IS LESS THAN

THE RETURN AIR TEMPERATURE SENSED BY TT-4 AND THE SUPPLY FAN STATUS IS ON. THE

DIGITAL CONTROL PANEL SHALL MODULATE DAMPERS D-1, D-2 AND D-3 TO MAINTAIN A SUPPLY AIR TEMPERATURE SENSED BY TT-5 AT 2°F (ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE COOLING

SETPOINT.

THE ECONOMIZER SHALL BE DISABLED WHENEVER THE MIXED AIR TEMPERATURE SENSED BY TT-5 IS LESS THAN 50°F (ADJ.) OR THE FREEZESTAT IS ON OR ON LOSS OF SUPPLY FAN STATUS.

PRESSURE SWITCH LOW

TO DISABLE RETURN FAN WHEN

SMOKE DAMPER IN RETURN DUCT

CLOSES

PRESSURE SWITCH HIGH

TO DISABLE FAN WHEN HIGH

PRESSURE LIMIT SETPOINT IS

REACHED

SCALE: NOT TO SCALE SCALE: NOT TO SCALE

SCALE: NOT TO SCALE

V-3

LPS

V-4

STEAM HUMIDIFIER

[3000mm]

HT

2C

2C

HHL

SPS

10' MIN.

SUPPLY AIR TO

TERMINAL UNIT

DP

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

MECHANICAL CONTROL SEQUENCE

TMJ AJP

BGJ

M301

64 97

06054.032

DP

CHWR

HWR

H W R

(STANDBY)

4" CHWS FROM

CHILLER PLANT

AHU-1

PREHEAT

SAFETY VALVE, RV-1

AND

VENT THROUGH ROOF

AHU-1

HUMIDIFIER

5" (30 PSIG) LPS

CRV-1

VENT TO

ATMOSPHERE

2" PUMPED CONDENSATE

RETURN TO BOILER PLANT

STEAM PRV

ASSEMBLY

105 PSI TO 30 PSI

1/3 & 2/3 CONFIG.

SPRAY

CONDENSER

ST-1a HX-2

REHEAT

HOT

WATER

SYSTEM

HX-1

CP-2

CP-1

AHU-1

4" CHWR TO

CHILLER PLANT

HWP-1

HOT WATER WATER

PUMPS

WITH VFD, SPEED

CONTROLLED BY REMOTE

DIFFERENTIAL SENSOR.

A S

-2

RV-3

ET-1

PROVIDE DIFFERENTIAL

PRESSURE SENSOR AT

MOST

REMOTE COIL, SET TO 2 PSI

(USER ADJUSTABLE) SEE

PLANS FOR LOCATION

H X

-1

H X

-2

(S T

A N

D B

Y

TO HOT WATER REHEAT

DISTRIBUTION NETWORK, SEE

RISER DIAGRAM AND PLANS

FOR

FURTHER DETAILS

REHEAT COIL

3/4" CW FEED

TYPICAL TERMINAL BOX

VAV REHEAT FLOW DIAGRAM

NO SCALE

STEAM & CONDENSATE FLOW DIAGRAM

NO SCALE

CHILLED WATER FLOW DIAGRAM

NO SCALE

4"

4"

TO FD

3/4" 3/4"

4"

4"4"

3/4"

1/2"

4" 4"

TO ROOF

ST-1b

FROM AHU-1

HUMIDIFIER

CONDENSATE TRAP

(TYPICAL)

3" (105 PSI) MPS

FROM BOILER

PLANT

1/2"

1/2"

3"

1"

1"

1"

1"

3"

1-1/2"

2"

1-1/2"

2"

2"

2"

1"

2-1/2"

2"

2"

3"

1"

1"

5" 3" 3"

F C

U -A

3/4"

HWP-2 (STANDBY)

TYPICAL FAN COIL

TO CHILLED WATER

LOOP

PIPING OR RISER

TO HOT WATER

LOOP

PIPING OR RISER

INTEGRAL TO UNIT

CRV-2

HWEX-1

DOMESTIC

HOT

WATER

SYSTEM

HWEX-2

3"

2-1/2"

2"

2"

3"

1 1/2"

1 1/2"

3"

Drawing Title

Approved:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

TSA PROJECT NO.: Department of Veterans Affairs

CONSTRUCT CLC

COTTAGES - COTTAGE 1

636-123

3600 30TH ST. DES MOINES, IA

4/13/2018

MECHANICAL FLOW DIAGRAMS

TMJ AJP

BGJ

M302

65 97

06054.032

NOTE:

1.

2.

3.

4.

5.

6.

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR. FOLLOW

DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR

SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR

FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO DAMPER

FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" , 14 GAGE, TO PROVIDE 1"

MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA LPDS,

FIG. 2-13, SEAL JOINTS.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

PROVIDE 1/8" CLEARANCE PER EACH 12" OF DUCT HEIGHT AND WIDTH.

SLEEVE, NOTE 2

DUCT

CONNECTION

NOTE 4

DAMPER,

NOTE 1

DAMPER COLLAR

EXTENSION

INTEGRAL

PART OF SLEEVE

SLEEVE, NOTE 2

NOTE 6FIRE BARRIER

PARTITION OR FLOOR

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3

(NOTE FASTENED TO PARTITION)

ACCESS

PANEL

NOTE 5

[2 m m

SEAL HOLE…