D.6 ATTACHMENT 6 - EXHIBIT D - DAMPER REPORT [2018].pdf

PDF 70 KB Posted

Attached to
J012--Cancelled RFQ 36C26125Q0098
Solicitation number
36C26125Q0098
Issued by

About this file

This is a damper inspection report from September 15, 2018, for the San Francisco VA Health Care Systems, covering Buildings 200, 203, and 208. The inspection, conducted by Corry Railey, evaluated multiple fire and smoke dampers throughout the facilities.

The report details the inspection results of approximately 40 dampers across the three buildings, with each entry including the damper number, location, type (fire or smoke), and inspection status. Many dampers were marked as "NON-ACCESSIBLE" due to various issues including no access doors, pipe blockages, hard ceilings, or being beyond arm's reach. Of the accessible dampers, most received a "PASS" status, with only one damper (FD-001-003 in Building 203) receiving a "FAIL" status due to being bound in tracks (racking). The report appears to be supporting documentation for a fire alarm and fire suppression services contract opportunity (36C26125Q0098) for the VA's Veterans Integrated Service Network 21.

View the file

Other files

File Type Posted
36C26125Q0098 0006_1.docx DOCX document
36C26125Q0098 0006 Fire Suppression - Cancel RFQ.pdf PDF
MOD5 36C26125Q0098 0005 - Extend Due Date .pdf PDF
36C26125Q0098 0005_1.docx DOCX document
MOD4 36C26125Q0098 0004 Extend Date - Fire testing - Fire Suppression.pdf PDF
36C26125Q0098 0004_1.docx DOCX document
MOD3 36C26125Q0098 0003 - Fire Testing - Fire Suppression Services.pdf PDF
D.9 ATTACHMENT 9 - VASF TEST AND DEVICE COUNT.pdf PDF
REVISED D.4 ATTACHMENT 4 - EXHIBIT B VASF FA TEST SCHEDULE 2025-30.pdf PDF
36C26125Q0098 0003_1.docx DOCX document
36C26125Q0098 0002_1.docx DOCX document
MOD 2 36C26125Q0098 0002 - Fire Testing - Fire Suppression Services.pdf PDF
D.2 ATTACHMENT 2 - DOL WAGE DETMINATION 2015-5637 REV.28, DATED 12-23-2024 - SAN FRANCISCO-SAN MATEO.pdf PDF
D.8 ATTACHMENT 8 - SFVA STANDPIPE 5-YEAR BUILDING INSPECTIONS.pdf PDF
D.4 ATTACHMENT 4 - EXHIBIT B VASF FA TEST DEIVCE COUNT.pdf PDF
36C26125Q0098 0001_1.docx DOCX document
RFQ MOD 36C26125Q0098 0001 - Fire Testing - Fire Suppression Services.pdf PDF
D.7 ATTACHMENT 7 - STANDARD EP LIST AND FREQUENCY.pdf PDF
D.5 ATTACHMENT 5- EXHIBIT C VASF CORRECTIVE ACTION FORM.pdf PDF
D.1 ATTACHMENT 1 - PAST PERFORMANCE SURVEY.docx DOCX document
S02 RFQ 36C26125Q0098 - Fire Suppression.pdf PDF
D.3 ATTACHMENT 3 - EXHIBIT A TJC LIFE SAFETY EC DOCUMENT LIST REVIEW TOOL.pdf PDF
36C26125Q0098_1.docx DOCX document
D.2 ATTACHMENT 2 - DOL WAGE DETERMINATION 2015-5637 REV.27, SAN FRANCISCO-SAN MATEO.pdf PDF
D.4 ATTACHMENT 4 - EXHIBIT B VASF FA TEST SCHEDULE 2025-30.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contracted By: San Francisco VA Health Care Systems

Facility: San Francisco VA Health Care Systems

Last Inspection Date: September 15, 2018

Last Inspected By: Corry Railey

Building 200

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-00G-001 Above double doors to administrations offices

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-00G-002 Above double doors to administrations offices

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-001 Next to room

1b-103 and service elevator

Smoke Inspection PASS PASS

09/15/18 FD-001-002 Above door 1A-

Fire Inspection PASS PASS

09/15/18 FD-001-003 In hall by room

1A-229

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-004 In hall by room

1A-229

Fire Inspection PASS PASS

09/15/18 FD-001-005 In hall by room

1A-136

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-006 In hall by room

1A-136

Fire Inspection PASS PASS

09/15/18 FD-002-001 Above double doors by 2B-

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-002 Above double doors by 2B-

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-003 Inside hall by room 2A-159A and room 2A-

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-004 In hall by room

2A-127 and the exit stairs

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-003-001 Inside OR above room

#3A-145

Fire Inspection NON-

ACCESSIBLE

Hard Ceiling NON-

ACCESSIBLE

09/15/18 FD-003-002 Inside OR by pump room above the emergency exit stairs

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-003-003 Inside SPD station

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

Last Inspection Date: September 15, 2018

Last Inspected By: Corry Railey

Building 203

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-00B-001 Above double doors by room

BA-4 and BA-3

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FSD-00B-002 Above double doors by room

BA-4 and BA-3

Smoke Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FSD-00B-003 Above double doors by room

BA-4 and BA-3

Smoke Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FSD-00B-004 Above double doors by room

BA-4 and BA-3

Smoke Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-00B-005 Inside electrical equipment room by MRI zone 2

Fire Inspection PASS PASS

09/15/18 FD-00G-004 In hall by room

GB3

Fire Inspection PASS PASS

09/15/18 FD-00G-005 In hall by room

GB3

Fire Inspection PASS PASS

09/15/18 FD-00G-006 In hall by room

GB3

Fire Inspection PASS PASS

09/15/18 FD-00G-007 In hall by room

GA-18

Fire Inspection PASS PASS

09/15/18 FD-00G-008 In hall by room

GA-18

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-001-001 In hall by room

1DU-3

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-002 Inside room

1DU-3 by elevators

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-001-003 Inside room

1DU-3 by elevators

Fire Inspection FAIL Bound in tracks

(racking)

FAIL

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

Date Damper

Number

Damper

Location

Damper Type Job Type Result Issues Current Status

09/15/18 FD-001-004 Inside room

1DU-3 by elevators

Fire Inspection PASS PASS

09/15/18 FD-001-005 Inside room

1DU-3 by elevators

Fire Inspection PASS PASS

09/15/18 FD-001-006 In hall by room

1B-1

Fire Inspection NON-

ACCESSIBLE

Longer than arm's reach

NON-

ACCESSIBLE

09/15/18 FSD-001-007 In hall by room

1B26A

Smoke Inspection PASS PASS

09/15/18 FD-001-008 In hall by room

1A-24

Fire Inspection PASS PASS

09/15/18 FD-001-009 In hall by room

1A-24

Fire Inspection PASS PASS

09/15/18 FD-001-010 Inside room

1EL-1

Fire Inspection NON-

ACCESSIBLE

No access door NON-

ACCESSIBLE

09/15/18 FD-002-001 In hall by room

2DU-4

Fire Inspection PASS PASS

09/15/18 FD-002-002 In hall by room

2DU-4

Fire Inspection PASS PASS

09/15/18 FD-002-003 In hall by room

2A-25

Fire Inspection NON-

ACCESSIBLE

Pipes blocking NON-

ACCESSIBLE

09/15/18 FD-002-004 In hall by room

2A-25

Fire Inspection NON-

ACCESSIBLE

Longer than arm's reach

NON-

ACCESSIBLE

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

VHASFCTangcR Highlight

Last Inspection Date: September 15, 2018

Last Inspected By: Corry Railey

Building 208

Date Damper Number Damper Location Damper Type Job Type Result Issues Current Status

09/15/18 FD-00P-002 Inside penthouse Fire Inspection PASS PASS

09/15/18 FD-00P-003 Inside penthouse Fire Inspection PASS PASS

09/15/18 FD-00P-004 Inside penthouse Fire Inspection PASS PASS

09/15/18 FD-001-001 In hall by room 1A-108 Fire Inspection NON-ACCESSIBLE No access door NON-

ACCESSIBLE

VHASFCTangcR Highlight

VHASFCTangcR Highlight

File details come from the government source that posted it. Updated .