36C26118R0214-053.docx

DOCX document 54 KB Posted

Attached to
654-250 New Parking Structure
Solicitation number
36C26118R0214
Issued by

About this file

36C26118R0214 231000 Facility Fuel.docx

View the file

Other files

File Type Posted
36C26118R0214-0004001.pdf PDF
36C26118R0214-0004000.docx DOCX document
36C26118R0214-0003001.pdf PDF
36C26118R0214-0003000.docx DOCX document
36C26118R0214-0003002.pdf PDF
36C26118R0214-0002001.pdf PDF
36C26118R0214-0001001.docx DOCX document
36C26118R0214-024.pdf PDF
36C26118R0214-054.docx DOCX document
36C26118R0214-045.docx DOCX document
36C26118R0214-006.pdf PDF
36C26118R0214-070.docx DOCX document
36C26118R0214-071.docx DOCX document
36C26118R0214-058.docx DOCX document
36C26118R0214-022.pdf PDF
36C26118R0214-005.pdf PDF
36C26118R0214-027.docx DOCX document
36C26118R0214-008.pdf PDF
36C26118R0214-029.docx DOCX document
36C26118R0214-081.pdf PDF
36C26118R0214-057.docx DOCX document
36C26118R0214-037.docx DOCX document
36C26118R0214-009.pdf PDF
36C26118R0214-079.pdf PDF
36C26118R0214-025.docx DOCX document
36C26118R0214-031.docx DOCX document
36C26118R0214-048.docx DOCX document
36C26118R0214-010.pdf PDF
36C26118R0214-004.pdf PDF
36C26118R0214-069.docx DOCX document
36C26118R0214-061.docx DOCX document
36C26118R0214-001.docx DOCX document
36C26118R0214-044.docx DOCX document
36C26118R0214-075.pdf PDF
36C26118R0214-063.docx DOCX document
36C26118R0214-052.docx DOCX document
36C26118R0214-040.docx DOCX document
36C26118R0214-039.docx DOCX document
36C26118R0214-019.pdf PDF
36C26118R0214-074.pdf PDF
36C26118R0214-067.docx DOCX document
36C26118R0214-043.docx DOCX document
36C26118R0214-011.pdf PDF
36C26118R0214-078.pdf PDF
36C26118R0214-021.pdf PDF
36C26118R0214-002.pdf PDF
36C26118R0214-066.docx DOCX document
36C26118R0214-051.docx DOCX document
36C26118R0214-034.doc DOC document
36C26118R0214-000.docx DOCX document
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

08-01-17

SECTION 23 10 00

FACILITY FUEL OIL SYSTEMS

GENERAL

SPEC WRITER NOTES:

1.Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the Section and renumber the paragraphs.
2.Revise as necessary to conform to local and state regulations.
3.References to pressure are gauge pressure unless otherwise noted.
4.This spec does not cover heated burner fuel storage.
5.This specification covers all aboveground and underground fuel oil storage tanks, including day tanks.
6.VA National CAD Standard for underground oil storage tanks, 30,000 liters (8,000 gallons) and above.
SD231000-01.DWG

DESCRIPTION

SPEC WRITER NOTE: Verify that the contract drawings show complete info on the tank locations, capacities, piping arrangement.

Diesel fuel oil and unheated burner fuel oil tanks, piping, and accessories located outside, underground or aboveground as shown on contract drawings. Refer to contract drawings for type of fuel and for tank capacities.

Tank fluid level monitoring and alarm systems.

Leak detection system for tanks and underground piping.

Fuel oil quality maintenance system (water and particulate removal).

A complete listing of common acronyms and abbreviations are included in //Section 23 05 10, COMMON WORK RESULTS FOR BOILER PLANT AND STEAM GENERATION// //Section 23 05 11, COMMON WORK RESULTS FOR HVAC//.

RELATED WORK

Section 01 00 00, GENERAL REQUIREMENTS.

Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.

//Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.// Section 03 30 00, CAST-IN-PLACE CONCRETE.

Section 05 50 00, METAL FABRICATIONS.

Section 09 91 00, PAINTING.

//Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.// //Section 23 05 10, COMMON WORK RESULTS FOR BOILER PLANT AND STEAM GENERATION.// //Section 23 05 11, COMMON WORK RESULTS FOR HVAC.// Section 23 07 11, HVAC AND BOILER PLANT INSULATION.

//Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.// Section 23 09 11, INSTRUMENTATION AND CONTROL FOR BOILER PLANT.

Section 23 21 11, BOILER PLANT PIPING SYSTEMS.

Section 23 50 11, BOILER PLANT MECHANICAL EQUIPMENT.

Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION.

Section 26 42 00, CATHODIC PROTECTION.

Section 31 20 00, EARTHWORK.

APPLICABLE PUBLICATIONS

SPEC WRITER NOTE: Make material requirements agree with requirements specified in the referenced Applicable Publications. Verify and update the publication list to that which applies to the project, unless the reference applies to all mechanical systems. Publications that apply to all mechanical systems may not be specifically referenced in the body of the specification, but, shall form a part of this specification.

The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. Where conflicts occur these specifications and the VHA standard will govern.

American Petroleum Institute (API):

RP 1631-2001 Interior Lining and Periodic Inspection of Underground Storage Tanks American Society of Mechanical Engineers (ASME):

B16.5-2013Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24 Metric/Inch Standard.
B16.9-2012Factory Made Wrought Buttwelding Fittings
B16.11-2011Forged Fittings, Socket-Welding and Threaded
B31.1-2014Power Piping

American Society for Testing and Materials (ASTM):

A36/A36M-2014Standard Specification for Carbon Structural Steel
A53/A53M-2012Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
A105/A105M-2014Standard Specification for Carbon Steel Forgings for Piping Applications
A106/A106M-2015Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service
A126-04(R2014)Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe Fittings
A234/A234M-2015Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature Service
B62-2015Standard Specification for Composition Bronze or Ounce Metal Castings
D2996-2015Standard Specification for Filament-Wound “Fiberglass” (Glass-Fiber-Reinforced Thermosetting-Resin) Pipe

Federal Specifications (Fed. Spec.):

A-A-60005-1998 Frames, Covers, Grating, Steps, Sump and Catch Basin, Manhole NACE International (NACE):

SP0169-2013Control of External Corrosion on Underground or Submerged Metallic Piping Systems
3/SSPC–SP6Commercial Blast Cleaning
4/SSPC-SP7Brush-off Blast Cleaning

National Electrical Manufacturers Association (NEMA):

250-2014 Enclosures for Electrical Equipment (1000 Volts Maximum) National Fire Protection Association (NFPA):

30-2015Flammable and Combustible Liquids Code
31-2016Standard for the Installation of Oil-Burning Equipment
70-2014National Electrical Code (NEC)

Steel Tank Institute (STI):

F001-2014Flameshield® Standard for Fire Tested Tanks
F841-2006Standard for Dual Wall Underground Steel Storage Tanks
F894-2015ACT-100® Specification for External Corrosion Protection of FRP Composite Steel Underground Storage Tanks
F941-2015Fireguard: Specification for Fireguard Protected Aboveground Storage Tanks
F961-2015ACT-100U Specification for External Corrosion Protection of Composite Steel Underground Storage Tanks
P3-2015Specification and Manual for External Corrosion Protection of Underground Steel Storage Tanks
R891-2006Recommended Practice for Hold Down Strap Isolation

Underwriters Laboratories Inc. (UL):

58-1996 (R1998)Standard for Steel Underground Tanks for Flammable and Combustible Liquids
142-2006 (R2014)Standard for Steel Aboveground Tanks for Flammable and Combustible Liquids
971-2008Standard for Nonmetallic Underground Piping for Flammable Liquids
1316-2008Glass-Fiber-Reinforced Plastic Underground Storage Tanks for Petroleum Products, Alcohols, and Alcohol-Gasoline Mixtures
1746-2007 (R2014)Standard for External Corrosion Protection Systems for Steel Underground Storage Tanks
2085-2003Standard for Protected Aboveground Tanks for Flammable and Combustible Liquids

SUBMITTALS

Submittals, including number of required copies, shall be submitted in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Information and material submitted under this section shall be marked “SUBMITTED UNDER SECTION 23 10 00, FACILITY FUEL OIL SYSTEMS”, with applicable paragraph identification.

Manufacturer's Literature and Data including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, and capacity.

Underground Tanks:

Drawings of tanks, anchoring devices, heating coils (if required), tank manholes, tank manhole enclosures, access doors for the tank manhole enclosures and all accessories. Include overall dimensions and dimensional locations and sizes of all anchoring devices, pipe connections, and access openings.

Manufacturer's installation instructions describing recommended foundation, bedding and backfill material, support and anchoring devices, and method of installation.

Weight of entire tank assemblies, empty and flooded.

Certification of compliance with specified standards.

Certification that steel tank manufacturer participates in the Steel Tank Institute (STI) Quality Assurance Program.

Data certifying that tanks are designed for surcharge loads of backfill, traffic and other construction.

Design and construction of tanks, secondary containment, pipe connections, manholes, anchoring devices, access doors for tank manhole enclosures.

Application and performance data on tank coating (steel tanks) from manufacturer of coating.

Design of cathodic protection system (when specified) for steel tanks.

Aboveground Steel Tanks, Including Vault-type Tanks:

Drawings of tanks, supports, ladders, platforms, heating coils, tank manholes, emergency relief vents and all accessories. Include overall dimensions and dimensional locations and sizes of pipe connections, and access openings.

Recommended tank support locations.

Weight of entire tank assembly, empty and flooded.

Design and construction of primary tanks, insulation, secondary containment, supports, pipe connections, platforms.

Application and performance data on coatings from manufacturer of coatings.

Data certifying tanks are designed for surcharge loads of platforms shown.

Certification of compliance with specified standards.

Certification that steel tank manufacturer participates in Steel Tank Institute (STI) Quality Assurance Program.

Design, construction, performance, dimensions of emergency relief vents.

SPEC WRITER NOTE: Delete the following paragraph in a non-seismic project.

//Seismic Data: Refer to Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.// Fuel Piping:

ASTM and UL compliance.

Grade, class or type, schedule number.

Manufacturer.

Pipe Fittings, Unions, Flanges:

ASTM and UL compliance.

ASTM standards number.

Catalog cuts.

Pressure and temperature rating.

Foot Valves, Check Valves, Overfill Prevention Valves:

Catalog cuts showing design and construction.

Pressure and temperature ratings.

Pressure loss and flow rate data.

Materials of construction.

Accessories.

Secondary Containment System for Fuel Piping:

Sizes, materials, construction of containment system including end seals, sumps, coatings and pipe supports.

Layout of system.

Installation instructions.

Design of cathodic protection system (steel casing).

Leak Detection System:

Drawings, description and performance data on sensors, control units.

Description of operation.

Layout of system.

Installation and operating instructions.

Data on interconnecting wiring systems to be furnished.

Tank Fluid Level Monitoring Instrumentation System:

Drawings showing instruments and in-tank sensing units, with dimensions.

Design and construction of all elements of system.

Installation instructions.

Tank and Piping Accessories: Design, construction, and dimensions of vent caps, fill boxes, fill caps, spill containers and other accessories.

Fuel Quality Maintenance System:

Drawings and description of all components and arrangement of system.

Design and performance of pumps, filters.

Catalog data and operation of control system.

Installation instructions.

Complete operating and maintenance manuals including wiring diagrams, technical data sheets, information for ordering replacement parts, and troubleshooting guide:

Include complete list indicating all components of the systems.

Include complete diagrams of the internal wiring for each item of equipment.

Diagrams shall have their terminals identified to facilitate installation, operation and maintenance.

//Completed System Readiness Checklist provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.// //Submit training plans and instructor qualifications in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.//

QUALITY ASSURANCE

Approval by Contracting Officer is required of products or services of proposed manufacturers, suppliers and installers, and will be based on Contractor’s certification that:

Manufacturers regularly and currently manufacture tanks, tank and piping accessories, tank fluid level monitoring and leak detection systems, and fuel quality management systems.

Manufacturers of steel tanks participate in the Quality Assurance Program of the Steel Tank Institute (STI).

The design and size of each item of equipment provided for this project is of current production and has been in satisfactory operation on at least three installations for approximately three years. Current models of fluid level and leak detection systems with less than three years’ service experience are acceptable if similar previous models from the same manufacturer have at least three years’ service experience.

Apply and install materials, equipment and specialties in accordance with manufacturer’s written instructions. Conflicts between the manufacturer’s instructions and the contract drawings and specifications shall be referred to the COR for resolution. Provide copies of installation instructions to the COR two weeks prior to commencing installation of any item.

All equipment shall be free from defects that would adversely affect the performance, maintainability and appearance of individual components or overall assembly.

Tanks, Secondary Containment Systems for Piping, Plastic Piping and Containment Systems, Tank Level Monitoring Systems, Leak Detection Systems, Fuel Quality Management Systems, Cathodic Protection Systems: Authorized manufacturer’s representatives shall provide onsite training of installers and supervision of the installation and testing of the equipment and systems to assure conformance to written instructions of manufacturers.

Tank and piping installation contractor shall be certified as acceptable by local and state pollution control authorities.

Entire installation shall conform to requirements of local and state pollution control authorities.

Pipe Welding: Conform to requirements of ASME B31.1. Welders shall show evidence of qualification. Welders shall utilize a stamp to identify their work. Unqualified personnel will be rejected.

Assembly of Glass Fiber Reinforced Plastic Piping: Installation personnel shall have been trained, tested and certified under a procedure approved by the manufacturer of the piping. Proof of certification, in writing, shall be provided to the COR.

Where specified codes or standards conflict, consult the COR.

Label of Conformance (definition): Labels of accredited testing laboratories showing conformance to the standards specified.

Equipment and materials installed shall be compatible in all respects with other items being furnished and with existing items so that the result will be a safe, complete and fully operational system which conforms to contract requirements and in which no item is subject to conditions beyond its design capabilities.

AS-BUILT DOCUMENTATION

SPEC WRITER NOTE: Coordinate O&M Manual requirements with Section 01 00 00, GENERAL REQUIREMENTS. O&M manuals shall be submitted for content review as part of the close-out documents.

Submit manufacturer’s literature and data updated to include submittal review comments and any equipment substitutions.

Submit operation and maintenance data updated to include submittal review comments, VA approved substitutions and construction revisions shall be //in electronic version on CD or DVD// inserted into a three-ring binder. All aspects of system operation and maintenance procedures, including applicable piping isometrics, wiring diagrams of all circuits, a written description of system design, control logic, and sequence of operation shall be included in the operation and maintenance manual. The operations and maintenance manual shall include troubleshooting techniques and procedures for emergency situations. Notes on all special systems or devices shall be included. A List of recommended spare parts (manufacturer, model number, and quantity) shall be furnished. Information explaining any special knowledge or tools the owner will be required to employ shall be inserted into the As-Built documentation.

SPEC WRITER NOTE: Select and edit one of the bracketed options after the paragraph below to indicate the format in which the contractor must provide record drawing files. Select the hand-marked option only when the designer has been separately contracted to provide the record drawings from the contractor’s mark-ups. Select the BIM option only when a BIM model will be generated, which is typically only performed by the designer on some Design-Bid-Build projects or by the contractor on some Design-Build projects.

The installing contractor shall maintain as-built drawings of each completed phase for verification; and, shall provide the complete set at the time of final systems certification testing. Should the installing contractor engage the testing company to provide as-built or any portion thereof, it shall not be deemed a conflict of interest or breach of the ‘third party testing company’ requirement. Provide record drawings as follows:

//Red-lined, hand-marked drawings are to be provided, with one paper copy and a scanned PDF version of the hand-marked drawings provided on CD or DVD.// //As-built drawings are to be provided, with a copy of them on AutoCAD version // // provided on CD or DVD. The CAD drawings shall use multiple line layers with a separate individual layer for each system.// //As-built drawings are to be provided, with a copy of them in three-dimensional Building Information Modeling (BIM) software version // // provided on CD or DVD.// The as-built drawings shall indicate the location and type of all lockout/tagout points for all energy sources for all equipment and pumps to include breaker location and numbers, valve tag numbers, etc. Coordinate lockout/tagout procedures and practices with local VA requirements.

Certification documentation shall be provided to COR 21 working days prior to submitting the request for final inspection. The documentation shall include all test results, the names of individuals performing work for the testing agency on this project, detailed procedures followed for all tests, and provide documentation/certification that all results of tests were within limits specified. Test results shall contain written sequence of test procedure with written test results annotated at each step along with the expected outcome or setpoint. The results shall include all readings, including but not limited to data on device (make, model and performance characteristics), normal pressures, switch ranges, trip points, amp readings, and calibration data to include equipment serial numbers or individual identifications, etc.

PERMITS

Contractor shall obtain and complete all tank permit and registration forms required by governmental authorities.

PRODUCTS

UNDERGROUND STEEL TANKS

Factory-fabricated all welded double-wall steel, horizontal cylindrical configuration, atmospheric pressure, internal and external corrosion protection as specified. Tanks shall be fabricated in accordance with Steel Tank Institute (STI) design standards by manufacturer that participates in STI Quality Assurance Program.

Construction:

ASTM A36/A36M steel, UL 58 double-wall, 360-degree secondary containment.

Conform to NFPA 30 or NFPA 31 as applicable.

The bottom 60 degrees of all lap or offset circumferential interior seams shall be seal welded 30 degrees each way from bottom centerline to retard corrosion.

Design for surcharge loads such as backfill and paving as shown. In addition, in paved areas, design for AASHTO H-20 14,515 kg (32,000 pound) axle loading.

Leaks and abrasions are prohibited. Maximum outofroundness is one percent of the diameter.

Outer wall shall provide leak tight secondary containment that covers 100 percent of tank volume and shall permit migration of any inner tank leakage to the lowest part of the tank where leak detectors are located. Make provisions for leak detectors to be furnished at lowest part of interstitial space between tank walls.

Factory Cleaning: Clean interior and exterior. Remove all mill scale, dirt, rust, oil, welding debris, loose coatings and coatings and material incompatible with fuel stored or protective coating to be furnished. Sandblast exterior in accordance with NACE 3/SSPC-SP6 and STI corrosion protection system requirements.

SPEC WRITER NOTE: Select the Steel Tank Institute (STI) corrosion protection system in Par. D that is required for the project. Reference: www.steeltank.com

Factory Applied Exterior Corrosion Protection System: Steel Tank Institute (STI) //ACT-100 steel/FRP composite (STI F894)// //ACT-100-U urethane coating (STI F961)// //STI P3 coating/cathodic protection (STI F841// technology. Tank shall be labeled to indicate compliance. Provide signed holiday test results. Provide STI standard limited 30-year warranty against internal and external corrosion penetrating the tank.

Factory Applied Interior Coating: API RP 1631 coating from bottom of tank to 1 m (3 feet) from bottom.

SPEC WRITER NOTES:

1.ACT-100 and 100-U: paragraphs F and G are optional.
2.STI P3: Include paragraphs F and G. Where soil resistivity is less than 4000 ohm-cm, delete paragraphs F and G and specify complete cathodic protection system under Section 26 42 00, CATHODIC PROTECTION.

//Cathodic Protection: Conform to UL 1746 and STI P3 and NACE SP0169 consisting of galvanic anodes, wire conductors welded to the tank and connected to test stations and anodes, insulating devices to electrically isolate the tank from piping, test stations properly connected to permit required tests.// //Cathodic Protection System Test Stations:

STI P3 system for tanks.

Weatherproof high-impact-resistant plastic housing. Provide means to securely anchor housing. Locking cover for terminal board. Yellow color. Identification "CP TEST STATION" molded in cover or otherwise permanently marked.

High-impact-resistant plastic terminal board, cadmium-plated or zinc-plated hardware, accessible from front and rear, sufficient terminals for all required connections.// SPEC WRITER NOTE: Verify that drawings are coordinated with the following paragraph. Revise as necessary if concrete enclosure is to be provided.

Tank Manhole Enclosures:

Rectangular or cylindrical enclosures, sized as shown, designed to contain fuel spills from leaking piping. Locate all tank manholes and tank piping connections within the enclosure. Watertight pipe penetrations.

Steel, fiberglass or polyethylene. Reinforce to prevent deflection. Leak-tight attachment to tank. Clean and coat interior and exterior of steel enclosure as specified for exterior of tank.

In traffic areas, enclosure must be designed to withstand traffic loads (AASHTO H-20 wheel loading, 14,515 kg, (32,000 pound)) and must have flexible isolation system to prevent wheel loads being transmitted to tank.

For steel enclosures, provide cathodic protection system and test station as specified for the tanks.

Access to Manhole Enclosure: //Cast iron manhole frames and covers, rated for traffic, minimum opening as shown. Comply with Fed. Spec. A-A-60005.// //Sidewalk type metal doors as shown and as specified under Section 05 50 00, METAL FABRICATIONS.// Pipe Connections to Tanks:

Conform to UL 58.

Pipe sizes 100 mm (4 inches) and smaller, threaded. Pipe sizes 150 mm (6 inches) and larger, raised faced slip-on flanges, 1034 kPa (150 psig) ASME rating.

Welded joints required on steel piping located inside tanks.

Provide and coordinate tank connection quantities, sizes and types with requirements of fluid level gauge unit; leak detector sensor; sounding rod; vent, fill, supply and return pipes; and other pipes as shown.

Dielectric insulation on all connections to steel piping.

All tank piping connections, except vent, shall be within the tank manhole enclosure.

Tank Manholes: Provide quantity shown. Bolted cover type, gasketed. Zinc plated bolts, nuts, washers.

Internal Ladder: Provide as shown and shall have 50 mm x 6 mm (2 inch x 1/4 inch) sides, 20 mm (3/4 inch) diameter rungs on 300 mm (12 inch) centers. Provide slide supports to allow for tank movement.

Wear (Striker) Plates: Provide 300 mm (12 inch) square, 6 mm (1/4 inch) thick steel plates rolled and seal-welded to bottom of tank directly under all openings.

Lifting Lugs: Provide for rigging tanks.

Hold Down Straps: Provide quantity and design of EPDM-type rubber encased steel straps as recommended by tank manufacturer to anchor tank to concrete ballast slab. Hold down strap electrical isolation shall conform to STI R891. Straps shall have tension load capability equal to hold-down capability of ballast slab, with a minimum safety factor of two. Provide complete anchorage devices, including turnbuckles, for adjusting tension.

ABOVEGROUND STEEL TANKS

Type: Factory-fabricated all welded steel, horizontal cylindrical configuration, atmospheric pressure, internal and external corrosion protection as specified. In addition to specified requirements, tanks shall be fabricated in accordance with Steel Tank Institute (STI) design standards by manufacturer that participates in STI Quality Assurance Program.

Construction:

ASTM A36/A36M steel, conform to UL 142. Inner and outer tanks of double wall tanks shall both conform. Provide label of conformance.

Conform to NFPA 30 or NFPA 31 as applicable.

SPEC WRITER NOTE: For description of STI design features refer to www.steeltank.com. Insulated tank may not require dike. Contact local authorities for requirements.

//Double-wall, un-insulated, conforming to STI F001 “Flameshield” construction. Provide label of conformance.// //Double-wall, insulation between walls, conforming to STI F941 "Fireguard" construction, and to UL 2085. Provide label of conformance.// //Single-wall. No STI standards apply.// //Steel dike walls and floors conforming to STI standards. Provide minimum containment of 110 percent of primary tank contents. //Provide steel rain shields which cover the open areas between the tank and the dike wall.// // Design for surcharge load produced by tankmounted platforms and platform loadings shown. Design tanks for saddle supports furnished by tank manufacturer.

Leaks and abrasions are prohibited. Maximum permissible outofroundness of cylindrical shells is one percent of the diameter.

Provide lifting lugs for rigging tanks.

Make provisions for leak detectors to be installed at lowest part of interstitial space between walls of double-wall tanks.

Platforms, Stairs, Ladders and Handrails: Provide welded steel assemblies as shown, conforming to OSHA requirements. Provide welded steel tank attachments designed to support platform framing, stairs, ladders and live and dead loadings. Clean and coat all surfaces as specified for tank and steel dike exterior. Galvanizing is an acceptable alternative.

Factory Cleaning: Clean interior and exterior of tanks and steel dikes (if furnished). Remove mill scale, dirt, rust, oil, welding debris, loose coatings and coatings incompatible with fuel stored or protective coating. Sandblast exterior in accordance with NACE 3.

Factory Coating: Provide tanks and steel dikes (if furnished) with exterior coat of rust resistant metal primer, specified under Section 09 91 00, PAINTING. Coat interior from bottom of tank to 1 m (3 feet) above bottom in compliance with API RP 1631.

Field Painting: Clean and coat all surfaces as specified in Section 09 91 00, PAINTING.

Pipe Connections to Tanks:

Conform to UL 142.

Pipe sizes 50 mm (2 inches) and smaller, threaded. Pipe sizes 65 mm (21/2 inches) and larger, flanged, 1034 kPa (150 psig) ASME rating.

Welded joints required on steel piping located inside tanks.

Provide and coordinate tank connection quantities, sizes and types with requirements of tank level gauge unit; sounding rod; vent, fill, supply and return pipes; and other pipes as shown.

On double-wall tanks, provide valved drain of interstitial space.

Tank Manholes: Provide quantity shown. Bolted cover type, gasketed.

Internal Ladder: Provide as shown with 50 mm x 6 mm (2 inch x 1/4 inch) sides and 20 mm (3/4 inch) diameter rungs at 300 mm (12 inches) on center. Provide slide supports to allow for tank movement.

Wear (Striker) Plates: Provide 300 mm (12 inch) square, 6 mm (1/4 inch) thick steel plates welded to tank bottom directly under the sounding opening, the fuel return discharge, and the fill discharge.

Lifting Lugs: Provide for rigging tanks.

Emergency Relief Vents for Fire Exposure: Venting capacity shall conform to NFPA 30 or NFPA 31 as applicable. Standard product of a manufacturer, designed to automatically open at tank pressure of 17 kPa (2.5 psig) gauge. Aluminum or cast-iron construction with Teflon seating surface. Provide separate vents for primary and secondary tanks.

Provide fittings for grounding per NFPA 70.

SPEC WRITER NOTE: Delete the following paragraph in non-seismic project.

//Seismic Design: Refer to Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.//

ABOVEGROUND CONCRETE-INSULATED STEEL VAULT TANKS

Type: All-welded steel tank, horizontal cylindrical or rectangular configuration, atmospheric pressure, concrete insulation, double-containment, for aboveground installation as shown. Entire unit factory-fabricated, including steel tank and concrete insulation. Provide tank supports that can be anchored to a concrete foundation.

Construction:

Comply with UL 2085 for protected tanks, vehicle impact resistant and projectile resistant with secondary containment. Provide label of conformance.

Inner tank ASTM A36/A36M steel constructed in conformance with UL 142. Provide label of conformance. Steel tanks shall be supported as recommended by steel tank manufacturer. Top of secondary tank shall be sloped to shed rainwater. Test tanks for leaks with test pressure of 21 to 34 kPa (3 to 5 psig) gauge. Furnish certificate that inner and outer tanks have been tested and are leak-free and pressure-tight.

Concrete Insulation:

Shall consist of 20 MPa (3,000 psig) minimum concrete.

Shall be structurally designed to support the filled tank and a top live load of 4.8 kPa (100 lb./sq. ft.).

Monolithic pour with no cold joints, heat sinks. As an alternate, there may be one continuous shiplap joint located at horizontal center of vault sealed with fire and fuel resistant gaskets.

Construct in accordance with ACI and AASHTO standards including concrete placement, vibration, and quality assurance.

Conform to NFPA 30 or NFPA 31 fire safety standards as applicable. Design for two-hour fire exposure. Provide fittings for grounding per NFPA 70.

The tank assembly shall have capability of physical monitoring for leaks between primary and secondary containment.

Provide overfill containment (spill container) with internal drain and positive seal.

Factory Cleaning: Clean interior and exterior. Remove mill scale, dirt, rust, oil, welding debris, loose coatings and coatings incompatible with fuel stored or protective coating.

Factory Coatings: Provide coating of rust resistant red oxide primer on non-fuel side of steel tanks. For tanks with interior access, coat interior of primary tank from bottom to 1 m (3 feet) above bottom in conformance with API RP 1631. Provide two coats of fuel resistant epoxy coating on exposed surfaces of the external concrete tank.

Platforms, Ladders, Stairs, Handrails: Provide as shown. Shall be welded steel assemblies conforming to OSHA requirements. Paint in accordance with Section 09 91 00, PAINTING. Galvanizing is an acceptable alternative.

Pipe Connections to Tanks:

Pipe shall terminate 75 mm (3 inches) minimum from top of unit.

Conform to UL 142.

Pipe sizes 50 mm (2 inches) and smaller, threaded. Pipe sizes 65 mm (21/2 inches) and larger, 1034 kPa (150 psig) ASME flanged.

Welded joints required on steel piping located inside tanks.

Provide and coordinate tank connection quantities, sizes and types with requirements of tank level gauge unit; leak detector sensor; sounding rod; vent, fill, supply and return pipes; and other pipes as shown.

Provide valved drain on interstitial space.

Tank Manholes: Provide quantity and size shown. Bolted cover type, gasketed.

Emergency Relief Vents for Fire Exposure: Venting capacity shall conform to NFPA 30 or NFPA 31 as applicable. Provide separate vents for primary and secondary tanks. Standard product of a manufacturer, designed to automatically open at tank pressure of 17 kPa (2.5 psig). Aluminum or cast-iron construction, with Teflon-coated seating surface.

Internal Ladder: Provide as shown with 50 mm x 6 mm (2 inch x 1/4 inch) sides and 20 mm (3/4 inch) diameter rungs at 300 mm (12 inches) on center. Provide slide supports to allow for tank movement.

Wear (Striker) Plates: Provide 300 mm (12 inch) square, 6 mm (1/4 inch) thick steel plates welded to tank bottom directly under the sounding opening, the fuel return discharge, and the fill discharge.

Lifting Lugs: Provide for rigging tanks.

SPEC WRITER NOTE: Delete the following paragraph in a non-seismic project.

//Seismic Design: Refer to Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.//

UNDERGROUND FIBERGLASS REINFORCED PLASTIC TANKS

Type: Factoryfabricated, double-wall, fiberglass reinforced polyester (FRP), horizontal cylindrical configuration, atmospheric pressure, for underground installation as shown.

Construction:

UL 1316. Provide label of conformance.

Conform to NFPA 30 or NFPA 31 as applicable.

Design for surcharge loads due to backfill and paving as shown. In addition, in paved areas, design for AASHTO H-20 14,515 kg (32,000 pound) axle loading.

Leaks and abrasions are prohibited. Maximum outofroundness is one percent of the diameter.

Outer wall shall provide leaktight secondary containment that covers entire tank. Provide annular space between the walls arranged with flow channels to allow tank leakage at any point to flow to a leak detector at the bottom of the annular space. Provide connection point to outer wall and plastic pipe from tank connection to grade designed to accommodate leak detection device.

Factory Cleaning: Clean interior and exterior. Remove all dirt, debris, and coatings and material incompatible with fuel being stored.

Fiberglass Manhole Enclosures:

Cylindrical enclosures sized as shown, designed to contain fuel spills from tank piping. Locate all tank manholes and all tank piping connections within the enclosures.

Same material type and thickness as tank. Reinforce to prevent deflection. Provide leaktight connection to tank designed to allow removal of tank manway cover without disturbing connection between enclosure and tank. Coat all exposed steel surfaces, such as bolting, with two coats of urethane.

In traffic areas, enclosures and tank must have flexible isolation system to prevent wheel loads from being transmitted to the tank.

For burner fuel tanks, design enclosure to permit installation and removal from above grade of present or future heating coil as an assembled unit.

Access to Manhole Enclosure: //Fed. Spec. A-A-60005 cast iron manhole frames and covers rated for AASHTO H-20 14,515 kg (32,000 pound) axle loading minimum with opening size as shown.// //Sidewalk type metal doors as shown and as specified under Section 05 50 00, METAL FABRICATIONS.// Pipe Connections to Tanks:

Conform to UL 1316.

Pipe sizes 100 mm (4 inches) and smaller, threaded. Pipe sizes 125 mm (5 inches) and larger, 1034 kPa (150 psig) ASME flanged.

Welded joints required on steel piping located inside tanks.

Provide and coordinate tank connection quantities, sizes and types with requirements of level gauge unit; tank leak detector; sounding rod; vent, fill, supply and return pipes; and other pipes as shown.

All tank piping connections shall be within the tank manhole enclosures and sump/risers.

Tank Manholes: Provide quantity shown. Bolted cover type, gasketed, zincplated bolts, nuts and washers.

Internal Ladder: Provide as shown with 50 mm x 6 mm (2 inch x 1/4 inch) sides and 20 mm (3/4 inch) diameter rungs at 300 mm (12 inches) on center. Provide slide support to allow tank movement.

Wear (Striker) Plates: Provide 300 mm (12 inch) square, 6 mm (1/4 inch) thick steel plates attached to bottom of tank directly under the sounding opening, the fuel return discharge, and the fill discharge.

Lifting Lugs: Provide for rigging tanks.

Hold-Down Straps: Provide quantity and design of FRP straps as recommended by tank manufacturer to anchor tank to concrete ballast slab. Straps shall have tension load capability equal to hold-down capability of ballast slab, with a minimum safety factor of two. Provide complete anchorage devices, including turnbuckles, for adjusting tension.

SOIL SEPARATOR MAT

Material: Porous, non-woven polypropylene geotextile, Weight: 135 g per sq. meter (4 ounces per square yard), resistant to all alkalies and weak acids.

TANK AND PIPING ACCESSORIES

Vent Caps: Galvanized cast iron or cast aluminum with brass or bronze screens, arranged to permit full venting and to prevent entry of foreign material into the vent line. Same pipe size as vent pipe.

Fill Boxes:

Spill-container type enclosing a fill cap assembly with camlock hose connector with closure coordinated with fittings used by fuel supplier.

Watertight assembly, cylindrical body, quick-opening corrosion-resistant watertight sealable cover, polyethylene spill containment compartment with minimum //5// //10// //15// //25// gallon capacity. Integral drain valve with discharge to fill pipe.

Fill cap shall be lockable, tight-fill design with provision for padlock on the top of the cap. Fill cap shall screw onto threaded adapter that can be removed without removing fill box. Entire assembly shall seal tight with no leakage during filling and when cap is in place.

Provide special tools necessary for opening fill boxes and fill caps.

Protect spill container from traffic by ramped, drain-slotted cast iron body ring and cover. Design shall prevent transmission of traffic loads to the underground tank. Spill-container type not required at locations designated only for sounding tanks.

Fill caps located above grade without fill boxes shall be lockable, tight-fill design, operated by special wrench that shall be furnished. Entire assembly shall seal tight with no leakage during fill and when cap is in place.

Refer to Section 05 50 00, METAL FABRICATIONS, for access platforms shown for aboveground tanks.

Support horizontal portion of pipes located inside tank every 2100 mm (7 feet) maximum.

Furnish gauging chart, liters versus mm and gallons versus inches depth.

Furnish sounding rod for each tank size. Mark rods in increments representing five percent of tank capacity. Provide length of rod suitable for tank burial depth (if applicable). Rods shall be graduated in //liters// //gallons//.

Fill Point Identification:

Fill Boxes at Grade Level: Aluminum, brass or bronze plate, anchored to concrete fill box pad with stamped or engraved letters 20 mm (3/4 inch) high.

Fill Caps above Grade: Aluminum, brass or bronze plate, clamped to fill pipe, with stamped or engraved letters 20 mm (3/4 inch) high.

Legend: "BURNER FUEL OIL FILL" "DIESEL FUEL FILL” or "SOUNDING" as appropriate.

PIPING, VALVES, FITTINGS

Fuel supply and return, tank fill, vents, sounding, and pump out.

Steel Pipe and Fittings:

Piping: Steel, seamless or electric resistance welded (ERW), ASTM A53/A53M Grade B or ASTM A106/A106M Grade B, Schedule 40. Aboveground piping shall be painted. Refer to Section 09 91 00, PAINTING.

Joints: Socket or butt-welded. Threaded joints are prohibited except at valves, unions and tank connections.

Fittings:

Butt-welded joints: Steel, ASTM A234/A234M, Grade B, ASME B16.9, same schedule as adjoining pipe.

Socket-welded joints: Forged steel, ASME B16.11, 13,790 kPa (2000 psig) class.

Unions: Malleable iron, 2070 kPa (300 psig) class.

Companion flanges: Flanges and bolting, ASME B16.5.

Welding flanges: Weld neck, ASME B16.5, forged steel ASTM A105/A105M, 1034 kPa (150 psig).

SPEC WRITER NOTE: Delete the following paragraph if pipeline will be traced or if fuel temperature will exceed 65 degrees C (150 degrees F), or if fuel pressure can exceed 345 kPa (50 psig).

Glass Fiber Reinforced Plastic (FRP) Pipe and Fittings:

Conform to UL 971 and ASTM D2996 using a filament-winding process and epoxy or vinyl ester resins.

Design pipe, fittings and joining system for required fuel service, 65 degrees C (150 degrees F), 1034 kPa (150 psig) pressure, 68 kPa (20 inches Hg) vacuum.

Provide an integral resin-rich liner, 0.5 mm (0.020 inches) minimum thickness to enhance the corrosion resistance. Outer layer shall include ultra-violet inhibitors. Joining adhesive shall be designed for the pipe furnished and shall be supplied by the pipe manufacturer.

Plastic piping allowed in underground use only.

Check Valves - Fuel Pump Suction.

Pipe Sizes 50 mm (2 inches) and under: Rated for 1375 kPa (200 psig) water-oil-gas, swing-type, threaded ends, ASTM B62 bronze body. Provide union adjacent to valve.

Pipe Sizes 65 mm (21/2 inches) and above: Rated for 1380 kPa (200 psig) water-oil-gas, swing-type, 861 kPa (125 pounds) ASME flanged ends, ASTM A126 class B cast iron body.

Foot Valves - Fuel Pump Suction: Double poppet, lapped-in metal-to-metal seats, double-guided stems, 20 mesh inlet screen, same size as fuel suction piping. Foot valve shall be removable to above grade through the tank manhole enclosure or through extractor fitting.

Extractor Fittings: Arranged to permit removal of foot valves, overfill prevention valves, and other devices that are located below grade. Access point shall be through a cast iron fill box-type manhole located at grade. Provide extractor wrench.

Overfill Prevention Valve: Aluminum automatic valve designed for underground or aboveground tanks, as applicable. Removable through the extractor fitting on underground tanks. Locate valve near the top of the tank in the fill pipe. On underground tanks with gravity fill, provide two stage automatic float-operated valve. First stage operation at 92 percent tank capacity shall reduce flow to 0.3 L/s (5 gpm) or less. Second stage operation shall stop flow completely when tank is no more than 95 percent full. On aboveground tanks, or tanks pressure-filled, provide single stage valve, rated for fill flow and pressure, which stops flow completely at 95 percent of tank capacity. Valve shall include method for draining oil trapped above the valve into the tank.

SECONDARY CONTAINMENT FOR UNDERGROUND FUEL PIPING SYSTEMS

Enclose the fuel supply, return and fill pipes in factory-engineered and fabricated secondary containment conduit systems. The systems shall be complete with end seals, with 25 mm (1 inches) minimum continuous annular space, 40 mm (11/2 inches) between carrier pipes, which shall contain all leakage and which has provisions for leak detection system as specified.

SPEC WRITER NOTE: Where soil resistivity is less than 4000 ohm-cm, delete cathodic protection requirements below and specify complete cathodic protection system under Section 26 42 00, CATHODIC PROTECTION. Paragraphs B, C, D below can be contractor’s options or all but one of the paragraphs can be deleted to suit the project.

Steel Conduit with Fusion-Bonded Epoxy Coating and Cathodic Protection:

Galvanized carbon steel pipe, ASTM A53/A53M, Grade B, Schedule 40 for diameters through 125 mm (5 inches), 3.4 mm (0.134 inch) thick for diameters greater than 125 mm (5 inches) up through 660 mm (26 inches). All welded construction.

Sand blast exterior per NACE 3.

Coat exterior with 0.5 mm (20 mils) thick fusion-bonded epoxy.

Provide cathodic protection designed by corrosion specialist and consisting of galvanic anodes, test stations, interconnecting wiring in conformance with UL 1746 and NACE SP0169. Electrical isolation required between all connecting systems in manholes and buildings.

Steel Conduit with Fiberglass Reinforced Plastic (FRP) Coating:

Carbon steel pipe, ASTM A53/A53M, Grade B, Schedule 40 for diameters through 125 mm (5 inches), 3.4 mm (0.134 inch) thick for diameters greater than 125 mm (5 inches) up thru 660 mm (26 inches). All welded construction.

Blast clean exterior per NACE 4/SSPC-SP7.

Apply fiberglass reinforced polyester (FRP) external cladding at least 2.5 mm (0.10 inches) thick with ultra-violet inhibitor. Cladding on field joints shall be equivalent to factory-applied cladding applied on remainder of system.

Test entire system for holidays using a 35,000-volt holiday detector.

Glass Fiber Reinforced Plastic (FRP) Conduit:

Conform to UL 971 and ASTM D2996 using a filament-winding process and epoxy or vinyl ester resins.

Design pipe, fittings and joining system for carrier pipe fuel service, 65 degrees C (150 degrees F), 1034 kPa (150 psig) pressure, 68 kPa (20 inches Hg) vacuum.

Provide an integral resin-rich liner, minimum thickness 0.25 mm (0.010 inch). Outer layer shall include ultra-violet inhibitors.

Minimum total wall thickness 1.8 mm (0.07 inch) for diameters below 200 mm (8 inches), 2.8 mm (0.11 inch) for diameters 200 mm (8 inches) and 250 mm (10 inches), 5 mm (3/16 inch) for diameters 250 mm (10 inches) through 508 mm (20 inches), and 6 mm (1/4 inch) for diameters above 508 mm (20 inches).

Pipe Supports: Provide supports within conduit for fuel carrier pipes spaced 2100 mm (7 feet) apart except 3000 mm (10 feet) apart for carrier pipe size 50 mm (2 inches) through 100 mm (4 inches). Support design shall permit differential movement of pipes, allow drainage of leakage to sumps, and maintain alignment of carrier pipes.

Conduit End Seals: Same material and coating as conduit; leak tight.

Leak Detector Sensor Locations: On each piping system, provide sumps at the low points with water-tight openings above grade for access to leak detector sensors. Design sumps to intercept all potential leakage. Maximum spacing between sumps, 3000 mm (10 feet).

LEAK DETECTION SYSTEMS

Automatic digital continuous monitoring systems responsive to the presence of water and hydrocarbons in the interstitial space of the double-wall tanks, in the tank manhole access enclosures, and in the secondary containment of fuel piping systems. System shall distinguish between hydrocarbon and water and identify location of leak as to individual tank and piping system. //System may be combined with tank fluid level monitor and alarm system specified in paragraph, TANK FLUID LEVEL MONITOR AND ALARM SYSTEM.// Functions and Arrangement:

Single control station to monitor all sensing probes.

Visual indicator to monitor and identify leaks as water or hydrocarbon and location.

Indicators showing system status including faults and alarms.

On board printer that provides complete reports of all system functions upon command.

Panel circuit test button.

95 dB audible alarm with silencing control to sound when leak is detected.

Eight-hour memory backup system with battery.

NEMA 250 Type 4 cabinet.

UL or other accredited testing laboratory listing.

RS232 Modbus communications with //engineering control system// //boiler plant computer workstation// to indicate system in service and alarm conditions.

Sensors:

Designed for required locations including: Insertion between walls of double-wall tanks, in sumps in double-wall piping systems and in tank manhole enclosures. Sensing points shall be at lowest point of each tank or sump. Intrinsically safe design.

Sensing units shall detect presence of water and a minimum 3.2 mm (1/8 inch) thick layer of hydrocarbon on surface of water and minimum 50 mm (2 inch) thickness of hydrocarbon in area that has no water present.

Sensors shall be arranged to allow replacement of individual sensors without disturbing other portions of leak detection system or fuel storage and piping system. Underground sensors shall be accessed through caps as grade.

Materials of construction shall be non-corroding.

Transmit status signal to control unit.

Components:

Provide manholes at grade for each sensor cap similar in construction to fill boxes. Manholes shall be cast iron, quick-opening cover, watertight, minimum size necessary to accommodate sensor caps. Provide identification plates, similar to those specified for fill points, labeled “MONITORING/OBSERVATION WELL-DO NOT FILL”. Provide special tools if necessary for opening covers.

Sensor housings from tank and piping to grade shall be Schedule 40 PVC, or stainless steel.

Underground wiring between probes and control unit: Place in water-tight corrosion-resistant conduit system conforming to Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION.

TANK FLUID LEVEL MONITOR AND ALARM SYSTEMS

Digital systems for central monitoring of fuel and water levels in all fuel oil storage tanks in the project. High and low level visual and audible alarms. Volumetric tank-tightness testing. Complete with all transducing, transmitting, and receiving devices. On board printer to provide complete report of all system functions upon command. //System may be combined with leak detection system specified in paragraph, LEAK DETECTION SYSTEMS.// Fluid Level Monitor:

Digital continuous readout, showing tank oil and water levels in //liters// //gallons//, smallest reading //one liter// //one gallon//. Provide identification of product measured, measuring units, and the tank number.

Tank and fuel characteristics contained in preprogrammed non-volatile field-replaceable databases. Protected power supply.

High and Low Fluid Level Alarm System:

Automatic continuous on-line monitoring of all tanks.

Visual and audible indicators combined with fluid level monitor. Identify the tank that is in alarm condition.

Manual alarm test and silencing controls.

Low level alarm actuation adjustable 0-25 percent of tank capacity. High level alarm actuation adjustable 75-100 percent of tank capacity.

Locate all indicators, selector switches, alarms on face of wall-mounted NEMA 250, Type 4 panel.

Remote Alarm Annunciator:

Visual and audible high-level alarms adjacent to tank fill box locations. Locate in NEMA 250 Type 4X weatherproof exterior wall or pole-mounted panels.

Alarm shall include flashing red light with 180-degree visibility for each tank and 95 dB horn or 100 mm (4 inch) diameter bell. Provide alarm silence control.

Provide identification sign: "WHEN ALARM SOUNDS - FUEL TANK FILLED TO CAPACITY - DO NOT OVERFILL".

Modbus communication to //engineering control system// //boiler plant computer workstation// to indicate tank fluid level and alarm conditions. Telephone modem communication capability.

System Performance: Accuracy plus or minus 2.5 mm (0.10 inch) of fluid height in inventory mode and 0.25 mm (0.01 inch) in leak detection mode. Automatic compensation for fluid temperature changes. Volumetric tank tightness sensitivity of 0.4 lph (0.1 gph).

Sensors:

Provide sensor types such as magnetostrictive, capacitance, float, hydrostatic and other types as necessary for the applications.

Apply in accordance with manufacturer’s instructions with provisions for easy future replacement without need for…