660-15-111 Equipment Cut Sheets.pdf
PDF 14 MB Posted
- Attached to
- Z2DA--Legionella - Mixing Valves, Schematics, Controls Federal contract opportunity
- Solicitation number
- 36C25921R0015
About this file
This document provides details for a federal contract opportunity to complete the Legionella - Mixing Valves, Schematics, Controls project at the Salt Lake City VA Medical Center. The project scope includes construction services with a magnitude between $1,000,000 to $5,000,000. The solicitation number is 36C25921R0015 and responses are due on or about December 9, 2020. This opportunity is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. Offerors must be verified and listed in the Vendor Information Pages database. The point of contact for questions is Robyn Young, who can be reached at 307-433-3728 or robyn.young2@va.gov. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25921R0015 0007.pdf | ||
| 36C25921R0015 0006.pdf | ||
| 36C25921R0015 0005.pdf | ||
| S02 2016-10-20 Instructions to Offerors - PPT.pdf | ||
| UPDATED 660-15-111 Construction SOW.pdf | ||
| Specs-Final Combined set Legionella.pdf | ||
| NESHAP VA Limited ACM Bldg 1 SLC UT 01-04-20.pdf | ||
| Legionella questions.pdf | ||
| Past Performance Questionnaire.docx | DOCX document | |
| NESHAP VA Limited ACM Building 3 SLC UT 01-04-21.pdf | ||
| 36C25921R0015 0004.pdf | ||
| 36C25921R0015 0003.pdf | ||
| 2016-09-07 S04 -Site Visit Meeting Doc.pdf | ||
| Site Walk 1- attendance.pdf | ||
| Site Walk 2- attendance.pdf | ||
| 36C25921R0015 0002.pdf | ||
| 36C25921R0015 0001.pdf | ||
| C27 660-15-111 100 percent Drawings.pdf | ||
| 36C25921R0015_1.pdf | ||
| C27 Specs-Final Combined set.pdf | ||
| 36C25921R0015.docx | DOCX document |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Terminals Sonstige Daten
M9000-342 M9000-342 M9000-342 M9000-342
M9000-561 M9000-561 M9000-561
TE-6300 Series Temperature Sensors Product Bulletin 1
Refer to the QuickLIT website for the most up-to-date version of this document.
The TE-6300 Temperature Sensor line provides economical solutions for a wide variety of temperature sensing needs, including wall-mount, outdoor-air, duct, strap-mount, well-insertion, duct-averaging, and VAV Modular Assembly (VMA) flange-mount duct-probe applications. The TE-6300 line offers both a metal and a plastic enclosure for the most popular models.
Sensors are available in the following types:
• 1k ohm thin-film nickel
• 1k ohm nickel averaging
• 1k ohm thin-film platinum
• 100 ohm platinum equivalent averaging
• 1k ohm platinum equivalent averaging
• 2.2k (2,252) ohm thermistor
• 10k ohm thermistor, Johnson Controls® Type II
Each sensor is packaged with the necessary mounting accessories to maximize ordering and installation ease and reduce both commissioning time and cost.
Supports all your temperature sensing needs from a single supplier:
wall-mount, outdoor-air, duct, duct-averaging, strap-mount, well-insertion, and flange-mount duct-probe.
Simplifies ordering; provides a complete assembly in one box.
Increase sensor connection strength, which eliminates the need for a special adaptor.
Protect the sensor while increasing corrosion resistance.
Meets plenum requirements.
Allow you to lock the sensor holder into the conduit box.
Offers a durable, aesthetically pleasing design.
Provides a tamper-proof installation ideally suited for schools, sporting complexes, retailers, prisons, and more.
Supersedes April 18, 2013
TE-6300 Series Temperature Sensors Product Bulletin2
All TE-6300 Series sensors are two-wire, passive, resistance-output devices.
TE-63xxA Models The TE-63xxA (adjustable length) models:
• provide a thermoplastic mounting flange and gland nut to adjust the length of the probe
• include two hex-head self-drilling screws for mounting
• come equipped with a 10 ft (3 m) plenum-rated cable with a 2-position plug terminal block for 1/4 in. (6.35 mm) male tab terminals on
0.197 in. (5 mm) centers, for direct connection to Johnson Controls VMA controller products
TE-63xxF Models The TE-63xxF (flush mount) models:
• provide a low profile when installed in an electrical box
• feature thermally isolated sensor from the wall with a foam pad
• offer a rugged stainless steel cover
• provide 22 AWG lead wires with low voltage installation
TE-63xxM Models The TE-63xxM (metal enclosure) models:
• come with a corrosion-protected steel enclosure with a 0.88 in. (22 mm) hole for a 1/2 in. (12.7 mm) conduit fitting
• include two hex-head self-drilling screws for mounting the duct and duct averaging models
• offer (for well models only) either a direct-mount or 1/2-14 NPT threaded well sensor holder for mounting in TE-6300W Series thermowells (order the thermowell separately)
• provide optional well sensor holders (order separately) to mount duct models in thermowells
• meet UL 1995 plenum use requirements
• offer an optional accessory kit (order separately) to replace plastic hole plug and wiring bushing to meet International Mechanical Code (IMC) requirements
TE-63xxP Models The TE-63xxP (plastic enclosure) models:
• provide a thermoplastic conduit box with 1/2-14 NPT female thread for connecting to conduit
• provide aluminum mounting plate and 1/2-14 NPT threaded hub mounting options for the duct and duct-averaging models
• use the 1/2-14 NPT female thread to mount the Outdoor Air models directly to ridged conduit
• provide sensor holders included to mount duct models in thermowells (order thermowell separately)
• offer an optional accessory metal cover kit (order separately) to replace the plastic cover to meet UL 1995 plenum use requirements
• include a replaceable sensing probe on duct-probe, outdoor-air, and well-insertion models
TE-63x4P Wall Mount Models The TE-63x4P (plastic enclosure) models:
• come with a white thermoplastic ventilated cover with a brushed aluminum face plate and a steel mounting plate for surface mounting
• include faceplates for both horizontal and vertical mounting
• offer an accessory mounting kit for mounting to a standard electrical box
• offer optional covers
TE-63xS Models The TE-63xS (Strap-Mount) models:
• provide a 1/4 in. (6.35 mm) diameter stainless steel probe without an enclosure
• include three cable ties for mounting to pipe up to 2-5/8 in. (67 mm) diameter
• come equipped with a 10 ft (3 m) plenum-rated cable
• meet UL 1995 plenum use requirements
The TE-6300 Series Temperature Sensors are intended to provide an input to equipment under normal operating conditions.
Where failure or malfunction of the sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the sensor.
TE-6300 Series Temperature Sensors Product Bulletin 3
• offer an accessory mounting kit for mounting to a pipe up to 11 in. (280 mm) diameter
TE-63xxV Models The TE-63xxV (VAV flange mount) models:
• provide a stainless steel mounting flange with two hex-head self-drilling mounting screws
• come equipped with a 10 ft (3 m) plenum-rated cable with a 2-position plug terminal block for 1/4 in. (6.35 mm) male tab terminals on
0.197 in. (5 mm) centers, for direct connection to Johnson Controls VMA controller products
• meet UL 1995 plenum use requirements
Additional Product Information See Figure 2 for nickel and platinum sensor Resistance/Temperature (R/T) response characteristics. See Table 2 for all sensor Temperature/Resistance values.
Figure 2 shows 1k ohm platinum sensor characteristic. For 100 ohm platinum sensor characteristic, divide the resistance value by 10.
See Figure 3 for 2.2k and 10k ohm thermistor sensor R/T response characteristics.
-50
(-46) -20
(-29)
(-12) (4)
(21)
(38)
(54)
(71)
(88)
(104)
1M
100k
10k
1k
(104) -50
(-46) -20
(-29)
(-12) (4)
(88)
(71)
(54)
(38)
(21)
TE-6300 Series Temperature Sensors Product Bulletin4
Averaging Sensing Series-parallel wiring arrangements of four (2 x 2), nine (3 x 3), sixteen (4 x 4), or more sensors provide an average temperature reading in an area or large duct when one sensor cannot provide a representative reading. (See Figure 4.)
A series-parallel arrangement requires the same number of parallel-connected sensors as there are series-connected sensors. For example:
• with four sensors, connect two parallel legs with two sensors in series in each leg
• with nine sensors, connect three parallel legs with three sensors in series in each leg
All sensors in a series-parallel network must be of the same sensor type and value. For example, use all 100 ohm platinum or all 1k ohm nickel sensors.
-50 -46 674 821 109,905 489,981
-40 -40 699 843 75,487 366,185
-30 -34 725 865 52,584 233,990
-20 -29 751 887 37,123 165,085
-10 -23 777 908 26,544 117,978
0 -18 803 930 19,210 85,349
10 -12 830 952 14,063 62,464
20 -7 858 974 10,408 46,221
30 -1 885 996 7,783 34,562
40 4 914 1,017 5,879 26,103
50 10 942 1,039 4,482 19,903
60 16 971 1,061 3,449 15,313
70 21 1,000 1,082 2,676 11,883
80 27 1,030 1,104 2,094 9,298
90 32 1,060 1,125 1,651 7,333
100 38 1,090 1,147 1,312 5,827
110 43 1,121 1,168 1,050 4,663
120 49 1,152 1,190 846 3,757
130 54 1,184 1,211 686 3,048
140 60 1,216 1,232 560 2,488
150 66 1,248 1,254 460 2,043
160 71 1,281 1,275 380 1,687
170 77 1,314 1,296 315 1,401
180 82 1,348 1,317 263 1,170
190 88 1,382 1,339 221 982
200 93 1,417 1,360 186 828
210 99 1,452 1,381 158 701
220 104 1,487 1,402 134 597
1. For 100 ohm platinum sensors, divide resistance values by 10.
TE-6300 Series Temperature Sensors Product Bulletin 5
• Sensor model TE-63xAP-1
• Threadless Sensor Holder/Well Adaptor
• 6 in. (150 mm) probe
• includes well adaptor
• Sensor model TE-63x2P-1
• 1/2-14 NPT Threaded Sensor Holder/Well Adaptor
• 8 in. (200 mm) probe
• includes well adaptor
• Sensor model TE-63xAM-1
• Threadless Well Adaptor
• 6 in. (150 mm) probe
• includes well adaptor
• Sensor model TE-63x2M-1
• 1/2-14 NPT Threaded Well Adaptor
• 8 in. (200 mm) probe
• includes well adaptor
TE-6300 Series Temperature Sensors Product Bulletin6
For specific TE-6300 Series Temperature Sensor applications, see Table 3.
4 (102) 8 (203) 18 (457)
1k ohm Thin-Film Nickel 1k ohm Thin-Film Platinum 2.2k ohm Thermistor 10k ohm Thermistor Type II
• Ideal in freezer lockers or for mounting outside of the sensed area.
• Available with plastic enclosure, metal enclosure, flange mount, or with mounting bracket for adjustable length.
• Use TE-63xxM or TE-63xxV models for plenum applications.
• Use TE-6300-613 accessory kit with TE-63xxM models to meet
IMC requirements.
• Use TE-6001-13 metal cover kit with TE-63xxP models to meet UL 1995 plenum requirements.
• Order an optional TE-63xxP model accessory: 12 in. (300 mm) probe.
8 ft (2.4 m) 10 ft (3 m) 17 ft (5.2 m) 20 ft (6.1 m)
1k ohm Nickel Wire 100 ohm Platinum Equivalent Wire 1k ohm Platinum Equivalent Wire
• Use to sense duct temperature where stratification can occur, such as mixed air ducts.
• Duct averaging models come in three styles: plastic enclosure, metal enclosure, or flange mount.
• Use about 1 ft (0.3 m) of sensor per sq ft (0.09 m2) of duct cross section.
• Use a series-parallel sensor network to cover larger ducts.
• Use a TE-6001-8 element holder (recommended) when installing an averaging sensor in a duct.
• Use TE-63xxM or TE-63xxV models for plenum applications.
• Use TE-6300-613 kit with TE-63xxM models to meet IMC requirements.
• Use the TE-6001-13 metal cover kit with TE-63xxP models to meet
UL 1995 plenum requirements.
3 (76) 1k ohm Thin-Film Nickel 1k ohm Thin-Film Platinum 2.2k ohm Thermistor 10k ohm Thermistor, Type II
• Use to sense outside ambient temperature to determine efficient heating and cooling strategies.
• Mount the sensor out of direct sunlight and away from exhaust vents or equipment that can cause inaccurate temperature sensing.
3 (76) 1k ohm Thin-Film Nickel 1k ohm Thin-Film Platinum 10k ohm Thermistor, Type II
• Clamp the probe directly to a pipe or the device to be sensed.
• Mount the probe away from fans or radiant heat that can affect measurement of the sensed device.
• Use for plenum applications.
• Order an accessory mounting kit or use readily available hardware for pipe up to 11 in. (280 mm) diameter.
N/A 1k ohm Thin-Film Nickel 1k ohm Thin-Film Platinum 2.2k ohm Thermistor
• Use to sense room or space temperature.
• Order an accessory cover with a thermometer or to match the style of existing installations.
• Mount the sensor on an inside wall, out of direct sunlight and away from radiant heat.
N/A Flush Mount 1k ohm Nickel Sensor Flush Mount 1k ohm Platinum Sensor Flush Mount 10k ohm NTC Sensor
• Flush mount 10k ohm NTC sensor: do not install the flush mount sensor in temperatures beyond 0–40°C
• Use copper conductors only. Refer to installation diagrams for recommended wiring lengths.
TE-6300 Series Temperature Sensors Product Bulletin 7
6 (152) 8 (203) 1k ohm Thin-Film
Nickel 1k ohm Thin-Film Platinum 2.2k ohm Thermistor 10k ohm Thermistor Type II
• Metal enclosure.
• Mount the thermal well at an angle so condensation runs out of the well.
If not possible, seal the well adaptor and wiring end of the sensor probe with RTV silicone sealant.
• Use TE-63xxM models to meet UL 1995 plenum use applications.
• No separate well adaptor to order when using recommended thermowell and sensor model combinations.
• Threaded sensor holder has 1/2-14 NPT threads; threadless holder accommodates setscrew-type wells.
• Order TE-63x2M-1, which includes 1/2-14 NPT adaptor, for
TE-6300W-110 or retrofit applications of WZ-1000-2 and WZ-1000-4 thermowells.
• Order TE-63xAM-2 for use with direct-mount thermowells, TE-6300W-101 and TE-6300W-102.
• Order TE-63xAM-1, which includes threadless adaptor, for retrofit applications of TE-6300W-103 and WZ-1000-5 thermowells.
• Order compatible thermowells using Table 5 and Table 6.
1k ohm Thin-Film Nickel 1k ohm Thin-Film Platinum 2.2k ohm Thermistor
• Plastic enclosure.
• Mount the thermal well at an angle so condensation runs out of the well.
If not possible, seal the sensor holder and the wiring end of the sensor probe with RTV silicone sealant.
• Use TE-6001-13 metal cover kit with TE-63xxP models to meet UL 1995 plenum requirements.
• Use the accessory 12 in. (305 mm) probe with the TE-63xxP sensor in longer wells.
• No separate well adaptor to order when using recommended thermowell and sensor model combinations.
• Threaded sensor holder has 1/2-14 NPT threads; threadless holder accommodates setscrew-type wells.
• Order TE-63x2P-1, which includes 1/2-14 NPT adaptor, for TE-6300W-110 or retrofit applications of WZ-1000-2 and WZ-1000-4 thermowells.
• Order TE-63xAP-1, which includes threadless adaptor, for TE-6300W-103 or retrofit applications of WZ-1000-5 thermowells.
• Order compatible thermowells using Table 5 and Table 7.
TE-6300 Series Temperature Sensors Product Bulletin8
To order a TE-6300 Series temperature sensor, contact the nearest Johnson Controls representative. Specify the desired sensor product code number from Table 4 and accessories from Table 5, depending on the model.
Use the TE-63xxM or TE-63xxV model to meet plenum requirements where UL1995 rating is accepted, or replace the existing plastic cover on the TE-63xxP models with the TE-6001-13 Metal Cover Kit.
Use the TE-63xxM model and a TE-6300-613 Accessory Kit to replace the plastic bushing to meet International Mechanical Code (IMC) requirements.
Not all possible combinations are available. See Table 4 for available models.
Suffix
Probe Style Enclosure Type
Sensor Type
TE-6300 Series Temperature Sensors Product Bulletin 9
Adjustable 8 (203) TE-6311A-1
Averaging1 8 ft (2.4 m) TE-6315M-1
TE-6315P-1
TE-6315V-2
17 ft (5.2 m)
TE-6316M-1
TE-6316P-1
TE-6316V-2
Duct 4 (102) TE-631GM-1
8 (203) TE-6311M-1
TE-6311P-1
18 (457) TE-631JM-1
Flange 4 (102) TE-631GV-2
8 (203) TE-6311V-2
Flush N/A TE-6310F-0
TE-6310F-1
Outdoor Air 3 (76) TE-6313P-1
Strap- Mount
3 (76) TE-631S-1
Wall2 N/A TE-6314P-1
Well 6 (152) TE-631AM-13
TE-631AM-2
TE-631AP-1
8 (203) TE-6312M-1
TE-6312P-1
Adjustable 8 (203) TE-6351A-1
Duct 4 (102) TE-635GM-1
8 (203) TE-6351M-1
TE-6351P-1
18 (457) TE-635JM-1
Flange 4 (102) TE-635GV-2
8 (203) TE-6351V-2
Flush N/A TE-6350F-0
TE-6350F-1
Outdoor Air 3 (76) TE-6353P-1
Strap- Mount
3 (76) TE-635S-1
Wall2 N/A TE-6324P-1
Well 6 (152) TE-635AM-2
TE-635AP-1
8 (203) TE-6352M-1
TE-6352P-1
1k ohm Averaging1
10 ft (3 m) TE-6327P-1
20 ft (6.1 m)
TE-6328P-1
100 ohm Averaging1
10 ft (3 m) TE-6337P-1
20 ft (6.1 m)
TE-6338P-1
Adjustable 8 (203) TE-6341A-1
Duct 8 (203) TE-6341P-1
Flange 4 (102) TE-634GV-2
8 (203) TE-6341V-2
Outdoor Air 3 (76) TE-6343P-1
Wall2 N/A TE-6344P-1
Well 6 (152) TE-634AM-2
8 (203) TE-6342M-1
Adjustable 8 (203) TE-6361A-1
Duct 4 (102) TE-636GM-1
8 (203) TE-6361M-1
TE-6361P-1
18 (457) TE-636JM-1
Flange 4 (102) TE-636GV-2
8 (203) TE-6361V-2
Flush N/A TE-6360F-0
TE-6360F-1
Outdoor Air 3 (76) TE-6363P-1
Strap- Mount
3 (76) TE-636S-1
Well 6 (152) TE-636AM-2
8 (203) TE-6362M-1
1. Two TE-6001-8 Element Holders come with the platinum equivalent averaging sensors. Order separately to use with a nickel averaging sensor.
2. Order the TE-1800-9600 Mounting Hardware separately to mount the wall unit to a wallbox.
3. TE-631AM-1 includes TE-6300-612 brass threadless well adaptor for retrofit to TE-6300W-103 or WZ-1000-5 thermowells.
TE-6300 Series Temperature Sensors Product Bulletin10
Thermal Conductive Grease for Element Wells (8 oz. [.23 kg])
Wall Mount Cover (see Table 9)
Allen Head Tool for Wall Mount Cover Screws (order in multiples of 30)
Mounting Hardware for Mounting the Wall Mount Unit to a Wall Box
Element Holder for Mounting an Averaging Sensor (order in multiples of 10)
Metal Cover and Gasket Kit (5 per package)
12 in. (305 mm) (1k ohm) Nickel Probe (cut to an appropriate length)2
12 in. (305 mm) (1k ohm) Platinum Class A Probe (cut to an appropriate length)2
1/2-14 NPT Plastic Sensor Holder without retainer (order in multiples of 10)
12 in. (305 mm) (2.2k ohm) Thermistor Probe (cut to an appropriate length)2
IMC Kit, Metal Knockout Plug, Metal Clamp Connector (order in multiples of 10)
Cable Tie Mounting Kit, 0.50 to 2.625 in. (12.7 to 66.7 mm) Bundle Diameter (10 per package)
Cable Tie Mounting Kit, 11 in. (280 mm) Maximum Bundle Diameter
4 to 20 mA Output Transmitter for Use With the 100 ohm Platinum Sensor
Thermowell, brass with copper bulb, 2.38 in. (60.5 mm) immersion depth, with thermal grease, direct mount, no adaptor required, for use with 6 in. (150 mm) probe model TE-63xAM-2
Thermowell, stainless steel, 2.38 in. (60.5 mm) immersion depth, without thermal grease, direct mount, no adaptor required, for use with 6 in. (150 mm) probe model TE-63xAM-2
Thermowell, brass with copper bulb, 2.38 in. (60.5 mm) immersion depth, with thermal grease, threadless adaptor required, for use with 6 in. (150 mm) probe models TE-63xAM-1 (adaptor included) and TE-63xAP-1 (adaptor included)
Thermowell, stainless steel, 4.50 in. (114.3 mm) immersion depth, without thermal grease, 1/2-14 NPT adaptor required, for use with 8 in. (200 mm) probe models TE-63x2M-1 (adaptor included) and TE-63x2P-1 (adaptor included)
1. For accessory usage, see Table 6, Table 7, and Table 8.
2. Cut 12 in. (305 mm) probes to a minimum of 3 in. (76 mm).
TE-6300 Series Temperature Sensors Product Bulletin 11
X X
X X X
X X X X X
X X X X X X X X X X X X X X X X X X X
X X X X
X X X X
X
X X X
Direct-mount thermal wells TE-6300W-101 and TE-6300W-102 can be used only with the TE-6300M sensors.
TE-6300 Series Temperature Sensors Product Bulletin12
X X X
X X X
X X X X X X
X X X X X X X X X X X X X X X X X X
X
X
X
X
X
X X X X X X X X X X X X
X
X
X X
X
X
X X
X X X X
X X
X X
Direct-mount thermal wells TE-6300W-101 and TE-6300W-102 can be used only with the TE-6300M sensors.
TE-6300 Series Temperature Sensors Product Bulletin 13
Thermal Conductive Grease for element wells (8 oz.)
Cable Tie Mounting Kit, 0.50 to 2.625 in. (12.7 to 66.7 mm) Bundle Diameter (10 per package)
Cable Tie Mounting Kit, 11 in. (280 mm) Maximum Bundle Diameter
Brushed Aluminum/Beige
X
X X
X
X Brown and Gold/Beige
X X
X
X Brushed Aluminum/White
X X
X
1. Without Johnson Controls logo
TE-6300 Series Temperature Sensors Product Bulletin14
If the TE-63xxA, TE-63xxM, TE-63xS, or TE-63xxV Series temperature sensor fails to operate within its specifications, replace the unit. For a replacement temperature sensor, see Table 4 and contact the nearest Johnson Controls representative.
For a replacement sensor probe for TE-63xxP duct, well, and outdoor-air models, see Table 10.
8 in. (203 mm), 1k ohm Nickel Probe
8 in. (203 mm), 1k ohm Platinum Class A Probe
3 in. (76 mm), 1k ohm Nickel Probe
3 in. (76 mm), 1k ohm Platinum Class A Probe
1/2-14 NPT Threaded Plastic Sensor Holder with Retainer (10 per package)
8 in. (203 mm), 2.2k ohm Thermistor Probe
3 in. (76 mm), 2.2k ohm Thermistor Probe
Threadless Plastic Sensor Holder with Retainer (10 per package)
1/2-14 NPT Threaded Brass Sensor Holder (Order in multiples of 10)
Threadless Brass Sensor Holder (Order in multiples of 10)
TE-6300 Series Temperature Sensors Product Bulletin 15
TE-6300 Series Temperature Sensors (Part 1 of 3)
1k ohms at 70 F (21 C)
1k ohms at 32°F (0°C)
100 ohms at 32°F (0°C)
1k ohms at 32 F (0 C)
2,252 ohms at 77 F (25 C)
10.0k ohms at 77 F (25 C)
0.34F° at 70 F ( 0.19C at 21 C)
3.4F at 70 F ( 1.9C at 21 C)
0.35F° at 70°F ( 0.19C° at 21°C), DIN Class A
0.73F° at 70°F ( 0.41C° at 21°C), DIN Class B
1.0F at 70 F ( 0.58C at 21 C)
0.36F ( 0.2C ) in the range: 32 to 158 F (0 to 70 C)
0.9F ( 0.5C ) in the range: 32 to 158 F (0 to 70 C)
Approximately 3 ohms/F (5.4 ohms/C )
Approximately 2 ohms/F° (3.9 ohms/C°) 3,850 ppm/K
Approximately 0.2 ohms/F (0.39 ohms/C )
Approximately 2 ohms/F (3.9 ohms/C )
Nonlinear, Negative Temperature Coefficient (NTC)
Nonlinear NTC, Johnson Controls Type II
22 AWG (0.6 mm diameter) x 6 in. (152 mm) long
22 AWG (0.6 mm diameter) x 12 ft (3 m) braided copper wires, low voltage insulation, half-stripped ends
18 AWG (1.0 mm diameter) x 6 in. (152 mm) long
22 AWG (0.6 mm diameter) x 10 ft (3 m) long plenum-rated cable
22 AWG x 10 ft (3 m) long plenum-rated cable, with 2-position plug terminal block for 1/4 in. (6.35 mm) male tab terminals on 0.197 in. (5 mm) centers
TE-6300 Series Temperature Sensors Product Bulletin16
Nickel Averaging: 0.094 in. (2.4 mm) Outside Diameter (O.D.)
copper tubing
Nickel Averaging Adaptor: 0.25 in. (6.35 mm) O.D. Brass Platinum Averaging Probe: 0.19 in. (4.8 mm) Aluminum tubing All Others (except Averaging):0.25 in. (6.35 mm) O.D. Stainless Steel
Mounting Adaptor Plate and Gland: Thermoplastic
Flush Mount: Stainless Steel
Enclosure: Corrosion-Protected Steel Well Sensor Holder: 0.875 in. (22.2 mm) Hex Brass
Conduit box and Shield: Rigid Thermoplastic Mounting Plate: Aluminum Sensor Holder: Rigid Thermoplastic Wall Mount Base Plate: Corrosion-Protected Steel Wall Mount Cover: Rigid Thermoplastic (White) Wall Mount Face Plate: Brushed Aluminum
Mounting Flange: Stainless Steel
-50 to 140°F (-46 to 60°C)
Temperature Limits: 32 to 104°F (0 to 40°C)
-50 to 220°F (-46 to 104°C)
Enclosure: -50 to 122°F (-46 to 50°C) Sensor Probe: -50 to 220°F (-46 to 104°C)
Sensor Probe: -50 to 220°F (-46 to 104°C) Wire Harness: -50 to 122°F (-46 to 50°C)
0.2 lb (0.09 kg)
0.25 lb (113.4 kg)
Duct Averaging: 0.9 lb (0.41 kg) Duct Mount: 0.4 lb (0.18 kg) Well Insertion: 0.5 lb (0.23 kg)
Duct Averaging: 0.5 lb (0.23 kg) Duct Mount: 0.4 lb (0.18 kg) Outdoor Air: 0.5 lb (0.23 kg) Wall Mount: 0.2 lb (0.09 kg) Well Insertion: 0.35 lb (0.16 kg)
Strap-Mount: 0.2 lb (0.09 kg)
Duct Averaging: 0.7 lb (0.32 kg) Duct Mount: 0.2 lb (0.09 kg)
TE-6300 Series Temperature Sensors (Part 2 of 3)
Published in U.S.A. www.johnsoncontrols.com
TE-6300 Series Temperature Sensors Product Bulletin 17
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2013 Johnson Controls, Inc.
507 E. Michigan Street, Milwaukee, WI 53202
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
2.17 in. (55 mm) diameter plus 4 or 8 in.
(102 or 203 m) element
Flush Mount: 4-1/2 x 2-3/4 in. (114 x 70 mm)
Duct Averaging: 1.87 x 1.87 x 1.80 in.
(47.5 x 47.5 x 45.8 mm) plus 8 or 17 ft (2.4 or 5.2 m) element
Duct Mount: 1.87 x 1.87 x 1.80 in.
(47.5 x 47.5 x 45.8 mm) plus 4, 8, or 18 in.
(102, 203, or 457 mm) element
Well Insertion: 1.87 x 1.87 x 1.80 in.
(47.5 x 47.5 x 45.8 mm) plus 6 or 8 in.
(152 or 203 mm) element
Duct Averaging: 5.97 x 1.38 x 2.75 in. (152 x 35 x 70 mm) plus 8, 10, 17, or 20 ft (2.4, 3.0, 5.2, or 6.1 m) element
Duct Mount: 5.97 x 1.38 x 2.75 in. (152 x 35 x 70 mm) plus 6 or 8 in. (152 or 203 mm) probe
Outdoor Air: 5.97 x 3.47 x 4.46 in. (152 x 88 x 113 mm) Wall Mount: 2.09 x 3.12 x 1.80 in. (53 x 79 x 46 mm) Well Insertion: 5.97 x 1.38 x 2.75 in. (152 x 35 x 70 mm) plus 6 or 8 in. (152 or 203 mm) probe
Strap-Mount: 0.25 in. (6.4 mm) diameter x 3.00 in. (76 mm) long
Duct Averaging: 2.25 x 1.50 in. (57 x 38 mm) plus 8 or 17 ft (2.4 or 5.2 m) element
Duct Mount: 2.25 x 1.50 in. (57 x 38 mm) plus 4 or 8 in.
(102 or 203 m) element
TE-6300 Series Temperature Sensors (Part 3 of 3) ecocirc® XL High Efficiency Large Wet Rotor Circulator with Electronically Commutated Motor (ECM)
The ecocirc® XL circulator is designed with a highly efficient electronically commutated permanent magnet motor (ECM Technology).
designed for closed loop hydronic heating and cooling systems body for plumbing systems or open loop heating and cooling systems.
Pump Body: Cast Iron or Stainless Steel Impeller: Poly-phenylene Sulfide or Stainless Steel Shaft: AISI 420 Stainless Steel Rotor: Permanent Magnet Bearing: Carbon Sleeve Gasket/O-Ring: EPDM All Other Wetted Parts: AISI 304 Stainless Steel Motor Type: Electronically Commutated Permanent Magnet Motor Insulation Class: F
Maximum Working Pressure: 175 psi (12 Bar) Minimum Working Temperature: 14°F (-10°C) Maximum Working Temperature: 230°F (110°C) Ambient Temperature Range: 32°F - 104°F (0°C - 40°C)
MODEL NO.
FLOW HEAD
HP RPM
VOLTAGE CYCLE PHASE
SPECIALS
ecocirc XL 20-35 104300 ecocirc XL N 20-35 104450LF 1/12 115 1 50/60 6 - 85 0.1 - 1.3 ecocirc XL 36-45 104301 ecocirc XL N 36-45 104451LF 1/6 115 1 50/60 20 - 200 0.1 - 3.0 ecocirc XL 36-45 104302 ecocirc XL N 36-45 104452LF 1/6 208-230 1 50/60 20 - 200 0.1 - 1.5 ecocirc XL 15-75 104303 ecocirc XL N 15-75 104453LF 1/6 115 1 50/60 30 - 150 0.1 - 2.3 ecocirc XL 15-75 104304 ecocirc XL N 15-75 104454LF 1/6 208-230 1 50/60 30 - 150 0.1 - 1.1 ecocirc XL 55-45 104306 ecocirc XL N 55-45 104456LF 1/2 208-230 1 50/60 30 - 500 0.2 - 2.0 ecocirc XL 20-140 104308 ecocirc XL N 20-140 104458LF 1/2 208-230 1 50/60 35 - 470 0.2 - 2.0 ecocirc XL 65-130 104309 ecocirc XL N 65-130 104459LF 1 208-230 1 50/60 45 - 825 0.5 - 3.5 ecocirc XL 40-200 104312 ecocirc XL N 40-200 104462LF 1 208-230 1 50/60 45 - 825 0.5 - 3.5 ecocirc XL 70-145 104315 ecocirc XL N 70-145 104465LF 2 208-230 1 50/60 55 - 1400 0.6 - 6.0 ecocirc XL 40-275 104318 ecocirc XL N 40-275 104468LF 2 208-230 1 50/60 50 - 1400 0.5 - 6.0 ecocirc XL 65-130 104310 ecocirc XL N 65-130 104460LF 1 208-230/400-460 3 50/60 50 - 800 0.5 - 2.8/2.0 ecocirc XL 40-200 104313 ecocirc XL N 40-200 104463LF 1 208-230/400-460 3 50/60 50 - 800 0.5 - 2.8/2.0 ecocirc XL 95-160 104321 ecocirc XL N 95-160 104471LF 2 208-230/400-460 3 50/60 50 - 1250 0.5 - 4.4/2.0 ecocirc XL 27-320 104323 ecocirc XL N 27-320 104473LF 2 208-230/400-460 3 50/60 50 - 1500 0.5 - 4.4/3.0 ecocirc XL 110-180 104326 ecocirc XL N 110-180 104476LF 3 400-460 3 50/60 50 - 2000 0.5 - 3.7 ecocirc XL 45-375 104328 ecocirc XL N 45-375 104478LF 3 400-460 3 50/60 50 - 2150 0.5 - 4.0
Where potable water is pumped, use a stainless steel booster. ecocirc XL pumps are recommended for indoor use only.
* Nominal HP ecocirc XL 20-35 1/12 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10) ecocirc XL 36-45 1/6 9.94 (252) 6.38 (162) 8.20 (208) 4.19 (106) 7.20 (183) 4.72 (120) 19.8 (9) 22 (10) ecocirc XL 15-75 1/6 11.04 (280) 8.5 (216) 8.39 (213) 5.19 (132) 7.57 (192) 4.72 (120) 26.4 (12) 28.6 (13) ecocirc XL 55-45 1/2 11.89 (302) 6.38 (162) 10.18 (258) 4.19 (106) 8.12 (206) 5.02 (127) 26.4 (12) 28.6 (13) ecocirc XL 20-140 1/2 13.39 (340) 11.5 (292) 10.41 (264) 5.19 (132) 8.20 (208) 5.02 (127) 35.2 (16) 39.6 (18) ecocirc XL 65-130 1 14.84 (377) 11.5 (292) 11.80 (299) 4.62 (117) 9.53 (242) 5.77 (146) 39.6 (18) 44 (20) ecocirc XL 40-200 1 15.17 (385) 11.5 (292) 11.80 (299) 5.19 (132) 9.53 (242) 5.77 (146) 41.8 (19) 46.2 (21) ecocirc XL 70-145 2 14.84 (377) 11.5 (292) 11.80 (299) 4.62 (117) 9.53 (242) 5.77 (146) 38.4 (17.4) 44 (20) ecocirc XL 40-275 2 16.04 (407) 12.0 (305) 12.57 (319) 6.00 (152) 10.07 (256) 5.77 (146) 49.6 (22.5) 55 (25) ecocirc XL 65-130 1 14.96 (380) 11.5 (292) 11.85 (301) 2.87 (73) 10.43 (265) 5.31 (135) 39.6 (18) 44 (20) ecocirc XL 40-200 1 15.23 (387) 11.5 (292) 11.85 (301) 5.19 (132) 10.43 (265) 5.31 (135) 35.2 (16) 39.6 (18) ecocirc XL 95-160 2 14.44 (367) 11.5 (292) 11.37 (289) 2.87 (73) 10.43 (265) 5.31 (135) 39.6 (18) 44 (20) ecocirc XL 27-320 2 15.27 (388) 14.17 (360) 11.81 (300) 6.00 (152) 10.43 (265) 5.31 (135) 49.6 (22.5) 55 (25) ecocirc XL 110-180 3 14.44 (367) 11.5 (292) 11.37 (289) 2.87 (73) 10.43 (265) 5.31 (135) 38.4 (17.4) 44 (20) ecocirc XL 45-375 3 16.14 (410) 14.17 (360) 12.67 (321) 6.00 (152) 10.43 (265) 5.31 (135) 49.6 (22.5) 55 (25) ecocirc XL 20-35 3/4, 1, 1-1/4, 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101 01 - 101 04 101 LF - 101 LF ecocirc XL 36-45 3/4, 1, 1-1/4, 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101 01 - 101 04 101 LF - 101 LF ecocirc XL 15-75 2 4 5.18 (132) 4.06 (103) - 0.56 (14) 101215 10 216LF ecocirc XL 55-45 3/4, 1, 1-1/4, 2 4.19 (106) 3.16 (80) 2.62 (66) 0.47 (12) 101 01 - 101 04 101 LF - 101 LF ecocirc XL 20-140 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 10 216LF ecocirc XL 65-130 1, 1-1/4, 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101 05 - 101 7 101 LF - 101 LF ecocirc XL 40-200 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 10121 10 216LF ecocirc XL 70-145 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101 05-101 07 101 LF-101 LF ecocirc XL 40-275 3 4 6.00 (152) 5.06 (129) - 0.53 (13) 101217 10 218LF ecocirc XL 65-130 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101212LF - 101214LF ecocirc XL 40-200 2 4 5.19 (132) 4.06 (103) - 0.56 (14) 101215 10 216LF ecocirc XL 95-160 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205 - 101207 101212LF - 101214LF ecocirc XL 27-320 3 4 6.00 (152) 5.06 (129) - 0.53 (13) 101217 10 218LF ecocirc XL 110-180 1, 1-1/4, 1-1/2 2 4.62 (117) 3.44 (87) 2.86 (73) 0.47 (12) 101205-101207 101212LF-101214LF ecocirc XL 45-375 3 4 6.00 (152) 5.06 (129)) - 0.53 (13) 101217 10 218LF
1-1/2" is the diameter of the suction and discharge for the 2-bolt models.
Enclosure: Class 2, IP44 (equivalent to NEMA Type 2) UL Listed to UL 778; UL 1004-1, 1004-7; and UL 60730-1 cUL Listed to C22.2 #108 Electronically Thermally Protected (Integrated Motor Protection) Motor Insulation Class: F Stainless steel models are NSF/ANSI- certified.
The pump maintains a constant speed at any flow rate. The desired speed is set on the interface panel of the pump.
The pump maintains a constant differential pressure at any flow demand until the maximum speed is reached. The desired head of the pump can be set via user interface. Recommended for use in systems with small or constant pressure losses.
The differential pressure continuously increases or deceases based on the flow demand. The set point head can be set on the pump user interface. Use for systems with large pressure losses.
The pump will automatically reduce speed when there is an abrupt change in fluid temperature. The change in fluid temperature is from a boiler operating in night time setback mode. The built-in temperature sensor is used. (Fixed Speed, Constant Pressure, Proportional Pressure)
The nominal differential pressure set point is modified based on the fluid temperature.Uses the built-in temperature sensor.
The pump maintains a constant temperature in a system, such as domestic hot water system or a single temperature heating system.
Uses the built-in temperature sensor.
The pump maintains a constant differential temperature between the built-in and external temperature sensors.
One 0-10V (Analog): Speed Control by external controller One 4-20mA (Analog): Connection with an external pressure sensor for
One external temperature sensor input for Differential Temp operating mode.
One built-in temperature sensor for Set Point Temp and Differential-Temp
The pump can be monitored or controlled by a signal from BMS (Building Management System). Built-in protocols are BACnet and Modbus. Direct connection to a PC is available.
An optional module can be added to create a short range field for use with thermostat.
Normally Open Dry Contact Relay for Fault Mode indication.
1. Control mode button
2. Control mode indicators
3. Parameter button
4. Parameter indicators
5. Setting buttons
6. Numeric display
7. Power indicator
8. Status / Fault indicator
9. Remote control indicator
Xylem Inc.
8200 N. Austin Avenue Morton Grove, IL 60053 Phone: (847)966-3700 Fax: (847)965-8379 www.bellgossett.com Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2017 Xylem Inc.
File details come from the government source that posted it. Updated .