36C25919R0090-0001002.pdf

PDF 18 MB Posted

Attached to
Replace Air Handling Units Federal contract opportunity
Solicitation number
36C25919R0090
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

36C25919R0090 0001 Drawings Combined Signed Sealed.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Replace Air Handling Units, newest first.
File Type Posted
36C25919R0090-0007000.docx DOCX document
36C25919R0090-0006000.docx DOCX document
36C25919R0090-0005000.docx DOCX document
36C25919R0090-0004003.pdf PDF
36C25919R0090-0004001.pdf PDF
36C25919R0090-0004002.pdf PDF
36C25919R0090-0004000.docx DOCX document
36C25919R0090-0003000.docx DOCX document
36C25919R0090-0002000.docx DOCX document
36C25919R0090-0002003.pdf PDF
36C25919R0090-0002001.pdf PDF
36C25919R0090-0002002.pdf PDF
36C25919R0090-0001001.pdf PDF
36C25919R0090-0001000.docx DOCX document
36C25919R0090-006.pdf PDF
36C25919R0090-004.docx DOCX document
36C25919R0090-002.pdf PDF
36C25919R0090-005.docx DOCX document
36C25919R0090-001.docx DOCX document
36C25919R0090-007.pdf PDF
36C25919R0090-003.pdf PDF
36C25919R0090-000.docx DOCX document
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARCHITECTURE ENGINEERING CONSTRUCTION

PROJECT NUMBER 623-15-104

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

GENERAL NOTES

VA PROJECT TEAM

OWNER: OWNER'S CONTRACTING OFFICER:

DRAWING TITLEDWG NO.

SHEET OF #

ABBREVIATIONS

PHASING

SITE PLAN

ED101 BUILDING 1AB FIRST FLOOR ELECTRICAL DEMOLITION PLAN

GI001

WLFDJR, JAV

GENERAL INFORMATION

NORTH

E-501 ELECTRICAL DETAILS

SIGNATURE BLOCK

E-601

MECHANICAL EQUIP. CONNECTION & LUMINAIRE SCHEDULE

ED102 BUILDING 1AB SECOND FLOOR ELECTRICAL DEMOLITION PLAN

ED103 BUILDING 1AB THIRD FLOOR ELECTRICAL DEMOLITION PLAN

ED104 BUILDING 1AB FOURTH FLOOR ELECTRICAL DEMOLITION PLAN

ED105 BUILDING 1AB FIFTH FLOOR ELECTRICAL DEMOLITION PLAN

ED106 BUILDING 1AB ATTIC ELECTRICAL DEMOLITION PLAN

ED107 BUILDING 1C CRAWL SPACE ELECTRICAL DEMOLITION PLAN

ED110 BUILDING 1C THIRD FLOOR ELECTRICAL DEMOLITION PLAN

ED111 BUILDING 1C ROOF ELECTRICAL DEMOLITION PLAN

EP101 BUILDING 1AB FIRST FLOOR ELECTRICAL POWER PLAN

EP102 BUILDING 1AB SECOND FLOOR ELECTRICAL POWER PLAN

EP103 BUILDING 1AB THIRD FLOOR ELECTRICAL POWER PLAN

EP104 BUILDING 1AB FOURTH FLOOR ELECTRICAL POWER PLAN

EP105 BUILDING 1AB FIFTH FLOOR ELECTRICAL POWER PLAN

EP106 BUILDING 1AB ATTIC ELECTRICAL POWER PLAN

EP110 BUILDING 1C THIRD FLOOR ELECTRICAL POWER PLAN

EP111 BUILDING 1C ROOF ELECTRICAL POWER PLAN

ELECTRICAL

E-001

ELECTRICAL LEGEND, NOTES, AND ABBREVIATIONS

OF45

OF46

OF47

OF48

OF

OF51

OF50

OF

OF52

OF53

OF54

OF55

OF56

OF57

OF58

OF59

INDEX OF DRAWINGS

DRAWING TITLEDWG NO.

GENERAL INFORMATION OF

SHEET OF #

GI001

GENERAL

OF2

OF 3

OF18

MECHANICAL

MD101 BUILDING 1AB FIRST FLOOR MECHANICAL DEMOLITION PLAN

OF19

OF4

OF5

OF14

OF15

OF16

OF17

OF10

OF11

OF12

OF13

OF6

OF7

OF8

OF

OF21

OF20

OF

OF22

OF23

OF24

OF25

M-501 MECHANICAL DETAILS

OF26

OF27

OF28

OF29

OF30

OF31

OF32

OF33

OF34

OF35

OF36

OF37

OF9

M-605 STEAM PRESSURE REDUCING VALVES DIAGRAM

M-606 MECHANICAL SCHEDULES

MD102 BUILDING 1AB SECOND FLOOR MECHANICAL DEMOLITION PLAN

MD103 BUILDING 1AB THIRD FLOOR MECHANICAL DEMOLITION PLAN

MD104 BUILDING 1AB FOURTH FLOOR MECHANICAL DEMOLITION PLAN

MD105 BUILDING 1AB FIFTH FLOOR MECHANICAL DEMOLITION PLAN

MD106 BUILDING 1AB ATTIC MECHANICAL DEMOLITION PLAN

MD107 BUILDING 1C CRAWL SPACE MECHANICAL DEMOLITION PLAN

MD108 BUILDING 1C FIRST FLOOR MECHANICAL DEMOLITION PLAN

MD109 BUILDING 1C SECOND FLOOR MECHANICAL DEMOLITION PLAN

MD110 BUILDING 1C THIRD FLOOR MECHANICAL DEMOLITION PLAN

MD111 BUILDING 1C ROOF MECHANICAL DEMOLITION PLAN

MH101 BUILDING 1AB FIRST FLOOR MECHANICAL PLAN

MH102 BUILDING 1AB SECOND FLOOR MECHANICAL PLAN

MH103 BUILDING 1AB THIRD FLOOR MECHANICAL PLAN

MH104 BUILDING 1AB FOURTH FLOOR MECHANICAL PLAN

MH105 BUILDING 1AB FIFTH FLOOR MECHANICAL PLAN

MH106 BUILDING 1AB ATTIC MECHANICAL PLAN

MH107 BUILDING 1C CRAWL SPACE MECHANICAL PLAN

MH108 BUILDING 1C FIRST FLOOR MECHANICAL PLAN

MH109 BUILDING 1C SECOND FLOOR MECHANICAL PLAN

MH110 BUILDING 1C THIRD FLOOR MECHANICAL PLAN

MH111 BUILDING 1C ROOF MECHANICAL PLAN

ICRA TYPICAL PHASING AND ENLARGED AREA PLANSGI401

INFECTION CONTROL RISK ASSESSMENT DETAILSGI501

MH401 LARGE-SCALE MECHANICAL PLANS

M-001 MECHANICAL LEGENDS AND ABBREVIATIONS

OF38

OF39

M-502 MECHANICAL DETAILS

M-503 MECHANICAL DETAILS

M-504 MECHANICAL DETAILS

M-505 MECHANICAL CONTROLS

M-506 MECHANICAL CONTROLS

M-507 MECHANICAL CONTROLS

M-601 AIRFLOW DIAGRAMS

M-602 AIRFLOW DIAGRAMS

M-603 AIRFLOW DIAGRAMS

M-604 HYDRONIC FLOW DIAGRAMS

MD401 LARGE-SCALE MECHANICAL DEMOLITION PLANS

OF

OF41

OF40

OF

OF

OF61

OF60

OF

OF62

OF63

OF64

OF65

OF66

OF67

OF68

ED401 ENLARGED AREAS ELECTRICAL DEMOLITION PLANS

EP401 ENLARGED AREAS ELECTRICAL POWER PLANS

M-607 MECHANICAL SCHEDULES

OF42 OF

M-608 MECHANICAL SCHEDULES

OF43 OF

MP105 BUILDING 1AB FIFTH FLOOR MECHANICAL PIPING PLAN

OF44 OF

ARCHITECTURAL

A-105 BUILDING 1AB FIFTH FLOOR ARCHITECTURAL PLAN

EL105 BUILDING 1AB FIFTH FLOOR ELECTRICAL LIGHTING PLAN

MP104 BUILDING 1AB FOURTH FLOOR MECHANICAL PIPING PLAN

MP103 BUILDING 1AB THIRD FLOOR MECHANICAL PIPING PLAN

OF69

OF70

STRUCTURAL

S101 BUILDING 1C ROOF STRUCTURAL PLAN

OF71 82

M-508 MECHANICAL CONTROLS

OF49 82

OF72 82

AD101 BUILDING 1AB FIRST FLOOR ARCHITECTURAL DEMOLITION PLAN

AD102 BUILDING 1AB SECOND FLOOR ARCHITECTURAL DEMOLITION PLAN

AD103 BUILDING 1AB THIRD FLOOR ARCHITECTURAL DEMOLITION PLAN

AD104 BUILDING 1AB FOURTH FLOOR ARCHITECTURAL DEMOLITION PLAN

AD105 BUILDING 1AB FIFTH FLOOR ARCHITECTURAL DEMOLITION PLAN

A-101 BUILDING 1AB FIRST FLOOR ARCHITECTURAL PLAN

A-102 BUILDING 1AB SECOND FLOOR ARCHITECTURAL PLAN

A-103 BUILDING 1AB THIRD FLOOR ARCHITECTURAL PLAN

A-104 BUILDING 1AB FOURTH FLOOR ARCHITECTURAL PLAN

MECHANICAL (CONTINUED)

FIRE PROTECTION

FP105 BUILDING 1AB FIFTH FLOOR FIRE PROTECTION PLAN OF73

OF74

OF75

OF76

OF77

OF78

OF79

OF80

OF81 82

OF82 82

DocuSign Envelope ID: 4071FBF3-839D-481D-8146-381D02560B60

11/21/2018

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. ICRA CONTROL BOUNDARY. PROVIDE

TEMPORARY PARTITION. PARTITION SHALL BE

INSPECTED BY VA ICRA STAFF PRIOR TO START

OF CONSTRUCTION IN SPACE. MAINTAIN

NEGATIVE PRESSURE VENTILATION IN THE

CONSTRUCTION SPACE.

2. WORK AREA.

3. PROVIDE STICKY MAT

4. CONTRACTOR SHALL REMOVE OR COVER ALL

FURNITURE WITHIN ROOM WITH PLASTIC PRIOR

TO COMMENCING WORK IN A SPACE AND

REPLACE OR REMOVE COVER PRIOR TO

POST-CONSTRUCTION TERMINAL CLEANING.

5. EXHAUST NEGATIVE AIR MACHINE OUT WINDOW.

CONTRACTOR SHALL FABRICATE DEVICE FOR

TEMPORARY INSTALLATION OF THE EXHAUST

DUCT IN WINDOW. AFTER REMOVAL OF

NEGATIVE AIR PRESSURE MACHINE, WINDOW

TO BE SECURED AND CHECKED BY VA STAFF.

6. PROVIDE NEGATIVE PRESSURE TO SPACE

DURING CONSTRUCTION DISCHARGE AIR

THROUGH HEPA FILTRATION.

7. EXHAUST NEGATIVE AIR MACHINE OUT DOOR

OPENING. CONTRACTOR SHALL FABRICATE

DEVICE FOR TEMPORARY INSTALLATION OF THE

EXHAUST DUCT IN DOOR FRAME. AFTER

REMOVAL OF NEGATIVE AIR PRESSURE

MACHINE, DOOR TO BE SECURED AND CHECKED

BY VA STAFF.

8. CONTRACTOR TO COVER FLOOR WITH

PLYWOOD OR SIMILAR MATERIAL TO PREVENT

DAMAGE TO FLOOR COVERINGS.

1 AB

GI401

WLF DJR

ICRA TYPICAL PHASING AND

ENLARGED AREA PLANS

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. PROVIDE ENGINEERED ICRA CONTROL BOUNDARY

UNLESS OTHERWISE COORDINATED WITH THE VA.

EDGE-GUARD OR APPROVED EQUAL. WITH

NEGATIVE AIR PRESSURE WITH HEPA FILTERS IN

MACHINE. ALSO PROVIDE STEP-OFF PADS (STICKY

MATS).

4. WHERE THERE ARE NOT EXISTING FIRE

PROTECTION SPRINKLER HEADS ON BOTH SIDES

OF ICRA PARTITIONS, THE PARTITION MUST BE

CONSTRUCTED ON NON-COMBUSTABLE

MATERIALS.

GI501

WLFJMB3

INFECTION CONTROL RISK

ASSESSMENT DETAILS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. REMOVE ACOUSTICAL CEILING PANELS AND GRID

THIS AREA AS REQUIRED TO PERFORM

DEMOLITION WORK INDICATED ON MECHANICAL

AND ELECTRICAL DEMOLITION SHEETS.

2. EXISTING LOUVER TO REMAIN.

3. REMOVE PORTIONS OF EXISTING WALL AND

CEILING THIS ROOM AS REQUIRED TO COMPLETE

MECHANICAL AND ELECTRICAL WORK.

AD101

RMCDJR

BUILDING 1AB FIRST FLOOR

ARCHITECTURAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN, REFER

TO SHEET GI501 AND NARRATIVE.

DocuSign Envelope ID: BFD0B71E-8238-4B00-9E14-3CA9592C9A44

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

AD102

RMCDJR

BUILDING 1AB SECOND FLOOR

ARCHITECTURAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN, REFER

TO SHEET GI501 AND NARRATIVE.

1. REMOVE ACOUSTICAL CEILING PANELS AND GRID

THIS AREA AS REQUIRED TO PERFORM

DEMOLITION WORK INDICATED ON MECHANICAL

AND ELECTRICAL DEMOLITION SHEETS.

2. EXISTING LOUVER TO REMAIN.

3. REMOVE PORTIONS OF EXISTING WALL AND

CEILING THIS ROOM AS REQUIRED TO COMPLETE

MECHANICAL AND ELECTRICAL WORK.

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

AD103

RMCDJR

BUILDING 1AB THIRD FLOOR

ARCHITECTURAL DEMOLITION PLAN

N O

R T

H

1. REMOVE ACOUSTICAL CEILING PANELS AND GRID

THIS AREA AS REQUIRED TO PERFORM DEMOLITION

WORK INDICATED ON MECHANICAL AND

ELECTRICAL DEMOLITION SHEETS.

2. EXISTING LOUVER TO REMAIN.

3. REMOVE PORTIONS OF EXISTING WALL AND

CEILING THIS ROOM AS REQUIRED TO COMPLETE

MECHANICAL AND ELECTRICAL WORK.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

AD104

RMCDJR

BUILDING 1AB FOURTH FLOOR

ARCHITECTURAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

1. REMOVE ACOUSTICAL CEILING PANELS AND GRID

THIS AREA (OR GYPSUM BOARD CEILING WHERE

OCCURS) AS REQUIRED TO PERFORM DEMOLITION

WORK INDICATED ON MECHANICAL AND

ELECTRICAL DEMOLITION SHEETS.

2. EXISTING LOUVER TO REMAIN.

3. REMOVE PORTIONS OF EXISTING WALL AND

CEILING THIS ROOM AS REQUIRED TO COMPLETE

MECHANICAL AND ELECTRICAL WORK.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

AD105

RMCDJR

BUILDING 1AB FIFTH FLOOR

ARCHITECTURAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN, REFER

TO SHEET GI501 AND NARRATIVE.

1. REMOVE EXISTING CEILING TILES AND GRID THIS

ROOM.

2. EXISTING LOUVER TO REMAIN.

3. REMOVE PORTIONS OF EXISTING WALL AND

CEILING THIS ROOM AS REQUIRED TO COMPLETE

MECHANICAL AND ELECTRICAL WORK.

4. REMOVE EXISTING CEILING TILES THIS AREA.

EXISTING GRID TO REMAIN.

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

A-101

RMCDJR

BUILDING 1AB FIRST FLOOR

ARCHITECTURAL PLAN

N O

R T

H

1. REINSTALL EXISTING CEILING PANELS AND GRID

REMOVED DURING DEMOLITION. REPLACE ANY

CEILING PANELS OR GRID THAT WAS DAMAGED

DURING DEMOLITION. MATCH HEIGHT AND TYPE

OF EXISTING ADJACENT CEILING SYSTEM.

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN, REFER

TO SHEET GI501 AND NARRATIVE.

4. IF SOME OF THE EXISTING CEILING GRID AND/OR

TILE IS DAMAGED DURING CONSTRUCTION AND

MATCHING MATERIAL IS NOT AVAILABLE, REPLACE

CEILING AND/OR TILE IN ENTIRE ROOM WITH

MATERIAL SPECIFIED IN 09 51 00 ACOUSTICAL

CEILINGS.

5. MAINTAIN EXISTING FIRE SEPARATION HOUR

RATINGS AT ALL NEW PENETRATIONS.

A-102

RMCDJR

BUILDING 1AB SECOND FLOOR

ARCHITECTURAL PLAN

N O

R T

H

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. REINSTALL EXISTING CEILING PANELS AND GRID

REMOVED DURING DEMOLITION. REPLACE ANY

CEILING PANELS OR GRID THAT WAS DAMAGED

DURING DEMOLITION. MATCH HEIGHT AND TYPE

OF EXISTING ADJACENT CEILING SYSTEM.

2. PATCH ANY FLOOR OR WALL OPENINGS THAT

REMAIN AFTER DEMOLITION OF MECHANICAL AND

ELECTRICAL EQUIPMENT THIS ROOM. PATCH TO

MATCH EXISTING ADJACENT CONDITIONS.

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN, REFER

TO SHEET GI501 AND NARRATIVE.

4. IF SOME OF THE EXISTING CEILING GRID AND/OR

TILE IS DAMAGED DURING CONSTRUCTION AND

MATCHING MATERIAL IS NOT AVAILABLE, REPLACE

CEILING AND/OR TILE IN ENTIRE ROOM WITH

MATERIAL SPECIFIED IN 09 51 00 ACOUSTICAL

CEILINGS.

5. MAINTAIN EXISTING FIRE SEPARATION HOUR

RATINGS AT ALL NEW PENETRATIONS.

13 2

A-103

RMCDJR

BUILDING 1AB THIRD FLOOR

ARCHITECTURAL PLAN

N O

R T

H

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. REINSTALL EXISTING CEILING PANELS AND GRID

REMOVED DURING DEMOLITION. REPLACE ANY

CEILING PANELS OR GRID THAT WAS DAMAGED

DURING DEMOLITION. MATCH HEIGHT AND TYPE

OF EXISTING ADJACENT CEILING SYSTEM.

2. PATCH ANY FLOOR OR WALL OPENINGS THAT

REMAIN AFTER DEMOLITION OF MECHANICAL AND

ELECTRICAL EQUIPMENT THIS ROOM. PATCH TO

MATCH EXISTING ADJACENT CONDITIONS.

3. PATCH ANY DAMAGE TO ROOFING MATERIAL

RESULTING FROM DEMOLITION OF MECHANICAL

EQUIPMENT. PATCH TO MATCH EXISTING

ADJACENT ROOFING. COORDINATE ROOF

REPAIRS WITH VA AND ROOFING CONTRACTOR

TO MAINTAIN EXISTING ROOF WARRANTY.

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN, REFER

TO SHEET GI501 AND NARRATIVE.

4. IF SOME OF THE EXISTING CEILING GRID AND/OR

TILE IS DAMAGED DURING CONSTRUCTION AND

MATCHING MATERIAL IS NOT AVAILABLE, REPLACE

CEILING AND/OR TILE IN ENTIRE ROOM WITH

MATERIAL SPECIFIED IN 09 51 00 ACOUSTICAL

CEILINGS.

5. ANY ROOF PATCHING IS TO BE DONE IN

ACCORDANCE WITH THE CURRENT ROOF

MANUFACTURERS SPECIFICATIONS TO MAINTAIN

EXISTING ROOF WARRANTY.

6. MAINTAIN EXISTING FIRE SEPARATION HOUR

RATINGS AT ALL NEW PENETRATIONS.

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

A-104

RMCDJR

BUILDING 1AB FOURTH FLOOR

ARCHITECTURAL PLAN

N O

R T

H

1. REINSTALL EXISTING CEILING PANELS AND GRID

REMOVED DURING DEMOLITION. REPLACE ANY

CEILING PANELS OR GRID THAT WAS DAMAGED

DURING DEMOLITION. MATCH HEIGHT AND TYPE

OF EXISTING ADJACENT CEILING SYSTEM.

2. PATCH ANY FLOOR OR WALL OPENINGS THAT

REMAIN AFTER DEMOLITION OF MECHANICAL AND

ELECTRICAL EQUIPMENT THIS ROOM. PATCH TO

MATCH EXISTING ADJACENT CONDITIONS.

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN, REFER

TO SHEET GI501 AND NARRATIVE.

4. IF SOME OF THE EXISTING CEILING GRID AND/OR

TILE IS DAMAGED DURING CONSTRUCTION AND

MATCHING MATERIAL IS NOT AVAILABLE, REPLACE

CEILING AND/OR TILE IN ENTIRE ROOM WITH

MATERIAL SPECIFIED IN 09 51 00 ACOUSTICAL

CEILINGS.

5. ANY ROOF PATCHING IS TO BE DONE IN

ACCORDANCE WITH THE CURRENT ROOF

MANUFACTURERS SPECIFICATIONS TO MAINTAIN

EXISTING ROOF WARRANTY.

6. MAINTAIN EXISTING FIRE SEPARATION HOUR

RATINGS AT ALL NEW PENETRATIONS.

2 3

2 3

2 3

2 3

2 3

2 3

2 3

1 2

2 3

2 3

2 3

2 3

2 3

2 3

2 3

2 32 32 3

2 3 2 3 2 3

2 3

1 2

1 2

1 2

1 2

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. REPLACE EXISTING CEILING GRID AND

PANELS THIS CORRIDOR WITH NEW

ASSEMBLY (ACT-1). CEILING HEIGHT TO

MATCH HEIGHT OF EXISTING CORRIDOR

CEILINGS.

2. PATCH ANY FLOOR OR WALL OPENINGS

THAT REMAIN AFTER DEMOLITION OF

MECHANICAL AND ELECTRICAL EQUIPMENT

THIS ROOM. PATCH TO MATCH EXISTING

ADJACENT CONDITIONS.

3. PROVIDE NEW 2'X2' CEILING PANELS AND

GRID ASSEMBLY (ACT-1) THIS ROOM PER

SPECIFICATION SECTION 09 51 00. NEW

CEILING HEIGHT IS TO BE 8'-0" AFF.

A-105

RMCDJR

BUILDING 1AB FIFTH FLOOR

ARCHITECTURAL PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. IN ROOMS/CORRIDORS WHERE NEW CEILINGS WILL

BE INSTALLED LOWER THAN THE EXISTING

CEILINGS, PATCH AND SEAL EXISTING WALL

OPENINGS WHERE SIDE WALL GRILLES WERE

REMOVED.

4. MAINTAIN EXISTING FIRE SEPARATION HOUR

RATINGS AT ALL NEW PENETRATIONS.

11/20/18

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. AREA OF WORK.

2. DROP EXISTING SPRINKLER HEADS

APPROXIMATELY 2 FEET TO MATCH NEW CEILING

HEIGHT.

3. PROVIDE NEW SPRINKLER HEADS.

FP105

WLFRK

BUILDING 1AB FIFTH FLOOR FIRE

PROTECTION PLAN

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

DocuSign Envelope ID: 8B0D9B45-E8D6-491F-B574-0EC382C37ACB

CONTROL WIRING

LIMITS OF DEMOLITION

POINT OF CONNECTION TO EXISTING

SUPPLY DIFFUSER

RETURN GRILLE

FIRE DAMPER

DUCT SMOKE DETECTOR

DIFFUSER NECK SIZE

DIFFUSER CFM

T

THERMOSTAT

VOLUME DAMPER

8"Ø

SUPPLY TOP REGISTER OR GRILLE

(WALL TYPE)

EXHAUST OR RETURN REGISTER OR TOP

GRILLE (WALL TYPE)

FLEXIBLE DUCTWORK (INSULATED)

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

RETURN DUCT (UP & DOWN)

ROUND DUCTWORK

DN

DN

DNUP

UP

UP

8"Ø

RECTANGULAR DUCTWORK

10x10

VAV BOX

EXISTING DUCTWORK

DUCTWORK TO BE DEMOLISHED

AIRFLOW DIRECTION

PIPING DOWN

PIPING UP

TEE UP

TEE DOWN

EXISTING PIPING TO REMAIN

PIPING TO BE DEMOLISHED

TEST PLUG (PRESSURE/TEMPERATURE)

EXHAUST GRILLE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

M-001

WLFDJR

MECHANICAL LEGENDS AND

ABBREVIATIONS

DocuSign Envelope ID: 5F9F06D1-A25A-4512-B486-D4673CACB0C3

AREA SERVED BY CHAPEL 1-AHU-3

EA

EA

EX LOUVER

EX 1-EF-1

EX EA

EX CD

EX CD

EX CD

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. DISCONNECT EXHAUST DUCTS CONNECTED TO

FAN.

2. DISCONNECT POWER CONNECTION TO FAN AND

REMOVE VFD. DISPOSE OF VFD PER SPECIFICATION

REQUIREMENTS.

3. REMOVE EXHAUST FAN AND CONNECTING

DUCTWORK.

4. REMOVE EXISTING THERMOSTAT FOR

REPLACEMENT WITH NEW COMPATIBLE WITH NEW

CONTROLS SYSTEM.

5. EXISTING DUCTWORK TO REMAIN AS IS.

6. REMOVE EXISTING CEILING DIFFUSER TO BE

REPLACED AS INDICATED ON THE NEW WORK

SHEET.

MD101

WLF / JMB2DJR

BUILDING 1AB FIRST FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

12"Ø

8"Ø

6"Ø

6"Ø

8"Ø

8"Ø

8"Ø

10"Ø

6"Ø

EX 22x10 EA

EX HOOD

WITH (4)

EX 8"Ø EA

(TYP.)

AREA SERVED BY 1-AHU-4 LOCATED

AT FIRST FLOOR MECHANICAL ROOM

EA

EA

EX LOUVER

EX 1-EF-4

EX 1-EF-2

EX 1-EF-3

EX EA

16"Ø SA UP

16"x16" EA UP

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. DISCONNECT EXHAUST DUCTS CONNECTED TO

FAN.

2. DISCONNECT POWER CONNECTION TO FAN AND

REMOVE VFD. DISPOSE OF VFD PER SPECIFICATION

REQUIREMENTS.

3. REMOVE EXHAUST FAN AND CONNECTING

DUCTWORK.

4. DISCONNECT POWER AND DEMOLISH EXHAUST

FAN.

5. DEMOLISH EXISTING FAN COIL AND SUPPLY AIR

DUCTS, DIFFUSERS, AND CHILLED WATER PIPING

TO MAINS ABOVE CORRIDOR CEILING.

6. DEMOLISH EXISTING CAV BOX AND ASSOCIATED

DUCTWORK, AND GRILLES/DIFFUSERS.

7. DEMOLISH STEAM AND CONDENSATE PIPING

ASSOCIATED WITH REHEAT COILS TO MAINS ABOVE

CEILING.

8. DEMOLISH ALL CONTROLS ASSOCIATED WITH CAV

AND STEAM COIL. CUT AND CAP PNEUMATIC

TUBING UP TO MAIN ABOVE CEILING.

9. REMOVE EXISTING THERMOSTAT FOR

REPLACEMENT WITH NEW COMPATIBLE WITH NEW

CONTROLS SYSTEM.

10. EXISTING DUCTWORK TO REMAIN AS IS.

11. EXISTING DUCT RISERS TO BE REMOVED AND

REPLACED WITH NEW IN SAME LOCATION. SEE

NEW WORK PLAN FOR NEW DUCT INFORMATION.

MD102

WLF / JMB2DJR

BUILDING 1AB SECOND FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

E A

EX 24/9 EA

EX 10"Ø SA

EX 6"Ø EA

SEE 1C THIRD FLOOR

PLANS FOR

CONTINUATION

EX CD

EX RG

EX RG

EX CD

EX 6"Ø SA

EX 10"Ø SA

EX CD

EX 12"Ø EA

EX RG

EX CD

EX 6"Ø SA

EX 12"Ø EA

EX CD

EX 1-MB-1

EX 20x10 SA

EX RG

EX 8"Ø EA

EX 1-EF-6

EX 8"Ø SA

EX CD

EX RG

EX 1-CU-1

EX 1-CU-2

EX 1-EF-9

EX 1-EF-11

EX 1-EF-10

EX 8"Ø SA

EX CD

EX 10"Ø EA

EX 12x6 EA

EX RG

EX 8"Ø EA

EX CD

EX 6"Ø SA

EX CD

EX 6"Ø SA

EX 16x7 SA

EX CD

EX 8"Ø SA

EX RG

EX 12"Ø EA

EX RG

EX 8"Ø EA

EX RG

EX 6"Ø EA

EX RG

EX 6"Ø EA

EX 14x8 EA

EX 10"Ø SA

EX CD

EX RG

EX 12"Ø EA

EX CD

EX RG

EX 12"Ø EA

EX 12"Ø EA

EX RG

EX 12"Ø EA

EX RG

EX CD

EX CD

EX 10"Ø SA

EX 10"Ø SA

(2) EX12"Ø SA UP

(COLD & HOT)

EX 10"Ø SA

EX EA

EX EA

EX 10"Ø SA

EX 1-MB-2

EA

EA

EX LOUVER

EX 1-EF-5

EX 1-EF-7

EX 12"Ø SA

UP AND DOWN

EX 24x10 EA

UP AND DOWN

EX EA

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

MD103

WLF / JMB2DJR

BUILDING 1AB THIRD FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. DISCONNECT EXHAUST DUCTS CONNECTED TO

FAN.

2. DISCONNECT POWER CONNECTION TO FAN AND

REMOVE VFD. DISPOSE OF VFD PER SPECIFICATION

REQUIREMENTS.

3. REMOVE EXHAUST FAN AND CONNECTING

DUCTWORK.

4. DISCONNECT POWER AND DEMOLISH EXHAUST

FAN.

5. DEMOLISH DUCTWORK AND ASSOCIATED

GRILLES/DIFFUSERS.

6. DEMOLISH EXISTING DUAL DUCT MIXING BOX AND

ASSOCIATED CONTROLS.

7. EXISTING DUCTWORK TO REMAIN.

8. DISCONNECT POWER AND DEMOLISH

CONDENSING UNIT ALONG WITH ASSOCIATED

REFRIGERANT PIPING.

9. REMOVE REFRIGERANT PER LOCAL AND VA CODES.

10. PATCH ANY DAMAGE TO ROOFING MATERIAL

RESULTING FROM MECHANICAL DEMOLITION.

PATCH TO MATCH EXISTING ADJACENT ROOFING.

COORDINATE ROOF REPAIRS WITH

ARCHITECTURAL REQUIREMENTS, VA, AND

ROOFING CONTRACTOR TO MAINTAIN EXISTING

ROOF WARRANTY.

11. EXISTING DUCT RISERS TO BE REMOVED AND

REPLACED WITH NEW IN SAME LOCATION. SEE

NEW WORK PLAN FOR NEW DUCT INFORMATION.

EX 1-EF-13

EX 1-EF-14

EA

EX LOUVER

EX 1-EF-12

EX RG

EX 6x10 SA

EX 12x10 SA

EX 8"Ø SA

EX CD

EX 1-MB-6

EX 1-MB-3

EX 1-MB-7

EX 1-MB-4

EX 1-MB-8

EX 1-MB-5

EX 6"Ø SA

EX CD

(2) EX 15"Ø SA UP AND (2) 12"Ø DOWN

(COLD & HOT)

EX 8"Ø SA

EX CD

EX 10"Ø SA

EX CD

EX 10"Ø SA

EX CD

EX 10"Ø SA

EX CD

(2) EX 8"Ø SA

EX 8"Ø SA

EX 5x10 SA

EX 12x10 SA

EX CD

EX 8"Ø SA

EX 10"Ø SA

EX CD

EX 14"Ø SA

UP AND DOWN

EX 24x14 RA/EA

UP AND DOWN

EX 20x10/EA

EX RG AND 6"Ø EA

EX 16x8 EA

EX 20/10 EA

EX RG AND DUCT

EX 16x8 EA

EX SD AND DUCT

EX SD AND DUCT

EX SD AND DUCT

EX EA

EX CAV BOX

EX TSTAT

EX TSTAT

EX TSTAT

EX TSTAT

EX TSTAT

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

MD104

WLF / JMB2DJR

BUILDING 1AB FOURTH FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

1. DISCONNECT EXHAUST DUCTS CONNECTED TO

FAN.

2. DISCONNECT POWER CONNECTION TO FAN AND

REMOVE VFD. DISPOSE OF VFD PER SPECIFICATION

REQUIREMENTS.

3. REMOVE EXHAUST FAN AND CONNECTING

DUCTWORK.

4. DISCONNECT POWER AND DEMOLISH EXHAUST

FAN.

5. DEMOLISH DUCTWORK AND ASSOCIATED

GRILLES/DIFFUSERS.

6. DEMOLISH EXISTING DUAL DUCT MIXING BOX AND

ASSOCIATED CONTROLS.

7. EXISTING DUCTWORK TO REMAIN.

8. DEMOLISH STEAM AND CONDENSATE PIPING

ASSOCIATED WITH REHEAT COILS TO MAINS ABOVE

CEILING.

9. DEMOLISH ALL CONTROLS ASSOCIATED WITH CAV

AND STEAM COIL. CUT AND CAP PNEUMATIC

TUBING UP TO THE MAIN ABOVE CEILING.

10. DEMOLISH EXISTING CAV BOX AND ASSOCIATED

CONTROLS.

EX 18x18 SA UP

EX-1-EF-17

EX 1-EF-18

EA

EA

EX 14"Ø SA

UP AND DOWN

EX 24x14 RA/EA

UP AND DOWN

EX 12x8 SAEX 12x8 SA

EX CD

EX RR 20x8

EX 20x10 EA

EX RR 30x12

EX 18x10 SA

EX 18x8 SA

EX SD 20x8

EX RR 18x8

EX 18x14 SA UP

EX SD 20x8

EX 15x8 SA

EX RR 18x8

EX SD 20x8

EX RR 14x8

EX 20x14 EA

EX 18x10 SA

EX RR 20x8

EX 18x8 SA

EX RR 16x8

EX SD 20x8

EX RR 14x8

EX RR 14x8

EX 20x20 EA

EX 24x20 EA

EX 30x20 EA

EX 10x8 SA

EX CD

EX 30x20 EA

EX SD 20x8EX SD 20x8

EX

10x10

SA

EX SD 20x8

EX RR 20x8

EX 8x6 SA

EX CD

EX 12x8 SA

EX RR 20x8

EX SD 20x8

EX 20x10 EA

EX SD 20x8

EX RR 16x8

EX 16x16 SA UP

EX SD

20x8

EX

12x8

SA

EX RG

EX 6X6 EA

EX 24x12 EA

EX 24x18 EA

EX 12x8 SA

EX 18x20 SA UP

EX 24x20 EA

EX CD

EX 12"Ø SA

EX CD

EX 12"Ø SA

EX RG

EX 18x10 SA

EX RG

EX LOUVER

EX EF

EX EF

EX RR 20x8

EX EF

EX SD 20x8

EX 16x14 SA

EX SD 20x8

EX 18x8 SA

EX RR 30x12

EX SD 20x8

EX 18x8 SA

EX SD 20x8

EX SD 24x8

EX 18x12 SA

EX 14"Ø SA

EX CD

EX LOUVER

EX 1-EF-15

EX LOUVER

EX 1-EF-16

EX SD 20x8

EX SD 20x8

EX SD 20x8

(2) EX12"Ø SA UP

(COLD & HOT)

EX EA

EX EA

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

MD105

WLF / JMB2DJR

BUILDING 1AB FIFTH FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. AHU-MICU DUCTWORK REVISIONS AND HW PIPING

INSTALLATION SHALL BE PHASED BASED ON

INDIVIDUAL FLOORS STARTING ON THE 3RD FLOOR.

2. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

3. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

4. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

1. DISCONNECT EXHAUST DUCTS CONNECTED TO

FAN.

2. DISCONNECT POWER CONNECTION TO FAN AND

REMOVE VFD. DISPOSE OF VFD PER SPECIFICATION

REQUIREMENTS.

3. REMOVE EXHAUST FAN AND CONNECTING

DUCTWORK.

4. DISCONNECT POWER AND DEMOLISH EXHAUST

FAN.

5. DEMOLISH DUCTWORK AND ASSOCIATED

GRILLES/DIFFUSERS.

6. DEMOLISH EXISTING DUAL DUCT MIXING BOX

CONTROLS.

7. EXISTING DUCTWORK TO REMAIN.

H

C

H

C

C

H

C

H

C

EX-1-EF-21

EX 1-EF-22

EX 18x18 SA DOWN

EX 18x14 SA DOWN

EX 18x20 SA DOWN

EX 4" CHS/R

EX 4" CHS/R

EX 1-AHU-2

EX 14"Ø SA DUCT

EX OA DUCT AND LOUVER

EX 16" Ø RA DUCT

EX 16"Ø RA DUCT

EX 18x13 EA DUCT UP THRU ROOF TO EXHAUST HOOD

EX 16"Ø RA/EA DUCT

EX HEPA

FILTER BOX

EX 14"Ø

SA DOWN

EX 24x12

RA/EA DOWN

EX CONTROL PANEL

EX 1-AHU-1

EX 16x16 SA DOWN

EX OA DUCT

AND LOUVER

EX HOT AND COLD SA DUCTS (STACKED)

EX 4" CHS/R DOWN

ON EXTERIOR WALL

EX 2" CHS/R

EX LPS/LPR

H

EX STEAM PIPING

EX HOT AND COLD SA DUCTS (STACKED)

EX 1-EF-20

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. DISCONNECT POWER CONNECTION TO THE UNIT.

2. DISCONNECT DUCTS CONNECTED TO THE UNIT,

AND STEAM/CONDENSATE PIPING AND CHILLED

WATER SUPPLY/RETURN PIPING.

3. DEMOLISH EXISTING DUAL DUCT MIXING BOX AND

ASSOCIATED CONTROLS.

4. DEMOLISH SUPPLY, RETURN, AND EXHAUST DUCT

AS INDICATED.

5. EXISTING AHU TO BE REMOVED.

6. EXISTING 15"Ø DUCTS DOWN TO BE REMOVED.

7. DEMOLISH FILTER BOX AS INDICATED.

8. DISCONNECT POWER AND DEMOLISH RETURN AND

FAN.

9. EXISTING TO REMAIN.

MD106

WLF / JMB2DJR

BUILDING 1AB ATTIC MECHANICAL

DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

4. ROOF ACCESS HATCH MAY BE USED FOR REMOVAL

OF AHU, DUCTS, AND OTHER EQUIPMENT.

5. UNIT MAY BE DISASSEMBLED OR CUT IN SMALLER

SECTIONS TO FACILITATE REMOVAL.

EX CAPPED

EX UP TO

FCU ABOVE

EX CAPPEDEX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

EX 2" HWS/HWR UP

EX CAPPED

EX CAPPED

EX CAPPED

EX CAPPED

EX 2" HWS/HWR

EX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. DEMOLISH EXISTING HEATING HOT WATER PUMPS,

HEAT EXCHANGER, AIR SEPARATOR, EXPANSION

TANK, CHEM POT FEEDER AND CONTROLS.

2. DEMOLISH EXISTING DUPLEX CONDENSATE

TRANSFER PUMP.

3. DEMOLISH EXISTING HEATING HOT WATER PIPING

TO THE LIMITS OF DEMOLITION.

4. REMOVE ALL EXISTING INSULATION FOR

REPLACEMENT. IF ASBESTOS IS FOUND IN THE

INSULATION, STOP WORK AND INFORM COR.

MD107

WLF / JMB2DJR

BUILDING 1C CRAWLSPACE

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

189.3322

43.806652.9300

12.7772

EX UP TO

FCU ABOVE

EX 2" HWS/HWR DOWN

EX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

EX 1" HWS/HWR UP

EX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

EX UP TO

FCU ABOVE

EX 1-1/2"

HWS/HWR

EX 1-1/2"

HWS/HWR

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. REMOVE EXISTING HEATING HOT WATER RISERS.

MD108

WLF / JMB2DJR

BUILDING 1C FIRST FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

EX TO FCU

EX 1" HWS/HWR DOWN

EX TO FCU

EX 1"

HWS/HWR

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. DEMOLISH EXISTING HEATING HOT WATER DOWN

TO FIRST FLOOR. EXISTING WALL WILL NEED TO BE

REMOVED FOR ACCESS.

MD109

WLF / JMB2DJR

BUILDING 1C SECOND FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

EX. HX

CHS

CHR

S-30

S-15

HWS

HWR

CHS

CHS

CHR

CHR

EX. HWP

S-30

S-60 DN

CR-15

S-15 S-15

S-30

CR-15S-15

EX. AS

CR-15

CR-15

S-15

CHR

CHR

C H

R

CHS

CHS

C H

S

EX S-30 TO LAB

STERILIZERS

EX CHS/R UP

EX AHU-4

EX AHU-3

EX AHU-7

EX AHU-6

EX AHU-5

EX 24/9 EA

SEE 1AB THIRD FLOOR PLANS

FOR CONTINUATION

EX 24/9 EA UP TO FAN ON ROOF ABOVE

EX PRV-2EX PRV-1

EX PRV-3

EX AHU-2

CR-15

S-15

EX. HX

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1. DISCONNECT HEATING HOT WATER SUPPLY AND

RETURN PIPING TO HEAT EXCHANGER

(APPROXIMATELY 10 FEET).

2. DISCONNECT STEAM PIPING TO HEAT EXCHANGER

AS SHOWN.

3. DEMOLISH HEATING HOT WATER SYSTEM

CONSISTING OF HEAT EXCHANGERS, PUMPS, AIR

SEPARATOR, OTHER ACCESSORIES, AND

INTERCONNECTED PIPING.

4. DEMOLISH HEATING HOT WATER CONTROLS.

5. SHUT OFF HIGH PRESSURE STEAM SUPPLY MAINS.

6. DEMOLISH THREE EXISTING PRV'S: PRV-1, PRV-2,

AND PRV-3.

7. EXISTING MAIN SUPPLY, EXHAUST, AND RETURN

DUCT TO REMAIN FOR RE-USE AS INDICATED.

MD110

WLF / JMB2DJR

BUILDING 1C THIRD FLOOR

MECHANICAL DEMOLITION PLAN

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

EX 1-EF-8

EX 24x24 EA IN ROOF CURB

EX

CONDENSING

UNIT

EX 4" CHS/R UP ON

EXTERIOR WALL

EX 4" CHS/R EX 4" CHS/R

EX 30"Ø SA

EX 30"Ø SA UP ON

EXTERIOR WALL

EX 20"Ø SA DOWN

EX 48"Ø SA

EX 1-AHU-AB

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

MD111

WLF / JMB2DJR

BUILDING 1C ROOF MECHANICAL

DEMOLITION PLAN

N O

R T

H

1. DEMOLISH EXISTING EXHAUST FAN. EXISTING

DUCT BELOW, ROOF PENETRATION, AND CURB TO

REMAIN FOR USE WITH NEW RETURN AIR DUCT.

2. REMOVE SECTION OF EXISTING PIPING FOR

CONNECTION OF NEW PIPING AND ISOLATION

VALVES.

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO

BE DONE IN A MANNER TO MINIMIZE

DISRUPTIONS TO THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS.

WORK TO PRIMARILY TAKE PLACE AFTER

BUSINESS HOURS AND SCHEDULED WEEKEND

PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN

REFER TO SHEET GI501 AND NARRATIVE.

EX 1-EF-23

EX 1-SWHX-1

EX 1-HWP-1

EX DWH

EX DHW CIRC PUMP

EX AHU-4

EX CONTROL PANEL

EX AHU-3

EX AHU DISCONNECT

EX ELECTRICAL PANEL B-1

EX AHU DISCONNECT

EX 20x20 SA

EX 20x20 RA

EX 26x20 SA

EX 16x42 RA

1. DISCONNECT POWER AND DEMOLISH EXISTING AIR

HANDLING UNIT AS INDICATED.

2. DISCONNECT SUPPLY, RETURN, EXHAUST, AND

OUTSIDE AIR DUCTWORK CONNECTED TO THE AIR

HANDLING UNIT.

3. DISCONNECT HOT WATER SUPPLY AND RETURN

PIPING, CONTROL VALVE, ETC. FROM AIR HANDING

UNIT. DEMOLISH REFRIGERANT PIPING FROM UNIT

TO CONDENSING UNIT ON ROOF.

4. DISCONNECT OR DEMOLISH CONTROLS

ASSOCIATED WITH THIS SYSTEM, BOTH

ELECTRIC/ELECTRONIC AND PNEUMATIC. CAP OR

PLUG PNEUMATIC TUBING THAT REMAINS.

5. DISCONNECT POWER AND DEMOLISH EXISTING

HEATING HOT WATER PUMP, HEAT EXCHANGER,

AIR SEPARATOR, EXPANSION TANK, CHEM POT

FEEDER AND CONTROLS.

6. DISCONNECT EXISTING STEAM, CONDENSATE, AND

HOT WATER SUPPLY AND RETURN PIPING TO THE

HEAT EXCHANGER SYSTEM UP TO THE MAINS IN

THE ROOM.

7. REMOVE ALL PIPE INSULATION ON EXISTING

STEAM, CONDENSATE, AND HEATING HOT WATER

PIPING IN THIS ROOM SO IT CAN BE REINSULATED.

NORTH

KEY PLAN:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Revisions: Date: Apogee Project #

SHEET NOTES:

SHEET KEY NOTES:

100% CONSTRUCTION

DOCUMENTS

November 20, 2018

Replace Air Handling Units VA #623-15-104

FULLY SPRINKLERED

Muskogee, OK

Apogee Consulting Group 1151 Kildaire Farm Rd., Suite 120 Cary, NC 27511 919-858-7420 Josh VandenEnde

17-287

STRUCTURAL ENGINEER

ASCENT ENGINEERING

6707 WINCHESTER CIRCLE #100

BOULDER, CO 80301

(303) 499-3022

1AB

FULLY SPRINKLERED MD401

WLFDJR

ENLARGED AREAS MECHANICAL

DEMOLITION PLANS

N O

R T

H

1. FACILITY SHALL BE FULLY OCCUPIED

THROUGHOUT CONSTRUCTION. ALL WORK IS TO BE

DONE IN A MANNER TO MINIMIZE DISRUPTIONS TO

THE REST OF THE BUILDING.

2. COORDINATE WORKING HOURS WITH VA COR AS

INSTRUCTED IN GENERAL REQUIREMENTS. WORK

TO PRIMARILY TAKE PLACE AFTER BUSINESS

HOURS AND SCHEDULED WEEKEND PERIODS.

3. FOR WORK SEQUENCE AND PHASING PLAN REFER

TO SHEET GI501 AND NARRATIVE.

4. ROOF ACCESS HATCH MAY BE USED FOR REMOVAL

OF AHU, DUCTS, AND OTHER EQUIPMENT.

5. UNIT MAY BE…