36C25919R0061-0002001.pdf

PDF 35 KB Posted

Attached to
Install Fire Pump Federal contract opportunity
Solicitation number
36C25919R0061
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

36C25919R0061 0002 Questions and Answers 2.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Install Fire Pump, newest first.
File Type Posted
36C25919R0061-0003001.pdf PDF
36C25919R0061-0003000.docx DOCX document
36C25919R0061-0002000.docx DOCX document
36C25919R0061-0001000.docx DOCX document
36C25919R0061-0001005.jpg JPG image
36C25919R0061-0001004.jpg JPG image
36C25919R0061-0001003.pdf PDF
36C25919R0061-0001002.pdf PDF
36C25919R0061-0001001.pdf PDF
36C25919R0061-003.pdf PDF
36C25919R0061-005.pdf PDF
36C25919R0061-001.docx DOCX document
36C25919R0061-006.pdf PDF
36C25919R0061-007.pdf PDF
36C25919R0061-002.pdf PDF
36C25919R0061-004.pdf PDF
36C25919R0061-009.docx DOCX document
36C25919R0061-008.pdf PDF
36C25919R0061-000.docx DOCX document
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Please review Statement of Work, as some items have changed.

Question #1-Will the VA be providing the star up and commissioning of new pump and transfer switch they have purchased? Did this service come with the purchase of fire pump or should this be provided in current SOW?

Answer: Installation will require Manufacture Start Up and Commissioning for warranty purposes. We will also require a Fire Pump Test to ensure required flows and a Stand Pipe Flow Test IAW NFPA.

Question 2: Are you able to provide more details on the scope of work for what is needed for the Fire Alarm Spec portion for the Fire Pump?

Answer: No New alarms are required – no new boards are required.

Question 3: Who is the current Fire Alarm Contractor and will we be able to add programming if needed to service the Fire Pump System?

Answer: Banning installed the current system and York monitor the Fire Alarm System