26 05 26 Grounding and Bonding Electrical.doc

DOC document 87 KB Posted

Attached to
Y1DA--Replace PA System Bldg. 163 and 204 674-22-262 CTVHCS
Solicitation number
36C25722B0022
Issued by

About this file

This document contains technical specifications for grounding and bonding electrical systems for a federal construction project. The specifications cover requirements for grounding conductors, ground rods, connections, equipment bonding, and testing to achieve a maximum grounding resistance of 5 ohms. Key details include the types of conductors and components required, such as stranded copper, compression connectors, and exothermic welds. System grounding and bonding is specified for secondary service neutrals, separately derived systems, raceways, boxes, and other electrical equipment. Medical facilities additions require bonding of gases and suction piping outlets directly to room or patient ground buses.

View the file

Other files

File Type Posted
36C25722B0022 0002.docx DOCX document
163-4.pdf PDF
BLDG 204 - 4TH FLOOR-RECORD-Work.pdf PDF
270511 COMMUNICATIONS INSTALLATIONS.docx DOCX document
01 00 00 General Construction.doc DOC document
BLDG 204 - 5TH FLOOR-RECORD-Work.pdf PDF
26 05 11 Electrical installation.doc DOC document
BLDG 204 - BASEMENT - RECORD-Work.pdf PDF
BLDG 204 - 6TH FLOOR - RECORD-Work.pdf PDF
36C25722B0022 0001.docx DOCX document
26 27 26 Wiring for Low Voltage Devices.doc DOC document
07 84 00 Fire Stopping.doc DOC document
280513 CABLES FOR ELECTRONIC SAFETY AND SECURITY.doc DOC document
163-3.pdf PDF
BLDG 204 - 2ND FLOOR-RECORD-Work.pdf PDF
163-2.pdf PDF
28 16 00 INTRUSION DETECTION SYSTEM.doc DOC document
163-B.pdf PDF
BLDG 204 - 1ST FLOOR-RECORD-Work.pdf PDF
BLDG 204 - 3RD FLOOR-RECORD-Work.pdf PDF
26 05 21 Low Voltage.doc DOC document
163-5.pdf PDF
27 51 16 PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS.docx DOCX document
163-1.pdf PDF
36C25722B0022_1.docx DOCX document
01 00 00 General Construction.pdf PDF
26 05 11 Electrical installation.pdf PDF
26 05 21 Low Voltage.pdf PDF
270511 COMMUNICATIONS INSTALLATIONS.pdf PDF
28 16 00 INTRUSION DETECTION SYSTEM.pdf PDF
26 27 26 Wiring for Low Voltage Devices.pdf PDF
280513 CABLES FOR ELECTRONIC SAFETY AND SECURITY.pdf PDF
26 05 26 Grounding and Bonding Electrical.pdf PDF
07 84 00 Fire Stopping.pdf PDF
27 51 16 PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEMS.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

09-10

SECTION 26 05 26

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 ‑ GENERAL

1.1 DESCRIPTION

A.

This section specifies the general grounding and bonding requirements for electrical equipment and operations to provide a low impedance path for possible ground fault currents.

B.

“Grounding electrode system” refers to all electrodes required by NEC, as well as made, supplementary, and lightning protection system grounding electrodes.

C. The terms “connect” and “bond” are used interchangeably in this specification and have the same meaning.

1.2 RELATED WORK

A.

Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26.

B.

Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Low Voltage power and lighting wiring.

1.3 qualITY ASSURANCE

Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

1.4 SUBMITTALS

A.

Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

B.

Shop Drawings:

1.

Clearly present enough information to determine compliance with drawings and specifications.

2.

Include the location of system grounding electrode connections and the routing of aboveground and underground grounding electrode conductors.

C.

Test Reports: Provide certified test reports of ground resistance.

D.

Certifications: Two weeks prior to final inspection, submit four copies of the following to the COTR:

1.

Certification that the materials and installation are in accordance with the drawings and specifications.

2.

Certification by the contractor that the complete installation has been properly installed and tested.

1.5 APPLICABLE PUBLICATIONS

Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only.

A.

American Society for Testing and Materials (ASTM):

B1-07 Standard Specification for Hard-Drawn Copper Wire

B3-07 Standard Specification for Soft or Annealed Copper Wire

B8-04 Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft

B.

Institute of Electrical and Electronics Engineers, Inc. (IEEE):

81-1983 IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System

C2-07 National Electrical Safety Code

C.

National Fire Protection Association (NFPA):

70‑08 National Electrical Code (NEC)

99‑2005 Health Care Facilities

D.

Underwriters Laboratories, Inc. (UL):

44‑05 Thermoset‑Insulated Wires and Cables

83‑08 Thermoplastic‑Insulated Wires and Cables

467‑07 Grounding and Bonding Equipment

486A-486B-03 Wire Connectors

PART 2 ‑ PRODUCTS

2.1 GROUNDING AND BONDING CONDUCTORS

A.

Equipment grounding conductors shall be UL 44 or UL 83 insulated stranded copper, except that sizes No. 10 AWG [6 mm²] and smaller shall be solid copper. Insulation color shall be continuous green for all equipment grounding conductors, except that wire sizes No. 4 AWG [25 mm²] and larger shall be identified per NEC.

B.

Bonding conductors shall be ASTM B8 bare stranded copper, except that sizes No. 10 AWG [6 mm²] and smaller shall be ASTM B1 solid bare copper wire.

C.

Conductor sizes shall not be less than shown on the drawings, or not less than required by the NEC, whichever is greater.

D.

Isolated Power System: Type XHHW-2 insulation with a dielectric constant of 3.5 or less.

2.2 GROUND RODS

A.

Steel or copper clad steel, 0.75 in [19 mm] diameter by 10 ft [30 M] long, conforming to UL 467.

B.

Quantity of rods shall be as required to obtain the specified ground resistance.

2.3 concrete encased electrode

Concrete encased electrode shall be No. 4 AWG bare copper wire, installed per NEC.

2.4 MEDIUM VOLTAGE SPLICES AND TERMINATIONS

Components shall meet or exceed UL 467 and be clearly marked with the manufacturer, catalog number, and permitted conductor size(s).

2.5 ground connections

A.

Below Grade: Exothermic-welded type connectors.

B.

Above Grade:

1.

Bonding Jumpers: Compression-type connectors, using zinc-plated fasteners and external tooth lockwashers.

2.

Connection to Building Steel: Exothermic-welded type connectors.

3.

Ground Busbars: Two-hole compression type lugs, using tin-plated copper or copper alloy bolts and nuts.

4.

Rack and Cabinet Ground Bars: One-hole compression-type lugs, using zinc-plated or copper alloy fasteners.

2.6 equipment rack and cabinet ground bars

Provide solid copper ground bars designed for mounting on the framework of open or cabinet-enclosed equipment racks with minimum dimensions of 0.375 in [4 mm] thick x 0.75 in [19 mm] wide.

2.7 ground terminal blocks

At any equipment mounting location (e.g., backboards and hinged cover enclosures) where rack-type ground bars cannot be mounted, provide screw lug-type terminal locks.

2.8 GROUNDING BUS

Pre-drilled rectangular copper bar with stand-off insulators, minimum 0.25 in [6.3 mm] thick x 4 in [100 mm] high in cross-section, length as shown on drawings, with 0.281 in [7.1 mm] holes spaced 1.125 in [28 mm] apart.

PART 3 ‑ EXECUTION

3.1 GENERAL

A.

Ground in accordance with the NEC, as shown on drawings, and as specified herein.

B.

System Grounding:

1.

Secondary service neutrals: Ground at the supply side of the secondary disconnecting means and at the related transformers.

2.

Separately derived systems (transformers downstream from the service entrance): Ground the secondary neutral.

3.2 INACCESSIBLE GROUNDING CONNECTIONS

Make grounding connections, which are normally buried or otherwise inaccessible (except connections for which access for periodic testing is required), by exothermic weld.

3.3 SECONDARY voltage EQUIPMENT AND CIRCUITS

A.

Main Bonding Jumper: Bond the secondary service neutral to the ground bus in the service equipment.

B.

Metallic Piping, Building Steel, and Supplemental Electrode(s):

1.

Provide a grounding electrode conductor sized per NEC between the service equipment ground bus and all metallic water pipe systems, building steel, and supplemental or made electrodes. Provide jumper insulating joints in the metallic piping. All connections to electrodes shall be made with fittings that conform to UL 467.

2.

Provide a supplemental ground electrode and bond to the grounding electrode system.

C.

Service Disconnect (Separate Individual Enclosure): Provide a ground bar bolted to the enclosure with lugs for connecting the various grounding conductors.

D.

Switchgear, Switchboards, Unit Substations, Panelboards, Motor Control Centers and Panelboards, Engine-Generators, and Automatic Transfer Switches:

1.

Connect the various feeder equipment grounding conductors to the ground bus in the enclosure with suitable pressure connectors.

2.

For service entrance equipment, connect the grounding electrode conductor to the ground bus.

3.

Provide ground bars, bolted to the housing, with sufficient lugs to terminate the equipment grounding conductors.

4.

Connect metallic conduits that terminate without mechanical connection to the housing, by grounding bushings and grounding conductor to the equipment ground bus.

3.4 raceway

A.

Conduit Systems:

1.

Ground all metallic conduit systems. All metallic conduit systems shall contain an equipment grounding conductor.

2.

Non‑metallic conduit systems, except non-metallic feeder conduits that carry a grounded conductor from exterior transformers to interior or building-mounted service entrance equipment, shall contain an equipment grounding conductor.

3.

Conduit that only contains a grounding conductor, and is provided for its mechanical protection, shall be bonded to that conductor at the entrance and exit from the conduit.

4.

Metallic conduits which terminate without mechanical connection to an electrical equipment housing by means of locknut and bushings or adapters, shall be provided with grounding bushings. Connect bushings with a bare grounding conductor to the equipment ground bus.

B.

Feeders and Branch Circuits: Install equipment grounding conductors with all feeders and power and lighting branch circuits.

C.

Boxes, Cabinets, Enclosures, and Panelboards:

1.

Bond the equipment grounding conductor to each pullbox, junction box, outlet box, device box, cabinets, and other enclosures through which the conductor passes (except for special grounding systems for intensive care units and other critical units shown).

2.

Provide lugs in each box and enclosure for equipment grounding conductor termination.

D.

Wireway Systems:

1.

Bond the metallic structures of wireway to provide 100% electrical continuity throughout the wireway system, by connecting a No. 6 AWG [16 mm²] bonding jumper at all intermediate metallic enclosures and across all section junctions.

2.

Install insulated No. 6 AWG [16 mm²] bonding jumpers between the wireway system, bonded as required above, and the closest building ground at each end and approximately every 50 ft [16 M].

3.

Use insulated No. 6 AWG [16 mm²] bonding jumpers to ground or bond metallic wireway at each end for all intermediate metallic enclosures and across all section junctions.

4.

Use insulated No. 6 AWG [16 mm²] bonding jumpers to ground cable tray to column-mounted building ground plates (pads) at each end and approximately every 49 ft [15 M].

E.

Receptacles shall not be grounded through their mounting screws. Ground receptacles with a jumper from the receptacle green ground terminal to the device box ground screw and a jumper to the branch circuit equipment grounding conductor.

F.

Ground lighting fixtures to the equipment grounding conductor of the wiring system when the green ground is provided; otherwise, ground the fixtures through the conduit systems. Fixtures connected with flexible conduit shall have a green ground wire included with the power wires from the fixture through the flexible conduit to the first outlet box.

G.

Fixed electrical appliances and equipment shall be provided with a ground lug for termination of the equipment grounding conductor.

F.

Panelboard Bonding in Patient Care Areas: The equipment grounding terminal buses of the normal and essential branch circuit panel boards serving the same individual patient vicinity shall be bonded together with an insulated continuous copper conductor not less than No. 10 AWG [16 mm²]. These conductors shall be installed in rigid metal conduit.

3.5 corrosion inhibitors

When making ground and ground bonding connections, apply a corrosion inhibitor to all contact surfaces. Use corrosion inhibitor appropriate for protecting a connection between the metals used.

3.6 CONDUCTIVE PIPING

A.

Bond all conductive piping systems, interior and exterior, to the grounding electrode system. Bonding connections shall be made as close as practical to the equipment ground bus.

B.

In operating rooms and at intensive care and coronary care type beds, bond the gases and suction piping at the outlets directly to the room or patient ground bus.

3.7 electrical room grounding

Building Earth Ground Busbars: Provide ground busbar and mounting hardware at each electrical room and connect to pigtail extensions of the building grounding ring.

3.8 ground resistance

A.

Grounding system resistance to ground shall not exceed 5 ohms. Make any modifications or additions to the grounding electrode system necessary for compliance without additional cost to the Government. Final tests shall ensure that this requirement is met.

B.

Resistance of the grounding electrode system shall be measured using a four-terminal fall-of-potential method as defined in IEEE 81. Ground resistance measurements shall be made before the electrical distribution system is energized and shall be made in normally dry conditions not fewer than 48 hours after the last rainfall. Resistance measurements of separate grounding electrode systems shall be made before the systems are bonded together below grade. The combined resistance of separate systems may be used to meet the required resistance, but the specified number of electrodes must still be provided.

C.

Services at power company interface points shall comply with the power company ground resistance requirements.

D.

Below-grade connections shall be visually inspected by the COTR prior to backfilling. The contractor shall notify the COTR 24 hours before the connections are ready for inspection.

3.9 GROUND ROD INSTALLATION

A.

For outdoor installations, drive each rod vertically in the earth, until top of rod is 24 in [609 mm] below final grade.

B.

For indoor installations, leave 4 in [100 mm] of rod exposed.

C.

Where permanently concealed ground connections are required, make the connections by the exothermic process, to form solid metal joints. Make accessible ground connections with mechanical pressure-type ground connectors.

D.

Where rock prevents the driving of vertical ground rods, install angled ground rods or grounding electrodes in horizontal trenches to achieve the specified resistance.

‑ ‑ ‑ E N D ‑ ‑ ‑