This document outlines requirements for a federal contract opportunity for heat exchanger and hot water heater replacement services at the Central Texas VA Medical Center in Temple, Texas. The contractor shall remove and replace blown tube bundles on multiple heat exchangers in various buildings, relocate and install new larger capacity heat exchangers, replace tube bundles, install a new heat exchanger, and replace two hot water heaters converting them from pneumatic to electronic control. All work must be completed within 60 calendar days of the notice to proceed and ensure all equipment is fully tested and functional upon completion. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17.

36C25720Q0070 0001 Copy of Equipment Information.pdf

View the file

Other files

File Type Posted
36C25720Q0070-0002004.pdf PDF
36C25720Q0070-0002003.docx DOCX document
36C25720Q0070-0001009.pdf PDF
36C25720Q0070-0001008.docx DOCX document
36C25720Q0070-001.pdf PDF
36C25720Q0070-002.pdf PDF
36C25720Q0070-000.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bldg. location Exchanger# Make #SN BTU Equipment part number Heat Exchanger 163 BC150 1 TACO 446653 E10212-S4A1AT00 Heat Exchanger 163 BA229 1 TACO 391277 E08206-84A1AT00 Heat Exchanger 163 Penthouse 1 TACO B3611 G10212-S4A1AT00 Heat Exchanger 163 Penthouse 2 TACO S12156 G10206-TS4A1AT00

Heat Exchanger 163 1D127 Design: 80 GPM / 140F-180F / 30 psig steam plate & frame HX system.

• 2.5” control valve with electronic actuator

• Compound pressure gauge on steam inlet

• TS6M plate/frame HX with 316SS plates / EPDM gaskets, ASME rated for 150psig

• 3” SS waterside piping with EL2270 RTD

• APT14 pump trap with closed non-code reservoir, gauge glass, pre-piped motive / exhaust with motive drip trap and TSS300 air vent assy.

• Fully assembled with carbon steel frame, industrial paint, hydrostatic test

Heat Exchanger 202 1E176 1 Bell & Gossett 198166-01-1 BY526010096002 Heat Exchanger 202 1E176 2 Bell & Gossett 198166-01-2 BY526010096002

Bldg. location Water Heater# Make/Mod #SN STYLE Water heater 205 Mech Room 1 Airco/B+14 H-2-209 110311 Water heater 205 Mech Room 2 Airco/B+14 H-02-210