36C25518R0074-00001006.pdf

PDF 2 MB Posted

Attached to
Expand Parking Garage Project 589-401
Solicitation number
36C25518R0074
Issued by

About this file

36C25518R0074 00001 No 589-401 Drawings Vol 3.pdf

View the file

Other files

File Type Posted
36C25518R0074-00004000.docx DOCX document
36C25518R0074-00003001.pdf PDF
36C25518R0074-00003000.docx DOCX document
36C25518R0074-00002000.docx DOCX document
36C25518R0074-00002001.pdf PDF
36C25518R0074-00002002.pdf PDF
36C25518R0074-00001011.pdf PDF
36C25518R0074-00001013.pdf PDF
36C25518R0074-00001008.pdf PDF
36C25518R0074-00001009.pdf PDF
36C25518R0074-00001014.pdf PDF
36C25518R0074-00001000.docx DOCX document
36C25518R0074-00001010.pdf PDF
36C25518R0074-00001007.pdf PDF
36C25518R0074-00001003.pdf PDF
36C25518R0074-00001002.pdf PDF
36C25518R0074-00001012.pdf PDF
36C25518R0074-00001001.pdf PDF
36C25518R0074-00001005.pdf PDF
36C25518R0074-00001004.pdf PDF
36C25518R0074-009.pdf PDF
36C25518R0074-006.pdf PDF
36C25518R0074-002.docx DOCX document
36C25518R0074-004.pdf PDF
36C25518R0074-005.pdf PDF
36C25518R0074-008.pdf PDF
36C25518R0074-007.pdf PDF
36C25518R0074-003.pdf PDF
36C25518R0074-001.docx DOCX document
36C25518R0074-000.docx DOCX document
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FD FD FD FD

FD FD FD

C

D

E

F

G

H

1.1 2 3 4 5 6 7 8 9 10 10.9 11

F.4

1'-0" 12'-3" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 12'-3" 1'-0"

314'-6"

STAIR C STAIR D

F3

S-401

F3

S-402

CONTROL JOINTS,

TYPICAL, SEE D7

AND F7/S-510

5" CONCRETE SLAB ON GRADE,

TYPICAL. SEE NOTE 7

SNOW DUMP

AREA

SNOW DUMP

AREA

SEE NOTE 14

3'-6" 9'-4"

ELECTRICAL

ROOM

F1

S-101

SEE NOTE 15

SEE NOTE 15

727'-0"

727'-0"

726'-9

724'-8"

3'

-5

723'-3"

723'-3" 722'-8 " 723'-8"

3' -3

724'-3"

6' -4

725'-1 0 1

/2

5'

-7

726'-1"

726'-9 " 726'-9"

726'-9"

726'-9"

726'-9" 72 6' -9

728'-8" 728'-8

3'-1

0" 724'-2 1/2" 72

4' -7

727'-0"

6' -8

"726'-8"

727'-0"

730'-6

727'-0

726'-9

726'-9"

727'-0 " 727'-0"

'-9

727'-0"

726'-9

727'-0

726'-9

727'-0

727'-0"

730'-6"

ETW

ETW

GRID 3 TO 8

730'-6"

ETW

730'-6"

ETW

732'-5"

ETW

732'-5"

ETW

730'-9"

16'-0"

RAILING, SEE

ARCHITECTURAL

DRAWINGS

5" CONCRETE SLAB ON

GRADE, TYPICAL. SEE

NOTE 7

7'-0" 5'-0"

EDGE OF CONCRETE SLAB

F3

S-510

LINE G

TYP

AT COLUMN

COVERS TYP

A5

S-510

PROVIDE (2)

3/4"ø COIL

RODS FROM

COLUMN INTO

GRADE SLAB

WITH

HORIZONTAL

SLOTTED

INSERTS

EDGE OF

PHASE I SLAB

A5

S-510EDGE OF

PHASE I SLAB

F5

S-101

BOLLARD,

SEE C5/S-510

TYP

FLOOR DRAIN,

SEE D5/S-510 TYP

F5

S-510

TYP AT

COLUMNS

7' -0

730'-6"

730'-6"

730'-6"

ETW

ETW

ETW

728'-10"

ETW

NOTE 16

NOTE 16

726'-8

726'-8" 726'-8

729'-5"

ETW

733'-9"

ETW

729'-5"

ETW

BOLLARD, SEE B3/S-510

NOTE 16

NOTE 16

726'-3

726'-3

C7

S-510

727'-9"

SEE CIVIL FOR GRADE SLAB

SOUTH OF LINE G

E Q

E Q

E Q

E

Q EQ EQ EQ

1. REFER TO SHEET S-001 FOR GENERAL NOTES.

2. REFER TO DETAIL E7/S-101 FOR PLAN ELEVATION KEY.

3. REFER TO CIVIL DRAWINGS FOR EXTERIOR GRADE

ELEVATIONS.

4. REFER TO ARCHITECTURAL DRAWINGS FOR ENTRY /

EXIT PLANS.

5. REFER TO "S-400" SERIES AND ARCHITECTURAL

DRAWINGS FOR STAIR AND STAIR / ELEVATOR PLANS,

ELEVATIONS, STAIR DETAILS, AND SECTIONS.

6. REFER TO PLUMBING DRAWINGS FOR FLOOR DRAIN

LOCATIONS AND DETAILS.

7. CONCRETE INTERIOR SLAB ON GRADE SHALL BE 5"

THICK, UNDERLAIN BY 6" MINIMUM LAYER OF FREE

DRAINING BASE COURSE AND REINFORCED WITH #3 @

18" ON CENTER EACH WAY PLACED 2" CLEAR FROM TOP

OF SLAB. ALSO SEE GENERAL NOTE III.C.7 ON SHEET S-

001. GEOTECH SUPPLEMENTAL REPORT STATES TO

REMOVE 4 FEET OF EXISTING FILL BELOW FINISHED

GRADE AND REPLACE WITH ENGINEERED FILL. REFER

TO THE GEOTECHNICAL REPORT FOR ADDITIONAL

INFORMATION REGARDING SUBGRADE PREPARATION.

PROVIDE 1/2" JOINT FILLER AT GRADE SLAB AROUND

COLUMNS, TYPICAL. SEE F5/S-510.

8. USE STRAIGHT LINE INTERPOLATION FOR FLOOR

ELEVATION BETWEEN THOSE INDICATED.

9. PROVIDE CONSTRUCTION OR CONTROL JOINTS IN CIP

WALLS PER DETAIL A3/S-501 AND DETAIL B3/S-501 TO

MATCH JOINT IN SLAB ON GRADE.

10. PROVIDE CORNER REINFORCEMENT FOR CIP WALLS

PER DETAIL C3/S-501 AND DETAIL D3/S-501 AS

REQUIRED.

11. INDICATES PLAN MATCH LINE.

12. SEE SHEET S-321 FOR SHEAR WALL DETAILS.

13. REFER TO SHEET S-501 AND SHEET S-510 FOR TYPICAL

DETAILS.

14. GRADE SLAB IN ELECTRICAL ROOMS TO BE UNDERLAIN

BY 2" THICK LAYER OF SAND OVER A VAPOR RETARDER.

SEE SPECIFICATION 03 30 00.

15. GRADE SLAB IN SNOW DUMP AREAS TO BE 8" THICK AND

REINFORCED WITH #4 @ 6" OC PLACE AT MID-DEPTH.

USE FIBER-REINFORCED CONCRETE IN THESE AREAS

(MINIMUM DOSAGE FIBRILLATED POLY PROPYLENE

FIBERS PER SPECIFICATIONS)

16. FLOOR ELEVATIONS ALONG D ARE INTENDED TO MATCH

EXISTING FLOOR ELEVATIONS OF EXISTING GARAGE

ALONG LINE C. VERIFY IN FIELD.

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-111

BID ITEM 4, 5 AND 6 (DEDUCT) LEVEL P1 PLAN

EXPAND PARKING GARAGE 589-401

RES MAP

1/16" = 1'-0"F3

LEVEL P1 PLAN

(BID ITEM 4, 5 AND 6)

GENERAL SHEET NOTES

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO

VERIFY THAT THERE IS A MINIMUM OF HEADROOM

BETWEEN ALL DRIVING SURFACES AND OVERHEAD

BEAMS PRIOR TO PLACING CONCRETE.

8'-4"

N

S

W

E

BID ITEM 4 (DEDUCT) ISOMETRIC

BID ITEM 5 (DEDUCT) ISOMETRIC

BID ITEM 6 (DEDUCT) ISOMETRIC

C

D

E

F

G

H

1.1 2 3 4 5 6 7 8 9 10 10.9 11

F.4

1'-0" 12'-3" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 12'-3" 1'-0"

314'-6"

STAIR C STAIR D

F6

S-524

SEE NOTE 2

741'-9" 741'-9

741'-8"

0' -1

0"

741'-3"

0' -1

0"

741'-3"

0' -1

0" 741'-3"

0' -1

0"

741'-8

741'-9 "741'-9"

741'-8"

741'-8"

741'-8"

741'-8"

741'-8"

741'-8"

741'-8"

741'-8"

1'

-8

1' -8

1' -6

/2

741'-8"

741'-6 1/2"

1'

-5 " 740'-10" 74

1' -3

740'-10" 7 '-3

'-1

0" 74 1' -3

740'-10"

741'-5"

TYP

F8

S-524

AT

COLUMNS

F1

S-524

B1

S-524

F3

S-524

F5

S-401

F5

S-402

1. SEE SHEET S-103 FOR TYPICAL SHEET NOTES AND

LOCATIONS OF TYPICAL DETAIL REFERENCES (UNLESS

NOTED).

2. TRAFFIC TOPPING OVER ROOM. EXTEND 2'-0" PAST FACE

OF WALLS BELOW. SEE DETAILS B1 AND B3/S-502 FOR

TERMINATION DETAILS. CONCRETE FINISH AT TRAFFIC

TOPPING AREAS SHALL BE AS REQUIRED BY TRAFFIC

TOPPING INSTALLER.

3. RECESSED BOXES ANTICIPATED IN PRECAST CONCRETE

FOR EXTERIOR SCONCES ALONG LINE H. SEE ELECTRICAL

DRAWINGS.

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-112

BID ITEM 4, 5 AND 6 (DEDUCT) LEVEL P2 PLAN

EXPAND PARKING GARAGE 589-401

RES MAP

1/16" = 1'-0"F3

LEVEL P2 PLAN

(BID ITEM 4, 5 AND 6)

GENERAL SHEET NOTES

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO

VERIFY THAT THERE IS A MINIMUM OF HEADROOM

BETWEEN ALL DRIVING SURFACES AND OVERHEAD

BEAMS PRIOR TO PLACING CONCRETE.

8'-4"

N

S

W

E

BID ITEM 4 (DEDUCT) ISOMETRIC

BID ITEM 6 (DEDUCT) ISOMETRIC

C

D

E

F

G

H

1.1 2 3 4 5 6 7 8 9 10 10.9 11

F.4

1'-0" 12'-3" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 12'-3" 1'-0"

314'-6"

STAIR C STAIR D

F5

S-401

B3

S-522

B3

S-522

B5

S-522

F5

S-402

B3

S-522

B3

S-522

B5

S-522F1

S-522

1 TO 5

F1

S-522

6 TO 11

E5

S-522

F5

S-522

C2

S-551

F5

S-551

O.H.

F7

S-551

F5

S-551

3 TO 9

753'-5" 753'-5"

753'-4"

2' -6

752'-11"

2'

-6

752'-11"

2'

-6

752'-11"

2'

-6

753'-5" 753'-5

'-4

3' -4

753'-4"

753'-4"

753'-4"

753'-4"

753'-4"

753'-4"

753'-4"

753'-4"

753'-4"

3'

-4

3'

-2

/2

'-1

" 7 '-6

" 7 '-1

1" 7 2'-6" 75

2' -1

1" 752'-6" 75 2'

-1 1" 7

'-6

753'-1"

753'-2 1/2"

SEE B1/S-521 AT FLOOR DRAINS

AND D7/S-523 AT RISERS, TYP

F1

S-411

BID ITEM 5

(DEDUCT)

ONLY

F6

S-524

TYP

F8

S-524

AT COLUMNS

BID ITEM 3

AND 4

(DEDUCT)

F1

S-524

B1

S-524

F3

S-524

D1

S-524

AT COLUMNS

BID ITEM 5

AND 6

(DEDUCT)

E3

S-522

AT

COLUMNS

ELEVATION TOP OF P/C

TEE = 752'-6" + 11" TOPPING

ELEVATION TOP OF P/C

TEE = 752'-3" + 4" TOPPING

ELEVATION TOP OF P/C TEE

= 752'-6" + 11" TOPPING

ELEVATION TOP OF P/C

TEE = 752'-3" + 4" TOPPING

NOTE 18 NOTE 18

NOTE 18NOTE 18

F4

S-321

BID ITEM 6

(DEDUCT)

ONLY

TYP

F7

S-401

BID ITEM 3 AND 4

(DEDUCT)

BID ITEM 5 AND 6

(DEDUCT)

F7

S-402

BID ITEM 5 AND

6 (DEDUCT)

BID ITEM 3 AND

4 (DEDUCT)

(5) #5 x CONT

(5) #5 x CONT

(5) #5 x CONT

(5) #5 x CONT

(5) #5 x 28'-0"

(5) #5 x 16'-0"

(5) #5 x CONT

(5) #5 x CONT

(5) #5 x 28'-0"

(5) #5 x 16'-0"

(3) #5 x CONT

(3) #5 x CONT

(3) #5 x 14'-0"

NOTE 14

PROVIDE TYPE II THREADED

MECHANICAL REBAR SPLICE AT

ENDS OF (5) #5 CHORD STEEL

FOR FUTURE EXTENSION

PROVIDE TYPE II THREADED

MECHANICAL REBAR SPLICE AT

ENDS OF (5) #5 CHORD STEEL

FOR FUTURE EXTENSION

ELEVATION TOP OF P/C

TEE = 753'-1" + 4" TOPPING

ELEVATION TOP OF P/C

TEE = 753'-1" + 4"

TOPPING

NOTE 14

F8

S-523

BID ITEM 5 AND 6

(DEDUCT) ONLY

F8

S-523

BID ITEM 5 AND

6 (DEDUCT)

ONLY

NOTE 19 NOTE 19

NOTE 19

NOTE 19

F3

S-522

E7

S-522

E7

S-551

E7

S-551 F3

S-522

E7

S-522

B7

S-522

B7

S-522

F7

S-522

F7

S-522

O.H.

NOTE 20

1. REFER TO SHEET S-001 FOR GENERAL NOTES.

2. REFER TO DETAIL B6/S-101 FOR PLAN ELEVATION KEY.

3. REFER TO DETAIL B6/S-102 FOR TYPICAL BAY PLAN.

4. REFER TO PLUMBING DRAWINGS FOR FLOOR DRAIN

LOCATIONS AND DETAILS.

5. REFER TO SHEET S-551 FOR COLUMN DETAILS.

6. REFER TO SHEET S-520 FOR BEAM DETAILS.

7. REFER TO SHEET S-521 FOR TEE DETAILS.

8. NOT USED

9. REFER TO "S-400" SERIES AND ARCHITECTURAL

DRAWINGS FOR STAIR AND STAIR / ELEVATOR PLANS,

ELEVATIONS, DETAILS, AND SECTIONS.

10. REFER TO ELECTRICAL DRAWINGS FOR LIGHT FIXTURE

LOCATIONS AND INFORMATION.

11. REFER TO THIS SHEET FOR TYPICAL DETAIL

REFERENCES.

12. ALL COLUMNS ARE CENTERED ON GRID LINES, UNLESS

NOTED.

13. USE STRAIGHT LINE INTERPOLATION FOR FLOOR

ELEVATION BETWEEN THOSE INDICATED.

14. FOR BID ITEM 6 (DEDUCT), PROVIDE PLATES IN TOP OF

WALL FOR FUTURE VERTICAL EXPANSION OF SHEAR

WALL SIMILAR TO DETAIL F3/S-524. PROVIDE NMB SPLICE

SLEEVES AT PILASTER AND ENDS OF SHEAR WALL

SIMILAR TO D3/S-524.

15. REFER TO SHEET S-321 FOR LIGHT WALL AND SHEAR

WALL DETAILS.

16. INDICATES PLAN MATCH LINE..

17. SEE DETAIL F3/S-502, B7/S-502, AND F7/S-502 FOR

TYPICAL SEALANT REQUIREMENTS.

18. FLOOR ELEVATIONS SHOWN ALONG LINE D ARE MEANT

TO MATCH EXISTING FLOOR ELEVATIONS OF EXISTING

GARAGE ALONG LINE C. THESE REPRESENT THE TOP OF

A 1" WASH FOR THE EXISTING GARAGE. SEE DETAIL F7/S-

522 FOR CLARIFICATION. VERIFY EXISTING ELEVATIONS

IN FIELD.

19. PROVIDE CLOSURE PLATES AND ATTACH TO COLUMNS

C/3 AND C/9 SIMILAR TO B3/S-412. PROVIDE 12" WIDE x 3'-5" TALL x 1/4" THICK FLAT PLATE AND ATTACH TO

COLUMNS C/1 AND C/11. SEE B3/S-412 FOR REMAINING

INFORMATION.

20. PRECAST DESIGNER TO DESIGN ROOF TEES FOR RAIN

LOAD ASSUMING FLOOR DRAIN IS PLUGGED AND WATER

PONDS IN NEARBY VICINITY TO A HEIGHT EQUAL TO THE

HIGH POINT SEPARATING THE PLUGGED DRAIN FROM

THE NEXT DRAIN OVER.

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-113

BID ITEM 3, 4, 5 AND 6 (DEDUCT) LEVEL P3

PLAN

EXPAND PARKING GARAGE 589-401

RES MAP

1/16" = 1'-0"F3

LEVEL P3 PLAN

(BID ITEM 3, 4, 5 AND 6)

GENERAL SHEET NOTES

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO

VERIFY THAT THERE IS A MINIMUM OF HEADROOM

BETWEEN ALL DRIVING SURFACES AND OVERHEAD

BEAMS PRIOR TO PLACING CONCRETE.

8'-4"

N

S

W

E

BID ITEM 4 (DEDUCT) ISOMETRIC

BID ITEM 3 (DEDUCT) ISOMETRIC

BID ITEM 6 (DEDUCT) ISOMETRICBID ITEM 5 (DEDUCT) ISOMETRIC

C

D

E

F

G

H

1.1 2 3 4 5 6 7 8 9 10 10.9 11

F.4

1'-0" 12'-3" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 12'-3" 1'-0"

314'-6"

STAIR C STAIR D

765'-1" 765'-1"

765'-0" 76 4' -2

764'-7"

4'

-2 " 764'-7" 76

4' -2

" 764'-7"

4'

-2

765'-1" 765'-1

765'-0

5' -0

765'-0"

764'-10 1/2"

765'-0"

765'-0"

765'-0"

765'-0"

765'-0"

765'-0"

765'-0"

765'-0"

5' -0

4'

-1

1/ 2"

4' -9

4'-2" 7

'-7

" 764'-2" 7 '-7

764'-2" 7 '-7

" 7 4'-2"

764'-9"

F8

S-523

F6

S-524

TYP

D6

S-524

AT

COLUMNS

F1

S-524

B1

S-524

F3

S-524

F7

S-401

F7

S-402

F8

S-523

(4) #6 x 30'-0"

(4) #6 x 16'-0"

(4) #6 x CONT

(4) #6 x CONT

(4) #6 x CONT

(4) #6 x CONT

(4) #6 x CONT

(4) #6 x CONT

(4) #6 x 30'-0"

(4) #6 x 16'-0"

(3) #5 x CONT

(3) #5 x CONT

(3) #5 x 14'-0"

(3) #5 x 14'-0"

PROVIDE TYPE II THREADED

MECHANICAL REBAR SPLICE AT

ENDS OF (4) #6 CHORD STEEL

FOR FUTURE EXTENSION

PROVIDE TYPE II THREADED

MECHANICAL REBAR SPLICE AT

ENDS OF (4) #6 CHORD STEEL

FOR FUTURE EXTENSION

SEE NOTE 20

ON SHEET S-113

1. SEE SHEET S-103 FOR TYPICAL SHEET NOTES AND

LOCATIONS OF TYPICAL DETAIL REFERENCES (UNLESS

NOTED).

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-114

BID ITEM 2, 3 AND 4 (DEDUCT) LEVEL P4 PLAN

EXPAND PARKING GARAGE 589-401

RES MAP

1/16" = 1'-0"F3

LEVEL P4 PLAN

(BID ITEM 2, 3 AND 4)

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO

VERIFY THAT THERE IS A MINIMUM OF HEADROOM

BETWEEN ALL DRIVING SURFACES AND OVERHEAD

BEAMS PRIOR TO PLACING CONCRETE.

8'-4"

GENERAL SHEET NOTES

N

S

W

E

BID ITEM 2 (DEDUCT) ISOMETRIC

BID ITEM 3 (DEDUCT) ISOMETRIC

BID ITEM 4 (DEDUCT) ISOMETRIC

C

D

E

F

G

H

1.1 2 3 4 5 6 7 8 9 10 10.9 11

F.4

1'-0" 12'-3" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 12'-3" 1'-0"

314'-6"

STAIR C STAIR D

765'-1" 765'-1"

765'-0" 76 4' -2

764'-7"

4'

-2 " 764'-7" 76

4' -2

" 764'-7"

4'

-2

765'-1" 765'-1

765'-0

5' -0

'-0

'-0

'-0

'-0

5'

-0

5'

-0

'-0

" 765'-0"

F8

S-523

F1

S-411

F6

S-524

TYP

D6

S-524

AT

COLUMNS

F1

S-524

B1

S-524

F3

S-524

F1

S-401

F1

S-402

(4) #6 x CONT

(4) #6 x CONT

(4) #6 x CONT

(4) #6 x CONT

(3) #5 x CONT

(3) #5 x CONT

(3) #5 x 14'-0"

(3) #5 x 14'-0"

PROVIDE TYPE II THREADED

MECHANICAL REBAR SPLICE AT

ENDS OF (4) #6 CHORD STEEL

FOR FUTURE EXTENSION

PROVIDE TYPE II THREADED

MECHANICAL REBAR SPLICE AT

ENDS OF (4) #6 CHORD STEEL

FOR FUTURE EXTENSION

NOTE 3

NOTE 2

NOTE 3

NOTE 2

SEE NOTE 20

ON SHEET S-113

1. SEE SHEET S-103 FOR TYPICAL SHEET NOTES AND

LOCATIONS OF TYPICAL DETAIL REFERENCES (UNLESS

NOTED).

2. PROVIDE EMBED PLATES ON FACE OF SHEAR WALL FOR

FUTURE CONNECTIONS TO TOPPING SLAB SIMILAR TO

DETAIL B5/S-522. PAINT TO MATCH COLOR OF

CONCRETE.

3. PROVIDE EMBED PLATES FOR FUTURE SPANDREL PANEL

PER DETAIL F5/S-551. PAINT TO MATCH COLOR OF

CONCRETE.

LEVEL P2

EL 741'-8"

LEVEL P3

EL 753'-4"

LEVEL P4

EL 765'-0"

LEVEL P1

EL VARIES

ENTRY/EXIT

ENTRY/EXIT

DASHED LINE REPRESENTS

PHASE I STRUCTURE

EXIT

ENTRY

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-115

BID ITEM 5 (DEDUCT) LEVEL P4 PLAN

EXPAND PARKING GARAGE 589-401

RES MAP

0 8' 16' 32'

1/16" = 1'-0"

1/16" = 1'-0"F3

LEVEL P4 PLAN (BID ITEM 5)

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO

VERIFY THAT THERE IS A MINIMUM OF HEADROOM

BETWEEN ALL DRIVING SURFACES AND OVERHEAD

BEAMS PRIOR TO PLACING CONCRETE.

8'-4"

N

S

W

E

GENERAL SHEET NOTES

EL

LEVEL P1

730' - 0"

EL

LEVEL P2

741' - 8"

EL

FOUNDATION

726' - 6"

EL

LEVEL P3

753' - 4"

EL

LEVEL P4

765' - 0"

1 1.1 2 3 4 5 6 7 8 9 10 10.9 11

1'-0" 12'-3" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 36'-0" 12'-3" 1'-0"

314'-6"

VARIES

VARIES

SHEARWALLP/C IT BEAM,

TYPICAL

LIGHT POLE,

TYPICAL

P/C DOUBLE TEE,

TYPICAL

GRADE BEAM,

TYPICAL

DRILLED PIER ,

TYPICAL

DRILLED PIER CAP ,

TYPICAL

SNOW DUMP

AREA

P/C COLUMN,

TYPICAL

SEE D8/S-523 AT BASE OF

LIGHT POLES, TYPICAL

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-301

LONGITUDINAL BUILDING SECTION

EXPAND PARKING GARAGE 589-401

RES MAP

1/16" = 1'-0"F4

LONGITUDINAL BUILDING SECTION

30'-0"

S-511

F6

S-321

F7

P/C HAUNCH

24" x 24" SHEAR WALL

PILASTER

GRID

LEVEL P2

LEVEL P3

LEVEL P4

T.O. SHEAR WALL

ELEVATION 768'-9"

T.O. FOUNDATION

SEE FOUNDATION PLAN

SIMILARTYPICAL

AT EACH END

QUAKE

Fx = 21k

QUAKE

Fx = 157k

QUAKE

Fx = 116k

QUAKE

Fx = 74k

FUTURE PV SYSTEM

38'-0"

S-511

F6

S-321

F7

S-321

F4

S-524

F3

24" x 24" SHEAR WALL

PILASTER

P/C HAUNCH

LINE F, BID ITEMS 5 AND 6 ONLY

LINE G, TYP (EXCEPT BID ITEM 1)

LINE F, TYP (EXCEPT BID ITEMS 5 AND 6)

LINE G, BID ITEM 1 ONLYGRID

LEVEL P2

LEVEL P3

LEVEL P4

T.O. FOUNDATION

SEE FOUNDATION PLAN

SIMILARTYPICAL

AT EACH END

QUAKE

Fx = 26k

QUAKE

Fx = 194k

QUAKE

Fx = 141k

QUAKE

Fx = 89k

FUTURE PV SYSTEM

SIMILAR

1'-0"

SHEAR

WALL

4" 4"

P R

O J E

C T

IO

N

E M

B E

D M

E N

T L

E N

G T

H

T O

D E

V E

L O

P B

A R

S

T.O. FOUNDATION

SEE FOUNDATION PLAN

GROUT AFTER CONNECTION

IS COMPLETE WITH

NON-SHRINK NON-STAIN

GROUT

MORTAR GROUT BY

PRECASTER

NMB SLEEVES

REINFORCING WITH

STANDARD HOOK

CORRUGATED SLEEVE

AROUND BARS TO ALLOW

ALIGNMENT AT ERECTION,

GROUT SOLID AFTER

ALIGNMENT

TYPICAL AT EACH

END OF SHEAR WALL

PLAN

SECTION

NOTES:

1. CONNECTION BY PRECASTER. SEE NOTE 3.

6"6"

3'-6" WASH 3'-6" WASH

ETS

SEE PLAN

G

F

HAUNCH, TYPICAL

CHORD STEEL. SEE PLAN

AND DETAIL C1/S-521

BEARING PLATE AND

PAD, TYPICAL

SEE TOPPING

DETAIL C1/S-521

CIP TOPPING

P/C SHEARWALL

TOOLED JOINT WITH SEALANT

CONTINUOUS ETHAFOAM

CONCRETE DAM AS REQUIRED

P/C TEE

CONNECTION PERFORMANCE

DESIGN BY PRECASTER BASED

ON ANTICIPATED HORIZONTAL

LOADS SHOWN ON DETAIL

D4/S-321

#5x7'-0"@ 12" OC

#4 U-BAR WITH 2'-0"

LEGS @ 12" OC

AT BID ITEM 6, LINE F, PROVIDE

EMBED PLATES FOR FUTURE

VERT EXPANSION OF SHEAR

WALL. ASSUME LOADS FROM

FULL BASE BID STRUCTURE

TYP (EXCEPT BID ITEMS 5 AND 6)

BID ITEM 1 ONLY

xxxxx x x x x x

SW1. REFER TO SHEET S-001 FOR GENERAL NOTES.

SW2. SHEAR WALL DESIGN IS PERFORMANCE DESIGN

AND SHALL INCLUDE SIZE, NUMBER, AND LOCATION

` OF VERTICAL AND HORIZONTAL REINFORCING.

DESIGN SHALL ALSO INCLUDE BASE CONNECTIONS,

PIECE CONNECTIONS, HAUNCH OR LEDGE

REINFORCEMENT, AND SIZE, NUMBER, AND

SPACING OF INSERT/COIL ROD (OR OTHER SHEAR

TRANSFER) CONNECTIONS INTO CIP TOPPING FOR

SHEAR TRANSFER OF LATERAL LOADS. SEE

SPECIFICATION 03 41 00 FOR PRECAST CONCRETE.

SW3. FOR SHEAR WALL SIZES, SEE SHEAR WALL

ELEVATIONS THIS SHEET AND STRUCTURAL DETAILS.

SW4. FOR SHEAR WALL BASE CONNECTIONS SEE DETAILS

F6/S-511 AND F7/S-321.

SW5. FOR LATERAL LOADS DUE TO WIND AND SEISMIC,

SEE DETAIL D4 & D7/S-321. LOADS INDICATED

REPRESENT VERTICAL DISTRIBUTION OF FORCES

PER ASCE 7-10 (LOADS ARE REVERSIBLE).

SW6. FOR EMBEDDED PLATES TO RECEIVE WELDS AS

PART OF WELDED CONNECTIONS SEE DETAIL

B8/S523.

1. LATERAL SEISMIC LOADS SHOWN ON SHEAR WALL

ELEVATIONS ARE FACTORED LOADS. LOAD

COMBINATIONS SHALL FOLLOW ASCE 7-10, WHICH

INCLUDES THE VERTICAL COMPONENT Ev.

2. FOR DESIGN PURPOSES, LATERAL LOADS SHALL BE

CONSIDERED IN CONJUNCTION WITH ALL DEAD AND

LIVE LOADS.

3. WALL CONNECTIONS ARE PERFORMANCE DESIGN BY

PRECASTER AND SHALL COMPLY WITH ACI 318-11

SECTION 21.4 FOR INTERMEDIATE PRECAST

STRUCTURAL WALLS..

D7

SHEAR WALL PANEL ELEVATION

GENERAL SHEET NOTES

P/C SHEAR WALL NOTES

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-321

PRECAST SHEAR WALL

EXPAND PARKING GARAGE 589-401

RES MAP

1/8" = 1'-0"D4

SHEAR WALL PANEL ELEVATION

F7

SHEAR WALL BASE CONNECTION

DETAIL

F4

TOP OF SHEAR WALL DETAIL

1. REFER TO SHEET S-001 FOR GENERAL NOTES.

2. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL

DRAWINGS.

3. PRECAST STAIR/ELEVATOR TOWER CONSTRUCTION:

DESIGN IS PERFORMANCE DESIGN AND SHALL INCLUDE

TYPE, NUMBER, AND LOCATION OF REINFORCING FOR

ALL MEMBERS (WALLS, SLABS, ETC.). DESIGN SHALL

ALSO INCLUDE ALL MEMBER TO MEMBER AND BASE

CONNECTIONS. DESIGN SHALL ASSUME "BID ITEM 1"

TOWER IS FINAL FUTURE CONDITION. THE STAIRS

SHALL BE DESIGNED ACCORDING TO ALL THE

REQUIREMENTS IN IBC 2012, INCLUDING SUPPORTING

THEIR OWN WEIGHT PLUS A SUPERIMPOSED LIVE LOAD

EQUAL TO 100 psf. SEE SPEC SECTION 03 41 00 FOR

PRECAST CONCRETE.

4. ALL REFERENCES, DETAILS, REINFORCING, MEMBER

SIZES, CONNECTIONS, ETC. SHOWN ON C5/S-401 AND

F5/S-401 APPLY TO ALL SUPPORTED LEVELS UNLESS

NOTED OTHERWISE.

5. SEE ARCHITECTURAL DRAWINGS FOR MATERIAL

LEGEND.

6. FLOOR ELEVATION TOP OF CIP TOPPING AT MAIN

LANDING = 741'-6" AT LEVEL P2. ADD 11'-8" FOR EACH

FLOOR ABOVE.

G

1.1 2

F.4

2.1

1'-0" 12'-3" 4"

720'-6"

DP-5DPC-8

675'-0"

720'-6"

DPC-8 DP-5

675'-0" 720'-6"

DP-4DPC-7

675'-0"

720'-6"

DP-6DPC-6

675'-0"

GB-4

GB-4

COLUMN NOT PRESENT

FOR BID ITEMS 4, 5 AND 6.

PROVIDE ANCHOR BOLTS

(GALVANIZED) FOR FUTURE

COLUMNS. WRAP WITH

PLASTIC AND ENCASE IN

LEAN CONCRETE

B8

S-412

B8

S-412

B6

S-412

B8

S-412

720'-6"

GB-5GB-5

720'-6"

720'-6"

720'-6"

4" 4"

4" 4"

8"

CIP FOOTING FOR

BID ITEMS 4, 5

AND 6

1'-6"

10"

6"

C DP

AND CAP

L

C DPL

4"

C DP

AND CAP

L

C DP

AND CAP

L

C DP AND

CAP

L

4"

C DPL

C DP

AND CAP

L

C DP

AND CAP

L

G

1.1 2

F.4

2.1

1'-0" 12'-3" 4"

3'-11"

BOLLARDS, SEE

C5/S-510

D8

S-410

5" GRADE SLAB

SEE SHEET S-101

ETS = 723'-4"

10" P/C WALLS TYP

1" WASH

D3

S-412

G

1.1 2

F.4

2.1

1'-0" 12'-3" 4"

F1

S-403

F3

S-403

3'-11"

BOLLARDS, SEE

F7/S-523 TYP

4" 10" 10'-3" 10" 4" 1'-0"

EXPANSION JOINT,

SEE D1/S-502 AND

D3/S-502 TYP

D6

S-412

F6

S-412

D6

S-412

F5

S-410F1

S-410

E5

S-410

AT HORIZONTAL

JOINTS TYP

C5

S-410

AT CORNERS

TYP D3

S-410

AT SIDES OF

LANDING TYP

10" P/C WALLS

TYP

OUTLINE OF

LEDGE BELOW

OUTLINE OF

LEDGE BELOW

TURN EXPANSION

JOINT UP 6"

BETWEEN P/C

PIECES TYP

SEE B3/S-412 SIM FOR

CLOSURE PLATE

SEE B3/S-412 SIM FOR

CLOSURE PLATE

F8

S-410

SEE A5/S-523 AT

RAILINGS

G

1.1 2

F.4

2.1

1'-0" 12'-3" 4"

F1

S-403

F3

S-403

F6

S-411

F1

S-410

OUTLINE OF

LEDGE BELOW

OUTLINE OF

LEDGE BELOW

HOLD TOP OF

COLUMN BELOW

FLOOR LINE

HOLD TOP OF

COLUMN BELOW

FLOOR LINE

G

1.1 2

F.4

2.1

12'-3" 4"

D8

S-411

TYP ALL

AROUND

ROOF

4" 12'-4" 7"

1'-0"

FOR BID ITEMS 5 AND 6:

PROVIDE EMBED PLATES ALL

AROUND PERIMETER IN TOP OF

WALLS PER E5/S-410 FOR FUTURE

VERTICAL EXTENSION OF WALL.

DESIGN FOR FUTURE EXPANSION TO

MATCH STAIR TOWER SHOWN IN BID

ITEM 1 OF THESE DRAWINGS.

8" PRECAST SLAB.

FOR BID ITEMS 5 AND 6:

PROVIDE RECESSED LIFT

LOOPS/INSERTS FOR

EASY SLAB REMOVAL AT

TIME OF FUTURE

EXPANSION. PROTECT

FROM WEATHER WITH

PLASTIC CAPS AND

SEALANT

DOWN SPOUT,

SEE ARCHITECTURAL

ETS = 776'-4" TYP

ETS = 764'-8"

BID ITEMS 5 AND 6

B3

S-411

BID

ITEMS 5

AND 6

G

1.1 2

F.4

2.1

1'-0" 12'-3" 4"

3'-11"

BOLLARDS, SEE

C5/S-510

D8

S-410

5" GRADE SLAB

SEE SHEET S-101

ETS = 723'-4"

10" P/C WALLS TYP

G A

P

11" P/C WALL

PANEL

1" WASH

D3

S-412

G

1.1 2

F.4

2.1

F1

S-403

F3

S-403

1'-0" 12'-3" 4"

BOLLARDS, SEE

F7/S-523 TYP

EXPANSION JOINT,

SEE D1/S-502 AND

D3/S-502 TYP

4" 10" 10'-3" 10" 4"

1'-0"

D1

S-410

F5

S-410

3'-11" 5

F6

S-412

D6

S-412

E5

S-410

AT HORIZONTAL

JOINTS TYP

C5

S-410

AT CORNERS

TYP D3

S-410

AT SIDES OF

LANDING TYP

F1

S-410

F1

S-410

TURN EXPANSION JOINT

UP 6" BETWEEN P/C

PIECES TYP

B1

S-410

OH

OH

10" P/C WALLS

TYP

OUTLINE OF

LEDGE BELOW

OUTLINE OF

LEDGE BELOW

SEE B3/S-412 SIM FOR

CLOSURE PLATE

F8

S-410

SEE A5/S-523 AT

RAILINGS

G

1.1 2

F.4

2.1

F1

S-403

F3

S-403

1'-0" 12'-3" 4"

BID ITEMS 5 AND 6:

REVISE TOWERS TO 3 LEVELS BY

REMOVING LEVEL P4 AND

RELOCATING TOP OF ROOF LEVEL

TO ELEVATION 764'-8"

F6

S-411

F1

S-410

OUTLINE OF

LEDGE BELOW

OUTLINE OF

LEDGE BELOW

HOLD TOP OF

COLUMN BELOW

FLOOR LINE

HOLD TOP OF

COLUMN BELOW

FLOOR LINE

FOR BID ITEMS 5 AND 6, THIS PIECE TO

BE DETAILED FOR EASY REMOVAL

AT TIME OF FUTURE EXPANSION

(BOLT CONNECTIONS, RECESSED

LIFT LOOPS LEFT IN PLACE, ETC)

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-401

STAIR C - ENLARGED PLAN

EXPAND PARKING GARAGE 589-401

RES MAP

GENERAL SHEET NOTES

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C1

FOUNDATION PLAN

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C3

LEVEL P1 PLAN

(BID ITEM 1, 2 AND 3)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C5

LEVEL P2 PLAN

(BID ITEM 1, 2 AND 3)

LEVEL P3 PLAN (BID ITEM 1 AND 2)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C7

LEVEL P4 PLAN (BID ITEM 1)

N

S

W

E

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F1

ROOF LEVEL PLAN

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F3

LEVEL P1 PLAN

(BID ITEM 4, 5 AND 6)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F5

LEVEL P2 PLAN

(BID ITEM 4, 5 AND 6)

LEVEL P3 PLAN (BID ITEM 3 AND 4)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F7

LEVEL P4 PLAN

(BID ITEM 2, 3 AND 4)

LEVEL P3 PLAN (BID ITEM 5 AND 6)

1. REFER TO SHEET S-001 FOR GENERAL NOTES.

2. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL

DRAWINGS.

3. PRECAST STAIR/ELEVATOR TOWER CONSTRUCTION:

DESIGN IS PERFORMANCE DESIGN AND SHALL INCLUDE

TYPE, NUMBER, AND LOCATION OF REINFORCING FOR

ALL MEMBERS(WALLS, SLABS, ETC.). DESIGN SHALL

ALSO INCLUDE ALL MEMBER TO MEMBER AND BASE

CONNECTIONS. DESIGN SHALL ASSUME "BID ITEM 1"

TOWER IS FINAL FUTURE CONDITION. THE STAIRS

SHALL BE DESIGNED ACCORDING TO ALL THE

REQUIREMENTS IN IBC 2012, INCLUDING SUPPORTING

THEIR OWN WEIGHT PLUS A SUPERIMPOSED LIVE LOAD

EQUAL TO 100 psf. SEE SPEC SECTION 03 41 00 FOR

PRECAST CONCRETE.

4. ALL REFERENCES, DETAILS, REINFORCING, MEMBER

SIZES, CONNECTIONS, ETC. SHOWN ON C5/S-402 AND

F5/S-402 APPLY TO ALL SUPPORTED LEVELS UNLESS

NOTED OTHERWISE.

5. SEE ARCHITECTURAL DRAWINGS FOR MATERIAL

LEGEND.

6. FLOOR ELEVATION TOP OF CIP TOPPING AT MAIN

LANDING = 741'-6" AT LEVEL P2. ADD 11'-8" FOR EACH

FLOOR ABOVE.

7. PROVIDE HSS8x4x3/8 ABOVE TOP MOST LANDING FOR

CURTAIN WALL SUPPORT. LINE UP WITH HORIZONTAL

MULLION TO OBSCURE STEEL BEAM FROM EXTERIOR

VIEW. SEE F3/S-410 FOR CONNECTIONS AT ENDS.

G

10 10.9 11

F.4

9.9

4" 12'-3" 1'-0"

723'-6"

DP-6DPC-6

700'-0"

700'-0" 723'-6"

DP-5DPC-8

700'-0"

723'-6"

DP-5DPC-8

700'-0"

GB-4

GB-4

COLUMN NOT PRESENT

FOR BID ITEMS 4, 5 AND

6. PROVIDE ANCHOR

BOLTS (GALVANIZED)

FOR FUTURE COLUMNS

AND WRAP WITH PLASTIC

AND ENCASE IN LEAN

CONCRETE

WALL PANEL NOT PRESENT FOR

BID ITEMS 4, 5 AND 6. PROVIDE

EMBED PLATE FOR FUTURE WALL

PANEL AND EPOXY PAINT

723'-6"

723'-6"

723'-6" 723'-6"

GB-5 GB-5

B8

S-412

B8

S-412

B8

S-412

D8

S-412

"9

8" 4"

10" 4" 5" 8" 4"

1"

10"

C DP

AND CAP

L

C DP

AND CAP

L

C DP

AND CAP

L

C DPL

" 1

C DPL

4" C DP

AND CAP

L

4"

C DP

AND CAP

L

6"

C DP

AND CAP

L

723'-6"

DPC-7 DP-4

G

10 10.9 11

F.4

9.9

4" 12'-3" 1'-0"

3'-11"

BOLLARD, SEE

C5/S-510

B3

S-410

5" GRADE SLAB

SEE SHEET S-101

ETS = 725'-10 1/2"

F8

S-412

ETS = 727'-0"

A3

S-410

1" WASH

1" WASH

D3

S-412

G

10 10.9 11

F.4

9.9

4" 12'-3" 1'-0"

F5

S-403

F8

S-403

3'-11"

BOLLARDS, SEE

F7/S-523 TYP

EXPANSION JOINT,

SEE D1/S-502 AND

D3/S-502 TYP

1'-0"1'-0" 4"

D3

S-410

AT SIDES OF

LANDING TYP

D6

S-412

F5

S-410 F1

S-410

F6

S-412

D6

S-412

1'-0" 4" 10" 10'-3" 10" 4"

OUTLINE OF

LEDGE BELOW

C5

S-410

AT CORNERS

TYP

E5

S-410

AT HORIZONTAL

JOINTS TYP

1'-0" WIDE P/C

BEAM

TURN EXPANSION

JOINT UP 6" BETWEEN

P/C PIECES TYP

SEE B3/S-412 FOR CLOSURE PLATE

SEE B3/S-412 FOR CLOSURE PLATE

SEE A5/S-523 AT

RAILINGS

F8

S-410

G

10 10.9 11

F.4

9.9

4" 12'-3" 1'-0"

F5

S-403

F8

S-403

F6

S-411

OUTLINE OF

LEDGE BELOW

HOLD TOP OF

COLUMNS BELOW

FLOOR LINE

HOLD TOP OF

COLUMNS BELOW

FLOOR LINE

OUTLINE OF

LEDGE BELOW

NOTE 7

G

10 10.9 11

F.4

9.9

4" 12'-3" 1'-0"

12'-11" 4"

D8

S-411

F8

S-411

D8

S-411

D8

S-411

8" PRECAST SLAB.

FOR BID ITEMS 5 AND 6:

PROVIDE RECESSED LIFT

LOOPS/INSERTS FOR

EASY SLAB REMOVAL AT

TIME OF FUTURE

EXPANSION. PROTECT

FROM WEATHER WITH

PLASTIC CAPS AND

SEALANT

FOR BID ITEMS 5 AND 6:

PROVIDE EMBED PLATES ALL

AROUND PERIMETER IN TOP

OF WALLS PER E5/S-410 FOR

FUTURE VERTICAL EXTENSION

OF WALL. DESIGN FOR

FUTURE EXPANSION TO

MATCH STAIR TOWER SHOWN

IN BID ITEM 1 OF THESE

DRAWINGS.

D6

S-411

BID ITEMS

5 AND 6

ONLY

B8

S-411

BID ITEMS

5 AND 6

ONLY

B8

S-411

BID ITEMS

5 AND 6

ONLY

DOWN SPOUT,

SEE ARCHITECTURAL

ETS = 776'-4" TYP

ETS = 764'-8"

BID ITEMS 5 AND 6

B3

S-411

BID

ITEMS

5 AND 6

G

10 10.9 11

F.4

9.9

4" 12'-3" 1'-0"

3'-11"

BOLLARD, SEE

C5/S-510

5" GRADE SLAB

SEE SHEET S-101

ETS = 725'-10 1/2"

F8

S-412

ETS = 727'-0"

B3

S-410

A3

S-410

1" WASH

D3

S-412

G

10 10.9 11

F.4

9.9

F5

S-403

F8

S-403

4" 12'-3" 1'-0"

3'-11"

BOLLARDS, SEE

F7/S-523 TYP

EXPANSION JOINT,

SEE D1/S-502 AND

D3/S-502 TYP

1'-0"1'-0" 4"

D3

S-410

AT SIDES OF

LANDING TYP

D6

S-412

F5

S-410

F1

S-410

F6

S-412

1'-0" 4" 10" 10'-3" 10" 4"

C5

S-410

AT CORNERS

TYP

E5

S-410

AT HORIZONTAL

JOINTS TYP

1'-0" WIDE P/C

BEAM

TURN EXPANSION

JOINT UP 6" BETWEEN

P/C PIECES TYP

D1

S-410

B1

S-410

F1

S-410

OUTLINE OF

LEDGE BELOW

OUTLINE OF

LEDGE BELOW

SEE B3/S-412 FOR

CLOSURE PLATE

SEE A5/S-523 AT

RAILINGS

F8

S-410

G

10 10.9 11

F.4

9.9

F5

S-403

F8

S-403

4" 12'-3" 1'-0"

BID ITEMS 5 AND 6:

REVISE TOWERS TO 3 LEVELS BY REMOVING

LEVEL P4 AND RELOCATING TOP OF ROOF

LEVEL TO ELEVATION 764'-8"

D1

S-410

F6

S-411

OUTLINE OF

LEDGE BELOW

HOLD TOP OF

COLUMNS BELOW

FLOOR LINE

HOLD TOP OF

COLUMNS BELOW

FLOOR LINE

OUTLINE OF

LEDGE BELOW

FOR BID ITEMS 5 AND 6, THIS PIECE TO

BE DETAILED FOR EASY REMOVAL

AT TIME OF FUTURE EXPANSION

(BOLT CONNECTIONS, RECESSED

LIFT LOOPS LEFT IN PLACE, ETC)

NOTE 7

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-402

STAIR D - ENLARGED PLAN

EXPAND PARKING GARAGE 589-401

RES MAP

GENERAL SHEET NOTES

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C1

FOUNDATION PLAN

N

S

W

E

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C3

LEVEL P1 PLAN

(BID ITEM 1, 2 AND 3)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C5

LEVEL P2 PLAN

(BID ITEM 1, 2 AND 3)

LEVEL P3 PLAN (BID ITEM 1 AND 2)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"C7

LEVEL P4 PLAN (BID ITEM 1)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F1

ROOF LEVEL PLAN

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F3

LEVEL P1 PLAN

(BID ITEM 4, 5 AND 6)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F5

LEVEL P2 PLAN

(BID ITEM 4, 5 AND 6)

LEVEL P3 PLAN (BID ITEM 3 AND 4)

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F7

LEVEL P4 PLAN

(BID ITEM 2, 3 AND 4)

LEVEL P3 PLAN (BID ITEM 5 AND 6)

8" P/C SLAB

10" P/C WALL

LEVEL P4

LEVEL P3

LEVEL P2

LEVEL P1

TOP OF ROOF

BID ITEMS 5 AND 6:

REVISE TOWERS TO 3 LEVELS BY

REMOVING LEVEL P4 AND

RELOCATING TOP OF ROOF LEVEL TO

ELEVATION 764'-8"

Fx = 3.2k QUAKE

Fx = 2.4k QUAKE

Fx = 2.0k QUAKE

Fx = 2.2k QUAKE

TOP OF FOUNDATION

SEE PLAN

8" P/C SLAB

10" P/C WALL

LEVEL P4

LEVEL P3

LEVEL P2

LEVEL P1

BID ITEMS 5 AND 6:

REVISE TOWERS TO 3 LEVELS BY

REMOVING LEVEL P4 AND RELOCATING

TOP OF ROOF LEVEL TO ELEVATION

764'-8"

TOP OF ROOFFx = 2.2k QUAKE

Fx = 2.0k W

Fx = 3.2k QUAKE

Fx = 3.9k W

Fx = 2.4k QUAKE

Fx = 3.7k W

Fx = 2.0k QUAKE

Fx = 4.8k W

TOP OF FOUNDATION

SEE PLAN

8" P/C SLAB

10" P/C WALL

LEVEL P4

LEVEL P3

LEVEL P2

LEVEL P1

BID ITEMS 5 AND 6:

REVISE TOWERS TO 3 LEVELS BY

REMOVING LEVEL P4 AND

RELOCATING TOP OF ROOF LEVEL TO

ELEVATION 764'-8"

TOP OF ROOFFx = 2.9k QUAKE

Fx = 4.1k QUAKE

Fx = 3.0k QUAKE

Fx = 2.5k QUAKE

TOP OF FOUNDATION

SEE PLAN

8" P/C SLAB

10" P/C WALL

LEVEL P4

LEVEL P3

LEVEL P2

LEVEL P1

BID ITEMS 5 AND 6:

REVISE TOWERS TO 3 LEVELS BY

REMOVING LEVEL P4 AND RELOCATING

TOP OF ROOF LEVEL TO ELEVATION 764'-

8"

TOP OF ROOF

Fx = 2.2k QUAKE

Fx = 2.0k W

Fx = 3.2k QUAKE

Fx = 3.9k W

Fx = 2.4k QUAKE

Fx = 3.7k W

Fx = 2.0k QUAKE

Fx = 4.8k W

TOP OF FOUNDATION

SEE PLAN

1. REFER TO SHEET S-001 FOR GENERAL NOTES.

2. SHEAR WALL DESIGN IS PERFORMANCE DESIGN AND

SHALL INCLUDE SIZE, NUMBER, AND LOCATION OF

VERTICAL AND HORIZONTAL REINFORCING. DESIGN

SHALL ALSO INCLUDE BASE CONNECTION, PIECE

CONNECTIONS, SIZE, NUMBERS, AND SPACING OF

SHEAR TRANSFER CONNECTIONS FOR TRANSFER OF

LATERAL LOADS. SEE SPECIFICATION 03 41 00 FOR

PRECAST CONCRETE.

3. FOR SHEAR WALL SIZES, SEE ELEVATIONS THIS SHEET

AND STRUCTURAL DETAILS.

4. LATERAL LOADS ARE DUE TO WIND OR SEISMIC AS

INDICATED. LOADS INDICATED REPRESENT VERTICAL

AND HORIZONTAL DISTRIBUTION PER ASCE 7-10.

5. FOR SHEAR WALL BASE CONNECTION SEE F7/S-321 AND

E5/S-410

6. WIND LOADS AND SEISMIC LOADS ARE ULTIMATE.

7. SEISMIC CONTROLS WHERE NO WIND LOADS ARE

SHOWN.

8. DETAILS ON THIS SHEET ARE ONLY INTENDED TO

PROVIDE ENOUGH INFORMATION FOR PROPER

APPLICATION OF LATERAL LOADS. THESE DETAILS ARE

PURPOSELY MISSING INFORMATION. ARCHITECTURAL

ITEMS AND CERTAIN STRUCTURAL ITEMS HAVE BEEN

OMITTED FOR CLARITY.

9. ALSO REFER TO GENERAL SHEET NOTES ON SHEET S-

321.

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-403

P/C PANEL ELEVATIONS

EXPAND PARKING GARAGE 589-401

RES MAP

F1

EAST/WEST WALLS OF STAIR

TOWER C

F3

NORTH/SOUTH WALLS OF STAIR

TOWER C

F5

WEST WALL OF STAIR TOWER D

F8

NORTH/SOUTH WALLS OF STAIR

TOWER D

GENERAL SHEET NOTES

V A

R

IE

S S

E E

P L A

N

VARIES SEE ARCH VARIES SEE ARCH VARIES SEE ARCH

1"

3/4" C

LR

T Y P

11"

MIN

11"

MIN

10"

ETS

SEE PLANx x x xxx

P/C CONCRETE

NOTE: PLACEMENT OF ADDITIONAL

REINFORCING SHOWN APPLIES TO

LANDING AT TOP OF A STAIR

FLIGHT.

ADD'L REINF AS REQ'D BY P/C

SUPPLIER DUE TO ORIENTATION

DURING HANDLING

CIP CONC W/ 6 x 6

- W1.4 x W1.4 WWR

EMBEDDED METAL

ABRASIVE NOSING

TYP, SEE ARCH &

SPECIFICATIONS

(3) #4 @ 3" O.C. x CONT.

AT TOPPING MID-DEPTH

(3) #4 @ 3" O.C. x

CONT. AT TOPPING

MID-DEPTH

TOOLED JOINT

WITH SEALANT

TOOLED JOINT

WITH SEALANT

NOTE: STAIR SLAB DESIGN BY PRECASTER TO WITH STAND HORIZONTAL AND VERTICAL

LOADS FROM CURTAIN WALL SYSTEM. COORDINATE LOADS WITH CURTAIN WALL SUPPLIER.

1'-6"

4"P/C STAIR

SLAB-ON-GRADE

#8 x 9" LONG

4" x 4" x 1/2" KOROLATH

SHIMS. GROUT AFTER

CONNECTION IS COMPLETE.

2"Ø x 4" DEEP HOLE

CAST-IN SLAB

2"Ø HOLE THROUGH

STAIR, GROUT FULL

P /C

P A

N E

L P

/C P

A N

E L

EXTERIOR INTERIOR

CONTINUOUS

SEALANT

CONTINUOUS

NON-SHRINK NON-STAIN

GROUT BETWEEN

CONNECTION TYPICAL

P /C

P A

N E

L P

/C P

A N

E L

BACKER ROD

AND SEALANT

EACH FACE

TYPICAL

CERAMIC FIBER

BLANKET INSULATION

IF FIRE RATING REQ'D.

SEE SPECS.

A T

P /C

T O

P /C

A T

P /C

T O

C A

S T

-I N

-P L A

C E

. EQUAL EQUAL

P /C

P A

N E

L P

/C P

A N

E L

O R

G R

A D

E B

E A

M O

R C

A S

T -I

N -P

L A

C E

G R

A D

E W

A L L

WELD PLATE

EXTERIOR SIDE INTERIOR SIDE

NOTES:

1. SEE DETAIL C8/S-410 FOR CONTINUOUS HORIZONTAL JOINT BETWEEN

CONNECTION.

2. (2) CONNECTIONS, MINIMUM, PER WALL PIECE.

EMBED PLATE

WITH ANCHORS

EMBED PLATE WITH

BARS x PANEL HEIGHT

NON-SHRINK

NON-STAIN

GROUT

NON-SHRINK

NON-STAIN GROUT

CONT

SEALANT

1"

5"

/2

WELD PLATE

P/C PANEL

P/C PANEL

V-GROOVE TO

MATCH PANEL

JOINTS

BACKER ROD

AND SEALANT

END OF PANEL

WHERE APPLICABLE

EMBED PLATE WITH

ANCHORS AND BARS

TYPICAL

NOTES:

1. SEE DETAIL A8/S-410 FOR JOINT BETWEEN CONNECTIONS.

2. (2) CONNECTIONS, MINIMUM, PER WALL PIECE.

NON-SHRINK

NON-STAIN GROUT

C L A

S S

B

L A

P S

P L

IC

E

STD. HOOKS

L-BAR w/ 2'-6" LEGS

3/4"

PLATE 3/8" x 4" x 4"

EMBED PLATE BY PRECASTER

HSS 8x4x3/8

P/C WALL

5/16

5/16

5/16

5/16

ANGLE 4" x 4" x 3/8" x 4" LONG

10"

ETS

SEE PLAN

P/C WALL

CIP TOPPING,

COVE SEALANT

P/C STAIR SLAB

CONNECTION BY

PRECASTER. (2)

CONNECTIONS, MIN, PER

SLAB PIECE

x x x

ETS

SEE PLAN

CIP TOPPING

CONTINUOUS BEARING PAD

CONNECTION BY

PRECASTER. (2)

CONNECTIONS, MIN, PER

SLAB PIECE

10" P/C WALL

P/C STAIR SLAB

COVE SEALANT

x x x

ETS

SEE PLANxxxx xx

TOOLED JOINT

WITH SEALANT

P/C STAIR SLAB

CONNECTIONS BY

PRECASTER

(2) CONNECTIONS PER

LANDING, MIN.CIP TOPPING

1'-0" 1'-0" 4" 10"

/2

2'-0" 2'-0"

B1

S-410

P/C COLUMN

(2) 3/4"ø INSERT/COIL RODS x 2'-6"

(GALVANIZED)

P/C SPANDREL

PANEL

P/C BEAM

P/C COLUMN COVER,

SEE D6 AND F8/S-524 SIM

10" P/C WALL

EXPANSION JOINT

TURN EXPANSION

JOINT UP 6" BETWEEN

PRECAST PIECES, TYP

1/4" x 8" x 10" x 3'-5" TALL BENT PLATE

LOCATED 1" ABOVE THE FLOOR (GALVANIZE

AND PAINT TO MATCH COLOR OF PRECAST)

ATTACH TO STAIR TOWER WALL ONLY WITH

3/8"ø HILTI KWIK BOLT TZ (STAINLESS

STEEL) EXPANSION ANCHORS AT 18" OC

PROVIDE LONG-SLOTTED HOLES IN PLATE

9.9

G

1'-0" 1'-0" 1/2"

1'-0"

8"

9.9

2.1

P/C IT BEAM

P/C COLUMN

P/C COLUMN COVER. HANG

FROM TOP MOST HAUNCH.

PROVIDE CAVITY AROUND

OTHER HAUNCHES

BEARING PAD AT TOP

MOST SUPPORT

P/C HAUNCH AT EACH

SUPPORTED LEVEL

PERFORMANCE DESIGN

BY PRECASTER TO

SUPPORT FUTURE IT

BEAM AND FLOOR LOADS

AS SHOWN IN BID ITEM 1

1/2" BEARING PADS. GLUE

TO COLUMN

OH

/2

1'-6"

4"

9"

ETS

SEE PLAN2

(2) #4 x CONT.

GRADE SLAB, SEE SHEET S-101

FOR INFORMATION

P/C STAIR

#8 x 9" LONG

4" x 4" x 1/2" KOROLATH

SHIMS. GROUT AFTER

CONNECTION IS COMPLETE.

2"Ø x 4" DEEP HOLE

CAST-IN SLAB

2"Ø HOLE THROUGH

STAIR, GROUT FULL

#4 @ 12" OC WITH STANDARD

HOOK EACH END

1'-6"

MINIMUM

SEE ARCHITECT

1'-0"

" 1

1'-0"

SEE PLAN

ETS

SEE PLAN

ETS

S E

E

A R

C H

IT

E

C T

" M

IN

IM

U M3" C

LE

A R

(1) #4 x CONTINUOUS

EMBEDDED METAL ABRASIVE

NOSING TYPICAL, SEE

SPECIFICATIONS

#4 @ 18" OC EACH WAY

(2) #4 x CONTINUOUS

GRADE SLAB, SEE

SHEET S-101 FOR

INFORMATION

1/2" FIBERBOARD

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-410

STAIR DETAILS

EXPAND PARKING GARAGE 589-401

RES MAP

F8

TYPICAL STAIR SECTION

D8

P/C STAIR/SLAB DETAIL

C8

HORIZONTAL PANEL/PANEL

DETAIL

A8

VERTICAL PANEL/PANEL DETAIL

JOINT

E5

CONNECTION DETAIL

C5

VERTICAL PANEL/PANEL

CONNECTION

A5

CORNER REINFORCEMENT DETAIL

F3

STAIR DETAIL

D3

WALL/SLAB DETAIL

F1

BEAM/SLAB DETAIL

F5

STAIR SLAB DETAIL

D1

WALL/COLUMN DETAIL

B1

COLUMN DETAIL

B3

WALL DETAIL

A3

STAIR ON GRADE DETAIL

ETS

SEE PLAN

3/8" xxx xx

TOOLED JOINT

WITH SEALANT

P/C STAIR SLAB

CONNECTIONS BY PRECASTER.

(2) CONNECTIONS, MIN., PER SLAB

PIECE. PROVIDE BOLTED CONNECTIONS

AT BASE OF SLAB AT BID ITEMS 5 AND 6 FOR

EASY REMOVAL AT TIME OF FUTURE

EXPANSION

CIP TOPPING

EXPANSION JOINT

AND P/C BEAM,

SEE F6/S-412

L 6" X6" X 1/2" X CONTINUOUS

SLAB SUPPORT ANGLE(GALV.)

WITH CONTINUOUS BEARING

PAD ATTACHED TO ANGLE

WITH 3/16" DIAMETER S.S.

SCREWS AT 12" OC

P/C TOP

LANDING SLAB

CONTINUOUS

BEARING PAD

P/C LEDGE

STAIR D CONDITION SHOWN.

FLIP DIRECTION OF ANGLE

IN OPPOSITE DIRECTION

FOR STAIR C

TOOLED JOINT

WITH SEALANT

SEE PLAN

ETS

FLASHING AND

ROOFING MATERIAL.

SEE ARCHITECTURAL.

SLOPE TO DRAIN PER

ARCHITECTURAL

DRAWINGS.

P/C SLAB

CURTAIN WALL SYSTEM,

SEE ARCHITECTURAL.

CONNECTION TO P/C SLAB

PERFORMANCE DESIGN BY

CURTAIN WALL SUPPLIER.

COORDINATE WITH PRECASTER

10"

SEE PLAN

ETS

CONNECTIONS BY PRECASTER.

(2) CONNECTIONS, MIN., PER SLAB

PIECE.

10" P/C WALL

CONTINUOUS

BEARING PAD

GUTTER AND ROOFING

MATERIAL. SEE

ARCHITECTURAL.

SLOPE TO DRAIN PER

ARCHITECTURAL

DRAWINGS.

P/C SLAB

SEALANT BOTH

SIDES

MIN (2) THREADED INSERTS AND BOLTS

REQUIRED AT EACH CONNECTION FOR

EASY REMOVAL OF ROOF FOR BID ITEMS 5 AND 6.

WELDED CONNECTION IS ACCEPTABLE

FOR BID ITEM 1 AND OTHER BID ITEM DEDUCTS

#4 HAIRPIN

10"

J O

IN

T

SEE PLAN

ETS

FLASHING AND ROOFING MATERIAL.

SEE ARCHITECTURAL. SLOPE TO

DRAIN PER ARCHITECTURAL DRAWINGS.

P/C SLAB, NEEDS TO BE DESIGNED

TO BE EASILY REMOVED AND RELOCATED.

NEEDS TO SPAN IN NORTH-SOUTH DIRECTION

CURTAIN WALL SYSTEM,

SEE ARCHITECTURAL.

CONNECTION TO P/C SLAB

PERFORMANCE DESIGN BY

CURTAIN WALL SUPPLIER.

COORDINATE WITH PRECASTER

BACKER ROD

AND SEALANT

PRECAST BEAM, DESIGN TO SUPPORT

FUTURE VERTICAL D = 0.25KLF (SERVICE)

AND FUTURE HORIZONTAL W = 0.32 KLF

(FACTORED)

CONNECTIONS BY PRECASTER.

(2) CONNECTIONS, MIN., PER SLAB

PIECE.

MIN (2) THREADED INSERTS AND BOLTS

REQUIRED AT EACH CONNECTION FOR

EASY REMOVAL OF ROOF FOR BID ITEMS

5 AND 6

#4 HAIRPIN

CONTINUOUS

BEARING PAD

3"

MIN

P/C WALL

P/C ROOF SLAB

P/C BEAM

HIDDEN HAUNCH

SECTION A-A

HIDDEN HAUNCH

PLAN

P/C WALL

BEAM CONNECTION TO

WALL PERFORMANCE

DESIGN BY PRECASTER

TOP AND BOTTOM

FOR TORSION

A

A

P/C BEAM

(2) 1/2"ø BOLTS IN

SHORT SLOTTED

HOLES

1 1/2" 3" 1 1/2"

(2) 1/2"ø HILTI KWIK BOLT TZ x 4 1/2"

(GALVANIZED)

MC12 STRINGER

L3x3x6" LONG. PROVIDE

SEALANT ALL AROUND

/4

C

L R x xxxx

P/C TEE

CIP TOPPING

P/C IT BEAM

TOOLED JOINT WITH SEALANT

1/2"x8"x8" EMBED PLATE

PERFORMANCE DESIGN BY

PRECASTER AT EACH STAIR

STRINGER WITH 2 MORE

BETWEEN STRINGERS AT

EQUAL SPACING (4) TOTAL.

DESIGN TO CARRY STAIR

LOAD.

CONNECTION FOR STRINGERS

AND TREADS TO PRECAST

EMBEDS PERFORMANCE

DESIGN BY STEEL SUPPLIER.

MC12 STRINGER

NOTE: SEE F6/S-524 FOR REMAINING INFORMATION.

/4

C

L R

5/16

EA POST

5/16

ETS

SEE PLANxxxxxxx x xxxxxxx x

HSS 6x6x3/8

MC12 STRINGER

P/C TEE FLANGE

CIP TOPPING

HSS 6x6x3/8

MC12 STRINGER

1/4" NEOPRENE

PAD AT BOTTOM

IN ADDITION TO NORMAL TOPPING

WWR, PROVIDE (8) #3 @ 6" OC x 12'-0"

LONG CENTERED UNDER STEEL POSTS

PRECASTER TO PROVIDE 4'-0" WIDE STRIP

OF WWR EQUAL TO 0.18 IN /FT. CENTER

UNDER HSS 6x6 POSTS AND PROVIDE OVER

FULL WIDTH OF PRECAST DOUBLE TEE

HSS 8x4x3/8

10" x 10" x 3/8"

STEEL PLATE EACH

SIDE

(4) 3/4"ø THROUGH BOLTS

(GALVANIZED) AT 7 1/2" SPACING

1/4" CAP PLATES WELD

ALL AROUND WATER

TIGHT

NSNS GROUT

SEE PLAN

ETS

= 763'-11 1/2"

ETW

CONNECTIONS BY PRECASTER.

(2) CONNECTIONS, MIN., PER SLAB

PIECE.

10" P/C WALL

CONTINUOUS

BEARING PAD

P/C SLAB

SEALANT BOTH

SIDES

MIN (2) THREADED INSERTS AND BOLTS

REQUIRED AT EACH CONNECTION FOR

EASY REMOVAL OF ROOF FOR BID ITEMS

5 AND 6

P/C LEDGE FOR FUTURE STAIR SLAB

(2) #4 LEDGE TIES

AT EACH CONNECTION,

MIN

GUTTER AND ROOFING

MATERIAL. SEE

ARCHITECTURAL.

SLOPE TO DRAIN PER

ARCHITECTURAL

DRAWINGS.

F

10 10.9119.9

METAL RAILING

SEE ARCHITECTURAL

M C

S

T R

IN

G

E R

M C

S

T R

IN

G

E R

P/C COLUMN

P/C BEAM

P/C SPANDREL

P/C COLUMN COVER

GRIP-STRUT PREFORMED

METAL RISERS AND

LANDING PLANKS

NOTES:

1. STEEL STAIR CONSTRUCTION: CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CALCULATIONS PREPARED BY A MISSOURI LICENSED PROFESSIONAL ENGINEER FOR THE DESIGN OF PREFABRICATED METAL RISERS, KICK PLATES, LANDING PLANKS, THEIR CONNECTIONS TO THE STEEL STRINGERS AND SUPPORT FRAMING. THE STAIRS SHALL BE DESIGNED ACCORDING TO ALL BUILDING CODE (IBC 2012) REQUIREMENTS. DESIGN FOR DEAD LOAD DUE TO SELF-WEIGHT, 100 PSF LIVE LOAD, AND MINIMUM

SEISMIC LOAD EQUAL TO 10% OF DEAD LOAD.

A. RISER CONSTRUCTION: "GRIP-STRUT" PREFORMED STEEL RISERS

B. INTERMEDIATE LANDING FLOOR SURFACE: "GRIP-STRUT" PREFORMED METAL PLANKS.

2. GENERAL CONTRACTOR TO COORDINATE REQUIRED EMBED PLATE LOCATIONS AND SIZES FOR

CONNECTIONS BETWEEN STEEL STAIR MEMBERS AND PRECAST CONCRETE WITH PRECASTER.

3. HOT-DIP GALVANIZE AND PAINT ALL STEEL.

BOLLARDS,

SEE F7/S-523

2'-0" 5'-0" 4'-0"

1'-0"

4" 12'-3" 1'-0"

F3

S-411

B6

S-411

D3

S-411

HSS 8x4x3/8

HSS 6x6x3/8" HSS 6x6x3/8"

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-411

STAIR DETAILS

EXPAND PARKING GARAGE 589-401

RES MAP

F6

STAIR SLAB DETAIL

F8

ROOF SLAB DETAIL

D8

ROOF SLAB DETAIL

0 2' 4' 8'

1/4" = 1'-0"

1/4" = 1'-0"F1

STAIR - BID ITEM 5

D6

ROOF SLAB DETAIL BID ITEMS 5

AND 6

B8

HIDDEN HAUNCH DETAIL

B6

BOTTOM STAIR SECTION

F3

TOP STAIR SECTION

N

S

W

E

D3

INTERMEDIATE STRINGER

SUPPORT

B3

STAIR TOWER EXPANSION DETAIL

4" 4"

ETGB

SEE PLAN

ETS

SEE PLAN

10" P/C WALL

PANEL

CONNECTION PERFORMANCE

DESIGN BY PRECASTER.

DESIGN BASE CONNECTIONS

ASSUMING FULL HEIGHT TOWER

AS SHOWN IN BID ITEM 1 OF THESE

DRAWINGS

CIP GRADE BEAM, SEE SCHEDULE

COVE SEALANT,

SEE B5/S-502

GRADE SLAB. CAST TIGHT WITH

BOND BREAKER

COVE SEALANT,

SEE B5/S-502

SEE PLAN

SEE

PLAN

8" 4"

ETS

SEE PLAN

8" P/C WALL PANEL

ETGB

SEE PLAN

CONNECTION PERFORMANCE

DESIGN BY PRECASTER

CIP GRADE BEAM, SEE SCHEDULE

COVE SEALANT,

SEE B5/S-502

GRADE SLAB. CAST TIGHT

WITH BOND BREAKER

ETW

730'-6"

GLAZED ALUMINUM CURTAIN WALL

SYSTEM. SEE ARCHITECTURAL

PERIMETER DRAINAGE

SYSTEM, BY OTHERS,

SEE SPECIFICATIONS

3/4" TYPICAL

4'-0" WASH4"10"

1'-0" 1'-0"

ETS

SEE PLAN

F.4G xx x x xx x

P/C TEE TYPICAL

SLOPE BEARING PLATES IN BEAMS

AND SUPPORT PLATES IN COLUMNS,

AS REQUIRED TO PROVIDE UNIFORM

BEARING ON PADS, TYPICAL

P/C HAUNCH BEYOND

CIP TOPPING, TYPICAL

P/C BEAM, SEE F1/S-522 FOR INFO

WBA WABOCRETE II

SYSTEM WITH MM-800

MEMBRANE OR

ENGINEER APPROVED

EQUIVALENT. SEE

D1/S-502

CHORD STEEL, SEE PLAN

PROVIDE MINIMUM OF 1 SLEEVE THROUGH BEAM FOR

FUTURE CONDUIT, OR AS REQUIRED BY MEP DRAWINGS

#5 X 5'-0" AT EACH TEE

STEM

CIP TOPPING

CONTINUOUS

BEARING PAD

P/C LEDGE

CONNECTIONS BY

PRECASTER.

(2) CONNECTIONS,

MIN., PER SLAB PIECE.

COVE SEALANT

TOOLED JOINT WITH SEALANT

P/C STAIR SLAB

T E

E

WASH VARIES

SEE PLAN

4" 1'-0"

ETS

SEE PLAN

2.1

9.9 x x x x xx xx

CIP TOPPING

CHORD STEEL,

SEE PLAN AND

DETAIL C1/S-521

#4 x 5'-0" @ 16"

ON CENTER.

POSITION AT

MID-DEPTH

OF TOPPING.

P/C BEAMP/C STAIR TOWER

WALL

P/C SLAB

CIP TOPPING

WBA WABOCRETE II SYSTEM

WITH MM-800 MEMBRANE OR

ENGINEER APPROVED

EQUIVALENT. SEE D3/S-502

COVER PLATE ANCHOR

TO WALL SIDE ONLY.

SEE SPECIFICATIONS TOOLED JOINT

WITH SEALANT

CONNECTIONS BY

PRECASTER. (2)

CONNECTIONS,

MIN., PER SLAB

PIECE.

TOOLED JOINT

WITH SEALANT

P/C TEE

3" 2"

ETGB

SEE PLAN

ETS

SEE PLAN

CIP GRADE BEAM,

SEE SCHEDULE

PERIMETER DRAINAGE

BY OTHERS, SEE

SPECIFICATIONS

COVE SEALANT

GRADE SLAB CAST TIGHT

10" P/C WALL

EXTERIOR GRADE,

SEE CIVIL

3/4"ø x 2'-6" COIL ROD

AND INSERT @ 18" OC

WITH (2) #4 x CONT

CONNECTION PERFORMANCE

DESIGN BY PRECASTER.

DESIGN BASE CONNECTIONS

ASSUMING FULL HEIGHT TOWER

AS SHOWN IN BID ITEM 1 OF THESE

DRAWINGS

1'-0"

2"

4"

ETS

SEE PLAN

(3) #4 x CONTINUOUS

SLAB ON GRADE

CIP CONCRETE,

SEE CIVIL

DRAWINGS

1/2" JOINT FILLER

#4 x 4'-0" @ 12" OC

CENTERED ON JOINT,

PLACE BAR IN DOWEL

SLEEVE ON PARKING

STRUCTURE SIDE OF

JOINT

P/C WALL

CIP GRADE BEAM

FACE OF WALL

BEYOND

#4 @ 12" OC WITH

STANDARD HOOK

BY PRECASTER

11"1"

4"

F.4

P/C WALL

EXPANSION JOINT

1/4" x 8" x 10" x 3'-5" TALL BENT PLATE LOCATED

1" ABOVE THE FLOOR (GALVANIZE AND PAINT TO

MATCH COLOR OF PRECAST) ATTACH TO STAIR

TOWER WALL ONLY WITH 3/8"ø HILTI KWIK BOLT

TZ (STAINLESS STEEL) EXPANSION ANCHORS AT

18" OC. PROVIDE LONG-SLOTTED HOLES IN

PLATE

TURN EXPANSION

JOINT UP 6" BETWEEN

PRECAST PIECES, TYP

P/C SPANDREL

PANEL

P/C COLUMN

3/4"ø INSERT/COIL ROD x 2'-6"

(GALVANIZED)

P/C BEAM

P/C BEAM

LEDGE BELOW

STAIR TOWERGARAGE

ETS

SEE PLAN

(3) #4 x CONTINUOUS

SLAB ON GRADE

#4 x 4'-0" @ 18" OC

CENTERED ON JOINT.

PLACE BAR IN DOWEL SLEEVE

ON STAIR TOWER SIDE OF JOINT

P/C WALL

CIP GRADE BEAM

FACE OF WALL

BEYOND

#4 @ 12" OC WITH

STANDARD HOOK

BY PRECASTER

TOOLED JOINT

WITH SEALANT

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

07/08/16

S-412

STAIR DETAILS

EXPAND PARKING GARAGE 589-401

RES MAP

B8

GRADE BEAM/WALL DETAIL

D8

GRADE BEAM/WALL DETAIL

D6

BEAM/WALL DETAIL

F6

BEAM/WALL DETAIL

B6

GRADE BEAM/WALL DETAIL

F8

EDGE OF SLAB DETAIL AT STAIR

EXTERIOR DOORWAY

B3

COLUMN PLAN DETAIL

D3

SLAB DETAIL AT DOORWAY

8" 8" 8"

2'-0"

M

IN

IM

U M

U N

O O

N P

L A

N

S PROVIDE WASH WHERE

INDICATED ON PLANS.

WASH IS 4'-0" WIDE UNO

ON PLANS

T.O. FOUNDATION

SEE FOUNDATION PLAN

ETS

SEE PLAN

ETS

SEE PLAN

SLAB ON GRADE

CMU WALL WITH #5 @ 8"

VERTICAL AND ALL CELLS

GROUTED SOLID. EXTEND

EVERY THIRD VERTICAL BAR

2'-0" INTO MASONRY ABOVE

2'-8".

CMU WALL WITH #4 @

2'-0" ON CENTER ABOVE

2'-8". GROUT CELLS

SOLID AT REINFORCING.

SEE DETAIL F5/S-501 AT

ENDS.

SLAB ON GRADE

CAST-IN-PLACE

FOOTING

#5 x 3'-0" DOWELS

@ 8" ON CENTER

WITH STANDARD

HOOK

1/2" JOINT FILLER, TYPICAL

NOTES:

1. SEE DETAIL E5/S-501 FOR HORIZONTAL REINFORCEMENT. SEE

DETAIL F3/S-501 AT OPENING.

2. GROUT CELLS SOLID WHERE MEP EQUIPMENT IS MOUNTED TO

WALL. SEE MEP DRAWINGS.

SEE DETAIL A1/S-501

AND DETAIL C1/S-501

FOR TOP OF WALL

DETAILS

(2) # 5 x CONTINUOUS

EXTEND 1'-6" INTO

INTERSECTING

FOUNDATION

DAMPPROOFING, BOTH SIDES

C L E

A R

M

IN

IM

U

M

1/8" GAP BETWEEN

ANGLE AND WALL

TYPICAL

4" MIN

8" CMU WALL WITH #4

@ 2'-0" OC GROUT

CORES SOLID AT REINFORCING.

GROUT CELLS SOLID WHERE MEP

EQUIPMENT IS MOUNTED TO WALL.

SEE MEP DRAWINGS.

P/C TEE AND CIP

TOPPING

SLOT TOP CMU BLOCK

AS REQUIRED TO SLIDE

PAST REBAR

L 6x4x5/16 (LLV) x 0'-8"

LONG @ 4'-0" ON CENTER

(GALVANIZED) WITH (2) 3/8"Ø

(GALVANIZED) EXPANSION

ANCHORS WITH 2 1/2"

MINIMUM EMBED TYPICAL

@ 5" OC IN SHORT-SLOTTED

HOLES, PERPENDICULAR TO

WALL. PROVIDE FIRST

CONNECTION AT 4'-0" FROM

CORNERS. PROVIDE

L8x6x7/16…