Att.1 Drawing.pdf
PDF 353 KB Posted
- Solicitation number
- 36C25221B0017
About this file
This document package includes drawings and specifications for upgrading low-pressure steam risers at the Oscar G. Johnson VA Medical Center in Iron Mountain, Michigan, as well as the corresponding federal contract opportunity. The drawings depict details for equipment, piping, hangers, and various mechanical, electrical, and architectural components involved in the upgrade. The federal contract opportunity is a solicitation for furnishing all labor, materials, tools, transportation, insurance, and other items to complete the upgrade work. The scope of work involves demolishing some existing systems and installing new architectural, mechanical, and electrical systems on multiple floors, as outlined in the specifications and drawings. The period of performance is 240 calendar days from notice to proceed. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration VISN 12.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25221B0017 0002.docx | DOCX document | |
| 36C25221B0017 0001.docx | DOCX document | |
| S02 - Att4 Wage Rate Dickinson MI20200117dtd. 1.15.21.pdf | ||
| S02 - Att1 SOW 585-20-111.pdf | ||
| 36C25221B0017_2.docx | DOCX document | |
| S02 - Att2 Specifications 585-20-111.pdf | ||
| S02 - Att5 VHA Directive Seasonal Flu Shot.pdf | ||
| S02 - Att3 REV1 Drawings 585-20-111.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BALL VALVE
PROVIDE DIRT LEG UPSTREAM OF VALVES WHERE PIPED
3) PIPE FROM TOP OR SIDES OF MAIN WHEREVER POSSIBLE.
RATED PIPING SLEEVE DOWN
HEATING ELEMENT
PIPING EXPOSED
NOTE: 1) PIPING TO BE ON WARM
FROM LOWER SIDES OR BOTTOM.
BE LOCATED ABOVE THE CEILING.
2) AT CONTRACTOR DISCRETION THE VALVES CAN
FURRED WALL.
SIDE OF INSULATION IN
H W
S
DRAIN
CONTROL VALVE
BALL VALVE
UNION
THRU SLAB
H W
R
VENT
6"
(1 PER STAIR TOWER)
FOR RECESSED UNIT 1"
INSULATION AT BACK
FOR EXTERIOR WALL.
H W
S H
W R
H W
S H W
R
FILTER
ACCESS DOOR
FAN
HEATING COIL
AIR
FLOW
FINISHED FLOOR
PIPING EXPOSED
CABINET HEATER
HEATING COIL
ACCESS DOOR
UNION
2-WAY CONTROL VALVE
DRAIN W/VALVE
AIR FLOW
AIR
FLOW
BALANCING VALVE
BALL VALVE
NOTE: 1) PIPING SHALL BE IN WARM SIDE OF INSULATION.
2) PIPE FROM TOP OR SIDES OF MAIN WHEREVER POSSIBLE. PROVIDE
DIRT LEG WHERE UPSTREAM OF VALVES PIPED FROM LOWER SIDES OR BOTTOM.
AQUASTAT TO START FAN @ 120°F
6"
5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
-1312 14 -16 -
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 241814 16128 1064 532 2 1/21 1/21 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]
--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000 LB.
[453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1 -
SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 -
SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER INSULATION
SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
[2 5m m
1" M
AX
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
TYPICAL CONNECTIONS TO VERTICAL HOT
WATER UNIT HEATER
TYPICAL CONNECTIONS TO HORIZONTAL HOT
WATER UNIT HEATER
UNIT HEATER
HOT WATER
SUPPLY
HOT WATER
RETURN
HOT WATER
SUPPLY
HOT WATER
RETURN
UNIT HEATER
AIR VENT
TEST PLUG, TYP.
SHUTOFF BALL
VALVE, TYP.
WYE STRAINER,
TYP.
MV
MV
2-WAY CONTROL VALVE
AQUASTAT TO START
FAN @ 120°F
2-WAY CONTROL VALVE
AQUASTAT TO START
FAN @ 120°F
HEATING COIL
FLANGES FOR REMOVAL OF COIL.
THERMOMETER
BALL VALVE
BALANCING VALVE
VALVES AND SNUBBER
PRESSURE GAUGE W/BALL
UNION
1/4"
GHWR
GHWS
PETE'S PLUG
PROVIDE COIL
PULL SPACE
DRAIN
FLOW
AIR
VENTS
1.) HOT WATER SUPPLY CONNECTED TO
WATER OUTLET CONNECTION TO THE AIR
AIR OUTLET SIDE OF COIL. HOT
ENTERING SIDE OF COIL.
LOCATE PIPING WITH UNIONS OR
NOTES:
2.)
TWO-WAY ENERGY
CONTROL VALVE
USE 2x2x1/4" ALUMINUM ANGLE FRAME W/
FOR DUCT OR PIPING ON ROOF
2" SUPPORT STRAP (VERIFY HEIGHT)
4"
TREATED WOOD NAILER
CANT AND
1/2" INSULATION
THRU FLASHING W/ROOF
SEAL ALL PENETRATIONS
EQUIPMENT RAIL
WITH FASTENERS 8" O.C.
METAL COUNTERFLASHING
METAL CAP W/FASTENERS
24" O/C (BY GENERAL
ATTACH TO
STRUCTURE
CEMENT
(BY GEN TRADE)
TRADE)
(BY GENERAL TRADE)
ROOF CONSTRUCTION.
SEE ARCHITECTURAL
FOR TYPE.
PATCH ROOFING
UP NEW CANT &
CURB AND ATTACH
TO WOOD NAILER.
GENERAL TRADE TO
LPCR
LPS
6" LONG DIRT LEG
FULL SIZE OF LPS MAIN
PITCH
1.5 TIMES PIPE
DIAMETER (8" MIN.)
GATE VALVE
STRAINER
(WITH CAPPED VALVE)
UNION 3/4" F&T TRAP
CAPPED 1/2" GATE
VALVE TEST PORT
PITCH
TO CONDENSATE
TANK/MAIN
NOTE:
USE BUCKET TRAP AND CHECK
VALVE WHEN CONDENSATE PIPE
RISES AFTER TRAP DISCHARGE
1/2" DRAIN VALVE
(ALTERNATE LOCATIONS)
CHECK VALVE
AT RISE
STRUCTURE
ATTACH TO
ALL AROUND
1/4" NEOPRENE GASKET
THRU ROOF, SET CURB, AND PATCH
NOTE: GENERAL TRADE SHALL SAWCUT HOLES
ROOF CEMENT.
THRU CURB WITH
SEAL ALL PENETRATIONS
FASTENERS @ 8" 0/C
FLASHING WITH
METAL COUNTER
(CANT BY GENERAL TRADE)
INSULATED ROOF CURB
2 X 2 (ACQ) TREATED WOOD NAILER
" O
R
AS
N O
TE
D
INTERIOR METAL LINER
AS NOTED
INSULATION AND ROOFING INTO
EXISTING SYSTEM.
EXISTING ROOF CONSTRUCTION.
CURB
PREFABRICATED ROOF
CLAMP RUBBER
NIPPLE TO PIPE
CLOSE-UP UNUSED
PIPE NIPPLES
HOSE CLAMP
CURB COVER
INSULATE AS NOTED.
STOP INSULATION
AT CLAMP.
GHWS/R-UP/DN
D6
MK501
ROOF CONSTRUCTION.
SEE ARCHITECTURAL
FOR TYPE.
CORE DRILL HOLE THRU
CONCRETE STRUCTURE
FOR PIPING
DRILL (5) 1/8" HOLES.
NEW LPC MAIN
6" LONG 1" PIPE
WELDED TO LPC
NEW 3/4" MPC
FROM TRAP
ANGLE FRAME TO SUPPORT COIL
SEPARATELY ALL-AROUND (FRONT
AND BACK). CENTER COIL IN AHU
HOUSING.
ALL INTERNAL STEEL TO BE
GALVANIZED STEEL, STAINLESS
OR ALUMINUM ANGLES.
BLANK-OFF
SHEET METAL
PANEL AND
SEAL
ATTACH TO
CABINET
FLOOR
ATTACH TO
CABINET ROOF
BLANK-OFF
SHEET METAL
PANEL AND
SEAL
DETAILS
MK501
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMP
321 4 5 6 7 8 9 10
Berners-Schober Associates, Inc.
310 Pine Street Green Bay, WI 54301 Phone: (920) 432-4865
LOW-PRESSURE STEAM RISER
OSCAR G. JOHNSON VAMC
585-20-111
Project Director
MAY 17, 2021Revisions: Date:
50% DESIGN SUBMITTAL 02-11-2021
6163.07
BID DOCUMENT SET
95% DESIGN SUBMITTAL 03-31-2021
100% DESIGN SUBMITTAL 04-30-2021
BID DOCUMENT SET 05-17-2021
DWG. 36 OF 40
MK501
E5 CONVECTOR PIPING DIAGRAM
NO SCALE
MK501
F5 WALL MOUNTED CABINET HEATER
NO SCALE MK501
F6 HOT WATER UNIT HEATER PIPING
NO SCALE MK501
F8 PIPE HANGERS
NO SCALEMK501
F3 WATER COIL PIPING DIAGRAM
NO SCALE
MK501
E3 EQUIPMENT RAIL
NO SCALEMK501
E1 STEAM MAIN DRIP
NO SCALE
MK501
D6 PREFABRICATED ROOF CURB
NO SCALE MK501
D8 PIPE PORTAL
NO SCALE
MK501
C8 MPS DRIP TO LPC
NO SCALE
J.G.D. K.K.S.
MK501
F1 COIL SUPPORT
NO SCALE
| 21-B-069 - RICHARD GROUP RFI'S |
| MK501 DETAILS |
| Sheets and Views |
| MK501 |
| X616307-Det0076 CONVECTOR PIPING DIAGRAM |
| X616307-Det0096C WALL MOUNTED CABINET HEATER |
| X616307-SD230511-21 |
| X616307-SD238200-06 |
| X616307-Det0130B WATER COIL PIPING DIAGRAM |
| X616307-Det0052 EQUIPMENT RAIL |
| X616307-Det0002 STEAM MAIN DRIP |
| X616307-Det0051A PREFABRICATED ROOF CURB |
| X616307-Det0057 PIPE PORTAL |
| X001 - MPS DRIP TO LPC |
| X0012 COIL SUPPORT |