583-24-511 - Site Visit Summary.docx

DOCX document 15 KB Posted

Attached to
Z1DA--Correct Fire and Smoke Damper Deficiencies - 583-24-511
Solicitation number
36C25024B0056
Issued by

About this file

This document is a Site Visit Summary for a federal contract opportunity to correct fire and smoke damper deficiencies at a Department of Veterans Affairs (VA) facility.

The key details are:

  • The project requires correcting 109 deficient dampers, including replacing fusible links, repairing/replacing dampers, investigating/repairing unknown state dampers, inspecting/installing access doors, repairing access doors, and connecting/repairing actuators. It also requires replacing current smoke dampers with mixing dampers.
  • The Infection Control Risk Assessment (ICRA) indicates 76 dampers in low risk areas, 19 in medium risk areas, and 14 in high risk areas.
  • The related federal contract opportunity is Solicitation Number 36C25024B0056 - Z1DA--Correct Fire and Smoke Damper Deficiencies - 583-24-511, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

File Type Posted
2022 Damper Locations.pdf PDF
36C25024B0056 0002.docx DOCX document
IMG_0228.jpeg JPEG file
36C25024B0056 0001.docx DOCX document
IMG_0227.jpeg JPEG file
Bid Schedule.docx DOCX document
Attachment II - RFI Template.doc DOC document
36C25024B0056_1.docx DOCX document
Attachment VI - Damper Corrections.pdf PDF
Attachment V - Specifications.pdf PDF
Attachment III - EMR.docx DOCX document
Attachment IV - VHA Directive 1192-01.pdf PDF
Attachment I - Wage Determination.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

583-24-511 Correct Fire and Smoke Damper Deficiencies Site Visit 5/15/2024 COR: Sean Palmer

Project Requirements: Correct 109 Deficient Dampers

· Fire Dampers:

· Replace Fusible Links

· 10

· Repair/Replace Damper

· 18

· Unknown State, Investigate/Repair

· 37

· Inspect/Install Access Door

· 9

· Repair Access Door

· 3

· Connect/Repair Actuator

· 8

· Smoke Dampers

· Replace current smoke dampers with mixing dampers.

· 24

· Infection Control Risk Assessment (ICRA) Requirements

· Low Risk Areas:

· 76 Dampers

· Medium Risk Areas:

· 19 Dampers

· High Risk Areas:

· 14 Dampers

· Tour

· Smoke Dampers in A-6144

· Fire Dampers A-150 Mechanical Room

· Fire Dampers in D-Wing 3rd floor Electrical Room