539-CSI-204 DRAWINGS ADDENDUM 1.pdf
PDF 7 MB Posted
- Attached to
- C1DA--Prepare Site for PET-CT 539-CSI-204
- Solicitation number
- 36C25020B0056
About this file
This notice provides information for an upcoming solicitation for project 539-CSI204 entitled "Prepare Site for PET-CT" to be issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. The project scope involves preparing a site for a PET-CT scanner and related medical equipment and systems. The solicitation will be a 100% set-aside for small business concerns with a preference for service-disabled veteran-owned small businesses. The NAICS code is 236220 for commercial and institutional building construction with a size standard of $39.5 million. The contractor must be registered in the Vendor Information Pages and SAM databases. The project value is between $500,000 and $1 million and must be completed within 180 days of the notice to proceed. Bonds will be required. Interested offerors should register on the notice.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| PreBid meeting minutes for Prep Site for PET CT.pdf | ||
| 36C25020B0056 0004.docx | DOCX document | |
| RFI LPA response.docx | DOCX document | |
| Site Visit Sign in.pdf | ||
| CLARIFICATION OF BID SUBMISSIONS.docx | DOCX document | |
| 36C25020B0056 0003.docx | DOCX document | |
| 36C25020B0056 0002.docx | DOCX document | |
| Wage Determinations General Decision Number OH20200082.pdf | ||
| 36C25020B0056 0001.docx | DOCX document | |
| 539-CSI-204 SPECIFICATION 2020 0127.pdf | ||
| 539-CSI-204 CD DRAWINGS 0127-2020.pdf | ||
| Contractor Certification Regarding EMR 02.docx | DOCX document | |
| Contractor Certification Regarding EMR.docx | DOCX document | |
| RFI Form.docx | DOCX document | |
| 36C25020B0056_1.docx | DOCX document | |
| WAGE DETERMINATIONS.6.23.20.docx | DOCX document | |
| 539-CSI-204_Brand Name Justification Honeywell Fire Alarm -1851.docx | DOCX document |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M001
INDEX, LEGEND, AND GENERAL
NOTES 01
INDEX OF DRAWINGS
SHEET DESCRIPTION
PARTIAL FIRST FLOOR AND ROOF PLAN - REMOVALS AND NEW WORK
1-M104
SECOND FLOOR PLAN - REMOVALS AND NEW WORK1-M102
DETAILS, SCHEDULES, CONTROLS AND AUTOMATION
M601
JAC MNT
DUCT THERMOSTAT WITH AVERAGING ELEMENT
DUCT STATIC PRESSURE SENSOR
DUCT HUMIDITY SENSOR
ROOM SENSOR: TEMPERATURE, HUMIDITY
LENGTH IN DUCT WHEN SPACE PERMITS)
REMOTE BULB THERMOSTAT
ROOM CONTROL: THERMOSTAT, HUMIDISTAT
DIFFERENTIAL PRESSURE SWITCH
DUCT TEMPERATURE SENSOR WITH AVERAGING ELEMENT
SMOKE DETECTOR (SEE ELECTRICAL SPECIFICATIONS)
DUCT OR PIPE TEMP. SENSOR
DUCT OR PIPE THERMOSTAT (NOTE 1: PROVIDE 12" MIN.
AFTER FILTER
CURRENT SENSING RELAY
AIR FOIL WHEEL (FAN)
AIR HANDLING UNIT
ANALOG INPUT
AIR PRESSURE DROP
ANALOG OUTPUT
AUTOMATIC TEMPERATURE CONTROLS
BACKWARD INCLINED WHEEL (FAN)
AIR FLOW MEASURING DEVICE
ABOVE FINISHED FLOOR
DIFFERENTIAL OR STATIC PRESSURE TRANSMITTER
CLEAN OUT
CEILING GRILLE
CEILING DIFFUSER
CEILING REGISTER
COLD WATER (POTABLE)
DIGITAL OUTPUT
DIGITAL INPUT
DIRECT DIGITAL CONTROLS
DRY BULB TEMPERATURE, DEG. F
AUTOMATIC CONTROL DAMPER
EXHAUST FAN
ENGINEERING CONTROL CENTER
DOUBLE WIDTH DOUBLE INLET (FAN)
DOOR UNDERCUT BY GENERAL CONTRACTOR
ITEM. (TO BE USED AS AN AID IN COORDINATING THE
LISTED SIZE OF DUCT, PIPE, DEVICE OR EQUIPMENT
APPROXIMATE ELEVATION FROM FLOOR TO CENTER OF
MANUAL VOLUME DAMPER
U/C
VARIOUS TRADES.)
FIRE DAMPER
BUTTERFLY VALVE
CIRCUIT SETTER
BALL VALVE
COMBINATION BALANCING/SHUT-OFF VALVE
MANUAL AIR VENT
AUTOMATIC FLOW CONTROL VALVE
TEST PLUG (PRESSURE/TEMPERATURE)
SAFETY VALVE OR PRESSURE RELIEF
PRESSURE REDUCING VALVE
STRAIGHT-THRU TWO-POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
STRAIGHT-THRU MODULATING CONTROL VALVE
EX.
EF
EXISTING
DWDI
ECC
DI
DO
DB
DDC
D
Db
DECIBELS
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
EQUIPMENT ABBREVIATION (SUPPLY FAN)
SUPPLY FAN NO.3 IN BUILDING NO.1
SHEET NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
RETURN DUCT (UP & DOWN)
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
EXHAUST OR RETURN TOP REGISTER OR GRILLE,
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE,
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
SUPPLY DUCT (UP & DOWN)
INCLINED RISE, IN DIRECTION OF AIR FLOW
NEW DUCT - WIDTH X DEPTH
RECTANGULAR ELBOWS WITH VANES EVEN IF
VANED ELBOW (PROVIDE ALL SQUARE OR
INCLINED DROP, IN DIRECTION OF AIR FLOW
ACOUSTICAL DUCT LINING
STANDARD RADIUS ELBOW
R
10/8
FC
D
SYMBOL IS MISSING)
FLEXIBLE CONNECTION
UP
(WALL TYPE)
(WALL TYPE)
DN
UP
1-01
1-SF3
AIR HANDLING UNIT NUMBER
TERMINAL UNIT DESIGNATION
TYPICAL UNIT NO.
DN
SECTION LETTER
ECCENTRIC REDUCER
DIRECTION OF FLOW
CAPPED OUTLET
SIDE CONNECTION
EXISTING WORK.
ACCESSORIES
INVERTED BUCKET TRAP SET INCLUDING PIPING
POINT OF CONNECTION BETWEEN NEW AND
RISE OR DROP IN PIPE
BOTTOM CONNECTION, 45 DEG. OR 90 DEG.
TOP CONNECTION, 45 DEG. OR 90 DEG.
REDUCER OR INCREASER
DIRECTION OF PIPE PITCH (DOWN)
THERMOMETER
UNIVERSAL (2-BOLT) INVERTED BUCKET TRAP STATION
STRAINER
GATE VALVE
PRESSURE GAGE
CHECK VALVE
GLOBE VALVE
PIPING ACCESSORIES
FLOAT AND THERMOSTATIC TRAP SET INCLUDING
GATE VALVE WITH 3/4" HOSE END ADAPTER
EXISTING PIPE TO BE REMOVED
DRAIN LINE
UNION
D
CW
CR
CO
CG
CD
BIW
ATC
AFW
AI
APD
AO
AHU
AFM
AFF
AF
VENT LINE
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
LOW PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG & BELOW)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
NUMBER INDICATES STEAM PRESSURE
NUMBER INDICATES STEAM PRESSURE
LPR
V
HWS
HWR
LPS (5)
MPS (30)
MPR
HEATING
SP
S
F
T
H
T
T H
WET BULB TEMPERATURE, DEG. FWb
MAXIMUM
OUTSIDE AIR
PRE-FILTER
PUMPED CONDENSATE
PREHEAT COIL
RELATIVE HUMIDITY
SUPPLY FAN
STEAM HUMIDIFIER
TRANSFER GRILLE
UNIT HEATER
STATIC PRESSURE (INCHES OF WATER)
PRESSURE REDUCING VALVE
PRESSURE DROP (FEET OF WATER)
TOP REGISTER (WALL TYPE)
VARIABLE FREQUENCY DRIVE
STATIC PRESSURE SENSOR
DOOR UNDERCUT BY GENERAL CONTRACTOR
SPS
TR
U/C
VFD
UH
V
TG
VALVE
S.P.
SH
SF
Rh
PD
PF
PH
PRV
MAX
O.A.
NOM
MIN
PC
NOMINAL
MINIMUM
HEATING COIL
HORSEPOWER
FLR.
HC
HP
FLOOR
BLOW UNLESS OTHERWISE NOTED)
CEILING DIFFUSERS (FOUR WAY
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHS
CHR
AIR CONDITIONING
CONTROL CIRCUIT CONN.
H1 N
ETCHED CLEAR LACQUER
E.C.L.
WHITE BAKED ENAMELW.B.E.
BRAKE HORSEPOWER
BHP
BRITISH THERMAL UNIT
BTU
BRITISH THERMAL UNIT PER HOUR
BTUH
CUBIC FEET PER MINUTE
CFM
DEGREE
DEG
DIAMETER
DIA
DIFFERENTIAL PRESSURE SENSOR
DPS
ENTERING
ENT
F
FAHRENHEIT
FPM
FEET PER MINUTE
FT
FEET
GALLONS PER MINUTE
GPM
HEAD
HD
CHILLED WATER RETURN
CHR
CHILLED WATER SUPPLY
CHS
INCHES
IN
INCHES WATER COLUMN
IN WC
INCHES WATER GAUGE
IN WG
LEAVING AIR TEMPERATURE
LAT
LEAVING
LVG
MBH
1000 BTUH
MERV
MINIMUM EFFICIENCY REPORTING VALUE
NC
NOISE CRITERIA
REVOLUTIONS PER MINUTE
RPM
SMOKE DAMPER (SUPPLY)
SDS
SMOKE DAMPER (RETURN)
SDR
STEAM PRESSURE REDUCING VALVE
SPRV
VOLUME DAMPERVD
HIGH PRESSURE STEAM CONDENSATE RETURN
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
NUMBER INDICATES STEAM PRESSURE
HPS (125)
HPR
PIPE UP
PIPE DOWN
IN-LINE CENTRIFUGAL FAN
ICF
T
T
T
T
H dP
CS
DP SP
1-MS4
A
H7
9'-6"
MV
MANUAL AIR VENT
ABBREVIATIONS
CONTROLSPIPING SYMBOLS
DRAWING SYMBOLS
DUCTWORK SYMBOLS
GENERAL NOTES
GENERAL
VALVES
ABBREVIATIONS
EXHAUST DUCT (UP & DOWN)
UP DN
PUMPED CONDENSATE RETURNPC
EXPANSION TANK PIPE
ET
FCU
FAN COIL UNIT
PUMP
P
PROPELLER UNIT HEATER
PUH
RETURN FAN
RF
WATER FILTERWF
POWER TYPE ROOF VENTILATOR
RV
POWER TYPE WALL VENTILATORWV
COR
PROPELLER TYPE EXHAUST FANPEF
RETURN AIR
R.A.
SUPPLY AIR
S.A.
SINGLE WIDTH SINGLE INLET (FAN)
SWSI
SPECIFIC GRAVITY
SP. GR.
ACCESS DOOR
AD
FCW
FOWARD CURVED WHEEL (FAN)
FC
FLEXIBLE CONNECTION
ENERGY EFFICIENCY RATIO
EER
EXHAUST AIR
E.A.
CONTRACTING OFFICER'S REPRESENTATIVE
AIR SEPARATOR
AS
ANGLE GLOBE VALVE
PIPE GUIDE
PIPE ANCHOR
ORIFICE UNION
STAINLESS STEEL DUCT
DOMESTIC HOT WATER SUPPLYDHW
DOMESTIC HOT WATER RECIRCULATIONDHWR
COMBINATION AXIAL/BACKWARD CURVED WHEEL
A/BCW
UTILITY SET FANUSF
T
GENERAL
DOMESTIC COLD WATER
W
FLOW METER
PIPE MOUNTED DDC TEMPERATURE SENSOR
TOP GRILLE (WALL TYPE)TG
WATER GAUGEWG
WATTSW
VARIABLE AIR VOLUMEVAV
THERMOSTATTSTAT
TOTAL STATIC PRESSURETSP
SMOKE DETECTOR
SD
SUPPLY AIR TEMPERATURE
SAT
OUTSIDE DIAMETER
OD
N.C.
NORMALLY CLOSED
N.O.
NORMALLY OPEN
MCA
MINIMUM BRANCH CIRCUIT AMPACITY
LEAVING WATER TEMPERATURE
LWT
ENTERING WATER TEMPERATURE
EWT
EXTERNAL STATIC PRESSURE
ESP
DIRECT EXPANSION
DX
ENTERING AIR TEMPERATURE
EAT
1 ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED CHASE OR ABOVE THE SUSPENDED CEILING.
2 ACCESS PANELS IN NON ACCESSIBLE SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC.
3 FOR TYPICAL STEAM, WATER AND REFRIGERANT PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD DETAILS AND PIPING
SCHEMATICS.
4 PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO PROVIDE COUNTER FLOW BETWEEN HEATING
MEDIUM AND AIR.
5 WHERE DUCTS OR PIPES ARE REMOVED THRU BUILDING ELEMENT THAT IS TO REMAIN, PATCH BUILDING OPENING TO MATCH
EXISTING WHERE OPENING IS NOT RE-USED.
6 ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED.
7 ALL CUTTING AND PATCHING REQUIRED FOR THE PROJECT WORK SHALL BE INCLUDED IN THE CONTRACT. REFINISH ANY SURFACE
DISTURBED UNDER THIS WORK TO MATCH EXISTING.
8 COORDINATE ABOVE CEILING WORK WITH CEILING REPLACEMENT. REFER TO ARCHITECTURAL DRAWINGS.
9 ALL WALL & FLOOR PENETRATIONS SHALL BE FIRESTOPPED TO RETARD PASSAGE OF FIRE & SMOKE.
10 UNLESS NOTED OTHERWISE, ALL WORK IN CORRIDOR OUTSIDE OF PET-CT SUITE, OR WORK THAT REQUIRES SHUTDOWN OF
SYSTEMS SERVING AREAS OUTSIDE OF PET-CT SUITE, SHALL TAKE PLACE AT NIGHT (GENERALLY BETWEEN 7PM AND 5AM) OR ON
WEEKENDS - COORDINATE WITH COR.
11 ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE VA. ITEMS NOT DESIRED BY THE VA SHALL BE REMOVED FROM THE
PREMISES AND DISPOSED OF PROPERLY BY THE CONTRACTOR.
12 REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
13 THE CONTRACT DRAWINGS ARE NOT INTENDED TO SHOW EVERY VERTICAL OR HORIZONTAL OFFSET WHICH MAY BE NECESSARY
TO INSTALL THE SYSTEMS. COORDINATE WORK IN ADVANCE WITH ALL OTHER TRADES AND REPORT IMMEDIATELY ANY
ANTICIPATED INSTALLATION ISSUES.
14 FIELD VERIFY EXISTING CONDITIONS, INCLUDING DUCT, PIPE AND EQUIPMENT SIZES, SERVICES AND LOCATIONS PRIOR TO
PERFORMING WORK.
15 ALL EXISTING DUCTWORK, PIPING, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED SHALL BE REMOVED. THE MAJORITY OF WORK
TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL ABANDONED UTILITY ITEMS THAT MAY NOT BE SHOWN BUT ARE
ASSOCIATED WITH THE REMOVAL WORK.
16 RE-INSULATE DUCTWORK AND PIPING WHERE EXISTING INSULATION HAS BEEN DAMAGED OR REMOVED IN THE PERFORMANCE OF
WORK IN THIS PROJECT.
17 ALL WORK MUST BE COORDINATED WITH THE CONTRACTING OFFICER AND COR TO MAINTAIN OPERATION OF THE EXISTING
FACILITY.
18 EXISTING CONDITIONS SHOWN ARE BASED UPON AVAILABLE EXISTING DRAWINGS, AND MAY DIFFER FROM ACTUAL WORK IN PLACE.
THE CONTRACTOR SHALL TAKE ALL NECESSARY FIELD MEASUREMENTS AND FIELD VERIFY ALL CONDITIONS AFFECTING THE
EXECUTION OF THE WORK. ANY VARIATION BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT
DOCUMENTS WHICH MAY IMPACT THE PROGRESS OF THE WORK SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING
OFFICER IN WRITING FOR RESOLUTION BEFORE PROCEEDING WITH THE WORK.
19 CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS
SHALL BE COORDINATED WITH THE COR.
20. ALL NEW EQUIPMENT INCLUDING SPLIT-SYSTEM AC UNITS, CONDENSING UNITS, VAV BOXES, HUMIDIFIERS, ETC. SHALL BE
PROVIDED WITH AN EQUIPMENT LABEL. OUTDOOR EQUIPMENT LABELS SHALL BE WEATHER RESISTANT. COORDINATE ALL
EQUIPMENT NUMBERS WITH THE VA PRIOR TO ORDERING LABELS.
21. EQUIPMENT VA TAGS FOR ANY REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE COR PRIOR TO REMOVING THE EQUIPMENT
FROM THE SITE.
22. SELF-ADHESIVE MARKERS SHALL BE INSTALLED ON CEILING GRID TO IDENTIFY SHUTOFF VALVES.
DOMESTIC HOT WATER SUPPLY
DHW
DOMESTIC HOT WATER RECIRCULATION
DHWR
FREE STEAM (LOW PRESSURE STEAM)
FS(5)
M
VALVE ON RISE/DROP (LOCATED IN VERTICAL PIPE)
(REFER TO DETAIL FOR ADDITIONAL SPECIALTIES)
SST
CS
PT
SP
AFMS
AIRFLOW MEASURING STATION
CURRENT SWITCH (FAN STATUS INDICATION)
START-STOP RELAY FOR FAN
FAN SPEED CONTROL SIGNAL
PRESSURE TRANSMITTER
TT TEMPERATURE TRANSMITTER
OS ROOM OCCUPANCY SENSOR(S)
DPT DIFFERENTIAL PRESSURE TRANSMITTER
PS PRESSURE SWITCH
DETAILS
M501
INDEX, LEGEND, AND GENERAL NOTESM001
DUPLEX PLUME EXHAUST FAN PACKAGE
DPF
CONSTANT VOLUME REHEAT TERMINAL UNIT
CVR
VARIABLE VOLUME REHEAT TERMINAL UNITVVR
SIMPLEX PLUME EXHAUST FAN
SPF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i l e
P a t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201
PARTIAL SECOND FLOOR PLAN - AIR BALANCE1-M102C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201 1-M102
SECOND FLOOR PLAN - REMOVALS
& NEW WORK 01
SCALE: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - REMOVALS
JAC MNT
SCALE: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - NEW WORK
SECOND FLOOR KEY PLAN
NO SCALE
SECOND FLOOR KEY PLAN
NO SCALE
1. EXISTING DUCTWORK TO REMAIN.
2. REMOVE EXISTING SPLIT SYSTEM AC INDOOR UNIT, ASSOCIATED
REFRIGERANT PIPING, CONTROLS, SUPPORTS, ACCESSORIES,
ETC.
3. REMOVE ALL EXISTING SPLIT SYSTEM AC SUPPLY DUCTWORK.
4. REMOVE EXISTING SPLIT SYSTEM AC RETURN DUCTWORK TO
EXTENTS INDICATED.
5. REMOVE EXISTING SPLIT SYSTEM AC RETURN DUCTWORK BACK
TO THIS POINT AND CAP.
6. REMOVE EXISTING HOT WATER SUPPLY AND RETURN PIPING
BACK TO THIS POINT FOR RECONNECTION TO NEW WORK.
7. REMOVE EXISTING AIR DEVICE. EXISTING DUCTWORK AND
BALANCE DAMPER TO REMAIN.
8. REMOVE EXISTING AIR TERMINAL UNIT, ASSOCIATED DUCTWORK,
CONTROLS, SUPPORTS, ACCESSORIES, ETC.
9. EXISTING HEATING HOT WATER SUPPLY AND RETURN PIPING TO
REMAIN.
10. REMOVE EXISTING CONDENSATE PIPING BACK TO THIS POINT FOR
RECONNECTION TO NEW WORK.
11. REMOVE EXISTING DOMESTIC WATER SUPPLY PIPING BACK TO
MAIN AND CAP.
12. PROVIDE NEW HORIZONTAL MOUNTED ABOVE CEILING, DIRECT
DRIVE SPLIT SYSTEM AC INDOOR UNIT (1-AC1).
13. PROVIDE FLEXIBLE DUCT CONNECTIONS AT SPLIT SYSTEM
INDOOR UNIT INLET AND OUTLET.
14. REFRIGERANT PIPING UP TO CONDENSING UNIT ON THIRD FLOOR
ROOF. REFER TO SHEET 1-M104 FOR ROOFING PLAN.
15. PROVIDE REFRIGERANT PIPING AND ACCESSORIES PER THE
MANUFACTURER'S RECOMMENDATIONS. ROUTING OF
REFRIGERANT PIPING IS APPROXIMATE FROM SPLIT SYSTEM AC
INDOOR UNIT TO DUCT SHAFT UP TO CONDENSING UNIT ON ROOF.
16. MAINTAIN REQUIRED CLEARANCE TO SERVICE EQUIPMENT.
17. PROVIDE NEW AIR DEVICE AND CONNECT TO EXISTING
DUCTWORK. BALANCE TO INDICATED CFM.
18. PROVIDE NEW CONSTANT VOLUME AIR TERMINAL UNIT (22-04).
BALANCE TO 600 CFM.
19. CONNECT NEW TERMINAL UNIT DUCTWORK TO EXISTING SUPPLY
MAIN.
20. CONNECT NEW TERMINAL UNIT DUCTWORK TO EXISTING SPLIT
SYSTEM AC UNIT RETURN DUCTWORK AT THIS LOCATION.
21. CONNECT EXISTING DUCT TO NEW SPLIT SYSTEM AC RETURN
DUCTWORK.
22. PROVIDE NEW DUCT MOUNTED REHEAT COIL (1-RH1). PROVIDE
SPACE SENSOR LOCATED IN ROM C204B TO CONTROL DUCT
REHEAT CONTROL VALVE. SPACE SENSOR SHALL REUSE
EXISTING RACEWAY AND BOX FROM REMOVED THERMOSTAT.
23. CONNECT NEW EXHAUST DUCT TO EXISTING EXHAUST MAIN AT
THIS LOCATION.
24. CONNECT EXISTING CONDENSATE PIPING TO NEW AC UNIT
25. REROUTE EXISTING EXHAUST DUCTWORK SERVING ROOM C204F
LOCATED ABOVE THE CORRIDOR CEILING AS REQUIRED TO
ACCOMMODATE REMOVAL AND INSTALLATION OF VAV TERMINAL
BOX AND SUPPLY DUCTWORK.
26. REMOVE EXISTING AIR DEVICE AND ASSOCIATED DUCTWORK,
ACCESSORIES, ETC.
27. REMOVE EXISTING DUCT MOUNTED HOT WATER REHEAT COIL
AND ASSOCIATED CONTROLS, ACCESSORIES, SUPPORTS, ETC.
28. REMOVE EXISTING WALL MOUNTED HUMIDIFIER AND ASSOCIATED
CONTROLS, ACCESSORIES, SUPPORTS, ETC.
29. PROVIDE NEW DUCT MOUNTED REHEAT COIL (1-RH2). PROVIDE
SPACE SENSOR LOCATED IN ROM C204E TO CONTROL DUCT
REHEAT CONTROL VALVE. SPACE SENSOR SHALL REUSE
EXISTING RACEWAY AND BOX FROM REMOVED THERMOSTAT
FROM 1-AH1.
30. RELOCATE EXISTING SPRINKLER PIPING INSTALLED ADJACENT TO
EXISTING SPLIT SYSTEM AC UNIT AS REQUIRED TO
ACCOMMODATE THE NEW EQUIPMENT.
31. RELOCATE EXISTING DOMESTIC WATER PIPING INSTALLED ABOVE
EXISTING SPLIT SYSTEM AC UNIT AS REQUIRED TO
ACCOMMODATE THE NEW EQUIPMENT. NEW PIPING SHALL MATCH
EXISTING, INCLUDING PIPING MATERIAL, FITTING TYPE, JOINING
METHOD, HANGERS, AND INSULATION.
32. REMOVE EXISTING DUCT TO THIS POINT FOR RECONNECTION TO
NEW WORK.
33. PROVIDE NEW ELECTRIC HUMIDIFIER (1-HUM1).
34. THERMOSTAT FURNISHED BY 1-AC-1 EQUIPMENT MANUFACTURER
AND INSTALLED BY DIVISION 23.
35. PROVIDE CHECKPOINT TEMPERATURE AND HUMIDITY SENSORS
AND TIE INTO EXISTING VA CHECKPOINT MONITORING SYSTEM.
36. CONNECT TO FULL SIZE OF EXISTING DUCT AT THIS POINT.
PLAN NOTES
10"D
O
V
D
1.5"
1.25"
26/14
RH1
8/10
8"D
1-AH1
1"
12/12
12/12
0.75"
10/10
RH1
6/6
1"
1-AH1
0.5"
6/6
DUCT SHAFT
10"D
O
V
D
1.5"
1"
1.25"
1 1
25 25
12/12
1-AC1
1"
36/14
CG2-24x12
CG2-24x12
CG2-24x12
CG1-22x10
8"D
10"D
22-04
12/10
CD1-8"D
CD1-10"D
26/18
22/18 16/16
(4)CD1-14"D
1-AC1
1-RH1
CD1-10"D
12/12
CG1-24x24 x x
CG2-24x48
1-RH2
CAT Scan
Room
C204
Gamma
Camera
C205
Uptake
Prep Bay
C204A
Uptake
Area
C204B
Uptake
Prep Room
C204C
PET/CT
Scanner
C204D
Cath Lab
C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Control
Room
C204E
Tlt.
C204F
Tele.
C208
Gamma
Camera
C210
Closet
C216R
CAT Scan
Room
C204
Gamma
Camera
C205
Uptake
Prep Bay
C204A
Uptake
Area
C204B
Uptake
Prep Room
C204C
PET/CT
Scanner
C204D
Cath Lab
C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Control
Room
C204E
Tlt.
C204F
Tele.
C208
Gamma
Camera
C210
Closet
C216R
0.75"
0.5"
1 1
VOLUME
DAMPER
(TYP)
x
UP
DN UP DN
DN UP
UP
C2056
A/C Shaft
A/C Shaft
PET/CT
SCANNER
RM C204D
UP
DN UP DN
DN UP
UP
C2056
A/C Shaft
A/C Shaft
PET/CT
SCANNER
RM C204D
A. COORDINATE AND SCHEDULE (MINIMUM 3 WEEKS NOTICE) IN
ADVANCE WITH COR, DOWNTIME OF ALL UTILITIES REQUIRED FOR
PERFORMANCE OF THIS WORK.
B. REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS, AND
ADDITIONAL GENERAL NOTES.
GENERAL NOTES
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201 1-M102C
PARTIAL SECOND FLOOR PLAN -
AIR BALANCE 01
SCALE: 1/8" = 1'-0"
PARTIAL SECOND FLOOR PLAN
JAC GEH
NO SCALE
SECOND FLOOR KEY PLAN
NO SCALE
1. EXISTING AIR DEVICE TO REMAIN - BALANCE TO CFM INDICATED.
2. EXISTING AIR DEVICE TO REMAIN. PROVIDE SHEETMETAL CAP
OVER EXISTING AIR DEVICE AND ENSURE AIRTIGHT SEAL.
3. DURING AIR BALANCE, IF EXHAUST AIRFLOWS CANNOT BE
ACHIEVED FOR ANY OUTLETS ON THIS DUCT BRANCH,
GRADUALLY DECREASE CORRIDOR EXHAUST AIRFLOW BELOW
300 CFM UNTIL SPECIFIED BALANCE AIRFLOWS FOR ALL OTHER
OUTLETS ON THIS BRANCH CAN BE ACHIEVED, AND NOTE FINAL
AIRFLOW FOR CORRIDOR EXHAUST GRILLE.
PLAN NOTES
A. COORDINATE AND SCHEDULE (MINIMUM 3 WEEKS NOTICE) IN
ADVANCE WITH COR, DOWNTIME OF ALL UTILITIES REQUIRED FOR
PERFORMANCE OF THIS WORK.
B. REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS, AND
ADDITIONAL GENERAL NOTES.
C. REFER TO SHEET 1-M104 FOR LOCATION OF EXISTING EXHAUST
FAN 1-EF13 TO BE REBALANCED.
GENERAL NOTES
Reading
C202
CAT Scan
Room
C204
Uptake
Prep Bay
C204A
Uptake
Area
C204B
Uptake
Prep Room
C204C
PET/CT
Scanner
C204D
Echo Room Echo Rm
C250
Cath Lab
C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Control
Room
C204E
Tlt.
C204F
Tele.
C208
Chief Off.
Reading
Rm.
C250A
Off.
B235A
Off.
B234D
Cancer
Registry
B234E
Chief
B234F
Off.
B234G
Cardiac
Cath Lab
C216
Tele.
C220
Stor.
C221
Elec.
C222
Lockers
C223
Lab Lounge
C224
Hemo Stor.
C225
Mech.
C226
Storage
C232
HAC
C234
Storage
C235
Off.
C237
Break Rm.
C238
HAC
C239
Off.
C240
Off.
C241
Off.
C242
Off.
C243
Off.
C244
Stor.
C245
Exam
C246
EKG Rm.
C247
Tlt.
C248
Scope
Wash
C216A
Soil Ut.
C216B
Clean Linen
C216C
Observ.
C216D
Transfer
C216E
Radiology
Spec Rm.
C216F
Scrub Area
C216G
Cath Lab
C216H
Control
C216I
Equip
C216J
Prep Mon
C216K
Sterile
Supply
C216L
Vestibule
C216M
Control Rm.
C216N
Bone
Density Lab
C211
Tlt.
C216Q
Womens
C2001
Office
B235B
Closet
C216R
Mechanical
C232A
Up to
1-EF13
12/12 x
UP
DN UP DN
DN UP
UP
C2056
A/C Shaft
A/C Shaft
AREA OF
WORK
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201 1-M104
PARTIAL FIRST FLOOR AND ROOF
PLAN - REMOVALS & NEW WORK 01
JAC MNT
SCALE: 1/8" = 1'-0"
PARTIAL ROOF PLAN - REMOVALS AND NEW WORK
FOURTH FLOOR KEY PLAN
NO SCALE
SCALE: 1/8" = 1'-0"
PARTIAL FIRST FLOOR PLAN - REMOVALS AND NEW WORK
1. EXISTING EXHAUST FAN TO REMAIN.
2. EXISTING PLUMBING VENT TO REMAIN.
3. EXISTING CONDENSING UNIT AND ALL ASSOCIATED REFRIGERANT
PIPING, WIRING, ETC. TO REMAIN.
4. REFRIGERANT PIPING DOWN TO INDOOR SPLIT SYSTEM AC ON
SECOND FLOOR. RE-USE EXISTING ROOF CURB, AND SEAL
PENETRATIONS WEATHER TIGHT.
5. REPLACE EXISTING REFRIGERANT PIPING AND INSTALL NEW
REFRIGERANT PIPING AND ACCESSORIES PER THE
MANUFACTURER'S RECOMMENDATIONS.
6. REMOVE EXISTING CONDENSING UNIT AND REPLACE WITH NEW.
7. MODIFY EXISTING ROOF SUPPORTS AS REQUIRED TO
ACCOMMODATE NEW EQUIPMENT.
8. MODIFY EXISTING ROOF SUPPORTS FOR NEW REFRIGERANT
PIPING.
9. ACCESS TO THE ROOF FROM FOURTH FLOOR PENTHOUSE.
10. EXISTING AIR DEVICE TO REMAIN. COVER AND SEAL AIR DEVICE
WITH PLASTIC FOR THE DURATION OF ALL CONSTRUCTION
ACTIVITIES TO PREVENT DUST INTRUSION/CONTAMINATION.
11. EXISTING AIR DEVICE TO REMAIN. NO WORK REQUIRED.
12. EXISTING DX FAN COIL UNIT TO REMAIN. TURN OFF FAN COIL UNIT
INDOOR AND OUTDOOR UNITS FOR THE DURATION OF ALL
CONSTRUCTION ACTIVITIES, AND TURN BACK ON AFTER WORK IS
COMPLETE, AREA HAS BEEN CLEANED, AND TEMPORARY WALLS
HAVE BEEN REMOVED.
13. EXISTING AIR TERMINAL UNIT. COORDINATE WITH COR TO SET
SUPPLY AIR FLOW SETPOINT TO 0 CFM FOR THE DURATION OF ALL
CONSTRUCTION ACTIVITIES.
14. EXISTING AIR TERMINAL UNIT TO REMAIN. NO WORK REQUIRED.
15. EXISTING DUCTWORK TO REMAIN.
16. EXISTING WALL MOUNTED THERMOSTAT TO REMAIN. COVER AND
SEAL THERMOSTAT WITH PLASTIC FOR THE DURATION OF ALL
CONSTRUCTION ACTIVITIES TO PREVENT DUST
INTRUSION/CONTAMINATION.
17. PROVIDE HEPA FILTER FAN UNIT INSIDE TEMPORARY
CONSTRUCTION AREA TO MAINTAIN A MINIMUM OF 0.01" WG
NEGATIVE AIR PRESSURE INSIDE CONSTRUCTION AREA AT ALL
TIMES, RELATIVE TO ADJACENT PHARMACY C140. PROVIDE 24" X
24" EGG CRATE CEILING GRILLE IN CEILING OF C140, AND ROUTE
TEMPORARY DISCHARGE DUCT FROM HEPA FILTER FAN UNIT TO
CONNECT TO EGG CRATE GRILLE.
18. TEMPORARILY RELOCATE EXISTING DIFFUSER TO WEST SIDE OF
TEMPORARY WORK BARRIER. VERIFY EXACT PLACEMENT
LOCATION AT JOB SITE. EXTEND OR PROVIDE FLEX DUCT WORK
AS REQUIRED FOR THE RELOCATION. REINSTALL/PLACE
DIFFUSER IN ORIGINAL POSITION AFTER COMPLETION OF FIRST
FLOOR WORK.
19. EXISTING EXHAUST FAN SERVING 2ND FLOOR (INCLUDING PET/CT
SCANNER ROOM C204D AND ASSOCIATED TOILET ROOM C204F) TO
REMAIN. EXISTING FAN IS CONTROLLED BY VARIABLE
FREQUENCY DRIVE. REPLACE SHEAVES AS REQUIRED AND
REBALANCE FAN TO ACHIEVE 3,810 CFM EXHAUST AIRFLOW ON
2ND FLOOR - REFER TO SHEET 1-M102C FOR BALANCE AIRFLOWS.
PLAN NOTES
A. COORDINATE AND SCHEDULE (MINIMUM 3 WEEKS NOTICE) IN
ADVANCE WITH COR, DOWNTIME OF ALL UTILITIES REQUIRED FOR
PERFORMANCE OF THIS WORK.
B. REFER TO SHEET M001 FOR LEGEND, ABBREVIATIONS, AND
ADDITIONAL GENERAL NOTES.
GENERAL NOTES
DN
IRM
Network
Operation
Center
A437
Comp.
Programmer
Off.
A439
Computer
Off.
A440
Chief Rm.
A441
Corridor
C*4*1
Tlt.
A439A
Staff
Physician
B403A
Neuro
Office
B439
Regular
E.E.G
B403B
E.E.G.
Control &
Observation
B403
F. Tlt.
B406
M. Tlt.
B407
B433A
Mic Rotomy
B435
Microscope
Core
B436
Office
B437
Evoked
Potential
Lab
B438
Copier
Room
B437A
Mech Room
A456E
1-CU1
1-EF13
DN
A/C Shaft
A/C Shaft
A/C Shaft
FOURTH
FLOOR
ROOF
AREA
MOBILE SHELVING (TYP)
DN
Corridor
C*1*14
Off.
C129
Elec.
C126
Pharmacy
C140B
Compund
C140A
Stair 7
S*1*7
Storage
C135A
Corridor
C*1*22
APPROXIMATE WALL
LINE OF TEMPORARY
GYP CONSTRUCTION
BARRIER BY GENERAL
CONTRACTOR. (TYP 2)
11 11
15 (TYP)
15 (TYP)
15 (TYP)
(TYP)
TEMPORARY
CONSTRUCTION
DOOR
Receiving
C134G
APPROXIMATE AREA OF MAIN WORK SPACE BELOW
SECOND FLOOR (ABOVE 1ST FLOOR PHARMACY CEILING)
PERTAINING TO MECHANICAL WORK. VERIFY EXACT
EXTENT OF WORK SPACE PROVISIONS (LOCATION OF
TEMPORARY WORK BARRIERS) WITH ARCHITECTURAL
DRAWINGS AND COR. ALL WORK REQUIRED WITHIN ROOM
C140, C140A AND C134G IS TO BE COMPRISED OF 40 HOURS
OF CONTINUOUS WORK. THIS CONTINUOUS WORK SHALL
BE INCLUSIVE OF MULTIPLE SHIFTS AND 24 HOUR
COVERAGE. IT CAN BE ASSUMED THIS WORK TO BE IN
CONJUNCTION WITH WEEKEND OR HOLIDAY DATES. EXACT
DATES TO BE COORDINATED WITH COR.
Pharmacy
C140
M501
DETAILS
JAC MNT
CONICAL OUTLET
BRANCH DUCT
THERMAL INSULATION
SEE SPECIFICATIONS
THERMAL INSULATION
SEE SPECIFICATIONS
BRANCH DUCT
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
AIR
FLOW
AIR
FLOW
A I R
F L O
W
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
DAMPER
MANUAL VOLUME
DAMPER
1/4 W OR
4" MIN.
AIR
FLOW
MAIN SUPPLY
DUCT
W
A I R
F L O
W
SQUARE ELBOW SHOWN.
PROVIDE ROUND ELBOW
WHEN SHOWN ON PLANS
NOTES:
1.
2.
3.
4.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" RADIUS, 1 1/2" MAXIMUM
SPACE BETWEEN VANES AND A 3/4" TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20", VANES SHALL BE DOUBLE
VANE TYPE.
W
W1
VANE
VANE
NOTES:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL
OR BE
GREATER
THAN W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
W
R
R
W
W
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W W
W
W
1/6W
R
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
M
A
X
M
A
X
E Q
U I P
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
A
X
M
A
X
M A
X
M
A
X
FROM STRUCTURE
SAME AS DIFFUSER
INLET: 5'-0" MAX
FLEXIBLE DUCT SIZE
LENGTH.
12"
CEILING
SUPPORT SADDLE
VOLUME DAMPER W/
LOCKING QUAD
SADDLE
SHEET METAL
FOR CHANGE OF
DIRECTION GREATER
USE RIGID ELBOWS
THAN 45°
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
TYPICAL DIFFUSER
IN EXISTING PLASTER
OR LAY-IN CEILING
THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE MAIN DUCT CFM ANYTIME,
AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000 FPM OR LESS. THE AIR SPLIT DUCT
TAKE-OFF SHALL BE USED IN ALL OTHER CASES
MANUAL VOLUME
1/8" CLEARANCE
ALL AROUND
SECTIONSIDE ELEVATION
STIFFEN BLADE
AS REQUIRED
DUCT
1/2" ROUND ROD PIN
INSULATION
STAND-OFF
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
OUTSIDE END BEARING
DAMPER BLADE
INSULATION SEE
SPECIFICATION
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
NOTES:
1.
2.
420ONE 1 x 18 GA. STRAP36
TWO 1/2 DIA. RODS
TWO 3/8 DIA. RODS
ONE 1 x 16 GA. STRAP
50 700
ONE 1 x 22 GA. STRAP
QUANTITY/SIZE
MAX. DUCT
HANGER STRAPS OR RODS
MAX. LOAD
LBS.
MAX.
IN.
SPACING
DIA. - IN.
IN.
50" DIA. &
UNDER
LOAD RATED
FASTENERS
BAND OF SAME
SIZE AS HANGER
STRAP
HANGER RODS
OVER 50" DIA.
BAND
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
DUCTWORK TRANSITIONS
SUPPLY DUCTWORK TAKE-OFFS
DUCTWORK SQUARE VANE ELBOWS
FLEXIBLE AIR DUCT CONNECTOR
DUCTWORK RADIUS ELBOWS
VOLUME DAMPER DETAIL
ROUND DUCT HANGERS
DAMPER WHERE
TURNING VANES
STRAP HANGER
251 CFM TO 400 CFM - 10" DIA.
401 CFM TO 700 CFM - 12" DIA.
101 CFM TO 250 CFM - 8" DIA.
100 CFM AND LESS - 6" DIA.
ARE TO BE SIZED AS FOLLOWS:
BRANCH DUCT SIZES, UNLESS NOTED ON PLANS
BRANCH DUCT TAKE-OFF WITH MANUAL DAMPER.1
STRAP HANGER
SPIN-IN TAP
FITTING
6" MIN
RETURN/
EXHAUST DUCT
CEILING
CEILING DEVICE
RECTANGULAR
DUCT, NOTE 1
MANUAL
DAMPER
STRAP HANGER
SCHEDULED
SPIN-IN BRANCH TAP FITTING
WITH MANUAL DAMPER
SHEETMETAL PLENUM
SAME SIZE AS AIR DEVICE
NOTES:
RETURN OR EXHAUST GRILLE/REGISTER CONNECTION
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
ON THIS SHEET
ROUND DUCT - NOTE 2
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR FLOW
W
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
45 DEG.
EXHAUST OR RETURN
BRANCH DUCTWORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201
PIPE HANGERS
5 FT
6 8 10
9 1110 12
1312 14
1614 17 2219 23
28 3230
20 2418 14 16128
1064 532 2 1/2 1 1/2
1 1 1/4
THRU 3/4
7 7
SIDE VIEW TRAPEZE HANGER FOR UP TO 1000
LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE
43 - SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
1/2" DIA. HANGER
RODS WITH 36" MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
FT.
FT.
M
A X
NOTE: SEE SPECIFICATIONS FOR
DETAILED HANGER REQUIREMENTS
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED CONNECTION
ON FAN SIDE
WASHER
1-1/2" MIN. TO 3" MAX. INSTALLED. 6"
NOMINAL WITH MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" DRAW BAND
1"x1/8" BAND IRON
BOLT ON 4" CENTERS
5/16" FLANGE
DUCT
SHEET METAL SCREWS ON
12" CENTERS
RIVET ON 4"
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" BAND IRON
BOLT ON 4" CENTERS
1" FLANGE & HEMALTERNATE
POSITION
OF BOLT
1 1/2" POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1/2" 1/2" 1 1/2"
1 1/2" MIN. TO 3" MAX. INSTALLED. 6"
NOMINAL WITH MATERIAL TAUT
FLANGED
CONNECTION ON
FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
FLEXIBLE DUCT CONNECTIONS
STEEL EXPANSION SHIELD FOR EXISTING CONSTRUCTION AND
INSERTS FOR NEW CONSTRICTION. THIS TYPE SHALL BE USED
ONLY IN SLABS OR BEAMS OF 4" MIN DEPTH
3/8" MIN DIA EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND INSERTS
FOR NEW CONSTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGLE
NUTS & WASHERS
3/8" MIN DIA HANGER
RODS
FOR PIPES UNDER 2" IN SIZE USE 1-1/2"x1-1/2"x1/4"
ANGLE. ALL PIPES 2" & LARGER USE 3"x3"x1/4"
ANGLE
TURNBUCKLE
3/8" MIN DIA
HANGER RODS
3/8" MIN DIA INSERTS
NEW CONSTRUCTION
ONLY.
SECURING HANGER RODS IN CONCRETE
M601
DETAILS, SCHEDULES, CONTROLS
AND AUTOMATION 01
JAC MNT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201
AIR DISTRIBUTION DEVICES
SURFACE
TYPE MOUNTING
DESCRIPTION
EGGCRATE CEILING GRILLE
SYMBOL
CG1
LAY-IN
FINISH
E.C.L.
STEEL
ALUM.
MATERIAL
W.B.E.
SEE NOTE
SQUARE PLAQUE DIFFUSERCD1
HOT WATER HEATING COIL SCHEDULE
LOCATIONMARK
1-RH1
C204A
CFM
AIR TEMPERATURE
MAX
FACE VEL
FPM
MAX
APD
IN-WG
EAT (F)
DB
LAT (F)
DB
HOT WATER
FLOW
GPM
EWT
(DEG.F)
LWT
(DEG.F)
495 600 530.2 72 1.0 0%180
APPLICATION
REHEAT
GLYCOL
MINIMUM
TOTAL CAP
BTUH
10,350
1-RH2
C204E 235 600 530.2 72 0.5 0%180REHEAT 160 4,910
HVAC DESIGN DATA
DESIGN
CONDITIONS
OUTDOOR DESIGN
CONDITIONS
INDOOR DESIGN DATA
SUMMER
TEMP (DEG.F)
DB WB
%HUMIDITY
WINTER
TEMP (DEG.F)
DB DP
%HUMIDITY
PET-CT ROOM
92.7 75.1 44.6% 8.2 3.0 N/A
72.0 60.0 50% 68 40 35%
SPLIT SYSTEM AC UNIT SCHEDULE
CONDENSING
UNIT
MARK
1-AC1
1-CU1
FAN
CFM
NOMINAL
COOLING
CAPACITY
96 MBH
ELECTRIC
REHEAT
VOLTAGE PHASE FLA MOP
460 3 17.1 2511.5 kW
CONTROLS GENERAL NOTES
1 A COMPLETE SYSTEM OF AUTOMATIC TEMPERATURE CONTROLS SHALL
BE INSTALLED UNDER THIS PROJECT AS REQUIRED TO ACCOMPLISH THE
SPECIFIED SEQUENCES OF OPERATION.
2 DIVISION 26 SCOPE OF WORK INCLUDES A POWER SOURCE TO THE
MOTOR STARTERS. ALL HVAC POWER SOURCES REQUIRED BEYOND
THESE STARTERS OR BEYOND SOURCES EXPLICITLY SHOWN ON THE
DIVISION 26 DRAWINGS, SHALL BE PROVIDED UNDER THE TEMPERATURE
CONTROLS WORK. THIS SHALL INCLUDE BUT NOT BE LIMITED TO WIRING,
CONDUIT, TRANSFORMERS, RELAYS, FUSES, ETC.
3 THERMOWELLS FOR INSTALLATION OF TEMPERATURE SENSORS SHALL BE
FURNISHED UNDER THE TEMPERATURE CONTROLS WORK AND SHALL BE
INSTALLED AS PART OF THE HVAC PIPING WORK. PIPING WORK SHALL
INCLUDE PROPERLY SIZED WELDOLET OR THREADOLET FITTINGS PLACED
WHERE DIRECTED BY THE CONTROL SYSTEM SUPPLIER.
4 POINTS SHOWN ARE INTENDED AS AN AID TO THE CONTRACTOR
INDICATING THE MINUMUM POINTS REQUIRED FOR CONTROL AND
MONITORING. ALL INPUT AND OUTPUT POINTS, AND THEIR REQUIRED
INTERFACE AND ACCESSORY HARDWARE, SHALL BE PROVIDED FOR A
COMPLETE AND FUNCTIONAL CONTROL SYSTEM. IF ADDITIONAL POINTS
ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL
SPECIFIED, THESE POINTS, ALONG WITH ADDITIONAL DIRECT DIGITAL
CONTROL PANEL(S) (IF REQUIRED), SHALL ALSO BE PROVIDED.
5 AS-BUILT SEQUENCES OF OPERATION SHALL BE PROVIDED ON THE
CONTROL GRAPHICS FOR ALL EQUIPMENT.
ABSORPTION COFFICIENT (REFERENCE 10 [-12] WATTS) WITH 3" S.P. DIFFERENTIAL ACROSS UNIT AT MAXIMUM CFM SETTING.
1 CONTROL TYPES - C.V.: CONSTANT VOLUME TERMINAL, V.V.: VARIABLE VOLUME TERMINAL.
2 THE UNIT MAXIMUM SP IS ALSO THE MINIMUM PRESSURE REQUIRED AT THE UNIT INLET TO OBTAIN THE RATED CFM.
3 UNIT NOISE LEVEL SELECTION SHALL NOT EXCEED A ROOM NC OF 35 FROM BOTH AIRBORNE AND RADIATED NOISE, BASED ON A 10 DB ROOM
NOTES :
APPROX.
NO.
UNIT
22-04
CFM
INLET
SIZE
(IN.)
AIR TERMINAL UNIT SCHEDULE
ACROSS
UNIT AT
SOUND
REQUIREMENTS
ROOM NC
MAXIMUM
3.0"
UNIT
SP
AT
MAX.
MAX.
SP
CFM
(2)
0.35"
MAX.
NC
(3)
ROOM
TYPE
(1)
CONTROL
C.V.
NOTES :
D-1
A F
M D
T-1
T
TAG
DEVICE
DESCRIPTION
DEVICE
POINT TYPE
DI DO AI AO
AIR TERMINAL UNIT CONTROL POINT LIST
AFMS-1
SUPPLY AIRFLOW MONITORING STATION X
D-1
VAV PRIMARY AIR DAMPER X
AFMS-1
T-1
SUPPLY AIR TEMPERATURE SENSOR X
1. GENERAL
1.1
1.2
THE TERMINAL UNIT DAMPER SHALL BE MODULATED TO MAINTAIN A CONSTANT AIRFLOW VOLUME
OF 600 CFM TO PROVIDE OUTSIDE REQUIRED OUTSIDE AIRFLOW FOR THE PET-CT SUITE.
SUPPLY AIR TEMPERATURE SENSOR SHALL BE PROVIDED FOR REFERENCE ONLY.
AIR TERMINAL UNIT CONTROL DIAGRAM
H
C
V-1
H W
R
H W
S
T-1 T
SPACE SENSOR
TAG
DEVICE
DESCRIPTION
DEVICE
POINT TYPE
DI DO AI AO
DUCT REHEAT CONTROL POINT LIST
T-1
SPACE TEMPERATURE SENSOR X
HEATING WATER CONTROL VALVE
V-1
DUCT REHEAT CONTROL DIAGRAM
1. GENERAL
1.1 DDC ROOM THERMOSTAT (T-1) SHALL CONTROL THE HEATING WATER VALVE (V-1). ON A DROP IN
SPACE TEMPERATURE BELOW SPACE SETPOINT 72°F (ADJ), THE CONTROL SYSTEM SHALL
MODULATE THE HEATING WATER CONTROL VALVE OPEN. ON A RISE IN SPACE TEMPERATURE
ABOVE THE SPACE SETPOINT, THE HEATING WATER CONTROL VALVE SHALL CLOSE.
X
SPLIT SYSTEM AC UNIT INTEGRATION
1. GENERAL
1.1
1.2
INTEGRATE SPLIT SYSTEM AC UNIT TO BAS HEAD-END VIA BACNET INTERFACE AND PROVIDE
EQUIPMENT GRAPHICS AT HEAD-END. INTEGRATE ALL AVAILABLE BACNET POINTS, INCLUDING BUT
NOT LIMITED TO SPACE TEMPERATURE, SPACE HUMIDITY, OPERATING STATUS AND ALARMS.
PROVIDE OCCUPANCY SCHEDULE FOR NIGHT SETBACK OF SPACE TEMPERATURE. COORDINATE
INITIAL SCHEDULE AND TEMPERATURE SETPOINTS WITH THE VA.
DUCT COIL PIPING DETAIL
VAV BOX
SOLID DUCT
2'-0"
45 DEGREE
COMBINATION
BOOT SADDLE TAP
BRANCH DUCT
MAIN SUPPLY DUCT
DIRECTION OF AIRFLOW
TERMINAL UNIT DUCT DETAIL
TYPICAL MANUAL AIR VENT
AIR VENT
1/2" BALL VALVE
1/4" COPPER TUBING
1/2" x 4" NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS AS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO NEAREST DRAIN.
MV
OR
AV
DRAIN VALVE AND AIR VENT
CONNECTIONS (HYDRONIC SYSTEMS)
TYPICAL CHILLED AND HOT WATER PIPING DRAIN VALVE CONNECTIONS
ELEVATION
THREADED PIPING
ELEVATION
WELDED PIPING
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE
THREAD-PROVIDE HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
EGGCRATE FILTER GRILLECG2
1 WALL MOUNTED.
2 FURNISH WITH BLOWER PACK. MAINTAIN MANUFACTURER'S REQUIRED CLEARANCES.
3 RECONNECT TO EXISTING PLUMBING SUPPLY WATER PIPING AND DRAIN CONNECTIONS.
NOTES :
MARK
1-HUM1
CAPACITY
TYPE
ELECTRODE
HUMIDIFIER SCHEDULE
ELECTRICAL
REQUIREMENTS
VOLTAGE PHASE
GPM
FILL RATE
0.2
LBS/HR
CANISTER
AMPS
18 / 25
GPM
DRAIN
1.6
RATE
LB
NET/FULL
WEIGHT
83/93
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION CONNECTIONS
(TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MODULATING
CONTROL VALVE
AUTOMATIC FLOW
CONTROL VALVE
STRAINER WITH
BLOW DOWN
OA
CFM
E.S.P
1.2
MAXIMUM SIZE
W H
D
48.75" 26.5" 72"
EQUIPMENT DATA
1-CU1
OUTDOOR CONDENSING UNIT
OUTDOOR PROP FAN CONDENSING UNIT - R-407C REFRIGERANT
ELECTRIC: 460 VOLT, 3 PHASE, 18.1 FLA, 20.6 MCA, 30 MOP
SIZE: 53" W x 5.5" D x 36.25" H
UNIT SHALL INCLUDE ALLOW LOW AMBIENT OPERATION DOWN TO -30°F.
OUTDOOR RATING CONDITIONS: 95 DEG.F AMBIENT.
4 PROVIDE TOUCHSCREEN CONTROLLER TO DISPLAY HUMIDITY READING AND ADJUSTABLE HUMIDITY SETPOINT.
5 PROVIDE STANDARD DRAIN WATER COOLING TO COOL DRAIN WATER TO MEET LOCAL PLUMBING CODES.
1. PROVIDE WITH MICROPROCESSOR CONTROLS.
MCA
21.4
MAX. WT.
LB.
(FLA/MOCP)
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201 1-EL102
SECOND FLOOR LIGHTING PLAN -
REMOVALS & NEW WORK 01
SCALE: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - REMOVALS
TDL RJH
SCALE: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - NEW WORK
SECOND FLOOR KEY PLAN
NO SCALE
1. EXISTING WALL MOUNTED "X-RAY IN USE" LIGHTING FIXTURE TO
REMAIN.
2. EXISTING CEILING MOUNTED LIGHTING DEVICE. REMOVE AND
REINSTALL ON NEW CEILING SIMILAR TO CURRENT MOUNTING.
3. CONNECT TO EXISTING CRITICAL POWER 277V LIGHTING CIRCUIT
PREVIOUSLY SERVING LIGHTING IN THIS SPACE.
4. PROVIDE NEW DEVICE AS INDICATED. INSTALL IN EXISTING WALL
BOX.
5. DISCONNECT AND REMOVE EXISTING "CAN" LIGHTING FIXTURE.
6. DISCONNECT AND REMOVE EXISTING 2' X 4' LIGHTING FIXTURE.
7. FIXTURE A: PROVIDE NEW 2' X 4' X 4-3/8" DP WHITE ONE PIECE
20GA STEEL CONSTRUCTION VOLUMETRIC RECESSED TROFFER
LIGHTING FIXTURE: L.E.D., 4000K, WITH ACRYLIC LENS WITH
DIFFUSER TRIM RINGS, 90CRI, WITH MULTI-VOLT DRIVER AND
0-10V DIMMING DOWN TO 1%. FIXTURE SHALL BE ADDRESSABLE
AND CAPABLE OF COMMUNICATING WITH WALL CONTROL STATION
USING STANDARD CAT-6a CABLING FOR ON/OFF/DIMMING
CONTROL FEATURES AS INDICATED ON PLAN DRAWINGS. FIXTURE
SHALL HAVE ENERGY STAR LABEL. (A3=3000 LUMEN OUTPUT,
A4=4800LUMEN OUTPUT, A6=6000 LUMEN OUTPUT)
8. FIXTURE B: PROVIDE NEW 2' X 2' X 4-3/8" DP WHITE ONE PIECE
20GA STEEL CONSTRUCTION VOLUMETRIC RECESSED TROFFER
LIGHTING FIXTURE: L.E.D., 4000K, WITH ACRYLIC LENS WITH
DIFFUSER TRIM RINGS, 90CRI, 3000 LUMEN OUTPUT, WITH
MULTI-VOLT DRIVER AND 0-10V DIMMING DOWN TO 1%. FIXTURE
SHALL BE ADDRESSABLE AND CAPABLE OF COMMUNICATING WITH
WALL CONTROL STATION USING STANDARD CAT-6a CABLING FOR
ON/OFF/DIMMING FEATURES AS INDICATED ON PLAN DRAWINGS.
FIXTURE SHALL HAVE ENERGY STAR LABEL.
9. FIXTURE C: PROVIDE NEW 2' X 4' X 1/2" DP (1.70" DP INCLUDING
DRIVER) WHITE FLAT PANEL CONSTRUCTION RECESSED
MOUNTED LIGHTING FIXTURE: L.E.D., 4000K, WITH DIFFUSE LENS,
90CRI, 5000 LUMEN OUTPUT, WITH MULTI-VOLT DRIVER AND 0-10V
DIMMING DOWN TO 1%. FIXTURE SHALL BE ADDRESSABLE AND
CAPABLE OF COMMUNICATING WITH WALL CONTROL STATION
USING STANDARD CAT-6a CABLING FOR ON/OFF/DIMMING
FEATURES AS INDICATED ON PLAN DRAWINGS. FIXTURE SHALL
HAVE ENERGY STAR LABEL.
10. REMOVE DEVICE AS INDICATED FROM WALL BOX.
11. PROVIDE WARNING LIGHT CONTROL BOX. "X-RAY IN USE"
WARNING LIGHT SHALL BE "ON" WHILE PET/CT SCANNER IS IN USE.
PROVIDE ALL CONDUIT, BOXES, WIRING, RELAYS, ETC. FOR A
COMPLETE OPERATIONAL SYSTEM.
12. CONNECT LOAD TO EXISTING 120V CIRCUIT PREVIOUSLY SERVING
"X-RAY IN USE" LIGHTING.
13. PROVIDE LOW VOLTAGE CONTROLLER ABOVE CEILING AS
REQUIRED TO ACCOMPLISH ON/OFF DIMMING AT ASSOCIATED
WALL CONTROL STATION(S). PROVIDE ALL LOW VOLTAGE
CABLING AS REQUIRED FOR A COMPLETE DIMMING SYSTEM AS
INDICATED
PLAN NOTES
E
E
E
EE
E
E
E
E
E
CR2A
C2A
T1
LS2A R2F
R2B
R2A
DP2
CR2A1
L2A
E
E
E
EE
E
E
E
E
E
CR2A
C2A
T1
LS2A R2F
R2B
R2A
DP2
CR2A1
L2A
L
E
TYP
TYP
TYP
TYP
L 1
E
TYP
5 TYP
TYP
TYP
TYP
TYP
TYP
CAT Scan
Room
C204
Gamma
Camera
C205
Uptake
Prep Bay
C204A
Uptake
Area
C204B
Uptake
Prep Room
C204C
PET/CT
Scanner
C204D
Cath Lab
C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Control
Room
C204E
Tlt.
C204F
Tele.
C208
Gamma
Camera
C210
Closet
C216R
Gamma
Camera
C205
Cath Lab
C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Tele.
C208
Gamma
Camera
C210
Closet
C216R
D
D
D
D
10 TYP
10 TYP
10 TYP
TYP
10 TYP
10TYP
10 TYP
10 TYP
L
E
C
C
C
C
A4 A4
A4 A4
A4 A4
TYP (6)
L 1
E
ER
ER
ER
A3
A6
A3
TYP (3)
CAT Scan
Room
C204
Uptake
Prep Bay
C204A
Uptake
Area
C204B
Uptake
Prep Room
C204C
PET/CT
Scanner
C204D
Control
Room
C204E
Tlt.
C204F
ER
"C2A"
BB
B
C
C 13
C
C
LC
LC
LC
LC
LC
LC
ER
CP
CP
3/4" C. TO PDU
OS
PassagePassage
UP
DN UP DN
DN UP
UP
C2056
A/C Shaft
A/C Shaft
PET/CT
SCANNER
RM C204D
ELEC
RM C209
ELEC
RM A253A
NOTE - UNDER DEDUCT ALTERNATE 1:
EXISTING LIGHTING SHALL BE REMOVED FROM THE CEILING GRID AS
REQUIRED FOR ALL TRADES TO ACCOMPLISH WORK THEN CLEANED AND
REINSTALLED UPON WORK COMPLETION. EXISTING CIRCUITING AND
SWITCHING SHALL REMAIN AS IS.
TYPE A3, A4, A6, B AND (2 OF 4) C LIGHTING FIXTURES AS WELL AS
ASSOCIATED LOW VOLTAGE CONTROLLERS, OCCUPANCY SENSORS, WALL
SWITCHES, WALL CONTROL STATIONS AND ASSOCIATED CONDUIT AND
WIRING/CABLING WILL BE DELETED FROM THE PROJECT.
ONLY THE (2) TYPE C LIGHTING FIXTURES LOCATED IN THE PASSAGE AREA
OF CAT SCAN ROOM C204 WILL REMAIN IN THE PROJECT (REPLACING THE
TWO LIGHTING FIXTURES CURRENTLY LOCATED IN THEIR PLACE) AND BE
CONNECTED INTO THE EXISTING LIGHTING SWITCH LEG.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
F i t h
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PREPARE SITE FOR PET-CT
CINCINNATI, OH
539-CSI-204
Project Director
01/27/2020Revisions: Date:
Cincinnati V.A.
Medical Center
ADDENDUM #1 08/24/20201 1-EP102
SECOND FLOOR POWER PLAN -
REMOVALS & NEW WORK 01
SCALE: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - REMOVALS
TDL RJH
SCALE: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - NEW WORK
SECOND FLOOR KEY PLAN
NO SCALE
1. RECESSED WALL DUCT. SEE "PET/CT SCANNER ROOM - EAST
WALL ELEVATION" DETAIL, SHEET E001 FOR ADDITIONAL
INFORMATION.
2. PROVIDE (3) #2 AWG AND (1) #1/0 AWG IN 1-1/ 2" CONDUIT. CIRCUIT
TO EXISTING DISTRIBUTION PANEL "DS-1X" AS INDICATED.
CONDUCTORS SHALL HAVE NO SPLICES PER G.E. REQUIREMENTS.
NOTE: EXISTING CONDUIT MAY BE UTILIZED IF PRACTICAL. SEE
EAST WALL ELEVATION AND PARTIAL BASEMENT FLOOR PLAN ON
SHEET E-001 FOR ADDITIONAL INFORMATION. SEE KEY PLAN THIS
SHEET FOR LOCATION REFERENCE.
3. EXISTING STRUCTURALLY SUPPORTED RAIL/LIFT SYSTEM TO
REMAIN.
4. DISCONNECT AND REMOVE ELECTRICAL FEED SERVING EXISTING
ROOF-TOP CONDENSING UNIT. UNIT IS LOCATED ON THIRD FLOOR
ROOF DIRECTLY ABOVE. PREPARE EXISTING FEED FOR
RECONNECTION TO NEW UNIT. NEW UNIT TO BE INSTALLED IN
SIMILAR LOCATION. VERIFY EXACT REQUIREMENTS. SEE
MECHANICAL DRAWINGS.
5. DISCONNECT AND REMOVE EXISTING WEATHERPROOF
CONVIENCE RECEPTACLE ADJACENT TO ROOF-TOP CONDENSING
UNIT BACK TO POINT OF RECONNECTION. RECEPTACLE AND
ROOF-TOP CONDENSING UNIT ARE LOCATED ON THIRD FLOOR
ROOF DIRECTLY ABOVE.
6. DISCONNECT AND REMOVE ELECTRICAL FEED SERVING EXISTING
ABOVE CEILING AIR HANDLING UNIT COMPLETE BACK TO SOURCE.
EXISTING CONDUIT MAY BE REUSED IF PRACTICAL TO FEED NEW
UNIT. NEW UNIT TO BE INSTALLED IN SIMILAR LOCATION. VERIFY
EXACT REQUIREMENTS. SEE MECHANICAL DRAWINGS.
7. REMOVE EXISTING 25A/3P CIRCUIT BREAKER IN PANEL "C2A"
(POSITIONS 14,16,18) CURRENTLY SERVING ROOF-TOP
CONDENSING UNIT. PROVIDE NEW 30A/3P CIRCUIT BREAKER IN
SAME POSITION TO MATCH EXISTING.
8. RECONNECT TO EXISTING CIRCUIT PREVIOUSLY SERVING
REMOVED CONDENSING UNIT. ROUTE (3) #10 AWG AND (1) #10
AWG GND IN 3/4" CONDUIT. PROVIDE FINAL CONNECTIONS TO
NEW ROOF-TOP CONDENSING UNIT.
9. REMOVE EXISTING 20A/3P CIRCUIT BREAKER IN PANEL "C2A"
(POSITIONS 2,4,6) CURRENTLY SERVING AIR HANDLING UNIT.
PROVIDE NEW 25A/3P CIRCUIT BREAKER IN SAME POSITION TO
MATCH EXISTING.
10. ROUTE (3) #10 AWG AND (1) #10 AWG GND IN 3/4" CONDUIT TO NEW
CIRCUIT BREAKER IN PANEL "C2A". PROVIDE FINAL CONNECTIONS
TO NEW AIR HANDLING UNIT.
11. PROVIDE NEW WEATHER PROOF GFCI RECEPTACLE. EXTEND
EXISTING CIRCUIT AS REQUIRED. PROVIDE ALL MOUNTING
HARDWARE FOR A COMPLETE INSTALLATION. VERIFY EXACT
REQUIREMENTS.
12. DISCONNECT LIGHTNING PROTECTION SYSTEM CONDUCTOR
CURRENTLY BONDED TO EXISTING ROOF TOP MECHANICAL
EQUIPMENT AS REQUIRED TO ACCOMMODATE THE EQUIPMENT'S
REMOVAL.
13. DISCONNECT AND REMOVE EXISTING 100A/3P CIRCUIT BREAKER IN
RECESSED ENCLOSURE. REMOVE FEEDER CONDUCTORS AND
CONDUIT BACK TO SOURCE (DS-1X). OPENING TO BE REPAIRED
BY GENERAL CONTRACTOR. NOTE: EXISTING CONDUIT MAY BE
REUSED FOR NEW FEEDER IF PRACTICAL. SEE NOTE 2, THIS
SHEET.
14. PROVIDE 30A/3P NON-FUSED HEAVY DUTY DISCONNECT SWITCH IN
NEMA ENCLOSURE AS INDICATED. PROVIDE ALL MOUNTING
HARDWARE AS REQUIRED FOR A COMPLETE INSTALLATION.
VERIFY EXACT REQUIREMENTS.
15. DISCONNECT AND REMOVE "EMERGENCY POWER OFF" BUTTON.
16. NEW 4-WIRE "EMERGENCY POWER OFF" BUTTON FURNISHED BY
G.E. AND INSTALLED BY ELECTRICAL CONTRACTOR. TO BE
INSTALLED IN EXISTING WALL BOX FROM PREVIOUS "EPO" SWITCH.
PROVIDE ALL CONDUIT, WIRING, BOXES ETC. FOR A COMPLETE
AND OPERATIONAL SYSTEM.
17. DISCONNECT AND REMOVE ELECTRICAL FEED TO EXISTING
HUMIDIFIER UNIT. REWORK EXISTING FEED FOR EXTENSION TO
NEW HUMIDIFIER. REMOVE EXISTING 3-POLE CIRCUIT BREAKER
FROM BRANCH PANEL CURRENTLY SERVING THE UNIT. VERIFY
EXACT REQUIREMENTS.
18. PROVIDE 25A/2P CIRCUIT BREAKER IN BRANCH PANEL TO MATCH
EXISTING IN SPACE CREATED FROM REMOVED 3-POLE CIRCUIT
BREAKER. PROVIDE STAINLESS STEEL COVER PLATE AND ELBOW
FITTING AT EXISTING WALL BOX. EXTEND EXISTING ELECTRICAL
FEED FROM WALL BOX TO NEW HUMIDIFIER UNIT AND PROVIDE
LIQUID-TIGHT CONDUIT FINAL CONNECTIONS. COORDINATE WORK
WITH DIV 23.
19. EXISTING CEILING MOUNTED WI-FI DEVICE. TEMPORARILY HOLD
AND PROTECT UNIT ABOVE CEILING LINE. REINSTALL ON NEW
CEILING SIMILAR TO CURRENT MOUNTING.
20. DISCONNECT, REMOVE AND RELOCATE EXISTING CAMERA PER
OWNER'S DIRECTIVE. EXTEND CIRCUIT AS REQUIRED FOR A
COMPLETE RELOCATION.
21. DISCONNECT AND REMOVE FEEDER TO EXISTING PET/CT POWER
DISTRIBUTION UNIT.
22. DISCONNECT AND REMOVE 120V CIRCUIT CURRENTLY SERVING
EXISTING POWER DISTRIBUTION UNIT BACK TO SOURCE.
23. ELECTRICAL CONTRACTOR SHALL REROUTE SEVERAL
(APPROXIMATELY 10) EXISTING 3/4" OR 1" CONDUITS AND
ASSOCIATED JUNCTION BOXES CURRENTLY LOCATED ABOVE AND
ADJACENT TO EXISTING AIR HANDLING UNIT AS REQUIRED TO
ACCOMMODATE THE INSTALLATION OF NEW AIR HANDLING UNIT.
FIELD VERIFY AND COORDINATE EXACT REQUIREMENTS.
24. EXISTING RECEPTACLE TO REMAIN LOCATED IN CABINETRY.
25. EXISTING WALL CABINET TO REMAIN.
26. EXISTING WALL SWITCH FOR POWER TO RAIL/LIFT SYSTEM.
RELOCATE TO THE WEST APPROXIMATELY 24". SEE NEW WORK
PLAN.
PLAN NOTES
E
E
E
EE
E
E
E
E
E
CR2A
C2A
T1
LS2A R2F
R2B
R2A
DP2
CR2A1
L2A
E
E
E
EE
E
E
E
E
E
CR2A
C2A
T1
LS2A R2F
R2B
R2A
DP2
CR2A1
L2A
1-AH1
1-AC1
J
J
1-CU1
J
1-CU1
J
E
E
E E E
E
E
E
E
E
WP
H
A
B
G F
D
C
E
E
E
E E E
E
E
E
E
ER
E
E
CAT Scan
Room
C204
Gamma
Camera
C205
Uptake
Prep Bay
C204A
Uptake
Area
C204B
Uptake
Prep Room
C204C
PET/CT
Scanner
C204D
Cath Lab
C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Control
Room
C204E
Tlt.
C204F
Tele.
C208
Gamma
Camera
C210
Closet
C216R
CAT Scan
Room
C204
Gamma
Camera
C205
Uptake
Prep Bay
C204A
Uptake
Area
C204B
Uptake
Prep Room
C204C
PET/CT
Scanner
C204D
Cath Lab
C216O
Stor.
C216P
I.V. Prep
Rm.
C207
Elec.
C209
Control
Room
C204E
Tlt.
C204F Tele.
C208
Gamma
Camera
C210
Closet
C216R
E
C
EPO EPO
J
J
WP
E
E
ER
EM
EM
EM
E
E
E
E
E
E
E
E
E
E
E
EM
EM
EM
E
E
E
E
E
E
C2A-14,16,18
C2A-2,4,6
EXISTING 277/480V
BRANCH PANEL "C2A"
200A MCB
EXISTING 277/480V
BRANCH PANEL "C2A"
200A MCB
J
J
J
J
E
ER
E
I
DS-1X
C
ER
E
3R
480V/3PH
FLA 18.1A
480V/3PH
FLA 17A
SD
1-HUM1
208V/1PH
FLA 18A
UP
DN UP DN
DN UP
UP
C2056
A/C Shaft
A/C Shaft
PET/CT
SCANNER
RM C204D
ELEC
RM C209
ELEC
RM A253A
ELEC RM C008
IN BASEMENT
BELOW
PET/CT EQUIPMENT
A. PET/CT SCANNER GANTRY - FURNISHED/INSTALLED BY G.E.
B. CHILLER - FURNISHED/INSTALLED BY G.E.
C. PARC 4 - FURNISHED/INSTALLED BY G.E.
D. POWER DISTRIBUTION UNIT - FURNISHED/INSTALLED BY G.E.
E. OPERATOR'S CONSOLE - FURNISHED/INSTALLED BY G.E.
F. UPS - FURNISHED/INSTALLED BY G.E.
G. MAIN DISCONNECT - FURNISHED BY G.E., INSTALLED BY E.C.
H. POWER DISTRIBUTION BOX - FURNISHED BY G.E., INSTALLED BY E.C.
I. PATIENT TABLE - FURNISHED/INSTALLED BY G.E.
NOTE: SEE G.E. PIM DRAWINGS AND COORDINATE WITH G.E. PROJECT
MANAGER FOR ADDITIONAL/EXACT ELECTRICAL CONTRACTOR
INSTALLATION REQUIREMENTS.
NOTE:
CURRENTLY (3) MISCELLANEOUS ELECTRICAL PANELS HAVE BEEN FIELD
VERIFIED AS HAVING EQUIPMENT IDENTIFICATION LABELS WITH
ERRONEOUS VOLTAGE INFORMATION. EACH PANEL IS INDICATED AS
HAVING A 208 VOLTAGE BUT EACH IS A 480 VOLT PANEL. ELECTRICAL
CONTRACTOR SHALL PROVIDE A NEW IDENTIFICATION LABEL MATCHING
EXISTING STYLE BUT WITH THE CORRECTED 480V INFORMATION INCLUDED
FOR EACH OF THE FOLLOWING (3) ELECTRICAL PANELS. IDENTIFICATION
LABELS TO READ AS FOLLOWS:
(LOCATED IN ELEC RM C008) PANEL "DS-1X, 3 PH, 480V, FED FROM: US-1X"
(LOCATED IN ELEC RM C008) PANEL "DS-1P, 3 PH, 480V, FED FROM: US-1P"
(LOCATED IN ELEC RM A253A) PANEL "XRAY, 3 PH, 480V, FED FROM: US-1X"
SEE KEY PLAN THIS SHEET AND PARTIAL BASEMENT FLOOR PLAN ON
SHEET E001 FOR ELECTRICAL ROOM LOCATIONS. FIELD VERIFY ALL
ACTUAL VOLTAGES PRIOR TO RE-LABELING.
27. RELOCATED WALL SWITCH FOR POWER TO RAIL/LIFT SYSTEM.
RECESS MOUNT ON WALL AT 48" AFF. COORDINATE EXACT
LOCATION.
28. DISCONNECT, REMOVE AND RELOCATE EXISTING RECEPTACLE TO
SIMILAR LOCATION IN NEW FURRED OUT WALL.
29. EXISTING RECEPTACLE TO REMAIN LOCATED IN CABINETRY.
30. RECONNECT LIGHTNING PROTECTION SYSTEM CONDUCTOR TO
NEW MECHANICAL EQUIPMENT. MATCH EXISTING MATERIALS AND
WORKMANSHIP.
31. CONNECT SMOKE DUCT DETECTOR TO EXISTING BUILDING FIRE
ALARM SYSTEM FOR AIR HANDLING UNIT SHUT DOWN UPON
ACTIVATION OF DETECTOR. PROVIDE ALL RELAYS, CONDUIT,
WIRING, BOXES, ETC FOR A COMPLETE INSTALLATION. VERIFY
CORRECT OPERATION OF INITIATING CIRCUIT. COORDINATE
WORK WITH DIVISION 23.
32. PROVIDE REMOTE KEY TEST STATION WITH INDICATOR LAMPS
AND IDENTIFICATION NAMEPLATE (EXAMPLE: DUCT SMOKE
DETECTOR 1-AC1). PROVIDE ALL CONDUIT, BOXES, WIRING ETC
FOR A COMPLETE INSTALLATION. COORDINATE EXACT
PLACEMENT IN ADJACENT CEILING TILE.
PLAN NOTES (CONTINUED)
NOTE:
G.E. PET/CT INSTALLATION REQUIREMENT DRAWINGS HAVE BEEN
INCLUDED IN THE EQ-SERIES SHEETS OF THIS DRAWING SET FOR
GENERAL INFORMATION AND BIDDING PURPOSES. ELECTRICAL
CONTRACTOR SHALL REFER TO AND BE RESPONSIBLE FOR ANY
ADDITIONAL INSTALLATION REQUIREMENTS AS DEFINED IN THE
COMPLETE DISCOVERY MI PET/CT PROJECT INSTALLATION MANUAL.
COORDINATE ALL REQUIREMENTS WITH THE G.E. PROJECT
INSTALLATION MANAGER.
| G001 - ADDENDUM 1 |
| 1-A102 SECOND FLOOR PLAN |
| M001-M001 |
| M001 |
| M-FP-02-1-M102 |
| 1-M102 |
| M-FP-02_Balance-1-M102C |
| 1-M102C |
| M-FP-04-1-M104 |
| 1-M104 |
| M501-M501 |
| M501 |
| M601-M601 |
| M601 |
| EL-FP-02-1-EL102 |
| 1-EL102 |
| EP-FP-02-1-EP102 |
| 1-EP102 |