This document contains an addendum and federal contract opportunity notice. The addendum provides revisions to drawings and specifications for a project to correct medical unit privacy issues on the sixth floor of the Cincinnati VA Medical Center. Revisions include safety requirements for cranes, cubicle curtain track options, door hardware additions, and changes to cabling categories. The federal contract opportunity is a pre-solicitation notice for construction of a 6,130 square foot single story addition atop an inpatient bed tower. Required work includes new finishes, mechanical, electrical, technology, controls, fire alarm and security systems, with integration into existing equipment. The estimated period of performance is 780 calendar days. The solicitation is set aside for service-disabled veteran-owned small businesses. The North American Industry Classification System code is 236220 and size standard is $39.5 million. Bonds, a site visit, and registration on various websites are required.
36C25020B0005 0001 Addendum 01 - Specs, Drawings and Misc Explanations.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25020B0005-0006000.docx | DOCX document | |
| 36C25020B0005-0005000.docx | DOCX document | |
| 36C25020B0005-0003002.pdf | ||
| 36C25020B0005-0003001.pdf | ||
| 36C25020B0005-0003000.docx | DOCX document | |
| 36C25020B0005-0002000.docx | DOCX document | |
| 36C25020B0005-0001078.pdf | ||
| 36C25020B0005-0001074.docx | DOCX document | |
| 36C25020B0005-0001079.pdf | ||
| 36C25020B0005-0001080.pdf | ||
| 36C25020B0005-0001076.pdf | ||
| 36C25020B0005-0001077.pdf | ||
| 36C25020B0005-0001075.pdf | ||
| 36C25020B0005-077.docx | DOCX document | |
| 36C25020B0005-084.pdf | ||
| 36C25020B0005-083.docx | DOCX document | |
| 36C25020B0005-085.pdf | ||
| 36C25020B0005-078.pdf | ||
| 36C25020B0005-089.pdf | ||
| 36C25020B0005-090.pdf | ||
| 36C25020B0005-087.pdf | ||
| 36C25020B0005-086.pdf | ||
| 36C25020B0005-088.pdf | ||
| 36C25020B0005-080.pdf | ||
| 36C25020B0005-081.pdf | ||
| 36C25020B0005-091.pdf | ||
| 36C25020B0005-079.pdf | ||
| 36C25020B0005-082.docx | DOCX document | |
| 36C25020B0005-092.pdf |
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Correct Medical Unit Privacy Issues (6th Floor)
Cincinnati VAMC
Addendum No. 1
March 26, 2020
3200 Vine Street
Cincinnati, OH 45220
This Addendum supplements and amends the original Drawings and Specifications for the above referenced project. This Addendum shall be forwarded to all Prime Bidders and all appropriate building code authorities. This Addendum shall be taken into account in the preparation of bids and shall become a part of the Contract Documents.
Receipt of this Addendum must be acknowledged on the Bid Form.
This addendum consists of the following items:
General
1. Crane lifts are to be coordinated with COR and scheduled for evening and weekend times.
Specifications
Replace the specification manual in total. Reference clouds for revisions. The following is a summary of the changes in each section.
1. 01 35 25 Safety Requirements (1.19 Cranes):
a. Crane Operators shall not carry loads:
i. Over the general public or VA personnel.
ii. Over any occupied building unless:
1. The top two floors are vacated.
2. Or overhead protection with a design live load of 300 psf is provided.
2. 10 21 23 Cubicle Curtain Track
a. Contractors may use Imperial Fastener Company Track #IFC-98 with nylon roller, Inpro Optitrac or equivalent products.
3. 08 71 00 Door Hardware
a. Provide Automatic Door Bottoms (411ARL Mortise- PE) at doors 6008, 605, 616, 618, 603, 662, 670, 673, & 662.
b. Provide smoke seals at doors 605, 616, 618, 662, 673, & 662.
4. Specification Section 270511, 271000, 271100, 271500, 280500, 280513, 281300
a. Change all reference to Category 5E, and Category 6 to CATEGORY 6A. All horizontal structured cabling including jacks, cable, and patch panels to be Category 6A UTP solution.
Drawings
Replace the drawing set in total. Reference clouds for revisions. The following is a summary of the changes on each sheet.
1. 1AD106N
a. Correct empty keynotes: 2.13, 2.15, 2.18, 2.29, 2.76.
2. 1AD106S
a. Correct empty keynotes: 2.13, 2.15, 2.18, 2.29, 2.76.
3. A001
a. Wall types S1.0A and S2.0A added.
4. 1A106-A
a. Wall types S1.0A and S2.0A identified in rooms # A6007, A6007A, A6007B, A6006, A6006A, A6006B, A6005, A6005A, A6004, A6004A, A6003, A6003A.
5. 1A106-B
a. Correct empty keynotes: 2.13, 2.15.
6. 1A106-C
a. Correct empty keynotes: 2.13, 2.15.
7. 1A106-D
a. Correct empty keynotes: 2.13, 2.15.
8. 1A106-E
a. Correct empty keynotes: 2.13, 2.15.
9. 1A106-F
a. Correct empty keynotes: 2.13, 2.15.
10. 1A106-G
a. Correct empty keynotes: 2.13, 2.15.
b. Room A668 changed to Office.
c. Dimensions changes at Rooms A668 & A669.
11. 1A201
a. Correct inconsistent elevation numbers.
12. 1A202
a. Correct inconsistent elevation numbers.
13. 1A301
a. Correct inconsistent elevation numbers.
14. 1A302
a. Correct inconsistent elevation numbers.
15. 1A402
a. Changed keynote 12.51 to 12.43.
16. 1A601
a. Update Door Schedule to remove missing “Between RM” values.
b. Correct empty keynote: 9.21.
17. 1A612
a. Correct empty keynote: 9.21.
18. FX106
a. Revised room name and hazard classification in A668.
19. PP106S
a. Revised room name A668.
20. MD105
a. Revised piping note for reconnection in lieu of capping. Piping for new convector in Office A668 to be extended to this riser.
21. MD106N
a. Eliminated work associated with quench vents.
22. MD106NT
a. Eliminated work associated with quench vents.
23. MD106S
a. Revised per updated architectural for Office A668.
24. MH106N
a. Revised per updated architectural for Office A668.
b. Revised diffuser layout in corridor.
c. Revised room pressure monitor note.
d. Added room pressure monitors to Rooms A614, A621 & A624.
25. MH106S
a. Revised per updated architectural for Office A668.
b. Revised diffuser layout in corridor.
26. MH107
a. Eliminated work associated with quench vents.
b. Replaced motors on relocated fans.
27. MP103
a. Replaced chilled water bypasses in AHUs 2 & 3.
28. MP106N
a. Changed pipes running to MP106S to 2.5”.
b. Added Checkpoint pressure sensor to Rooms A614, A621 & A624.
29. MP106S
a. Added convector to Office A668.
30. M601
a. Revised fan coil schedule for Office A668.
b. Revised fan schedule.
31. M701
a. Revised control sequence for room pressure monitor.
32. EL106S
a. Revised per updated architectural for Office A668.
33. EP103
a. Revised as shown for updated starter and VFD locations.
34. EP106
a. Revised as shown for updated FCU.
35. EP106S
a. Revised per updated architectural for Office A668.
36. EP107
a. Revised as shown for updated starter, VFD locations and circuits.
37. ET106S
a. Revised per updated architectural for Office A668.
38. E401
a. Updated per corrected motor information.
39. E603
a. Updated MCC per revised motors and circuitry.
40. E604
a. Updated per revised motor information and new FCU.
41. E701
a. Notes 16, 19 ,22 Change Category reference to 6A for all voice/data cabling.
b. Note 6 – Change default outlet to two (2) data.
End of Addendum No. 1