Attachment C - Trinka-Davis Equipment Schedule - REV19.xlsx
XLSX spreadsheet 12 KB Posted
- Attached to
- 36-Month Electrical Distribution Testing
- Solicitation number
- 36C24727Q0044
About this file
This is an equipment schedule attachment that lists detailed specifications and pricing information for electrical distribution testing equipment and related services required under a 36-month contract with the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 7.
The schedule outlines multiple line items for electrical testing equipment, diagnostic tools, and associated support services necessary for the VA's electrical distribution testing program. Each line item includes equipment descriptions, quantities, unit pricing, and extended costs organized in a tabular format. The document serves as a pricing template and cost baseline for the solicitation 36C24727Q0044, enabling offerors to understand the scope of equipment and services required and allowing the government to evaluate proposals based on standardized pricing information. The schedule appears to be revision 19, indicating multiple iterations during the solicitation development process. This attachment is essential for bidders to accurately prepare their cost proposals and for the government to establish fair and reasonable pricing benchmarks for the 36-month performance period.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24727Q0044 0001.pdf | ||
| 36C24727Q0044_1 36-Month Electrical Distribution Testing.docx | DOCX document | |
| Attachment D - Equipment and Test Matrix - REV19.docx | DOCX document | |
| Attachment A - Main Campus Equipment Schedule - REV19.xlsx | XLSX spreadsheet | |
| Attachment B - Fort McPherson Equipment Schedule - REV19.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment C
| ATTACHMENT C | EQUIPMENT SCHEDULE | Trinka-Davis Veterans Village Clinic (Carrollton, GA) | ||||||||
| Electrical distribution inspection, testing, maintenance, calibration, and infrared scanning. The required test and maintenance level for each equipment class is stated in Attachment D and in the Statement of Work. This schedule governs asset identity, asset location, and base quantities (SOW Section 3.1). Individual low-voltage power circuit breaker, electronic trip-unit, and protective-relay testing is not base scope; it is performed only when the Contracting Officer orders it under the separately ordered unit-price CLIN 0004 in the price schedule. Quantities are field-verified for nameplate data and exact location; a quantity change is authorized only by the Contracting Officer under SOW Section 15.0 and CLIN 0004. | ||||||||
| Solicitation attachment control: Revision 19 | Date: August 25, 2026 | Atlanta VA Health Care System (Station 508) | Issued with the solicitation as a bidder-facing equipment schedule. | ||||||||
| Item | Building | Location | Equipment tag / description | Equipment class | VA asset number / Maximo asset ID | Make / model | Voltage / rating | Notes |
| 1 | CBOC/CLC | CBOC E096 | H1A-1 | Distribution panelboard | GE AD | 480V | ||
| 2 | CBOC/CLC | CBOC E096 | H1A-2 | Distribution panelboard | GE AD | 480V | ||
| 3 | CBOC/CLC | CLC-A A016 | HN1 | Distribution panelboard | GE AE | 480V | ||
| 4 | CBOC/CLC | CLC-B B016 | HN2 | Distribution panelboard | GE AE | 480V | ||
| 5 | CBOC/CLC | CLC-C C016 | HE | Distribution panelboard | GE AE | 480V | ||
| 6 | CBOC/CLC | CLC-D D016 | HW | Distribution panelboard | GE AE | 480V | ||
| 7 | CBOC/CLC | CBOC E096 | T-L1A | Dry-type transformer | dry-type | 480/208V, 75 kVA | ||
| 8 | CBOC/CLC | CBOC E096 | T-L1B | Dry-type transformer | dry-type | 480/208V, 75 kVA | ||
| 9 | CBOC/CLC | CLC-A A016 | T-LN1 | Dry-type transformer | dry-type | 480/208V, 75 kVA | ||
| 10 | CBOC/CLC | CLC-B B016 | T-LN2 | Dry-type transformer | dry-type | 480/208V, 75 kVA | ||
| 11 | CBOC/CLC | CLC-C C016 | T-LE | Dry-type transformer | dry-type | 480/208V, 75 kVA | ||
| 12 | CBOC/CLC | CLC-D D016 | T-P1 | Dry-type transformer | dry-type | 480/208V, 75 kVA | ||
| 13 | FOB | Outside Facility Operations Bldg | Main Distribution Transformer | Medium-voltage main distribution transformer (liquid-filled) | 20608196173 | ERMCO | 750 kVA; 12,470GY/7,200 to 480Y/277 | Liquid-filled mineral oil; VA-owned/maintained |
| 14 | FOB | Facility Operations Bldg G004 | MDP MSA | Main switchboard / MDP | Eaton Cutler Hammer | 480V, 400A | Fed from main distribution transformer | |
| 15 | FOB | F.O.B. G004 | MSA BRKR PNL L1A | Distribution panelboard | GE / Eaton | 480V | ||
| 16 | FOB | F.O.B. G004 | MSA BRKR PNL L1B | Distribution panelboard | GE / Eaton | 480V | ||
| 17 | FOB | F.O.B. G004 | MSA BRKR PNL HP | Distribution panelboard | GE / Eaton | 480V | ||
| 18 | FOB | F.O.B. G004 | INV Equip BRKR PNL EGHA | Distribution panelboard | GE / Eaton | 480V | ||
| 19 | FOB | F.O.B. G004 | MSA BRKR PNL H1A | Distribution panelboard | General Electric | 480V | Source-side panel at FOB; field-verify | |
| 20 | FOB | F.O.B. G004 | MSA BRKR PNL HN1 | Distribution panelboard | General Electric | 480V | Source-side panel at FOB; field-verify | |
| 21 | FOB | F.O.B. G004 | MSA BRKR PNL HN2 | Distribution panelboard | General Electric | 480V | Source-side panel at FOB; field-verify | |
| 22 | FOB | F.O.B. G004 | MSA BRKR PNL HE | Distribution panelboard | General Electric | 480V | Source-side panel at FOB; field-verify | |
| 23 | FOB | F.O.B. G004 | MSA BRKR PNL HW | Distribution panelboard | General Electric | 480V | Source-side panel at FOB; field-verify | |
| 24 | FOB | GEN ENCL | ATS #1 | Automatic transfer switch | Eaton Cutler Hammer | 480V | Emergency-power distribution | |
| 25 | FOB | GEN ENCL | ATS #2 | Automatic transfer switch | Eaton Cutler Hammer | 480V | Emergency-power distribution | |
| 26 | FOB | GEN ENCL | ATS #3 | Automatic transfer switch | Eaton Cutler Hammer | 480V | Emergency-power distribution | |
| 27 | FOB | GEN ENCL | ATS #4 | Automatic transfer switch | Eaton Cutler Hammer | 480V | Emergency-power distribution | |
| 28 | FOB | FOB G004 Mech Rm | MDP BRKR (GEN 1) | Generator output / main breaker | General Electric | 480V | Output breaker only; generator set excluded | |
| 29 | FOB | FOB G004 Mech Rm | MDP BRKR (GEN 2) | Generator output / main breaker | General Electric | 480V | Output breaker only; generator set excluded | |
| 30 | FOB | FOB G004 Mech Rm | MDP BRKR (GEN 3) | Generator output / main breaker | General Electric | 480V | Output breaker only; generator set excluded | |
| 31 | FOB | FOB G004 Mech Rm | MDP BRKR (GEN 4) | Generator output / main breaker | General Electric | 480V | Output breaker only; generator set excluded |
File details come from the government source that posted it. Updated .