36C24618R0842-006.pdf
PDF 7 MB Posted
- Attached to
- Project 659-16-101, Correct Operating Room Deficiencies Federal contract opportunity
- Solicitation number
- 36C24618R0842
About this file
36C24618R0842 CONTRACT ATTACHMENT A - DRAWINGS - FILE 5 - Plumbing.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24618R0842-0002002.pdf | ||
| 36C24618R0842-0002000.docx | DOCX document | |
| 36C24618R0842-0002004.pdf | ||
| 36C24618R0842-0002003.pdf | ||
| 36C24618R0842-0002001.pdf | ||
| 36C24618R0842-005.pdf | ||
| 36C24618R0842-008.docx | DOCX document | |
| 36C24618R0842-003.pdf | ||
| 36C24618R0842-001.docx | DOCX document | |
| 36C24618R0842-009.pdf | ||
| 36C24618R0842-007.pdf | ||
| 36C24618R0842-002.pdf | ||
| 36C24618R0842-004.pdf | ||
| 36C24618R0842-000.docx | DOCX document |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
6-M2L-OXAVN2WM
SINGLE POINT POWER CONNECTION. PROVIDE OPTIONAL SUCTION FILTER, OIL LEVEL PROTECTION SWITCH IN OIL SUMP CAVITY, AND HIGH TEMP SWITCH FOR EXHAUST.
NOTE:
LOCATION
87.0 SCFM 2 87.0
87.0
10 HP.
3 SEQUENCING
DUPLEX,208V, 200 OXY ASSURED
CLAW OIL LESS N/A
@19" Hg.
MAX. CALC.
SYS. DEMANDNO.
UNIT
REQ'D
PUMPS
PUMP @ 19" Hg
MIN. SCFM &
MAX. HP EA. STARTER
VOLTAGE
HP.
PHASE
CAPACITY
MINIMUM
RECEIVER
PER PUMP
PUMP TYPE
WATER
REQ.
MODEL: VHS10D-200V-D
MANUFACTURE: BEACONMEDAES
REMARKS
PROVIDE TRIPLEX SKID MOUNTED VACUUM PLANT WITH ONE PUMP IN RESERVE.
* P.C. SHALL PROVIDE ALL SIGNAL WIRING, CONDUIT AND SHALL MAKE FINAL CONNECTION TO THE OWNERS BMS.
MV-1
ACCEPTED EQUALS - PATTONS MEDICAL
W/GAUGES
LOCATION
OXYGEN
LINE
PRESS.
HIGH
VACUUM
LINE
PRESS.
LOW
LINE
LOW
WAGD
PRESS.
MANUFACTURER
MODEL NO.ALARM
PRESS.
LINE
O.R.SUITE
CONTROL AREA
AREA
BEACON MEDAES
BEACON MEDAES
PRE/POST RECOV
NURSES STATION
LINE
PRESS.
LOW
NITROUS OXIDE
LINE
PRESS.
HIGH
LINE
PRESS.
LOW
MED AIR
LINE
PRESS.
HIGH
LINE
PRESS.
LOW
NITROGEN
LINE
PRESS.
HIGH
LINE
PRESS.
LOW
* ALL SENSOR WIRING SHALL BE INSTALLED IN CONDUIT AND PER THE LATEST ADDITION OF NFPA 99.
PROVIDE ALL SENSOR WIRING, PRESSURE SWITCHES, TRANDUCERS AND CHECK VALVES FOR A COMPLETE OPERATING SYSTEM PER NFPA 99.
NOTE:
LINE
LOW
CO2
PRESS.
HYBRID 1 & 2
* AREA ALARM PANELS SHALL BE DUPLICATED AT BOTH THE NURSES STATION A154 AND THE OPERATING SUITE CONTROL ROOM A179.
BEACON MEDAES
LOCATION
MIN SCFM
& MAX HP
COMP @
120 PSI
217.2MA-1
17.2
SYSTEM
MAX CALC
DEMAND
@50 PSI.
NO.
UNIT
COMP.
NUMBER
REQ'D
TOTAL
17.2 803 5 hp. SEQUENCING DUPLEX
CAP.
TANK
STOR.
CONTROL SYSTEM
HP
PHASE
VOLT.
DUPLEX, 208V, WITH
COMPRESSOR
TYPE
MEDICAL SCROLL YES
COOLED
AIR
REMARKS
PROVIDE DUPLEX COMPRESSORS WITH TRIPLEX CONTROLS AND SKID FOR FUTURE THIRD COMPRESSOR.
NOTE:
MODEL: SAS5D-080V-D
MANUFACTURE: BEACONMEDAES
SINGLE POINT POWER CONNECTION. PROVIDE DUPLEX DESICCANT DRYERS/FILTERS/REGULATOR BANK. PROVIDE DEW POINT AND CO MONITORS AND ALARMS.
* P.C. SHALL PROVIDE ALL SIGNAL WIRING, CONDUIT AND SHALL MAKE FINAL CONNECTION TO THE OWNERS BMS.
ACCEPTED EQUALS - PATTONS MEDICAL
PENTHOUSE
ENCLOSURE
PENTHOUSE
ENCLOSURE
CHANGE
HIGH/LOW
PRESS.
IN USE
(OR LOW)
RESERVE
HIGH
TEMP
OXYGEN
RESERVE
LOW
PRESS
MALFUNC
VAC
PUMP
LOCATION
VACUUM
BACK
PUMP
UP AIR
LOW
LEVEL
LIQUID
NITROUS OXIDE
CHANGE
PRESS.
HIGH/LOW
LINE
HIGH
POINT
DEW
HIGH/LOW
PRESS.
LINE OVER
MEDICAL AIR AND SUPPORT AIR
COMP
BACK
UP
TEMP
AIR
HIGH
LOW
IN USE
RESERVE
PRESS.
HIGH/LOW
LINE
CARBON DIOXIDE
RESERVE
IN USE
W/GAUGES
NITROGEN
HIGH/LOW
PRESS.
LINE
HIGH
CO
AIR
MALFUNC
COMPLINE
IN USE
RESERVE
LOW
OVER
LINE
PANEL
MASTER PRESS.
ALARM
OVER
CHANGE
LOW
WAGD
MODEL NO.
MANUFACTURER
PRESS.
LINE
HIGH/LOW
PRESS.
LINE
LOW
MANNED
6-M2L-OXAVCVWN9R
BEACON MEDAES
60 POINT PANEL
* ALL SIGNAL WIRING SHALL BE INSTALLED PER THE LATEST ADDITION OF NFPA 99.
NOTE:
* PROVIDE ALL SENSOR WIRING, PRESSURE SWITCHES, TRANDUCERS AND CHECK VALVES FOR A COMPLETE OPERATING SYSTEM PER NFPA 99.
* P.C. SHALL PROVIDE ALL SIGNAL WIRING, CONDUIT AND SHALL MAKE FINAL CONNECTION TO THE OWNERS BMS. COORDINATE AND VERIFY
THE EXACT LOCATION AND SIGNAL REQUIREMENTS FROM THE OWNER.
* P.C. TO VERIFY ALL SIGNALS FROM NEW EQUIPMENT TO MATCH NEW MASTER ALARM.
LOCATION
EXISTING
N/A N/A
6-M2L-OXAVN2WM
6-M2L-OXAVN2WM
MAINTENANCE
* P.C. SHALL PROVIDE ALL SIGNAL WIRING, CONDUIT AND SHALL MAKE FINAL CONNECTION TO THE MASTER ALARM PANEL. COORDINATE AND VERIFY
THE EXACT LOCATION AND SIGNAL REQUIREMENTS FROM THE OWNER.
ZURN, JOSAM, SMITH, PPI, INC.
33 - 60
61 - 113
12 - 32
1 - 11
ZURN, JOSAM, SMITH, PPI, INC.
ZURN, JOSAM, SMITH, PPI, INC.
ZURN, JOSAM, SMITH, PPI, INC.
PIPE CONTINUES
ELBOW UP
ELBOW DN
MEDICAL AIR
MEDICAL VACUUM
OXYGEN
GENERAL
A
V
OXY
MEDICAL GAS PIPING & SYMBOLS
CARBON DIOXIDE
NITROUS OXIDE
NITROGEN
CO2
N2O
N
GATE VALVE
CONNECT TO EXISTING
WASTE ANESTHESIA GAS DISPOSAL WAGD
FIXTURES AND PIPING TO BE DEMOLISHED
MEDICAL GAS WALL OUTLETS
REMARKSITEM MANUFACTURER AND MODEL NO.
NOTE: ALL MEDICAL GAS EQUIPMENT SHALL COMPLY WITH NFPA 99.
MEDICAL GAS ZONE VALVES
2"4" 1" -P-10
P-40 1-1/2"2" 1/2" 1/2"
P-30 2" 1/2" 1/2"1-1/2"
CONTRACTOR TO MATCH
EXISTING
PROVIDE WITH PRESSURE
AND VACUUM GAUGES.
MEDICAL AIR: BEACON MEDAES DISS OUTLETS MODEL #234512
OXYGEN: BEACON MEDAES DISS OUTLETS MODEL #234510
VACUUM: BEACON MEDAES DISS INLETS MODEL #234513
SLIDE: BEACON MEDAES VACUUM SLIDE BRACKET MODEL #234500
BEACON MEDAES ZONE VALVE BOX ASSEMBLY MODEL #ZVB3-D-ENG
MEDICAL NITROUS OXIDE: BEACON MEDAES DISS OUTLETS MODEL #234511
NITROGEN: BEACON MEDAES DISS OUTLETS MODEL #234514
CARBON DIOXIDE: BEACON MEDAES DISS INLETS MODEL #234520
WASTE ANESTHETIC GAS DISPOSAL (WAGD): BEACON MEDAES DISS OUTLET BRACKET MODEL #234519
1-1/2"
FEBCO
APOLLO ACCEPTED EQUALS -
BY THE SPECIFICATIONS, ARE FOLLOWED.
LISTED WILL BE ACCEPTED UNLESS THE PROCEDURES FOR SUBSTITUTION AS INDICATED
RESEMBLES AND PERFORMS EQUAL TO THE SPECIFIED PRODUCT. ONLY THE MANUFACTURERS
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY
WATTS SERIES LF008PCQT BACKFLOW PREVENTER. ANIT-SIPTON, SPILL-RESISTANT, VACUUM BREAKER.
SYMBOL DESCRIPTION REMARKS
VACUUM OUTLET
OXYGEN OUTLET
VACUUM BOTTLE SLIDE S
V
O
MEDICAL AIR OUTLET A
NITROUS OXIDE OUTLET NO
WASTE ANESTHESIA GAS DISPOSAL OUTLET W
CARBON DIOXIDE OUTLET CO2
ZONE VALVE BOX ZVB
DESCRIPTION
MEDICAL GAS LEGEND
PLUMBING FIXTURE SCHEDULE
MEDICAL GAS EQUIPMENT
DRAWING INDEX
PUMP SCHEDULE
DRAIN SCHEDULE
CLEANOUT SCHEDULE
PLUMBING LEGEND
SHOCK ARRESTOR SCHEDULE
MEDICAL VACUUM PUMP SCHEDULE
MEDICAL GAS AREA ALARM PANEL SCHEDULE
MEDICAL AIR COMPRESSOR SCHEDULE
TRAP PRIMER SCHEDULE
DESCRIPTION
BACKFLOW PREVENTER SCHEDULE
MEDICAL GAS MASTER ALARM PANEL SCHEDULE
HWR
HW
FCO
VB
DN
ABBREVIATIONS
CO
CW
AFG
CONNECT TO EXISTING
FLOOR DRAIN
BALL VALVE
PIPE CONTINUES
ELBOW UP
ELBOW DN
GENERAL
PIPING
HOT WATER
HOT WATER RETURN
WALL CLEANOUT
FLOOR CLEANOUT
DOWN
COLD WATER
CLEANOUT
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR AFF
BACKFLOW PREVENTER BFP
FLOOR DRAIN FD
HOSE BIBB HB
SHOCK ARRESTOR & PDI SIZE SA-A
VENT THROUGH ROOF VTR
PLUMBING DRAINAGE INSTITUTE P.D.I.
VACUUM BREAKER
(E)EXISTING
WCO
DEMO TO EXISTING
SYMBOL DESCRIPTION
ACCEPTED EQUALS -
FCO
WCO
JOSAM
J.R. SMITH
SYMBOL
ACCEPTED EQUALS -
JOSAM
J.R. SMITH
HD-A
SHOCK ARRESTOR
ROOF LEADER BELOW FINISHED FLOOR RW
VOLTAGE,
PHASE, CYCLE
PUMP
G.P.M.
SERVICE TYPE
CAPACITY
HEAD(FT) UNIT IS BASED ON
MFG. & MODEL NO.
H.P.
ACCEPTED EQUALS - APPROVED EQUAL
SP-1 ELEVATOR
SUMP
74 37 115V,1PH,60HZ 1/2SUBMERSIBLE
BUILDING AUTOMATION SYSTEM BAS
BFFBELOW FINISHED FLOOR
REMARKSDESCRIPTIONSYMBOL
CONNECTIONS
VW CW HW
SPECIFICATIONS
ACCEPTED EQUALSPECIFIED PRODUCT
LAVATORY -
WALL MOUNT -
ADA -
P-50 MOP BASIN - 2"3" 3/4" 3/4"
P-51 SCRUB SINK - 2" 1/2" 1/2"
SELF-CLOSING
P-90 WALL BOX - 1-1/2"2" 1/2" 1/2"
DRAIN -
DRAWING TITLE
P001
P400B P400C P401B P401C
P402B P402C P500A P500B P500C P501A P501B P501C P502A P502B P502C
PD400B
PD400C
PD401B
PD401C
PD402B
PD402C
PD500A
PD500B
PD500C
PD501A
PD501B
PD501C
PD502A
PD502B
PD502C
PLUMBING - SCHEDULES, NOTES, AND LEGENDS
PLUMBING - FOURTH FLOOR - NEW WORK - GRAVITY - AREA B
PLUMBING - FOURTH FLOOR - NEW WORK - GRAVITY - AREA C
PLUMBING - FOURTH FLOOR - NEW WORK - DOMESTIC - AREA B
PLUMBING - FOURTH FLOOR - NEW WORK - DOMESTIC - AREA C
PLUMBING - FOURTH FLOOR - NEW WORK - MEDICAL GAS - AREA B
PLUMBING - FOURTH FLOOR - NEW WORK - MEDICAL GAS - AREA C
PLUMBING - FIFTH FLOOR - NEW WORK - GRAVITY - AREA A
PLUMBING - FIFTH FLOOR - NEW WORK - GRAVITY - AREA B
PLUMBING - FIFTH FLOOR - NEW WORK - GRAVITY - AREA C
PLUMBING - FIFTH FLOOR - NEW WORK - DOMESTIC - AREA A
PLUMBING - FIFTH FLOOR - NEW WORK - DOMESTIC - AREA B
PLUMBING - FIFTH FLOOR - NEW WORK - DOMESTIC - AREA C
PLUMBING - FIFTH FLOOR - NEW WORK - MEDICAL GAS - AREA A
PLUMBING - FIFTH FLOOR - NEW WORK - MEDICAL GAS - AREA B
PLUMBING - FIFTH FLOOR - NEW WORK - MEDICAL GAS - AREA C
PLUMBING - FOURTH FLOOR - DEMOLITION - GRAVITY - AREA B
PLUMBING - FOURTH FLOOR - DEMOLITION - GRAVITY - AREA C
PLUMBING - FOURTH FLOOR - DEMOLITION - DOMESTIC - AREA B
PLUMBING - FOURTH FLOOR - DEMOLITION - DOMESTIC - AREA C
PLUMBING - FOURTH FLOOR - DEMOLITION - MEDICAL GAS - AREA B
PLUMBING - FOURTH FLOOR - DEMOLITION - MEDICAL GAS - AREA C
PLUMBING - FIFTH FLOOR - DEMOLITION - GRAVITY - AREA A
PLUMBING - FIFTH FLOOR - DEMOLITION - GRAVITY - AREA B
PLUMBING - FIFTH FLOOR - DEMOLITION - GRAVITY - AREA C
PLUMBING - FIFTH FLOOR - DEMOLITION - DOMESTIC - AREA A
PLUMBING - FIFTH FLOOR - DEMOLITION - DOMESTIC - AREA B
PLUMBING - FIFTH FLOOR - DEMOLITION - DOMESTIC - AREA C
PLUMBING - FIFTH FLOOR - DEMOLITION - MEDICAL GAS - AREA A
PLUMBING - FIFTH FLOOR - DEMOLITION - MEDICAL GAS - AREA B
PLUMBING - FIFTH FLOOR - DEMOLITION - MEDICAL GAS - AREA C
WALL BOX - ACORN MODEL 8200-1 STAINLESS STEEL RECESSED WASTE DRAIN
BOX WITH 18 GAUGE STAINLESS STEEL CONSTRUCTION, LESS DOOR
SCRUB SINK - AMERCIAN STANDARD 9047.093 28"x 22" SINGLE CENTER FAUCET
HOLE, VITREOUS CHINA FIXTURE.
CARRIER - MANUFACTURER RECOMMENDED CARRIER.
PROVIDE INLINE CHECKS AT
COLD AND HOT WATER SUPPLIES.
PROVIDE FIAT 889-CC MOP
HANGER AT 60" A.F.F., PROVIDE
FIAT 832-AA HOSE AND HOSE
BRACKET. SEE DETAIL X FOR
MOUNTING CONFIGURATION.
BASIN - FIAT MODEL TSB3002 36"x36"x12" TERRAZZO MOP BASIN WITH
STAINLESS STEEL FACTORY INSTALLED DRAIN BODY COMPLETE WITH JOINT
CONNECTOR FOR A 3" DRAIN PIPE, COMBINATION DOME STRAINER, MOP HANGER,
HOSE BRACKET WITH HOSE, STAINLESS STEEL LINT BASKET, AND MSG WALL
GUARDS.
FAUCET- AMERICAN STANDARD MODEL 8344.212 CHROME PLATED FAUCET WITH
INTEGRAL STOPS, VACUUM BREAKER, CERAMIC CARTRIDGES, GARDEN HOSE
THREAD OUTLET, PAIL HOOK, AND WALL BRACE.
LAVATORY - AMERICAN STANDARD "LUCERNE" 0356.015 20-1/2"X18-1/4"
WHITE VITREOUS CHINA WALL MTD. LAVATORY WITH 8" FAUCET CENTERS, AND
WALL HANGAR SUPPORT
FAUCET - CHICAGO FAUCETS MODEL 786-E29XKCP LEAD FREE DECK MOUNTED
8" SPREAD CHROME PLATED FAUCET WITH 4" WRIST BLADE, 5 14"C-C RIGID
SPOUT, AND 2.2GPM HANDLES, CERAMIC CARTRIDGES, LAMINAR FLOW OUTLET.
ANGLE STOP - MCGUIRE MODEL LF2165LK LEAD FREE LAVITORY SUPPLY KIT
WITH (2)12"IPS X 38"ODLOOSE KEY STOPS, 15"FLEXIBLE COPPER SUPPLY "IPS X
WITHLINES, AND SHALLOW STEEL FLANGES. ALL SUPPLY KIT COMPONENTS SHALL
BE CHROME PLATED.
DRAIN - MCGUIRE MODEL 155A 114"X6" HEAVY DUTY CAST BRASS WITH
SEAMLESS TAILPIECE ALL COMPONENTS CHROME PLATED.
P-TRAP - MCGUIRE MODEL 8902 114"X112" 17GA SEAMLESS BRASS
CONSTRUCTION AND BRASS SLIP NUTS; ALL COMPONENTS CHROME PLATED.
CARRIER - ZURN MODEL Z1227-2 CARRIER WITH DURA COATED STEEL
STANCHIONS, WELDED FEET, ADJUSTABLE SUPPORT PLATES, MOUNTING BOLTS,
AND TRIM.
PROVIDE WITH TRUEBRO
STAINLESS STEEL
SINK -
STAINLESS STEEL SINK - ELKAY MODEL LR2219 18 GAUGE TYPE 304
STAINLESS STEEL SINK WITH FULLY COATED UNDERSIDE, U-CHANNEL
MOUNTING, 4"CENTERSET MOUNTING.
FAUCET - CHICAGO FAUCETS MODEL 786-E29XKCP LEAD FREE DECK MOUNTED
8" SPREAD CHROME PLATED FAUCET WITH 4" WRIST BLADE, 5 14"C-C RIGID
SPOUT, AND 2.2GPM HANDLES, CERAMIC CARTRIDGES, LAMINAR FLOW OUTLET.
ANGLE STOP - MCGUIRE MODEL BV2165R15 LEAD FREE CONVERTIBLE QUARTER
TURN LAVATORY SUPPLY KIT WITH (2) 12"IPS X 38"OD BRASS BALL VALVES, 15"
FLEXIBLE COPPER SUPPLY LINES, AND SHALLOW STEEL FLANGES. ALL SUPPLY
KIT COMPONENTS SHALL BE CHROME PLATED.
DRAIN - MCGUIRE MODEL 155A 114"X6" HEAVY DUTY CAST BRASS WITH SEAMLESS
TAILPIECE; ALL COMPONENTS CHROME PLATED.
P-TRAP - MCGUIRE MODEL 8902 114 "X 12" 17GA SEAMLESS BRASS CONSTRUCTION
AND BRASS SLIP NUTS; ALL COMPONENTS CHROME PLATED.
EYE WASH - RE-INSTALL EYEWASH REMOVED DURING DEMOLITION PHASE. PROVIDE
AND INSTALL GUARDIAN G3600 THERMOSTATIC MIXING VALVE.
TOILET - AMERICAN STANDARD MADERA MODEL 3461.001 1.6GPF VITREOUS
CHINA ELONGATED TOILET WITH 112" TOP SPUD, 2 18" TRAPWAY, 16 12" RIM HEIGHT,
AND BOLT CAPS.
FLUSH VALVE - SLOAN ROYAL 111 FLUSHOMETER WITH ADA COMPLIANT HANDLE,
VANDAL RESISTANT STOP CAP WITH SET SCREW, SWEAT SOLDER ADAPTER WITH
COVER TUBE, CAST SET SCREW WALL FLANGE.
SEAT - AMERICAN STANDARD MODEL #5905.100 EXTRA HEAVY DUTY OPEN
FRONT SEAT, WITH STAINLESS STEEL CHECK HINGES AND LESS COVER.
WATERCLOSET -
FLOOR MOUNTED -
FLUSH VALVE -
ADA
FAUCETS -
CHINA -
SINK TRIM -
S.S. SINKS -
FLUSH VALVES -
WATER COOLERS -
CARRIERS/INTERCEPTORS -
ICE MAKER BOX -
EMERGENCY EYEWASH/SHOWER -
CHICAGO, T&S BRASS, DELTA
AMERICAN STANDARD, KOHLER, ZURN
MCGUIRE, ZURN, KEENEY
ELKAY, JUST, MOEN
SLOAN, ZURN, DELANY
ELKAY, OASIS, HALSEY TAYLOR
ZURN, JAY R. SMITH, MiFAB
IPS, PPP INC, BRADLEY
SPEAKMAN, GUARDIAN
GENERAL NOTES:
1. PROVIDE TRUEBRO 'LAV-GUARD' INSULATING SAFETY COVERS FOR ADA ACCESSIBLE SINKS WITH
EXPOSED HOT AND COLD WATER SUPPLIES, DRAINS, AND P-TRAPS. COLOR SHALL MATCH THE
FIXTURE. COORDINATE WITH PROJECT ARCHITECT.
2. ALL FAUCETS, VALVES, AND EQUIPMENT SHALL BE LEAD FREE, BEARING NFS 61 APPROVAL
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY RESEMBLES AND PERFORMS EQUAL TO THE SPECIFIED PRODUCT. ONLY THE MANUFACTURERS LISTED WILL BE ACCEPTED UNLESS THE PROCEDURES FOR SUBSTITUTION AS INDICATED BY THE SPECIFICATIONS, ARE FOLLOWED. NO
PRIVATE LABELED PRODUCTS WILL BE ACCEPTED FOR THOSE SPECIFIED WITHIN.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY RESEMBLES AND PERFORMS EQUAL TO THE SPECIFIED PRODUCT. ONLY THE MANUFACTURERS LISTED WILL BE ACCEPTED UNLESS THE PROCEDURES FOR SUBSTITUTION AS INDICATED BY THE SPECIFICATIONS, ARE FOLLOWED. NO PRIVATE LABELED PRODUCTS WILL BE ACCEPTED FOR THOSE SPECIFIED WITHIN.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY RESEMBLES AND PERFORMS EQUAL TO THE SPECIFIED PRODUCT. ONLY THE MANUFACTURERS LISTED WILL BE ACCEPTED UNLESS THE PROCEDURES FOR SUBSTITUTION AS INDICATED BY THE SPECIFICATIONS, ARE FOLLOWED. NO PRIVATE LABELED PRODUCTS WILL BE ACCEPTED FOR THOSE SPECIFIED WITHIN.
4TH FLOOR ELEVATOR
SHAFT SUMP PITS
STANCOR SE-50A EFFLUENT PUMP,
PROVIDE W/ REMOTE ALARM SYSTEM.
* NOTE: ALL MOTORS TO BE PREMIUM EFFICIENCY MOTORS PER NEMA MG-1 2006.*
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING THE MODEL WHICH MOST CLOSELY RESEMBLES AND PERFORMS EQUAL TO THE SPECIFIED PRODUCT. ONLY THE MANUFACTURERS LISTED WILL BE ACCEPTED UNLESS THE PROCEDURES
FOR SUBSTITUTION AS INDICATED BY THE SPECIFICATIONS, ARE FOLLOWED.
REMARKS/PUMP LOCATION
* NOTE: SET ALL FLOOR DRAINS A MINIMUM OF 3/4" BELOW FINISHED FLOOR TO ALLOW FOR FLOOR SLOPE.*
ZURN ZN-1400-VP LEVEL-TROL CLEANOUT, DURA-COATED CAST IRON BODY, NO-HUB CONNECTION, GAS AND WATERTIGHT TAPERED THREADED
ABS PLUG AND ROUND SCORIATED NICKEL BRONZE TOP AND VANDAL RESISTANT FASTENERS.
ZURN Z-1445 OR Z-1446 CLEANOUT TEE, DURA-COATED CAST IRON BODY, NO-HUB CONNECTION, GAS AND WATERTIGHT TAPERED THREADED ABS PLUG AND SMOOTH STAINLESS STEEL WALL ACCESS COVER WITH VANDAL RESISTANT FASTENERS. LOCATE 18" OR LESS ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED.
SPDSUMP PUMP DISCHARGE ABOVE FINISHED CEILING
RW
RL
ROOF LEADER BELOW FINISHED FLOOR
ROOF LEADER ABOVE FINISHED CEILING
RWEXISTING ROOF LEADER BELOW FINISHED FLOOR
RL
EXISTING SYSTEM TO BE DEMOLISHED
EXISTING ROOF LEADER ABOVE FINISHED CEILING
EXISTING HOT WATER RECIRC. ABOVE FINISHED CEILING
EXISTING HOT WATER ABOVE FINISHED CEILING
EXISTING COLD WATER ABOVE FINISHED CEILING
EXISTING SANITARY VENT ABOVE FINISHED CEILING
EXISTING SANITARY WASTE BELOW FINISHED FLOOR
HOT WATER RECIRC. ABOVE FINISHED CEILING
HOT WATER ABOVE FINISHED CEILING
COLD WATER ABOVE FINISHED CEILING
SANITARY VENT ABOVE FINISHED CEILING
SANITARY WASTE BELOW FINISHED FLOOR
ZURN ZN-415-H-VP FLOOR DRAIN, DURA COATED CAST IRON BODY WITH BOTTOM OUTLET, COMBINATION INVERTIBLE MEMBRANE CLAMP / ADJUSTABLE COLLAR WITH
SEEPAGE SLOTS AND "TYPE H " POLISHED NICKEL BRONZE, LIGHT-DUTY STRAINER.
ZURN Z-211-S HUB DRAIN, DURA COATED CAST IRON BODY WITH BOTTOM OUTLET.
FD-A
GENERAL NOTES:
1. ALL SHOCK ARRESTORS SHALL BE LEAD FREE, BEARING NFS 61 APPROVAL
SA-C
SA-DD
C
B SA-B
SA-AA
MANUFACTURER OR EQUALFIXTURE UNITSFIXTURE
TAG
P.D.I.
SIZE
P-91 WALL BOX - 1-1/2"2" 1/2"
DRAIN -
WALL BOX - ACORN MODEL 8200-1 STAINLESS STEEL RECESSED WASTE DRAIN
BOX WITH 18 GAUGE STAINLESS STEEL CONSTRUCTION, LESS DOOR
PROVIDE12" QUARTER TURN COMPRESSION VALVE FOR ICE MAKER
CONNECTION.
P002 PLUMBING - DETAILS
PLUMBING - GROUND FLOOR - NEW WORK - GRAVITY - AREA CP100C
LAV SHIELD
CO ZURN Z-1470 BRONZE CLEANOUT PLUG, COUNTERSUNK, BRONZE CLEANOUT PLUG.
DRAIN - MCGUIRE NO. 152N WIDE TOP STRAINER WITH 1 1/2" x4" BRASS 20 GA
TAILPIECE AND LOCK AND SLIP NUTS.
PRECISION PLUMBING PRODUCTS P1-500 WITH A DU-4 DISTRIBUTION UNIT. TRAP PRIMER SHALL BE INSTALLED ABOVE CEILING AND DISTRIBUTION
UNIT SHALL BE MOUNTED IN A ACCESSIBLE LOCATION.
SYMBOL
TP-1
BFP-1
SLOAN, SKYTRONSCRUB SINKS -
MIXING VALVE
PROVIDE ZURN MODEL 12-ZW1017C
UNDERCOUNTER VALVE FOR EACH
SINK. PLUMBING CONTRACTOR TO
INSTALL AND SET BLENDING
TEMPERATURE AT OWNERS
MIXING VALVE
REQUEST FOR EACH SINK AS
REQUIRED.
PROVIDE ZURN MODEL 12-ZW1017C
UNDERCOUNTER VALVE FOR EACH
SINK. PLUMBING CONTRACTOR TO
INSTALL AND SET BLENDING
TEMPERATURE AT OWNERS
REQUEST FOR EACH SINK AS
REQUIRED.
PLUMBING - FOURTH FLOOR - NEW WORK - MEDICAL GAS - AREA AP402A
PLUMBING - FOURTH FLOOR - DEMOLITION - MEDICAL GAS - AREA APD402A
DOUBLE KNEE
ACTION VALVE-
FAUCET - AMERICA STANDARD 7522.155 GOOSENECK SPOUT. TUBULAR BRASS
GOOSENECK SPOUT WITH 2.2 GPM AERATOR.
ANGLE STOP - MCGUIRE MODEL LF2165LK LEAD FREE LAVATORY SUPPLY KIT WITH
(2) 1/2" IPS x 3/8" OD LOOSE KEY STOPS, 15" FLEXIBLE COPPER SUPPLY AND SHALLOW
STEEL FLANGES. ALL SUPPLY KIT COMPONENTS SHALL BE CHROME PLATED.
KNEE ACTION MIXING VALVE - AMERICAN STANDARD MODEL 7676.029 WITH
WALL-MOUNTED CAST ALUMINUM BRACKET.
FS-A ZURN ZN-1910-16-VP FLOOR DRAIN, SANI-FLOR RECEPTOR 8 X 8 X 6 DEEP CAST IRON BODY SQUARE, MEDIUM-DUTY GRATE WITH 7/16" SLOTTED OPENINGS, WHITE ACID ACID RESISTING PORCELAIN ENAMEL INTERIOR AND TOP, COMPLETE WITH WHITE ABSANIT-SPASH INTERIOR BOTTOM DOME STRAINER.
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:1
3:
P M
M :\l oc al re vi t f ile s\
C
E
C en tra l M od el
.rv t
P001
SCHEDULES, NOTES,
AND LEGENDS
15-0014-00
CORRECT OPERATING
ROOM DEFICIENCIES
RAE
GAT
Salisbury, NC
100% FINAL DESIGN
11/10/16
Item Date Description
1 05/08/17 Revision 1
CHECK VALVE
SHUT OFF
VALVE
ON FIRST LEVEL
STANCOR OIL-MINDER SYSTEM
PUMP MODEL: SE-50
RATING: 74 GPM 37 TDH
MOTOR: .5 HP 3600 RPM
ELEC: 1 PH 60 HZ 115 V
ELEC: 14 FL AMPS
STANCOR MODEL SE-50 SUBMERSIBLE EFFLUENT PUMP
.5 HP, 115 V, 3600 RPM WITH 2" DISCHARGE CONNECTION
STANCOR OIL MINDER 115V 1 PHASE CONTROL SYSTEM WITH
BUILT IN AUDIBLE AND VISUAL ALARM WHEN PUMP DOES NOT
RUN DUE TO OIL IN PIT OR HIGH LIQUID ALARM. PROVIDE
SILENCING BUTTON FOR AUDIBLE ALARM BUILT INTO PANEL.
PANEL SHALL HAVE ADDITIONAL CONTACT FOR A REMOTE ALARM
LOCATION IF IN THE FUTURE IT IS NEEDED. JUNCTION BOX WILL
BE PROVIDED WITH MULTI-PIN CONNECTOR AND CORD IN LENGTHS
AS REQUIRED. 25 FT INCREMENTS. LIGHTS PROVIDED FOR OIL
SPILL, POWER, HIGH LIQUID LEVEL, OVERLOAD AND PUMP RUN.
JUNCTION BOX WILL BE PROVIDED WITH MULTI-PIN CONNECTOR
AND CORD IN LENGTHS AS REQUIRED, 25 FT. IS STANDARD WITH
OPTIONAL 25 FT. INCREMENTS AVAILABLE.
OIL MINDER CABLE, POWER CABLE, PROBE CABLE, HIGH LIQUID
ALARM CABLE AND PUMP ON FLOAT CABLE.
HIGH LIQUID ALARM FLOAT WITH CLAMP DEVICE TO MOUNT TO
PUMP DISCHARGE PIPING.
PUMP "ON" FLOAT
OIL MINDER PROBE
SPECIFIC NOTES
OIL MINDER CONTROL PANEL
VERIFY EXACT LOCATION OF
PANEL ON THIRD FLOOR ELECTRIC
(ALLOW 250'-0" OF CABLE)
** INSTALL ALL PUMP AND COMPONENTS AS INDICATED WITHIN
MANUFACTURER'S INSTALLATION INSTRUCTIONS. **
PER ASME A17.1a 2008
3000 GPH PER ELEVATOR.
THIS PROJECT CONTAINS
THE PUMP PROVIDED IS
CAPABLE OF 3000 GPH
DESIGN CRITERIA
ELEVATOR SUMP #1 (SP-1)
1.0 HP, 115 V, 3600 RPM WITH 2" DISCHARGE CONNECTION
ESP-1
STANCOR MODEL SE-50 SUBMERSIBLE EFFLUENT PUMP
ROUTE TO ROOF AREA
2" TO ABOVE CEILING
ROOM 3162
OXY
AIR
VAC
3'- 0"
V
VAC
VAC
VAC
AIR
OXY
V V
A O V
V V
A O
ROOMS XXXX - XXXX
ALARM PANEL
MONITORING
MEDICAL GAS
ELEV. SHAFT WALL
ROOMS XXXX - XXXX
ALARM PANEL
MONITORING
MEDICAL GAS
3 3
NTS
FINISHED FLOOR
TEST
TEE
STAINLESS STEEL
COVER PLATE WITH
SECURING SCREW
FINISHED WALL
SURFACE
THREADED
CLEANOUT
PLUG
AIR TIGHT SEAL WITH
TAPERED THREAD
BRASS PLUG
CAULK INSIDE
ROUND SCORIATED
STAINLESS STEEL
TOP
NOTES:
1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING ASSEMBLY FOR PARTITION TYPE
& RATING ENCOUNTERED.
2. THROUGH PENETRATION - PROVIDE FIRE STOPPING ASSEMBLY FOR SIZE & MATERIAL OF
THROUGH PENETRATION UTILIZED.
3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR WALL ASSEMBLY &
THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR CAVITY ACCORDING TO
THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM UTILIZED.
ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL LISTED FIRE STOP
SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE SEPARATION PENETRATED AND THE
THROUGH PENETRATION MATERIAL.
DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE AVAILABLE AT THE
PROJECT SITE FOR THE DURATION OF CONSTRUCTION AND SHALL BE PROVIDED TO THE
BUILDING OWNER AT THE PROJECT COMPLETION.
PROVIDE WALL OR FLOOR LABELS INDICATING THE SYSTEM MANUFACTURER AND UL LISTED
ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE STOPPING SYSTEM IS INSTALLED.
Section A-A
A
A
GENERAL NOTES:
1. PROVIDE DIELECTRIC UNIONS AT ALL CONNECTION POINTS CONNECTING DISSIMILAR
METALS.
2. PROVIDE FLOW CONTROL DEVICE SHOWN ABOVE OR APPROVED EQUAL AT ALL
LOCATIONS WHERE BALANCING VALVES ARE REQUIRED.
BALL
VALVE
(TYP.)
CHECK VALVE
STRAINER
UNION
GRISWOLD THREADED COMBO VALVE 1-14
PSID BRONZE BODY, S.S. CARTRIDGE. SEE
PLANS FOR FLOW QUANTITY. MODEL 3631 OR
3641 OR EQUAL WITH BODY TAG INDICATING
GPM.
INSULATE AS REQD
ATTACH TO
STRUCTURE
TYPE 1 CLEVIS HANGER
WITH PROTECTIVE
SADDLE OR SHIELD
NTS
COUNTERTOP SURFACE
BACKSPLASH
GUY GREY B200
ENSURE BOX FITS FULLY
BELOW MILLWORK COUNTERTOP
CONNECTION OF DRAIN PIPING INTO DRAIN BOX
PLUMBING CONTRACTOR TO MAKE FINAL
PIPING
CONCEALED
(CASEWORK)
P-TRAP
±18"AFF
MAINTAIN
2"AIR GAP MIN.
ICE MACHINE
COUNTER TOP
PROVIDE SPILL PROOF VACUUM
BREAKER (POLISHED CHROME)
PROVIDE EXCUTCHEON
IN COLD WATER LINE
AT WALL. INSTALL VB
AT REQUIRED HEIGHT.
(CASEWORK)
(CONCEALED IN WALL)
RIGID COPPER DRAIN LINE
FROM ICE MACHINE
ICE MACHINE DRAIN BOX
PROTECT DISSIMULAR
METALS AT PENETRATION
PIPE GROMMET
INTO BOX.
SLEEVE THRU
DISTRIBUTION UNIT FOR
1/2" TRAP PRIMER LINE
SLAB FLOOR SLAB
FLOOR DRAIN
MULTIPLE LINES
TRAP PRIMER VALVE
DOMESTIC WATER LINE
1/2" TRAP PRIMER SUPPLY
NTS
NTS
FLOOR DRAIN DETAIL
NO-HUB BAND
DRAIN BODY
MEMBRANE CLAMP
FLOOR SLAB
RECESSED GRATE
FINISHED FLOOR
PIPE AS SCHEDULED
PROVIDE WATER
TIGHT SEAL
WATER PROOF
MEMBRANE
MOP BASIN
18"
72"
36"
3" PIPE
30" HOSE
HOSE BRACKET
SERVICE FAUCET
WITH VACUUM
APPLY SILICONE
BASIN AT WALLS
SETTING CEMENT
1"THICK LAYER OF
FINISHED FLOOR.
SEALANT AROUND
TOP AND SIDES OF
MOP (BY OTHERS)
AND FLOOR.3" INTEGRAL
DRAIN.
P-60
BREAKER.
MOP HANGER
NTS
MOP SINK BASIN DETAIL 7
NTS
NTS
NTS
WALL CLEANOUT 2
3FLOOR CLEANOUT DETAIL
1THROUGH PENETRATION FIRESTOP SYSTEM
(PROVIDE UL LISTED SYSTEM)
FLOW CONTROL DEVICE
TYPICAL MEDICAL GAS
3/4"
1/2"
OUTLET/INLET PIPING DROP
INDIVIDUAL OVERHEAD PIPING
DROPS REQUIRED FOR EACH
OUTLET/INLET. (TYPICAL)
CONCEALED WALL OUTLETS/
INLETS. SEE ARCHITECTURAL
PLANS FOR LOCATION AND
NUMBERS OF GASES INCLUDING
VACUUM SLIDES. (TYPICAL).
INDIVIDUAL PIPING WALL
DROPS REQUIRED FOR EACH
OUTLET/INLET. (TYPICAL)
SEE PLANS FOR
SYSTEM PIPE SIZE.
TYPE 1 CLEVIS HANGER
TYPICAL AREA ALARM PANEL
AREA ALARM PANEL
PROVIDE SIGNAGE PER
SPECIFICATIONS INDICATING
ROOMS SERVED AND AS
REQUIRED PER NFPA 99
CURRENT EDITION.
MED GAS PURGE VALVE
MEDICAL GAS ZONE VALVE BOX
FIN.FLR.
OPEN POSITION
CAP
CAP
NTS
NTS
NTS
NTS
5'-6" A.F.F. CONFIRM
HEIGHT WITH HOSPITAL
PROVIDE NUMBER OF
MODULES NECESSARY TO
MONITOR ALL INSTALLED
MEDICAL GASES AS
REQUIRED BY NFPA 99
NTS
5'-6"AFF
VERIFY W/OWNER
DOOR SHOWN IN
OPEN POSITION
(NOTE:
ARRANGEMENT AND
TYPE OF MEDICAL
GASES MAY VARY)
NTS
1/8" NPT PORT SEALED
WITH BRASS HEX HEAD
PLUG USING TEFLON
TAPE (TYPICAL)
PURGE
PORT
(TYPICAL)
LINE SIZE BALL VALVE
FULL SIZE TEE
LINE SIZE BALL VALVE
FULL SIZE PURGE (BALL VALVE)
NTS
TYP. WHEELCHAIR LAVATORY TYPICAL SS SINK
VACUUM EXHAUST
TO MEDICAL VACUUM SYSTEM
BALL VALVE
VACUUM GAUGE
PRESSURE SWITCH
FINISHED FLOOR
MV-1
CONTROL
(TYPICAL)
PANEL
4" THICK HOUSEKEEPING
PAD
RECEIVER
FLEX CONNECTOR (TYPICAL)
3'-0"
RECEIVER DRAIN
TO FLOOR DRAIN
CLEARANCE
MINIMUM
ROOF LINE
(INSULATE PER MANUF.
RECOMMENDATIONS)
DUPLEX MEDICAL VACUUM PUMP
TERMINATE @ 48" ABOVE
INTAKE-FILTER/MUFFLER
ROOF
AIR INTAKE
TO MEDICAL AIR SYSTEM
BALL VALVE
PRESSURE GAUGE
PRESSURE SWITCH
FINISHED FLOOR
MA-1
CONTROL
DUAL DESICCANT DRYERS
AND FILTERSDEWPONT
TRANSMITTER &
CO MONITOR
(TYPICAL)
PANEL
4" THICK HOUSEKEEPING
PAD
RELIEF VALVE
RECEIVER
FLEX CONNECTOR (TYPICAL)
FAN OR O.A. INTAKE. INSTALL PER
25'-0" FROM ANY VENT, EXHAUST
INTAKE SHALL BE A MINIMUM OF
NFPA 99.
NOTE:
3'-0"
RECEIVER DRAIN TO FLOOR DRAIN
CLEARANCE
MINIMUM
ROOF LINE
DUPLEX MEDICAL AIR COMPRESSOR
SEE ROOF PLAN
FOR PENETRATION
(CONT. PRESSURE TYPE)
ICE MACHINE CONNECTION DETAIL
FOR WATER CONN.
MILLWORK
PENETRATIONS.
PIPE GROMMETS AT
TO SEWER
TO VALVE
VERIFY WITH EQUIP. MANUF.
VERIFY WITH EQUIP. MANUF.
CEILING
FOR DRAIN CONN.
ICE
MAKER
FINISH FLOOR
DRAIN BOX
CONCEALED IN WALL
3/4" SUPPLY. 1/2" DRAIN
1/2" DRAIN LINE
MOD. AP117 CARBON FILTER
STAINLESS STEEL HOUSING WITH
3/4" AQUA-PURE MOD. AP-1610
FROM ABOVE CEILING
WATER SUPPLY
1/2" BACKFLOW PREVENTER
ICE MACHINE DRAIN DETAIL
s"
FIN.FLR.
NTS
NTS
SUBMERSIBLE SUMP PUMP
NTS
SUBMITTED & INSTALLED
TRAP PRIMER DETAIL
NTS
MEDICAL GAS MANIFOLD
PROTECTIVE
RUBBER MAT
HEAVY GAUGE
GAUGE & PRESSURE SWITCH
EXISTING PRESSURE
WITH PIPE CLAMPS FOR MANIFOLD
EXISTING UNISTRUT SUPPORTS
DISTRIBUTION PIPING.
MANIFOLD
EXISTING MAIN SHUT OFF VALVE
LOCKED IN OPEN
POSITION.
FLOOR LINE
BALL VALVE
A. PROVDE ALL NECESSARY GUAGES,
REGULATORS, CHECK VALVES, FILTERS
C. INSTALL AS PER NFPA 99c.
B. PROVIDE RELIEF VALVE AND VENT LINE.
AND PRESSURE INDICATORS FOR THE
INSTALLATION OF THE MANIFOLD.
NTS
CYLINDERS
PROVIDED BY GAS
CY
LI
ND
ER
EX
IS
TI
NG
G
AS
NE
W
G
AS
CY
LI
ND
ER
TO WALL (INCLUDING SPARES)
EA. CYLINDER TO BE SECURED
CHAINS & MOUNTING BRACKET.
PER NFPA. PC SHALL PROVIDE
NOTES:
PROVIDER.
TERMINATE AT ROOF
CY
LI
ND
ER
EX
IS
TI
NG
G
AS
CY
LI
ND
ER
EX
IS
TI
NG
G
AS
CY
LI
ND
ER
EX
IS
TI
NG
G
AS
NE
W
G
AS
CY
LI
ND
ER
PROVIDE SIGNAGE PER
SPECIFICATIONS INDICATING
ROOMS SERVED AND AS
REQUIRED PER NFPA 99
CURRENT EDITION.
DIGITAL TOUCH
SCREEN PAD.
FINISHED FLOOR
(8
M M
ESCUTCHEON
TRAP PARALLEL
TO WALL
OFFSET WASTE
LOOSE KEY
STOP
LAMINAR FLOW
FAUCET
SEE SCHEDULE
CONTROL DEVICE
10 3/4"
(270 MM) ±
8 " (200 MM)
(4
M M
WALL CLEANOUT WALL CLEANOUT FINISHED FLOOR
ESCUTCHEON
TRAP PARALLEL
TO WALL
OFFSET WASTE
LOOSE KEY
STOP
LAMINAR FLOW
FAUCET
SEE SCHEDULE
CONTROL DEVICE
6 1/2"
MAX
8 " (200 MM)
(4
M M
APRON. REFER TO
REMOVABLE ANGLED
ARCH'S DETAILS.
WALL CLEANOUT WALL CLEANOUT
SEE SCHEDULE
ROOF WITH RETURN BEND AND INSECT SCREEN
VACUUM EXHAUST TO TERMINATE @ 36" ABOVE
INTAKE THRU ROOF. EXHAUST SHALL BE A MINIMUM
OF 25'-0" FROM ANY VENT, FAN OR OUTSIDE AIR
INTAKE. INSTALL PER NFPA 99.
1 1/2"
2"
2" s"
D
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:1
4:
P M
M :\l oc al re vi t f ile s\
C
E
C en tra l M od el
.rv t
P002
PLUMBING - DETAILS
15-0014-00
CORRECT OPERATING
ROOM DEFICIENCIES
RAE
GAT
Salisbury, NC
100% FINAL DESIGN
11/10/16
UP
G050
LINEN
G055
TOILET
135 SF
G061
CORRIDOR
288 SF
G045
SPD OFFICE
162 SF
G051
SPD OFFICE
158 SF
G003
CLOTH. RM OFFICE
1194 SF
G003A
STOR.
G003B
CHANG'G RM
84 SF
G004
SPD STOR
253 SF
G006 M.T.
70 SF
G008
SPD OFFICES
G040
SPD STORAGE
1832 SF
G049
STAIR
G042
DISPATCH
G047
ELEC CL
G060
MECH
39 SF
G041
ELECT. CLS
G082
MOP CLOSET
G083
MOP CLOSET
FIRST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
FIFTH FLOOR
SUMP PIT
SUBMERSIBLE
SUMP PUMP
ELEVATOR
SHAFT
(CONTROL PANEL)
COORDINATE
LOCATION OF PANEL
ON THIRD FLOOR IN
ELECTRICAL ROOM
3162.
2" SPD
2" SPD
2" SPD
2"SPD TO BE
DISCHARGED ONTO
GROUND LEVEL AREA
WAY. TO VERIFY
LOCATION OF
DISCHARGE SEE 1/P402C.
NTS
2SUMP PUMP DISCHARGE RISER DIAGRAM
AF AG AJ AK ALAH AN
A6
A12
A11
A13
A15
A18
ED
EC
EBEA
A2
B9
B8
WJ
E1
A3
A5
A7
A8
A4
A9
A14
A16
A17
A10
F2
F9
F1
D9
D5
D10
F
2"SPD
2"SPD
2"SPD DN FROM
ELEVATOR SHAFT
ON 4TH FLOOR
DISCHARGE 2"SPD ONTO
GROUND LEVEL ROOF. TO
BE COLLECTED BY FLOOR
DRAIN NEAR MECHANICAL
EQUIPMENT.
ROUTE PIPING HIGH
TO STRUCTURE.
2"SPD DN
2"SPD DN
KEY PLAN
C
A B
GRAPHIC SCALE
( in Feet )
1 inch = 4 ft.
4 42 8 16
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:0
5:
P M
M :\l oc al re vi t f ile s\
C
E
C en tra l M od el
.rv t
P100C
PLUMBING - GROUND
FLOOR - NEW WORK -
GRAVITY - AREA C
15-0014-00
CORRECT OPERATING
ROOM DEFICIENCIES
RAE
GAT
Salisbury, NC
100% FINAL DESIGN
11/10/16
1/4" = 1'-0"1 PLUMBING - GROUND FLOOR - NEW WORK - GRAVITY PIPING AREA C
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES TO
ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK PERFORMED BY THIS CONTRACTOR
THAT RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN TRADES, SHALL BE
CHANGED AS DIRECTED BY THE ARCHITECT/ENGINEER WITHOUT ADDITIONAL COMPENSATION
TO THE CONTRACTOR.
THE CONTRACTOR SHALL COORDINATE ROUTING OF PLUMBING TO ENSURE PIPING DOES NOT
PASS OVER ELECTRICAL PANELS.
THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE, WHEN
INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.
ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME LENGTH MAY
BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE OWNERS
DISCRETION.
ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING CONSTRUCTION SHALL BE
REMOVED AND REPLACED WITH NEW INSULATION TO MATCH ADJACENT INSULATION AND
COVERING.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING. THE PROJECT WILL BE CONSTRUCTED IN
PHASES AND EACH AREA OUTSIDE OF THE CURRENT PHASE SHALL REMAIN OPERATIONAL.
A.
B.
C.
D.
E.
F.
GENERAL NOTES
AJ AK AL
AN
A6
A11
ED
EC
EB
EA
A1
A2
WJ
E2
E4
E3
E1
E5
E6
E7
A3
A5
A7
A8
A4
A9
A10
F2
F9
F1
D9
D5
F
STAIRS
TOILET
TOILET
WOMEN'S
LOCKERS
MEN'S
LOCKERS
4130A
ELECTRICAL
STORAGE
4017A
PRE OP
SHOWER
SCRUB
OR #1
OR #2
EQ.
STORAGE
CYSTO
STORAGE
STERILE
SUPPLY
SOIL HOLD
CLEAN
CORE
STAIRS
CORRIDOR
NEPTUNE
DOCK
C-ARM
ALCOVE
P-51
P-90
(E
(E
(E
(E
4"(E)WS
3"(E)VS
1 1/4"(E)A.V.
4"(E)WS
3"(E)VS
1 1/4"(E)AV
2"W
3"W
2"V
3"(E)VS
4"(E)RD
2"W
4"(E)WS
4"(E)VS
3"W2"V
CO
2"W
2"W
4"(E)W 4"(E)V
2"W
3"W
2"V
2"V UP TO
FIFTH FLOOR
2"V
2"V
2"V
2"V
3"(E)W 3"(E)V
4"(E)W
4"(E)VTR
P-31
P-31
P-31
4" VTR
3"V
4"V
3"V
3"V
4"(E) W
FD-A
FS-A
3"W
3"W
2"V
2"V
3"W
3 2"(E) V UP TO
FIFTH FLOOR
2"(E)AV THRU ROOF
2"(E)V THRU ROOF
2"(E)V FROM
FLOOR
BELOW
3"(E)WS
3"(E)VS
KEY PLAN
C
A B
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES
TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK PERFORMED BY THIS
CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION
BETWEEN TRADES, SHALL BE CHANGED AS DIRECTED BY THE ARCHITECT/ENGINEER
WITHOUT ADDITIONAL COMPENSATION TO THE CONTRACTOR.
THE CONTRACTOR SHALL COORDINATE ROUTING OF PLUMBING TO ENSURE PIPING
DOES NOT PASS OVER ELECTRICAL PANELS.
THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE,
WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.
ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME
LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE
OWNERS DISCRETION.
ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING CONSTRUCTION
SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO MATCH ADJACENT
INSULATION AND COVERING.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING. THE PROJECT WILL BE
CONSTRUCTED IN PHASES AND EACH AREA OUTSIDE OF THE CURRENT PHASE SHALL
REMAIN OPERATIONAL.
ANY HANGERS OR SUPPORTS THAT ARE REPLACED DURING CONSTURCTION SHALL
FOLLOW THE INTERNATIONAL PLUMBING CODE (IPC), SECTION 220511 AS REQUIRED IN
THE COMMON WORK RESULTS FOR PLUMBING SPECIFICATION SECTION.
A.
B.
C.
D.
E.
F.
G.
GENERAL NOTES
CONTRACTOR TO CONNECT NEW SANITARY PIPING TO EXISTING SANITARY STACK BELOW
FINISH FLOOR. FIELD VERIFY LOCATION OF EXISTING SANITARY STACK.
CONTACTOR TO CONNECT NEW VENT PIPING TO EXISTING VENT STACK ABOVE CEILING.
FIELD VERIFY LOCATION OF EXISTING VENT STACK.
NEW FLASH STERILIZER PROVIDED BY OWNER. PLUMBING CONTRACTOR TO MAKE FINIAL
CONNECTIONS.
KEYED NOTES
GRAPHIC SCALE
( in Feet )
1 inch = 4 ft.
4 42 8 16
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:0
5:
P M
M :\l oc al re vi t f ile s\
C
E
C en tra l M od el
.rv t
P400B
PLUMBING - FOURTH
FLOOR - NEW WORK -
GRAVITY - AREA B
15-0014-00
CORRECT OPERATING
ROOM DEFICIENCIES
RAE
GAT
Salisbury, NC
100% FINAL DESIGN
11/10/16
1/4" = 1'-0"1 PLUMBING - FOURTH FLOOR - NEW WORK - GRAVITY - AREA B
AF AG AJ AK ALAH
A12
A13
A15
A18
ED
A14
A16
A17
D10
PACU PH 1
NURSE
STATION
NEW ELEV
EQ ALCOVE
TOILET
4017B
PH2 / RM1
PH2 / RM2
TOILET /
SHW
PH2 / RM3
PH2 / RM4
PH2 / RM5
DUMBWAITER
MECH
STORAGE
LINEN
VENDING
4154A
ELEC
IT
NEW ELEVATOR
SUMP PUMP
4"(E)WS
2"(E)VS
2 1/2"(E)AV
4"(E)VS
4"(E)W
3"(E)V
4"(E)VS
4"(E)RD
3"(E)WS
2"(E)VS
4"(E)RD
P-91
2"W
2"SPD DN TO
GROUND FLOOR
SP-1
2"SPD UP TO
4TH FLOOR
CEILING
2"SPD
2"SPD
2"SPD
3"(E)WS
3"(E)VS
4"(E)V
3"(E)W
3"(E)V 4"(E)VS
KEY PLAN
C
A B
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES
TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK PERFORMED BY THIS
CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN
TRADES, SHALL BE CHANGED AS DIRECTED BY THE ARCHITECT/ENGINEER WITHOUT
ADDITIONAL COMPENSATION TO THE CONTRACTOR.
THE CONTRACTOR SHALL COORDINATE ROUTING OF PLUMBING TO ENSURE PIPING
DOES NOT PASS OVER ELECTRICAL PANELS.
THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE,
WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.
ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME
LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE
OWNERS DISCRETION.
ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING CONSTRUCTION
SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO MATCH ADJACENT
INSULATION AND COVERING.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING. THE PROJECT WILL BE
CONSTRUCTED IN PHASES AND EACH AREA OUTSIDE OF THE CURRENT PHASE SHALL
REMAIN OPERATIONAL.
ANY HANGERS OR SUPPORTS THAT ARE REPLACED DURING CONSTURCTION SHALL
FOLLOW THE INTERNATIONAL PLUMBING CODE (IPC), SECTION 220511 AS REQUIRED IN
THE COMMON WORK RESULTS FOR PLUMBING SPECIFICATION SECTION.
A.
B.
C.
D.
E.
F.
G.
GENERAL NOTES
CONTRACTOR TO CONNECT NEW SANITARY PIPING TO EXISTING SANITARY STACK BELOW
FINISH FLOOR. FIELD VERIFY LOCATION OF EXISTING SANITARY STACK.
CONTACTOR TO CONNECT NEW VENT PIPING TO EXISTING VENT STACK ABOVE CEILING.
FIELD VERIFY LOCATION OF EXISTING VENT STACK.
NEW FLASH STERILIZER PROVIDED BY OWNER. PLUMBING CONTRACTOR TO MAKE FINIAL
CONNECTIONS.
KEYED NOTES
GRAPHIC SCALE
( in Feet )
1 inch = 8 ft.
8 84 16 32
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:0
5:
P M
M :\l oc al re vi t f ile s\
C
E
C en tra l M od el
.rv t
P400C
PLUMBING - FOURTH
FLOOR - NEW WORK -
GRAVITY - AREA C
15-0014-00
CORRECT OPERATING
ROOM DEFICIENCIES
RAE
GAT
Salisbury, NC
100% FINAL DESIGN
11/10/16
1/4" = 1'-0"1 PLUMBING - FOURTH FLOOR - NEW WORK - GRAVITY - AREA C
AN
A6
A11
ED
EC
EB
EA
A1
A2
WJ
E2
E4
E3
E1
E5
E6
E7
A3
A5
A7
A8
A4
A9
A10
F2
F9
F1
D9
D5
F
P-51
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
(E
(E
(E
(E
ELECTRICAL
STORAGE
4017A
PRE OP
SCRUB
OR #1
OR #2
EQ.
STORAGE
CYSTO
STORAGE
STERILE
SUPPLY
SOIL HOLD
CLEAN
CORE
STAIRS
NEPTUNE
DOCK
C-ARM
ALCOVE
CORRIDOR
1/2"HW
1/2"CW
1/2"CW
1/2"HW
1/2"HW
1/2"CW
3/4"CW
1/2"HW
1/2"HW
1/2"CW
1/2"HW
1/2"CW
3/4"CW
3/4"HW
1/2"CW
1/2"HW
1/2"HW
1/2"HW
1/2"HW
WET RISER
1"(E)CW
3/4"(E)HW
1/2"(E)HWR
P-90
11/2"CW 1/2"CW
1/2"CW
P-31
P-31
P-31
OFFSET DOMESTIC WATER SERVICE IN
3RD FLOOR CEILING. COORDINATE TO
NEAREST WALL ON FOURTH FLR. REMOVE
EXISTING WET RISER TO THE FIFTH FL00R.
PROVIDE NEW BALANCING & CHECK VALVE
FOR HOT WATER RECIRC. IN FOURTH FLR
CEILING.
OFFSET DOMESTIC WATER
SERVICE IN 3RD FLOOR CEILING.
COORDINATE SERVICE TO
NEAREST WALL ON FOURTH FLR.
1/2" CW MAKE-UP WATER
PROVIDED FOR HUMIDIFIERS.BFP-1
1/2"CW
3/4"CW
3/4"CW
3/4"CW
3/4"CW PROVIDED
TO STERILIZER
BFP-1
STAIRS
MEN'S
LOCKERS
4130A
MEN'S
LOCKERS
CORRIDOR
4012WOMEN'S
LOCKERS
TOILET
TOILET
CORRIDOR
CLEAN
CORE
STAIRS
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
KEY PLAN
C
A B
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES
TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK PERFORMED BY THIS
CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN
TRADES, SHALL BE CHANGED AS DIRECTED BY THE ARCHITECT/ENGINEER WITHOUT
ADDITIONAL COMPENSATION TO THE CONTRACTOR.
THE CONTRACTOR SHALL COORDINATE ROUTING OF PLUMBING TO ENSURE PIPING
DOES NOT PASS OVER ELECTRICAL PANELS.
THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE,
WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.
ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME
LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE
OWNERS DISCRETION.
ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING CONSTRUCTION
SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO MATCH ADJACENT
INSULATION AND COVERING.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING. THE PROJECT WILL BE
CONSTRUCTED IN PHASES AND EACH AREA OUTSIDE OF THE CURRENT PHASE SHALL
REMAIN OPERATIONAL.
ANY HANGERS OR SUPPORTS THAT ARE REPLACED DURING CONSTURCTION SHALL
FOLLOW THE INTERNATIONAL PLUMBING CODE (IPC), SECTION 220511 AS REQUIRED IN
THE COMMON WORK RESULTS FOR PLUMBING SPECIFICATION SECTION.
A.
B.
C.
D.
E.
F.
G.
GENERAL NOTES
CONTRACTOR TO CONNECT NEW DOMESTIC WATER PIPING TO EXISTING DOMESTIC
WATER STACKS ABOVE CEILING. FIELD VERIFY LOCATION OF EXISTING DOMESTIC WATER
PIPING.
NEW FLASH STERILIZER PROVIDED BY OWNER. PLUMBING DESIGN CANNOT BE
COMPLETED AT THIS TIME DUE TO UNKNOWN UTILITY REQUIREMENTS.
KEYED NOTES
GRAPHIC SCALE
( in Feet )
1 inch = 4 ft.
4 42 8 16
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:0
9:
P M
M :\l oc al re vi t f ile s\
C
E
C en tra l M od el
.rv t
P401B
PLUMBING - FOURTH
FLOOR - NEW WORK -
DOMESTIC - AREA B
15-0014-00
CORRECT OPERATING
ROOM DEFICIENCIES
RAE
GAT
Salisbury, NC
100% FINAL DESIGN
11/10/16
1/4" = 1'-0"1 PLUMBING - FOURTH FLOOR - NEW WORK - DOMESTIC - AREA B
A11
A13
A15
A18
ED
A14
A16
A17
D10
WET RISER
1 1/2"(E)CW
3/4"(E)HW
1/2"(E)HWR
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
PRE OP
P-91
1/2"CW
WET RISER
1 1/4"(E)CW
1"(E)HW
1/2"(E)HWR
WET RISER
3/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
WET RISER
1 1/4"(E)CW
3/4"(E)HW
1/2"(E)HWR
PACU PH 1
NURSE
STATION
PH2 / RM1
TOILET
4017B
PH2 / RM2
TOILET /
SHW
PH2 / RM3
PH2 / RM4
EQ ALCOVE
DUMBWAITER
STORAGE
LINEN
VENDING
4154A
NEW ELEV
IT
ELEC
STAIRS
KEY PLAN
C
A B
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES
TO ELIMINATE CONFLICT WITH OTHER TRADES. ANY WORK PERFORMED BY THIS
CONTRACTOR THAT RESULTS IN CONFLICT, DUE TO LACK OF COORDINATION BETWEEN
TRADES, SHALL BE CHANGED AS DIRECTED BY THE ARCHITECT/ENGINEER WITHOUT
ADDITIONAL COMPENSATION TO THE CONTRACTOR.
THE CONTRACTOR SHALL COORDINATE ROUTING OF PLUMBING TO ENSURE PIPING
DOES NOT PASS OVER ELECTRICAL PANELS.
THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE,
WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.
ALL SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS
REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME
LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE
OWNERS DISCRETION.
ANY EXISTING PIPE OR DUCT INSULATION THAT IS DAMAGED DURING CONSTRUCTION
SHALL BE REMOVED AND REPLACED WITH NEW INSULATION TO MATCH ADJACENT
INSULATION AND COVERING.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING. THE PROJECT WILL BE
CONSTRUCTED IN PHASES AND EACH AREA OUTSIDE OF THE CURRENT PHASE SHALL
REMAIN OPERATIONAL.
ANY HANGERS OR SUPPORTS THAT ARE REPLACED DURING CONSTURCTION SHALL
FOLLOW THE INTERNATIONAL PLUMBING CODE (IPC), SECTION 220511 AS REQUIRED IN
THE COMMON WORK RESULTS FOR PLUMBING SPECIFICATION SECTION.
A.
B.
C.
D.
E.
F.
G.
GENERAL NOTES
CONTRACTOR TO CONNECT NEW DOMESTIC WATER PIPING TO EXISTING DOMESTIC
WATER STACKS ABOVE CEILING. FIELD VERIFY LOCATION OF EXISTING DOMESTIC
WATER PIPING.
NEW FLASH STERILIZER PROVIDED BY OWNER. PLUMBING CONTRACTOR TO MAKE
FINIAL CONNECTIONS.
KEYED NOTES
GRAPHIC SCALE
( in Feet )
1 inch = 4 ft.
4 42 8 16
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:0
5:
P M
M :\l oc al re vi t f ile s\
C
E
C en tra l M od el
.rv t
P401C
PLUMBING - FOURTH
FLOOR - NEW WORK -
DOMESTIC - AREA C
15-0014-00
CORRECT OPERATING
ROOM DEFICIENCIES
RAE
GAT
Salisbury, NC
100% FINAL DESIGN
11/10/16
1/4" = 1'-0"1 PLUMBING - FOURTH FLOOR - NEW WORK - DOMESTIC - AREA C
OUTLET LEGEND
MEDICAL GAS EQUIPMENT/
AREA ALARM - WIRE REQUIRED PRESSURE SWITCHES FROM
ZONE VALVE BOX - WITH PRESSURE GAUGES
ALARM PANEL TO LINE SWITCH. COORDINATE WIRING OF NEW
EQUIPMENT DESCRIPTION
A
ZV
AA
SYMBOL
MASTER ALARM - WIRE REQUIRED PRESSURE SWITCHES
FROM MASTER PANEL TO SOURCE SWITCH. COORDINATEMA
B
ANESTHESIA BOOM OUTLETS, PROVIDED BY OWNER AND
FINAL CONNECTION BY PC - 2 OXY, 1 AIR, 2 VACUUM, 3 SLIDE
FINAL CONNECTION BY PC. - 1 CARBON DIOXIDE , 1
EQUIPMENT BOOM OUTLETS, PROVIDED BY OWNER AND
NITROGEN, 2 VACUUM, 2 SLIDE.
1 WAGD, 1 NITROUS OXIDE
C INSTALLED BY PC. - 1 OXY, 1 VACUUM, 2 SLIDE,
ADDITATIONAL WALL DISS OUTLETS PROVIDED
1 NITROUS OXIDE, 1 WAGD, 1 MED AIR.
D
E
LOCATION OF PANEL WITH BUILDING MAINTENANCE.
INSTALLED BY PC. - 1 NITROGEN, 1 VACUUM, 1 SLIDE.
ADDITIONAL WALL DISS OUTLETS PROVIDED AND
F OWNER TO PROVIDE HEAD WALL AND ADDITIONAL PIPING TO
OUTLETS. PC TO MAKE FINIAL CONNECTION - 2 OXY, 1 AIR,
INSTALLED BY PC. - 2 NITROGEN , 1 CARBON DIOXIDE,
ADDITIONAL WALL DISS OUTLETS PROVIDED AND
1 VACUUM, 1 SLIDE.
AREA ALARM PANEL TO EXISTING MASTER ALARM PANEL.
3 VACUUM, 3 SLIDE.
DN
KEY PLAN
C
A B
AF AG
AEAC
AH
AD3.9
3.10
3.6
3.1
3.2
A6
A11
ED
EC
EB
EA
A1
A2
B9
B7
B5
B6
B8
B4
B3
B2
A3
A5
A7
A8
A4
A9
A10
F2
F9
F1
D9
D5
D10
F
TOILET
TOILET
SHOWER
4130B
MEN'S
LOCKERS
4130A
STAIRS
HAC
MED GAS
SOILED
UTILITY
OR #5
SUB
STERILE
OR #6
OR #7
EQ
STORAGE #2
SURGICAL
CORRIDOR
STAIR
EQUIPMENT
STORAGE #1
HAC
CLEAN
ELEVATOR
ELEVATOR
LOBBY
SURGICAL
CORRIDOR
OFFICE
4127B
RELOCATED
NEPTUNE
DOCK
STAFF
WORKSTATION
SUPPLIES /
CLEAN
UTILITY
TOILET
SOILED
UTILITY
LINEN
CHUTE
CONNECT TO EXISTING
MANIFOLD APON VERIFYING
EXISTING MEDICAL GAS
MANIFOLDS CAPACITY
MANIFOLDS MAY NEED
RESIZED
NEW SERVICE VALVES
MED GAS PIPING
CONTINUES TO SERVE OR'S
OUTSIDE AREA OF WORK
CO2, N , N20 UP
TO 5TH FLR
(E)A (E)O
(E)N
(E)CO2
N
2ON
C O
(E)MV
EXISTING AREA ALARM
PANEL FOR OR'S 1,2. TO BE
RECONNECTED TO SERVICE
AFTER CONSTRUCTION IS
COMPLETE
EXISTING AREA ALARM
PANEL FOR OR 5,6 & 7.
1"O
3/4"CO2 3/4"N
3/4"N2O
3/4"CO2
3/4"N 3/4"N2O
EXISTING NITROGEN
MANIFOLD
EXISTING CARBON
DIOXIDE MANIFOLD
EXISTING NITROUS
OXIDE MANIFOLD
(E)
(E)
(E)
(E)
(E)
(E)
PROVIDE 2 ADDITION
CONNECTION POINTS FOR
CARBON DIOXIDE MANFOLD.
VERIFY LOAD REQUIRMENT FOR
ADDITION SERVICE.
PROVIDE 4 ADDITION
CONNECTION POINTS FOR
NITROGEN MANFOLD. VERIFY
LOAD REQUIRMENT FOR
ADDITION SERVICE.
PROVIDE 2 ADDITION
CONNECTION POINTS FOR
NITROUS OXIDE MANFOLD.
VERIFY LOAD REQUIRMENT
FOR ADDITION SERVICE.
PROVIDE CYLINDER-SAFE TANK
STORAGE RACKS. (TYPICAL)
(E)N
(E)CO2
(E)N2O
(E)
(E)
EXTENT OF NEW WORK
FOR MED GAS 4128 IS
OUT OF CONSTRUCTION
SCOPE OF WORK.
CONTRACTOR TO VERIFY EXISTING
LOCATION OF MASTER ALARM PANEL
IN AOD OFFICE ON GROUND LEVEL.
PROVIDE AND COORDINATE
REQUIREMENTS FOR NEW WIRING TO
BE INSTALLED FOR MEDICAL ALARM
PANELS AND MEDICAL EQUIPMENT
FOR 4TH AND 5TH FLOOR LEVEL.
GRAPHIC SCALE
( in Feet )
1 inch = 4 ft.
4 42 8 16
5838 Monroe Road, Suite 100 Charlotte, NC 28212
704 531 3000 Project No. 3588
Charlotte Engineers, LLP
This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.
It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.
It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.
Project
City, State
Project Number
Drawn By
Checked By
Seal / Signature
Sheet Title
Date
Sheet Number
Issued For
Architect of Record
5960 Fairview Road Suite 500 Charlotte, NC 28210
887.3500
887.3507 fax
Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212
704.531.3000 PHONE
704.531.3001 FAX
MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:
Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031
704.987.9114 PHONE
704.987.9938 FAX
STRUCTURAL:
Program Manager
13620 Reese Blvd.
Suite 100
Huntersville, NC 28078
401.2040
401.2067 fax
5/ 8/
:0
6:
P M
M :\l…