36C24618R0842-004.pdf

PDF 16 MB Posted

Attached to
Project 659-16-101, Correct Operating Room Deficiencies Federal contract opportunity
Solicitation number
36C24618R0842
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

36C24618R0842 CONTRACT ATTACHMENT A - DRAWINGS - FILE 3 - Electrical.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Project 659-16-101, Correct Operating Room Deficiencies, newest first.
File Type Posted
36C24618R0842-0002004.pdf PDF
36C24618R0842-0002002.pdf PDF
36C24618R0842-0002000.docx DOCX document
36C24618R0842-0002003.pdf PDF
36C24618R0842-0002001.pdf PDF
36C24618R0842-007.pdf PDF
36C24618R0842-006.pdf PDF
36C24618R0842-002.pdf PDF
36C24618R0842-005.pdf PDF
36C24618R0842-008.docx DOCX document
36C24618R0842-003.pdf PDF
36C24618R0842-001.docx DOCX document
36C24618R0842-009.pdf PDF
36C24618R0842-000.docx DOCX document
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C

H

M

PS

PS D

V

PTZ

PB

SS

SS

K

KPCR

EXIT

ELC

PP

CR

ES

AL

PB

ML

ERS

BR

BA

NL

EMO

DAS

VFD

W

S

SS

SS

SS S

3050A

ANESTH.

WORK.B

S

SEE LUMINAIRE SCHEDULE number of ballasts in fixture

N/A total exterior wattage specified vs allowed

* total interior wattage specified vs allowed

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

total wattage per fixture ballast type used in the fixture

PerformancePrescriptive

METHOD OF COMPLIANCE :

ELECTRICAL SYSTEM AND EQUIPMENT

SEE LUMINAIRE SCHEDULE

number of lamps in fixture lamp type required in fixture Lighting schedule

** Lighting shall have a source efficacy of at least 45 lumens per watt.

PerformancePrescriptive

ENERGY CODE

ASHRAE 90.1

506.2.1 MORE EFFICIENT MECHANICAL EQUIPMENT

506.2.2 REDUCED LIGHTING POWER DENSITY

506.2.3 ENERGY RECOVERY VENTILATION SYSTEMS

506.2.4 HIGHER EFFICIENCY SERVICE WATER HEATING

506.2.5 ON-SITE SUPPLY OF RENEWABLE ENERGY

506.2.6 AUTOMATIC DAY LIGHTING CONTROL SYSTEMS

ELECTRICAL ENERGY CODE SUMMARY

DRAWING TITLE

ELECTRICAL SYMBOLS

RL = EXISTING DEVICE TO BE RELOCATED.

DASHED SYMBOLS INDICATE EXISTING DEVICES.

DOORBELL TRANSFORMER.

DOORBELL BUTTON.

DOORBELL CHIME.

MISCELLANEOUS

WHERE CEILING HEIGHT EXCEEDS 9'-0".

RLD = RELOCATED DEVICE SHOWN IN FINAL LOCATION.

RM = EXISTING DEVICE TO REMAIN.

RV = EXISTING DEVICE TO BE REMOVED.

FLOOR PLAN KEYED NOTES, SEE FLOOR PLAN.

DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.

ON CENTER.

ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.

TELEPHONE TERMINAL BOARD.

EMPTY CONDUIT.

ABBREVIATIONS

AFF

EC

OC

TTB

+60"

NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.NL

TELEPHONE OUTLET, FLUSH FLOOR MOUNTED.

TELEPHONE OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE.

SECURITY SYSTEM CLOSED CIRCUIT T.V. CAMERA. SUBSCRIPT INDICATES PAN/TILT/ZOOM CONTROL.

SECURITY SYSTEM DURESS ALARM PUSHBUTTON STATION. SURFACE MOUNTED 42" AFF.

PUBLIC ADDRESS SYSTEM MICROPHONE OUTLET, WALL MOUNTED 18" AFF. COORDINATE TYPE OF

PUBLIC ADDRESS SYSTEM HORN, WALL MOUNTED 7'-6" AFF. UNLESS OTHERWISE INDICATED.

PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.

OUTLET WITH OWNER'S EQUIPMENT.

W = WALL MOUNTED STATION

INTERCOM OUTLET WALL MOUNTED 42" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION

VOICE/DATA OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE OR SECURITY CAMERA.

MODIFIERS FOR INTERCOM:

S = SUB STATION

M = MASTER STATION

TELEPHONE OUTLET, WALL MOUNTED 48" AFF.

VOICE/DATA OUTLET, WALL MOUNTED 42" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH.

PROVIDE 3/4"C. FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.

OR 6" FROM BOTTOM OF OUTLET TO COUNTERTOP.

TELEPHONE OUTLET WALL MOUNTED 42" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH,

PROVIDE FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE. PROVIDE 1 1/4" EMPTY

CONDUIT WITH NYLON PULL CORD FROM JUNCTION BOX TO ABOVE ACCESSIBLE CEILING FOR

VOICE/DATA WIRING TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION

MODIFIERS FOR VOICE/DATA & TELEPHONE OUTLETS:

COMMUNICATIONS

VOICE/DATA OUTLET, FLUSH FLOOR MOUNTED.

PUBLIC ADDRESS SYSTEM VOLUME CONTROL SWITCH, WALL MOUNTED 42" AFF.

CONDUIT SLEEVES. SEE PLANS FOR SIZE AND QUANTITY.

FIRE ALARM DUCT MOUNTED SMOKE DETECTOR.

FIRE ALARM TAMPER SWITCH CONNECTION TO SPRINKLER SYSTEM.

FIRE ALARM CENTRAL PROCESSING UNIT/STATUS COMMAND CENTER.

FIRE ALARM AUDIO & VISUAL ALARM SIGNAL. WALL MOUNTED 80" AFF TO BOTTOM OF DEVICE.

FIRE ALARM FLOW SWITCH CONNECTION TO SPRINKLER SYSTEM.

FIRE ALARM SPEAKER MOUNTED IN ELEVATOR CAB.

FIRE ALARM THERMAL DETECTOR.

FIRE ALARM SYSTEM TRANSPONDER.

FIRE ALARM SMOKE DETECTOR.

FIRE ALARM ELEVATOR CONNECTION.

FIRE ALARM MAGNETIC DOOR HOLDER. PROVIDE 120V POWER FROM LIFE-SAFETY BRANCH

FIRE ALARM CEILING MOUNTED REMOTE INDICATING LIGHT. W = WALL MOUNTED 12" BELOW CEILING.

120V CEILING MOUNTED SMOKE DETECTOR.

FIRE ALARM CHIME & VISUAL ALARM SIGNAL, WALL MOUNTED 80" AFF TO BOTTOM OF DEVICE.

FIRE ALARM REMOTE ANNUNCIATOR PANEL. BOTTOM 56" AFF TO TOP OF DEVICE.

FIRE ALARM SPEAKER, CEILING MOUNTED. W = WALL MOUNTED (12" BELOW CEILING OR

FIRE ALARM CONTROL PANEL. MOUNT AT 6'-6" AFF TO TOP.

FIRE ALARM MANUAL PULL STATION, 42" AFF.

CIRCUIT PANEL BOARD PROVIDE 20A/1P CIRCUIT BREAKER. WIRE WITH 2#12+1#12G, 3/4"C.

PROVIDE TRANSFORMER AS REQUIRED BY DOOR HOLDER.

FIRE ALARM

FIRE ALARM CHIME & VISUAL ALARM SIGNAL, CEILING MOUNTED.

FIRE ALARM VISUAL ALARM SIGNAL, WALL MOUNTED 80" AFF TO BOTTOM OF DEVICE.

FIRE ALARM VISUAL ALARM SIGNAL, CEILING MOUNTED.

96" AFF WHERE CEILING HEIGHT EXCEEDS 9'-0").

FLUORESCENT LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.

LED, COMPACT FLUORESCENT, OR HID LIGHTING FIXTURE, CEILING OR WALL MOUNTED,

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

DRAWINGS. SEE SCHEDULE FOR TYPE (*).

CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON

EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED

OTHERWISE. CONNECT UNSWITCHED.

LIGHTING

LED, COMPACT FLUORESCENT, OR HID LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.

TRACK LIGHTING FIXTURE. SEE PLANS/SCHEDULE FOR TRACK LENGTH AND NUMBER OF TRACK HEADS.

NURSE CALL PSYCHIATRIC PATIENT STATION, 42" AFF TO CENTER OF DEVICE.

MONITOR OUTLET. COORDINATE EXACT LOCATION WITH OWNER/ARCHITECT.

NARCOTICS CABINET SWITCH CONNECTION.

ELAPSED TIME CLOCK (6'-6" AFF) AND CONTROLS (5'-0" AFF).

DOCTORS' DICTATION OUTLET WALL, MOUNTED 18" AFF, OR 8" ABOVE COUNTER,

NURSE CALL CORRIDOR ZONE LIGHT, CEILING MOUNTED.

NURSE CALL STAFF STATION, 44" AFF TO CENTER OF DEVICE.

NURSE CALL CONNECTION TO DOOR.

OR 2" ABOVE BACKSPLASH.

NURSE CALL DOUBLE PATIENT STATION. SEE PATIENT ROOM ELEVATION FOR MOUNTING HEIGHT, NURSE CALL SINGLE PATIENT STATION. SEE PATIENT ROOM ELEVATION FOR MOUNTING HEIGHT, NURSE CALL SIDECOM INTERFACE MODULE.

NURSE CALL PSYCHIATRIC SPEAKER, CEILING MOUNTED.

NURSE CALL MASTER STATION, DESK MOUNTED.

NURSE CALL KEYED SWITCH STATION, 42" AFF.

NURSE CALL EMERGENCY PSYCHIATRIC PUSHBUTTON, 42" AFF.

NURSE CALL EMERGENCY STATION W/ PULL CORD, 70" AFF.

NURSE CALL EMERGENCY STATION W/ PULL CORD, 30" AFF.

NURSE CALL EMERGENCY STATION W/ PUSH BUTTON WITH 6' CORD, 42" AFF.

NURSE CALL DUTY STATION, 42" AFF TO CENTER OF DEVICE.

NURSE CALL CORRIDOR DOME LIGHT, CEILING MOUNTED.

NURSE CALL CENTRAL EQUIPMENT, MOUNT AT 6'-6" AFF TO TOP.

NURSE CALL CODE BLUE STATION, 42" AFF TO CENTER OF DEVICE.

NURSE CALL ANNUNCIATOR PANEL, WALL RECESSED, MOUNT AT 6'-0" AFF TO TOP.

IF NONE SHOWN MOUNT AT 44" AFF TO CENTER OF DEVICE.

IF NONE SHOWN MOUNT AT 44" AFF TO CENTER OF DEVICE.

NURSE CALL

NARCOTICS ALARM LIGHT.

NURSE CALL SYSTEM LOW VOLTAGE CONTROLLER.

LOW VOLTAGE TV.

EQUIPMENT IDENTIFICATION

HORSEPOWER RATING

MOTOR CONNECTION. SPECIAL VOLTAGES AS SHOWN ON DRAWING.

ENCLOSED CIRCUIT BREAKER. NUMERAL INDICATES TRIP AMPERE RATING.

FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.

NON-FUSIBLE SAFETY SWITCH. NUMERAL INDICATES AMPERE RATING.

SIZE AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH CIRCUIT BREAKER. TOP NUMERAL INDICATES CIRCUIT BREAKER

MOTOR STARTER. NUMERAL INDICATES NEMA SIZE.

AMPACITY. SEE FEEDER SCHEDULE.

ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER

WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.

WIRING SYSTEM BELOW FLOOR OR BELOW GRADE.

ETC. DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, WIRING SYSTEM TURNED UP.

WIRING SYSTEM TURNED DOWN.

WIRING SYSTEM EXPOSED.

OVER CURRENT PROTECTION DEVICE NUMBER.

DRY TYPE TRANSFORMER.

NEC REQUIRED GROUND.

EF-1, 10 HP.460V, 3PH

208V, 3PH

120V, 1PH

MOTOR RATED SWITCH.

CONNECTION TO WALL MOUNTED FILM ILLUMINATOR. PROVIDE RECEPTACLE IN FLUSH OUTLET BOX AT

LOWER RIGHT HAND CORNER OF UNIT IF SURFACE MOUNTED. HARD WIRE IF RECESSED.

JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.

CEILING FAN 120V. MANUFACTURER (HUNTER#21252 GREEN FINISH W/ INTEGRATED 240W LIGHT FIXTURE)

CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

CONNECTION TO EXHAUST FAN. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

PANELBOARD SURFACE MOUNTED.

REMOTE ALARM PANEL FOR ISOLATED POWER PANEL BOARD WALL MOUNTED AT 5'-0" AFF.

GENERATOR REMOTE ALARM ANNUNCIATOR. WALL MOUNTED AT 5'-0" AFF.

BLANK = NORMAL BRANCH

U = UNGROUNDED (ISOLATION) PANEL

Q = EQUIPMENT BRANCH

C = CRITICAL BRANCH

L = LIFE SAFETY BRANCH

M = MOTOR CONTROL CENTER

L = 120/208 VOLT

H = 277/480 VOLT

PANELBOARD FLUSH MOUNTED.

1,2,3 = FLOOR

A,B,C = LOCATION

PANELBOARD NAMING CONVENTION

JUNCTION OR PULL BOX. W = WEATHERPROOF.

CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.

HARDWIRE CONNECTION FROM FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE AND 3/4" LIQUID TIGHT FLEXIBLE METALLIC WHIP TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT SUPPLIER/INSTALLER. EIGHT(8) WIRE SYSTEM PROVIDES FOUR(4) CIRCUITS.

POWER

SURFACE MOUNTED MULTIOUTLET ASSEMBLY. 46" AFF OR 8" ABOVE COUNTER

TV = TELEVISION, SEE DETAIL.

G = GROUND FAULT CIRCUIT INTERRUPTER.

EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER

P = PEDESTAL

WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.

DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

OR 2" ABOVE BACKSPLASH. SHADED AREA INDICATES RECEPTACLE.

DUPLEX RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED.

SIMPLEX RECEPTACLE MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 42" AFF TO CENTER OF OUTLET

OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES

OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY

DUPLEX RECEPTACLE, MOUNTED 42" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH

DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED. SLASH INDICATES

SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.

MODIFIERS FOR RECEPTACLES:

SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.

LH2A-1

CH2A

EQUIPMENT CONNECTION DESIGNATION, SEE SCHEDULE FOR DETAILS.

RATING AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH FUSED SWITCH. TOP NUMERAL INDICATES FUSETRON AMPERE

LIGHTNING PROTECTION SYSTEM GROUND ROD.

75KVA

LIGHTNING PROTECTION SYSTEM AIR TERMINAL.

TR = TAMPER RESISTANT

3 = THREE WAY

MODIFIERS FOR SWITCHES:

SINGLE POLE SWITCH.

THREE SINGLE POLE SWITCHES IN A 3-GANG BOX.

PHOTO ELECTRIC CELL MOUNTED ON CONDUIT STUBBED 6" ABOVE ROOF, FACING NORTH.

SWITCHES

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX.

PROVIDE DIVIDER FOR DIFFERENT VOLTAGES OR BRANCHES.

4 = FOUR WAY

D = DIMMER

DT = DOUBLE THROW

LV = LOW VOLTAGE

PROVIDE DIVIDER(S) FOR DIFFERENT VOLTAGES OR BRANCHES.

OS = OCCUPANCY SENSOR

TIME CLOCK. PROVIDE POWER CIRCUIT AND 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE.

a,b,c = MULTIPLE SWITCH LEGS

T = TIMER

INDICATED.

INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTUAL RCP FOR EXACT

LUMINAIRE, 2x4, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED). SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION/CEILING TYPE.

LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

SEE SCHEDULE FOR TYPE (*).

SEE SCHEDULE FOR TYPE (*).

REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.

HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.

UNLESS NOTED OTHERWISE.

WITH EQUIPMENT SUPPLIER/INSTALLER.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).

NURSE CALL PILLOW SPEAKER.

NURSE CALL SINGLE CALL CORD.

NURSE CALL HEADEND EQUIPMENT.

FIRE ALARM SPEAKER AND VISUAL ALARM SIGNAL, CEILING MOUNTED.

HEADWALL. SEE PLAN FOR NUMBER.HW#

POWER COLUMN. SEE PLAN FOR NUMBER.PC#

POWER SYSTEM.

CONNECTED TO THE EMERGENCY POWER SYSTEM.

FLUORESCENT STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY

GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

ELECTRIC STRIKE. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

WALL MOUNTED LOCAL ALARM BUZZER, 85dBA.

DURESS ALARM BUTTON RECESSED IN COUNTER.

MAGNETIC LOCK FOR DOOR.

PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.

REMOTE LINE ISOLATION MONITOR.

CABLE TV OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.

PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

VARIABLE SPEED DRIVEVSD

FIRE ALARM SMOKE DETECTOR, CEILING MOUNTED.

WIRELESS TELEMETRY ANTENNA

WIRELESS TELEMETRY DEVICE

EXPEDITER BUTTON PANEL

EXAM LIGHT CONTROLLER

EMERGENCY EGRESS PUSH BUTTON

KEY PAD CARD READER

FIRE ALARM SPEAKER AND VISUAL ALARM SIGNAL, WALL MOUNTED.

EMERGENCY RELEASE SWITCH. PROVIDE TAMPER RESISTANT COVER WITH A SOUNDING HORN.

RP = EXISTING DEVICE TO BE REPLACED WITH NEW DEVICE.

PNEUMATIC TUBE STATIONPTS

BUTTON RELEASE.

BADGE ACCESS.

NURSE LOCATOR.

EMERGENCY MANUAL OVERRIDE.

DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.

SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

SYMBOL LOCATION LEADER

POWER CONNECTION TO FIRE DAMPER. SEE DETAIL.

POWER AND FIRE ALARM CONNECTION TO SMOKE DAMPER OR FIRE/SMOKE DAMPER. SEE DETAIL.

NURSE CALL CORRIDOR DOME LIGHT, WALL MOUNT ABOVE DOOR AT 4" FROM THE TOP OF THE

DOOR FRAME TO THE BOTTOM OF THE DEVICE.

NURSE CALL CORRIDOR ZONE LIGHT, WALL MOUNT ABOVE DOOR AT 4" FROM THE TOP OF THE

DOOR FRAME TO THE BOTTOM OF THE DEVICE.

ROOM TAG

ELAPSED TIME CONTROL. MOUNT 48" AFF

BOOM LIGHT CONTROLLER

PUSH BUTTON

CONNECT LIFE SAFETY CIRCUIT TO MEDICAL GAS ALARM PANEL. 120V, 20A

WIRELESS ACCESS POINT

CODE BLUE RECEIVER

FIRE ALARM CONNECTION TO KNOX BOX.

PROVIDE DISCONNECT SWITCH AND CONNECTION TO MOTOR OPERATED DOOR. COORDINATE WITH

HARDWARE VENDOR.

INTERCOM STATION WITH BUILT IN CAMERA.

INTERCOM STATION WITH BUILT VIDEO MONITOR.

PROVIDE CONNECTION TO OWNER FURNISHED ELAPSED TIME CLOCK. MOUNT 84" AFF.

RV RM

RM

DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACH SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.

CARBON MONOXIDE DETECTOR. CEILING MOUNT.

FIRE ALARM CONNECTION TO KNOX BOX.

FIRE ALARM CONNECTION TO AUTOMATIC DOOR.

( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )

GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE OUTLET. SLASH INDICATES

CONNECTED TO THE EMERGENCY POWER SYSTEM.

TAMPER RESISTENT DUPLEX RECEPTACLE OUTLET. SLASH INDICATES

CONNECTED TO THE EMERGENCY POWER SYSTEM.

LUMINAIRE, 2X2, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED). SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION/CEILING TYPE.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

M

C

C

30CB

DB

DT

E

F

H

GA

J

J

M

LIM

P

PE

RA

T

TC

CB

FAC

CO

AD

CL

F

CL

DD

EC

ES

FACP

FARA

FATR

FD

FS

FS

H

FSD

KB

OS

L

HL

LD

L

SD

RL

SL

SD

TD

TS

SL

BL

D

DR

ET

ETC

IC

IM

M

MGA

MOD

NA

NA

NC

NC

NBO

NCL

NB

NCL

NCS

NEC

NEB

ND

NEC

NEP

NHE

NKS

NLV

NMS

NZL

NZL

NPP

NP1

NP2

NS

PS1

SCC

TV

WA

ET

G

TR TR

G

S

ELECTRICAL - SYMBOL SCHEDULE, NOTES AND DRAWING INDEX

ELECTRICAL - DETAILS AND NOTES

ELECTRICAL - LUMINAIRE SCHEDULE AND DETAILS

ELECTRICAL - LIGHTNING PROTECTION DETAILS

ELECTRICAL - VENDOR DETAILS

ELECTRICAL - FOURTH FLOOR - DEMOLITION PLAN

ELECTRICAL - FIFTH FLOOR - DEMOLITION PLAN

ELECTRICAL - FOURTH FLOOR - NEW WORK - LIGHTING - AREA A

ELECTRICAL - FOURTH FLOOR - NEW WORK - LIGHTING - AREA B

ELECTRICAL - FOURTH FLOOR - NEW WORK - LIGHTING - AREA C

ELECTRICAL - FOURTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA A

ELECTRICAL - FOURTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA B

ELECTRICAL - FOURTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA C

ELECTRICAL - FIFTH FLOOR - NEW WORK - LIGHTING - AREA A

ELECTRICAL - FIFTH FLOOR - NEW WORK - LIGHTING - AREA B

ELECTRICAL - FIFTH FLOOR - NEW WORK - LIGHTING - AREA C

ELECTRICAL - FIFTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA A

ELECTRICAL - FIFTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA B

ELECTRICAL - FIFTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA C

ELECTRICAL - ROOF PLAN - NEW WORK - POWER

E001 E002 E003 E004 E005

ED400

ED500

E400A E400B E400C E401A E401B E401C E500A E500B E500C E501A E501B E501C E600

CONNECTION TO PRE-FABRICATED HEADWALL UNIT. WITH NORMAL AND CRITICAL POWER

CIRCUITS AND COMMUNICATION SERVICES.

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX. EITHER SWITCH INBOARD AND OUTBOARD LAMPS

SEPARATELY OR STEP-DIM BOTH LAMPS TO 50%.

ELECTRICAL - ROOF - DEMOLITION PLANED600

ELECTRICAL - PANEL SCHEDULESE010

ED300 ELECTRICAL - THIRD FLOOR - DEMOLITION PLAN

E100 ELECTRICAL - GROUND FLOOR - NEW WORK - POWER

ELECTRICAL - THIRD FLOOR - NEW WORK - LIGHTING - AREA CE300C

ELECTRICAL - THIRD FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA CE301C

ELECTRICAL - PANEL SCHEDULESE011

ELECTRICAL - DETAILSE006

ELECTRICAL - POWER RISER DIAGRAME007

FIRE ALARM ISOLATION MODULE.ISO

DURESS ALARM SYSTEM INTRFACE CONNECTIONS.

(1 VOICE/1 DATA DENOTES QUANTITY OF VOICE/DATA OUTLETS)

* No new lighting load added.

VARIABLE FREQUENCY DRIVE.

ELECTRICAL - SITE PLANE020

CONNECTED TO THE EMERGENCY POWER SYSTEM.

VOICE/DATA OUTLET, CEILING MOUNTED.

GENERAL NOTES

A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE,

WHEN INDICATED IS INTENDED FOR GENERAL REFERENCE ONLY.

B. SHUTDOWNS SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS'

REPRESENTATIVE AND WILL REQUIRE ADVANCE NOTICE OF ONE WEEK. THIS TIME

LENGTH MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS AND SHALL BE AT THE

OWNERS' DISCRETION.

C. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY.

D. ELECTRICAL CONTRACTOR SHALL RELOCATE EXISTING EQUIPMENT THAT IS TO

REMAIN AS REQUIRED IN ORDER TO FACILITATE INSTALLATION OF NEW WORK.

E. ELECTRICAL CONTRACTOR IS NOT PERMITTED TO ROUTE WIRING CONNECTED TO THE

LIFE SAFETY OR CRITICAL BRANCH SOURCES OF POWER IN FLEXIBLE METAL

RACEWAYS OR METAL SHEATHED CABLE ASSEMBLIES, WITH THE EXCEPTIONS OF THE

EXEMPTIONS LISTED IN NEC 517.30.C.3.

F. ELECTRICAL CONTRACTORS SHALL PROVIDE SEPARATE RACEWAY, JUNCTION BOXES

OR CABINETS THAT ROUTE LIFE SAFETY AND/OR CRITICAL BRANCH CIRCUITS WIRING

FROM ALL WIRING AND EQUIPMENT CONNECTED TO OTHER BRANCHES OF POWER.

G. ALL FIXED ELECTRICAL EQUIPMENT FURNISHED BY ELECTRICAL CONTRACTOR SHALL

BE LISTED AND LABELED BY AN APPROVED NORTH CAROLINA TESTING AGENCY.

FACTORY ASSEMBLED LISTED COMPONENTS SHALL BE LISTED AND LABELED AS AN

ASSEMBLY. ANY ELECTRICAL EQUIPMENT NOT LISTED OR LABELED MUST BE

APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION AND HAVE A THIRD

PARTY TESTING LABEL OR SHALL BE REPLACED WITH EQUIPMENT THAT IS UL

LABELED/LISTED AT THE CONTRACTOR'S EXPENSE.

H. CONTRACTOR SHALL COORDINATE WITH THE FACILITY'S INFECTION CONTROL

OFFICER TO VERIFY THAT APPROPRIATE SAFEGUARDS ARE BEING TAKEN TO PROTECT

WORKERS INVOLVED IN DEMOLITION ACTIVITIES.

I. CONTRACTOR SHALL COORDINATE WITH FACILITY'S INFECTION CONTROL OFFICER TO

VERIFY THAT APPROPRIATE PRECAUTIONS ARE BEING TAKEN TO PROTECT FACILITY

STAFF AND PATIENTS DURING THE CONSTRUCTION ACTIVITIES.

J. ASBESTOS CONTAINING MATERIALS (IF PRESENT) WILL BE IDENTIFIED BY THE OWNER

AND WILL BE REMOVED FROM AHU'S, PIPING INSULATION, DUCT INSULATION, ETC. (IF

REQUIRED) PRIOR TO CONTRACTOR BEGINNING ANY WORK ON THE SITE. COORDINATE

WITH OWNER.

K. UNLESS NOTED OTHERWISE, ELECTRICAL CONTRACTOR SHALL INSTALL ALL

RACEWAY, BOXES, AND CABLES. ALL MEDICAL EQUIPMENT CABLES, UNLESS

OTHERWISE NOTED, SHALL BE PROVIDED BY MEDICAL EQUIPMENT VENDOR.

L. ALL ELECTRICAL WORK MUST BE COMPLETED IN PHASES, AS ESTABLISHED IN

"GENERAL CONDITIONS".

Q. BRANCH CIRCUIT WIRE SIZING WILL BE IN ACCORD WITH THE FOLLOWING TABLES:

VOLTS

120/208

DISTANCE

0' - 50'

HOME RUN

#12

REMAINDER

OF CIRCUIT

50' - 100' 100' - 150'

#10 #8

#12 #12 #10

VOLTS

277/480

DISTANCE

0' - 125'

HOME RUN

#12

REMAINDER

OF CIRCUIT

125' - 220' 220' - 330'

#10 #8

#12 #12 #10

P. ELECTRICAL CONTRACTOR SHALL USE MULTI-POLE BREAKERS FOR ALL SHARED

NEUTRALS OR PROVIDE SEPARATE NEUTRALS FOR EACH BRANCH CIRCUIT. ADJUST

PANEL SCHEDULES ACCORDINGLY TO MEET NEC 210.4.

O. CONDUCTORS SHALL BE COPPER, RATED AT NOT LESS THAN 600 VOLTS.

MINIMUM SIZE SHALL BE NO. 12 AWG UNLESS OTHERWISE NOTED ON THE DRAWINGS.

ALL WIRE #8 AWG AND LARGER SHALL BE STRANDED. #10 THRU #12 AWG

CONDUCTORS SHALL BE SOLID. ALL INSULATION TYPES SHALL BE THWN OR THHN.

N. A MAXIMUM OF THREE 20A, 1 POLE BRANCH CIRCUITS MAY BE COMBINED IN A

COMMON HOMERUN SHARING A COMMON NEUTRAL OR WITH SEPARATE NEUTRALS,

FOR A TOTAL OF SIX CURRENT - CARRYING CONDUCTORS. ALL BRANCH CIRCUITS

LARGER THAN 20A SHALL BE SEPARATELY HOMERUN TO PANEL TO MEET NEC 200.4.

M. PER NEC REQUIREMENTS, EQUIPMENT GROUNDING TERMINAL BUSES OF THE

NORMAL AND ESSENTIAL BRANCH-CIRCUIT PANELBOARDS SERVING THE SAME

INDIVIDUAL PATIENT CARE VICINITY SHALL BE CONNECTED TOGETHER WITH AN

INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 AWG.

ELECTRICAL - VENDOR DRAWINGSE008

ELECTRICAL - VENDOR DRAWINGSE009

ELECTRICAL - VENDOR DRAWINGSE012

ELECTRICAL - VENDOR DRAWINGSE013

ELECTRICAL - VENDOR DRAWINGSE014

DRAWING INDEX

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 3588

Charlotte Engineers, LLP

This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.

It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.

It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.

Project

City, State

Project Number

Drawn By

Checked By

Seal / Signature

Sheet Title

Date

Sheet Number

Issued For

Architect of Record

5960 Fairview Road Suite 500 Charlotte, NC 28210

887.3500

887.3507 fax

Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212

704.531.3000 PHONE

704.531.3001 FAX

MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:

Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031

704.987.9114 PHONE

704.987.9938 FAX

STRUCTURAL:

Program Manager

13620 Reese Blvd.

Suite 100

Huntersville, NC 28078

401.2040

401.2067 fax

/1

9/

:2 3:

P

M M

:\R ev it

\3

C E

C en tra l M od el .rv t

E001

ELECTRICAL - SYMBOL

SCHEDULE, NOTES AND

DRAWING INDEX

15-0014-00

CORRECT OPERATING

ROOM DEFICIENCIES

MMF

CLH

Salisbury, NC

100% FINAL DESIGN

11/10/16

Item Date Description

1 05/08/17 Revision 1 2 10/31/17 Revision 2 - Hybrid 2

C

H

M

PS

PS D

V

PTZ

PB

SS

SS

K

KPCR

EXIT

ELC

PP

CR

ES

AL

PB

ML

ERS

BR

BA

NL

EMO

DAS

VFD

W

S

SS

SS

SS S

3050A

ANESTH.

WORK.B

S

SEE LUMINAIRE SCHEDULE number of ballasts in fixture

N/A total exterior wattage specified vs allowed

* total interior wattage specified vs allowed

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

SEE LUMINAIRE SCHEDULE

total wattage per fixture ballast type used in the fixture

PerformancePrescriptive

METHOD OF COMPLIANCE :

ELECTRICAL SYSTEM AND EQUIPMENT

SEE LUMINAIRE SCHEDULE

number of lamps in fixture lamp type required in fixture Lighting schedule

** Lighting shall have a source efficacy of at least 45 lumens per watt.

PerformancePrescriptive

ENERGY CODE

ASHRAE 90.1

506.2.1 MORE EFFICIENT MECHANICAL EQUIPMENT

506.2.2 REDUCED LIGHTING POWER DENSITY

506.2.3 ENERGY RECOVERY VENTILATION SYSTEMS

506.2.4 HIGHER EFFICIENCY SERVICE WATER HEATING

506.2.5 ON-SITE SUPPLY OF RENEWABLE ENERGY

506.2.6 AUTOMATIC DAY LIGHTING CONTROL SYSTEMS

ELECTRICAL ENERGY CODE SUMMARY

DRAWING TITLE

ELECTRICAL SYMBOLS

RL = EXISTING DEVICE TO BE RELOCATED.

DASHED SYMBOLS INDICATE EXISTING DEVICES.

DOORBELL TRANSFORMER.

DOORBELL BUTTON.

DOORBELL CHIME.

MISCELLANEOUS

WHERE CEILING HEIGHT EXCEEDS 9'-0".

RLD = RELOCATED DEVICE SHOWN IN FINAL LOCATION.

RM = EXISTING DEVICE TO REMAIN.

RV = EXISTING DEVICE TO BE REMOVED.

FLOOR PLAN KEYED NOTES, SEE FLOOR PLAN.

DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.

ON CENTER.

ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.

TELEPHONE TERMINAL BOARD.

EMPTY CONDUIT.

ABBREVIATIONS

AFF

EC

OC

TTB

+60"

NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.NL

TELEPHONE OUTLET, FLUSH FLOOR MOUNTED.

TELEPHONE OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE.

SECURITY SYSTEM CLOSED CIRCUIT T.V. CAMERA. SUBSCRIPT INDICATES PAN/TILT/ZOOM CONTROL.

SECURITY SYSTEM DURESS ALARM PUSHBUTTON STATION. SURFACE MOUNTED 42" AFF.

PUBLIC ADDRESS SYSTEM MICROPHONE OUTLET, WALL MOUNTED 18" AFF. COORDINATE TYPE OF

PUBLIC ADDRESS SYSTEM HORN, WALL MOUNTED 7'-6" AFF. UNLESS OTHERWISE INDICATED.

PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.

OUTLET WITH OWNER'S EQUIPMENT.

W = WALL MOUNTED STATION

INTERCOM OUTLET WALL MOUNTED 42" AFF TO CENTER OF DEVICE, WITH DESK MOUNTED STATION

VOICE/DATA OUTLET, WALL MOUNTED 18" AFF TO CENTER OF DEVICE OR SECURITY CAMERA.

MODIFIERS FOR INTERCOM:

S = SUB STATION

M = MASTER STATION

TELEPHONE OUTLET, WALL MOUNTED 48" AFF.

VOICE/DATA OUTLET, WALL MOUNTED 42" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH.

PROVIDE 3/4"C. FROM OUTLET TO AN ACCESSIBLE SPACE ABOVE THE CORRIDOR LAY-IN CEILING.

OR 6" FROM BOTTOM OF OUTLET TO COUNTERTOP.

TELEPHONE OUTLET WALL MOUNTED 42" AFF, 2" FROM BOTTOM OF OUTLET TO BACKSPLASH,

PROVIDE FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE. PROVIDE 1 1/4" EMPTY

CONDUIT WITH NYLON PULL CORD FROM JUNCTION BOX TO ABOVE ACCESSIBLE CEILING FOR

VOICE/DATA WIRING TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION

MODIFIERS FOR VOICE/DATA & TELEPHONE OUTLETS:

COMMUNICATIONS

VOICE/DATA OUTLET, FLUSH FLOOR MOUNTED.

PUBLIC ADDRESS SYSTEM VOLUME CONTROL SWITCH, WALL MOUNTED 42" AFF.

CONDUIT SLEEVES. SEE PLANS FOR SIZE AND QUANTITY.

FIRE ALARM DUCT MOUNTED SMOKE DETECTOR.

FIRE ALARM TAMPER SWITCH CONNECTION TO SPRINKLER SYSTEM.

FIRE ALARM CENTRAL PROCESSING UNIT/STATUS COMMAND CENTER.

FIRE ALARM AUDIO & VISUAL ALARM SIGNAL. WALL MOUNTED 80" AFF TO BOTTOM OF DEVICE.

FIRE ALARM FLOW SWITCH CONNECTION TO SPRINKLER SYSTEM.

FIRE ALARM SPEAKER MOUNTED IN ELEVATOR CAB.

FIRE ALARM THERMAL DETECTOR.

FIRE ALARM SYSTEM TRANSPONDER.

FIRE ALARM SMOKE DETECTOR.

FIRE ALARM ELEVATOR CONNECTION.

FIRE ALARM MAGNETIC DOOR HOLDER. PROVIDE 120V POWER FROM LIFE-SAFETY BRANCH

FIRE ALARM CEILING MOUNTED REMOTE INDICATING LIGHT. W = WALL MOUNTED 12" BELOW CEILING.

120V CEILING MOUNTED SMOKE DETECTOR.

FIRE ALARM CHIME & VISUAL ALARM SIGNAL, WALL MOUNTED 80" AFF TO BOTTOM OF DEVICE.

FIRE ALARM REMOTE ANNUNCIATOR PANEL. BOTTOM 56" AFF TO TOP OF DEVICE.

FIRE ALARM SPEAKER, CEILING MOUNTED. W = WALL MOUNTED (12" BELOW CEILING OR

FIRE ALARM CONTROL PANEL. MOUNT AT 6'-6" AFF TO TOP.

FIRE ALARM MANUAL PULL STATION, 42" AFF.

CIRCUIT PANEL BOARD PROVIDE 20A/1P CIRCUIT BREAKER. WIRE WITH 2#12+1#12G, 3/4"C.

PROVIDE TRANSFORMER AS REQUIRED BY DOOR HOLDER.

FIRE ALARM

FIRE ALARM CHIME & VISUAL ALARM SIGNAL, CEILING MOUNTED.

FIRE ALARM VISUAL ALARM SIGNAL, WALL MOUNTED 80" AFF TO BOTTOM OF DEVICE.

FIRE ALARM VISUAL ALARM SIGNAL, CEILING MOUNTED.

96" AFF WHERE CEILING HEIGHT EXCEEDS 9'-0").

FLUORESCENT LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.

LED, COMPACT FLUORESCENT, OR HID LIGHTING FIXTURE, CEILING OR WALL MOUNTED,

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

DRAWINGS. SEE SCHEDULE FOR TYPE (*).

CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON

EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED

OTHERWISE. CONNECT UNSWITCHED.

LIGHTING

LED, COMPACT FLUORESCENT, OR HID LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.

TRACK LIGHTING FIXTURE. SEE PLANS/SCHEDULE FOR TRACK LENGTH AND NUMBER OF TRACK HEADS.

NURSE CALL PSYCHIATRIC PATIENT STATION, 42" AFF TO CENTER OF DEVICE.

MONITOR OUTLET. COORDINATE EXACT LOCATION WITH OWNER/ARCHITECT.

NARCOTICS CABINET SWITCH CONNECTION.

ELAPSED TIME CLOCK (6'-6" AFF) AND CONTROLS (5'-0" AFF).

DOCTORS' DICTATION OUTLET WALL, MOUNTED 18" AFF, OR 8" ABOVE COUNTER,

NURSE CALL CORRIDOR ZONE LIGHT, CEILING MOUNTED.

NURSE CALL STAFF STATION, 44" AFF TO CENTER OF DEVICE.

NURSE CALL CONNECTION TO DOOR.

OR 2" ABOVE BACKSPLASH.

NURSE CALL DOUBLE PATIENT STATION. SEE PATIENT ROOM ELEVATION FOR MOUNTING HEIGHT, NURSE CALL SINGLE PATIENT STATION. SEE PATIENT ROOM ELEVATION FOR MOUNTING HEIGHT, NURSE CALL SIDECOM INTERFACE MODULE.

NURSE CALL PSYCHIATRIC SPEAKER, CEILING MOUNTED.

NURSE CALL MASTER STATION, DESK MOUNTED.

NURSE CALL KEYED SWITCH STATION, 42" AFF.

NURSE CALL EMERGENCY PSYCHIATRIC PUSHBUTTON, 42" AFF.

NURSE CALL EMERGENCY STATION W/ PULL CORD, 70" AFF.

NURSE CALL EMERGENCY STATION W/ PULL CORD, 30" AFF.

NURSE CALL EMERGENCY STATION W/ PUSH BUTTON WITH 6' CORD, 42" AFF.

NURSE CALL DUTY STATION, 42" AFF TO CENTER OF DEVICE.

NURSE CALL CORRIDOR DOME LIGHT, CEILING MOUNTED.

NURSE CALL CENTRAL EQUIPMENT, MOUNT AT 6'-6" AFF TO TOP.

NURSE CALL CODE BLUE STATION, 42" AFF TO CENTER OF DEVICE.

NURSE CALL ANNUNCIATOR PANEL, WALL RECESSED, MOUNT AT 6'-0" AFF TO TOP.

IF NONE SHOWN MOUNT AT 44" AFF TO CENTER OF DEVICE.

IF NONE SHOWN MOUNT AT 44" AFF TO CENTER OF DEVICE.

NURSE CALL

NARCOTICS ALARM LIGHT.

NURSE CALL SYSTEM LOW VOLTAGE CONTROLLER.

LOW VOLTAGE TV.

EQUIPMENT IDENTIFICATION

HORSEPOWER RATING

MOTOR CONNECTION. SPECIAL VOLTAGES AS SHOWN ON DRAWING.

ENCLOSED CIRCUIT BREAKER. NUMERAL INDICATES TRIP AMPERE RATING.

FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.

NON-FUSIBLE SAFETY SWITCH. NUMERAL INDICATES AMPERE RATING.

SIZE AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH CIRCUIT BREAKER. TOP NUMERAL INDICATES CIRCUIT BREAKER

MOTOR STARTER. NUMERAL INDICATES NEMA SIZE.

AMPACITY. SEE FEEDER SCHEDULE.

ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER

WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.

WIRING SYSTEM BELOW FLOOR OR BELOW GRADE.

ETC. DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, WIRING SYSTEM TURNED UP.

WIRING SYSTEM TURNED DOWN.

WIRING SYSTEM EXPOSED.

OVER CURRENT PROTECTION DEVICE NUMBER.

DRY TYPE TRANSFORMER.

NEC REQUIRED GROUND.

EF-1, 10 HP.460V, 3PH

208V, 3PH

120V, 1PH

MOTOR RATED SWITCH.

CONNECTION TO WALL MOUNTED FILM ILLUMINATOR. PROVIDE RECEPTACLE IN FLUSH OUTLET BOX AT

LOWER RIGHT HAND CORNER OF UNIT IF SURFACE MOUNTED. HARD WIRE IF RECESSED.

JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.

CEILING FAN 120V. MANUFACTURER (HUNTER#21252 GREEN FINISH W/ INTEGRATED 240W LIGHT FIXTURE)

CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

CONNECTION TO EXHAUST FAN. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

PANELBOARD SURFACE MOUNTED.

REMOTE ALARM PANEL FOR ISOLATED POWER PANEL BOARD WALL MOUNTED AT 5'-0" AFF.

GENERATOR REMOTE ALARM ANNUNCIATOR. WALL MOUNTED AT 5'-0" AFF.

BLANK = NORMAL BRANCH

U = UNGROUNDED (ISOLATION) PANEL

Q = EQUIPMENT BRANCH

C = CRITICAL BRANCH

L = LIFE SAFETY BRANCH

M = MOTOR CONTROL CENTER

L = 120/208 VOLT

H = 277/480 VOLT

PANELBOARD FLUSH MOUNTED.

1,2,3 = FLOOR

A,B,C = LOCATION

PANELBOARD NAMING CONVENTION

JUNCTION OR PULL BOX. W = WEATHERPROOF.

CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.

HARDWIRE CONNECTION FROM FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE AND 3/4" LIQUID TIGHT FLEXIBLE METALLIC WHIP TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT SUPPLIER/INSTALLER. EIGHT(8) WIRE SYSTEM PROVIDES FOUR(4) CIRCUITS.

POWER

SURFACE MOUNTED MULTIOUTLET ASSEMBLY. 46" AFF OR 8" ABOVE COUNTER

TV = TELEVISION, SEE DETAIL.

G = GROUND FAULT CIRCUIT INTERRUPTER.

EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER

P = PEDESTAL

WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.

DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

OR 2" ABOVE BACKSPLASH. SHADED AREA INDICATES RECEPTACLE.

DUPLEX RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED.

SIMPLEX RECEPTACLE MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 42" AFF TO CENTER OF OUTLET

OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES

OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY

DUPLEX RECEPTACLE, MOUNTED 42" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH

DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED. SLASH INDICATES

SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.

MODIFIERS FOR RECEPTACLES:

SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.

LH2A-1

CH2A

EQUIPMENT CONNECTION DESIGNATION, SEE SCHEDULE FOR DETAILS.

RATING AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH FUSED SWITCH. TOP NUMERAL INDICATES FUSETRON AMPERE

LIGHTNING PROTECTION SYSTEM GROUND ROD.

75KVA

LIGHTNING PROTECTION SYSTEM AIR TERMINAL.

TR = TAMPER RESISTANT

3 = THREE WAY

MODIFIERS FOR SWITCHES:

SINGLE POLE SWITCH.

THREE SINGLE POLE SWITCHES IN A 3-GANG BOX.

PHOTO ELECTRIC CELL MOUNTED ON CONDUIT STUBBED 6" ABOVE ROOF, FACING NORTH.

SWITCHES

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX.

PROVIDE DIVIDER FOR DIFFERENT VOLTAGES OR BRANCHES.

4 = FOUR WAY

D = DIMMER

DT = DOUBLE THROW

LV = LOW VOLTAGE

PROVIDE DIVIDER(S) FOR DIFFERENT VOLTAGES OR BRANCHES.

OS = OCCUPANCY SENSOR

TIME CLOCK. PROVIDE POWER CIRCUIT AND 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE.

a,b,c = MULTIPLE SWITCH LEGS

T = TIMER

INDICATED.

INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTUAL RCP FOR EXACT

LUMINAIRE, 2x4, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED). SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION/CEILING TYPE.

LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

SEE SCHEDULE FOR TYPE (*).

SEE SCHEDULE FOR TYPE (*).

REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.

HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.

UNLESS NOTED OTHERWISE.

WITH EQUIPMENT SUPPLIER/INSTALLER.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).

NURSE CALL PILLOW SPEAKER.

NURSE CALL SINGLE CALL CORD.

NURSE CALL HEADEND EQUIPMENT.

FIRE ALARM SPEAKER AND VISUAL ALARM SIGNAL, CEILING MOUNTED.

HEADWALL. SEE PLAN FOR NUMBER.HW#

POWER COLUMN. SEE PLAN FOR NUMBER.PC#

POWER SYSTEM.

CONNECTED TO THE EMERGENCY POWER SYSTEM.

FLUORESCENT STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY

GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

CARD READER. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

ELECTRIC STRIKE. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

WALL MOUNTED LOCAL ALARM BUZZER, 85dBA.

DURESS ALARM BUTTON RECESSED IN COUNTER.

MAGNETIC LOCK FOR DOOR.

PUBLIC ADDRESS SYSTEM SPEAKER, CEILING MOUNTED.

REMOTE LINE ISOLATION MONITOR.

CABLE TV OUTLET, MOUNTED ADJACENT TO TV RECEPTACLE, UNLESS NOTED OTHERWISE.

PUSHPAD. PROVIDE BOX AND CONDUIT AS REQUIRED. COORDINATE WITH HARDWARE VENDOR.

VARIABLE SPEED DRIVEVSD

FIRE ALARM SMOKE DETECTOR, CEILING MOUNTED.

WIRELESS TELEMETRY ANTENNA

WIRELESS TELEMETRY DEVICE

EXPEDITER BUTTON PANEL

EXAM LIGHT CONTROLLER

EMERGENCY EGRESS PUSH BUTTON

KEY PAD CARD READER

FIRE ALARM SPEAKER AND VISUAL ALARM SIGNAL, WALL MOUNTED.

EMERGENCY RELEASE SWITCH. PROVIDE TAMPER RESISTANT COVER WITH A SOUNDING HORN.

RP = EXISTING DEVICE TO BE REPLACED WITH NEW DEVICE.PNEUMATIC TUBE STATIONPTS

BUTTON RELEASE.

BADGE ACCESS.

NURSE LOCATOR.

EMERGENCY MANUAL OVERRIDE.

DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.

SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

SYMBOL LOCATION LEADER

POWER CONNECTION TO FIRE DAMPER. SEE DETAIL.

POWER AND FIRE ALARM CONNECTION TO SMOKE DAMPER OR FIRE/SMOKE DAMPER. SEE DETAIL.

NURSE CALL CORRIDOR DOME LIGHT, WALL MOUNT ABOVE DOOR AT 4" FROM THE TOP OF THE

DOOR FRAME TO THE BOTTOM OF THE DEVICE.

NURSE CALL CORRIDOR ZONE LIGHT, WALL MOUNT ABOVE DOOR AT 4" FROM THE TOP OF THE

DOOR FRAME TO THE BOTTOM OF THE DEVICE.

ROOM TAG

ELAPSED TIME CONTROL. MOUNT 48" AFF

BOOM LIGHT CONTROLLER

PUSH BUTTON

CONNECT LIFE SAFETY CIRCUIT TO MEDICAL GAS ALARM PANEL. 120V, 20A

WIRELESS ACCESS POINT

CODE BLUE RECEIVER

FIRE ALARM CONNECTION TO KNOX BOX.

PROVIDE DISCONNECT SWITCH AND CONNECTION TO MOTOR OPERATED DOOR. COORDINATE WITH

HARDWARE VENDOR.

INTERCOM STATION WITH BUILT IN CAMERA.

INTERCOM STATION WITH BUILT VIDEO MONITOR.

PROVIDE CONNECTION TO OWNER FURNISHED ELAPSED TIME CLOCK. MOUNT 84" AFF.

RV RM

RM

DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACH SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.

CARBON MONOXIDE DETECTOR. CEILING MOUNT.

FIRE ALARM CONNECTION TO KNOX BOX.

FIRE ALARM CONNECTION TO AUTOMATIC DOOR.

( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )

GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE OUTLET. SLASH INDICATES

CONNECTED TO THE EMERGENCY POWER SYSTEM.

TAMPER RESISTENT DUPLEX RECEPTACLE OUTLET. SLASH INDICATES

CONNECTED TO THE EMERGENCY POWER SYSTEM.

LUMINAIRE, 2X2, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED). SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION/CEILING TYPE.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

GENERAL PROJECT NOTES

M

C

C

30CB

DB

DT

E

F

H

GA

J

J

M

LIM

P

PE

RA

T

TC

CB

FAC

CO

AD

CL

F

CL

DD

EC

ES

FACP

FARA

FATR

FD

FS

FS

H

FSD

KB

OS

L

HL

LD

L

SD

RL

SL

SD

TD

TS

SL

BL

D

DR

ET

ETC

IC

IM

M

MGA

MOD

NA

NA

NC

NC

NBO

NCL

NB

NCL

NCS

NEC

NEB

ND

NEC

NEP

NHE

NKS

NLV

NMS

NZL

NZL

NPP

NP1

NP2

NS

PS1

SCC

TV

WA

ET

G

TR TR

G

S

ELECTRICAL - SYMBOL SCHEDULE, NOTES AND DRAWING INDEX

ELECTRICAL - DETAILS

ELECTRICAL - LUMINAIRE SCHEDULE AND DETAILS

ELECTRICAL - LIGHTNING PROTECTION DETAILS

ELECTRICAL - DETAILS

ELECTRICAL - FOURTH FLOOR - DEMOLITION PLAN

ELECTRICAL - FIFTH FLOOR - DEMOLITION PLAN

ELECTRICAL - FOURTH FLOOR - NEW WORK - LIGHTING - AREA A

ELECTRICAL - FOURTH FLOOR - NEW WORK - LIGHTING - AREA B

ELECTRICAL - FOURTH FLOOR - NEW WORK - LIGHTING - AREA C

ELECTRICAL - FOURTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA A

ELECTRICAL - FOURTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA B

ELECTRICAL - FOURTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA C

ELECTRICAL - FIFTH FLOOR - NEW WORK - LIGHTING - AREA A

ELECTRICAL - FIFTH FLOOR - NEW WORK - LIGHTING - AREA B

ELECTRICAL - FIFTH FLOOR - NEW WORK - LIGHTING - AREA C

ELECTRICAL - FIFTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA A

ELECTRICAL - FIFTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA B

ELECTRICAL - FIFTH FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA C

ELECTRICAL - ROOF PLAN - NEW WORK - POWER

E001 E002 E003 E004 E005

ED400

ED500

E400A E400B E400C E401A E401B E401C E500A E500B E500C E501A E501B E501C E600

CONNECTION TO PRE-FABRICATED HEADWALL UNIT. WITH NORMAL AND CRITICAL POWER

CIRCUITS AND COMMUNICATION SERVICES.

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX. EITHER SWITCH INBOARD AND OUTBOARD LAMPS

SEPARATELY OR STEP-DIM BOTH LAMPS TO 50%.

ELECTRICAL - ROOF - DEMOLITION PLANED600

ELECTRICAL - PANEL SCHEDULESE010

ED300 ELECTRICAL - THIRD FLOOR - DEMOLITION PLAN

E100 ELECTRICAL - GROUND FLOOR - NEW WORK - POWER

ELECTRICAL - THIRD FLOOR - NEW WORK - LIGHTING - AREA CE300C

ELECTRICAL - THIRD FLOOR - NEW WORK - POWER AND SPECIAL SYSTEMS - AREA CE301C

ELECTRICAL - PANEL SCHEDULESE011

1. ALL FIXED ELECTRICAL EQUIPMENT FURNISHED BY ELECTRICAL CONTRACTOR SHALL BE LISTED AND LABELED BY AN APPROVED TESTING AGENCY APPROVED BY THE GOVERNMENT. FACTORY ASSEMBLED LISTED COMPONENTS SHALL BE LISTED AND LABELED AS AN ASSEMBLY. ANY ELECTRICAL EQUIPMENT NOT LISTED OR LABELED MUST BE APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION AND HAVE A THIRD PARTY TESTING LABEL OR SHALL BE REPLACED WITH EQUIPMENT THAT IS UL LABELED/LISTED AT THE CONTRACTOR'S EXPENSE.

2. FIRE ALARM APPLIANCES AND DEVICES SHOWN INDICATE TO PROVIDE COVERAGE IN THAT AREA. ELECTRICAL CONTRACTOR SHALL PROVIDE APPLIANCES AND DEVICES AS REQUIRED BY THE LATEST EDITION OF NFPA 72 AND LOCAL BUILDING CODE. NO CHANGE ORDERS WILL BE ALLOWED FOR APPLIANCES AND DEVICES REQUIRED BY

NFPA 72 AND THE NC STATE BUILDING CODE.

3. CONTRACTOR SHALL COORDINATE WITH THE FACILITY'S INFECTION CONTROL OFFICER TO VERIFY THAT APPROPRIATE SAFEGUARDS ARE BEING TAKEN TO PROTECT WORKERS INVOLVED IN DEMOLITION ACTIVITIES.

4. CONTRACTOR SHALL COORDINATE WITH FACILITY'S INFECTION CONTROL OFFICER TO VERIFY THAT APPROPRIATE PRECAUTIONS ARE BEING TAKEN TO PROTECT FACILITY STAFF AND PATIENTS DURING THE CONSTRUCTION

ACTIVITIES.

5. ASBESTOS CONTAINING MATERIALS (IF PRESENT) WILL BE IDENTIFIED BY THE OWNER AND WILL BE REMOVED FROM AHU'S, PIPING INSULATION, DUCT INSULATION, ETC. (IF REQUIRED) PRIOR TO CONTRACTOR BEGINNING ANY WORK

ON THE SITE. COORDINATE WITH OWNER.

6. UNLESS NOTED OTHERWISE, ELECTRICAL CONTRACTOR SHALL INSTALL ALL RACEWAY, BOXES, AND CABLES. ALL MEDICAL EQUIPMENT CABLES, UNLESS OTHERWISE NOTED, SHALL BE PROVIDED BY MEDICAL EQUIPMENT VENDOR.

ELECTRICAL - DETAILSE006

ELECTRICAL - POWER RISER DIAGRAME007

FIRE ALARM ISOLATION MODULE.ISO

DURESS ALARM SYSTEM INTRFACE CONNECTIONS.

(1 VOICE/1 DATA DENOTES QUANTITY OF VOICE/DATA OUTLETS)

* No new lighting load added.

VARIABLE FREQUENCY DRIVE.

ELECTRICAL - SITE PLANE020

CONNECTED TO THE EMERGENCY POWER SYSTEM.

VOICE/DATA OUTLET, CEILING MOUNTED.

DRAWING INDEX

5838 Monroe Road, Suite 100 Charlotte, NC 28212

704 531 3000 Project No. 3588

Charlotte Engineers, LLP

This document is the property of RPA Design and RPA Design retains all rights therein, including copyrights.

It may only be used in a manner consistent with RPA Design's rights while RPA Design is providing services for the specific project identified or referred to herein or extensions thereto.

It may not be used for any other purpose except with the express written agreement of, and compensation to, RPA Design.

Project

City, State

Project Number

Drawn By

Checked By

Seal / Signature

Sheet Title

Date

Sheet Number

Issued For

Architect of Record

5960 Fairview Road Suite 500 Charlotte, NC 28210

887.3500

887.3507 fax

Charlotte Engineers, LLP 5838 Monroe Road, Suite 100 Charlotte, NC 28212

704.531.3000 PHONE

704.531.3001 FAX

MECHANICAL/ELECTRICAL/PLUMBING/FIRE PROTECTION:

Fitzpatrick Engineering Group, PLLC 19520 West Catawba Ave., Ste. 311 Cornelius, NC 28031

704.987.9114 PHONE

704.987.9938 FAX

STRUCTURAL:

Program Manager

13620 Reese Blvd.

Suite 100

Huntersville, NC 28078

401.2040

401.2067 fax

5/ 8/

:4

3:

P M

E :\L oc al

R ev it\

\3

C E

- C en tra l M od el

.rv t

E001

ELECTRICAL - SYMBOLS

SCHEDULE, NOTES AND

DRAWING INDEX

15-0014-00

CORRECT OPERATING

ROOM DEFICIENCIES

MMF

CLH

Salisbury, NC

100% FINAL DESIGN

11/10/16

Item Date Description

S

J

F

F

RL

SD DD

COMBINATION TV RECEPTACLE OUTLET

NOTES:

A. THE TERMS PATIENT WALL SYSTEM AND HEADWALL ARE SYNONYMOUS OF

EACH OTHER AND ARE USED INTERCHANGEABLY.

B. HEADWALL ASSEMBLY AND DEVICES FURNISHED BY THE OWNER. WITH

EXCEPTION TO NURSE CALL.

C. VERIFY ARRANGEMENT WITH ARCHITECTURAL ELEVATIONS.

D. PROVIDE MULTI-PIN CONNECTION FROM BED SIDECOM CONTROLS TO LOW

VOLTAGE RELAY AT LIGHT FIXTURE.

HL LCL ADDRESSABLE

MAIN

TSFS

CL

SD

HL L

DD SD

SD

EXIT

TYPICAL FOR FLOORS 3,4 AND 5

FIRE, SMOKE, & FIRE/SMOKE DAMPER WIRING

DETAIL

NOTES:

1. ALL WIRING SHALL BE INSTALLED IN RACEWAY.

2. MULTIPLE DAMPERS CAN BE SERVED BY EACH JUNCTION BOX UP TO A MAXIMUM OF 10 AMPS PER

CIRCUIT.

WIRING FROM JUNCTION BOX

TO DISCONNECT SWITCH AND

FROM DISCONNECT SWITCH

TO DAMPER ACTUATOR BY

EC.

WIRING FROM

ELECTRICAL PANEL

TO JUNCTION BOX

PROVIDED BY EC.

FIRE, SMOKE, OR FIRE/SMOKE

DAMPER BY MC.

FIRE ALARM SYSTEM

CONNECTION,

REQUIRED FOR SMOKE

AND FIRE/SMOKE

DAMPERS.

PROVIDED

BY FIRE ALARM

CONTRACTOR.

S

NOT TO SCALE 3

TO OTHER

DAMPERS (SEE

NOTE 2)

DISCONNECT SWITCH (LEVITON #1221, OR

APPROVED EQUAL) WITH LOCKABLE

COVER ; AND INDICATOR LIGHT

(DAYTON/ZORO RED, OR APPROVED

EQUAL) MOUNTED IN STAINLESS STEEL

PLATE ON UTILITY BOX THAT IS MOUNTED

WITHIN 18 INCHES OF DAMPER ACCESS

DOOR. PROVIDE CIRCUIT LABEL ON

PLATE.

ELECTRICAL PANEL LOCATED IN

ELECTRICAL ROOM, PROVIDED BY EC.

PILOT LIGHT BY EC. ON

WHEN SWITCH IS ON.

MOUNT NEXT TO SWITCH.

NOT TO SCALEDEVICE LABELING DETAIL

PROVIDE ALL WIRING DEVICES WITH A SELF-

ADHESIVE METALLIC LABEL WITH BLACK LETTERING

INDICATING PANEL AND CIRCUIT NUMBER SERVING

THE DEVICE. THE LABEL SHALL MATCH THE

CURRENT FACILITY'S STANDARDS FOR NORMAL AND

EMERGENCY BRANCH CIRCUITS. 1/4" MINIMUM

LETTERING HEIGHT.

7FCL-3

GENERAL DETAIL NOTES:

A. COORDINATE LABELING WITH OWNER PRIOR TO INSTALLATION.

7FCL-1

NOT TO SCALEDEVICE MOUNTING DETAIL 4

TOP PLATE

STUDS

JUNCTION BOX ABOVE

CEILING MOUNTED ON

BRACKET, TOP PLATE,

OR BY THREADED

ROD FROM STRUCTURE.

HOMERUN

IN EMT.

EMT

EQUAL,

MOUNT TO

STUDS ON BOTH

SIDES.

SWITCH OR

RECEPTACLE.

10NOT TO SCALEWALL MOUNTED OCCUPANCY

SENSOR

8NOT TO SCALE

FEATURES

PATTERN: 360 DEGREES

COVERAGE: 46-186 SQ M (500-2000SF)

TIME DELAY: ADJUSTABLE 30 SECONDS TO 30 MINUTES

OPTIONS

PROVIDE DUAL RELAY IN SPACES WITH MULTIPLE SWITCHING.

CONTROL: MANUAL OFF, DUAL TECHNOLOGY, OR APPROVED EQUAL

LIGHTING CONTROL

GENERAL DESCRIPTION

HOUSING: IMPACT RESISTANT INJECTION MOLDED ABS

MOUNTING: CEILING BETWEEN 2440-3050 mm (8'-10') H

ELECTRICAL: 24 VOLT DC (FROM POWER PACK), 120 OR 277 VOLT AC

INPUT

FINISH: MATCH FACILITY'S STANDARDS

NOM. DIMENSIONS: 121 mm X 102 mm (4 3/4" DIA X 4"D)

CEILING MOUNTED OCCUPANCY

SENSOR

NOT TO SCALE 92-POLE CEILING MOUNTED OCCUPANCY SENSOR FOR

CONTROL OF DUAL LEVEL SWITCHING

N

LOAD

HN

LOAD

H

LIGHT SWITCH

LIGHTING CIRCUIT LIGHTING CIRCUIT

CONDUCTORS PER MANUFACTURER'S

PUBLISHED RECOMMENDATIONS

IN 3/4"C MINIMUM (TYPICAL)

FATC

KEY NOTES:

1. DEVICES SHOWN ARE TYPICAL. REFER TO COMMUNICATIONS SHEETS FOR DEVICE LOCATIONS

AND QUANTITIES.

2. PROVIDE END OF LINE RESISTORS AS REQUIRED.

3. ANNUNCIATION SHALL BE THREE TEMPORAL BEEPS.

4. DUCT SMOKE DETECTORS AND DAMPERS SHALL BE PROVIDED AND WIRED TO FATC AND POWER

BY ELECTRICAL CONTRACTOR. MECHANICAL CONTRACTOR SHALL INSTALL THEM.

5. FOR LARGER DUCTS, PROVIDE ADDITIONAL DUCT DETECTORS AS REQUIRED BY NFPA 72.

6. NEW EQUIPMENT MUST BE COMPATIBLE WITH THE EXISTING SYSTEM.

7. CONFIRM / INSTALL SMOKE DETECTOR IS LOCATED ABOVE MASTER FIRE ALARM CONTROL PANEL

OR EXISTING FATC. VERIFY EXACT LOCATION PRIOR TO ROUGH-IN.

8. MASTER FIRE ALARM CONTROL PANEL TO BE LOCATED IN A FIRE RATED ENCLOSURE . THE

MASTER FIRE ALARM CONTROL PANEL IS NOT REQUIRED TO BE LOCATED IN A FIRE RATED

ENCLOSURE IF THE BUILDING IS SPRINKLERED. CONFIRM / COORDINATE.

9. CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING A FIRE WATCH WHEN A FIRE ALARM

SYSTEM IS OUT OF SERVICE MORE THAN 4 OUT OF 24 HOURS OR A SPRINKLER SYSTEM IS OUT OF SERVICE MORE THAN 10 HOURS IN A 24 HOUR PERIOD IN AN OCCUPIED BUILDING. NOTIFICATION

AND FIRE WATCH TIMES ARE DOCUMENTED. PROVIDE WRITTEN VALIDATION OF FIRE WATCH

DURING OUTAGES.

10. FIRE ALARM SYSTEM IMPAIRMENT PROCEDURES SHALL COMPLY WITH NFPA 72.

FIRE ALARM RISER DIAGRAM NOT TO SCALE 12

EXISTING

RENOVATED

AREA

EXISTING

AREA

COVER PLATE AS SHOWN.

TWO GANG BACK BOX WITH

SNAP IN PLASTIC CLOSURE.

CONNECTOR. PROVIDE TEMPORARY

OPENING FOR SYSTEM

BARRIER

DUPLEX RECEPTACLE

ACCESSIBLE CEILING.

STUBBED TO ABOVE

WITH PULL STRING

3/4" EMPTY CONDUITSYMBOL:

NTS

TV

DOOR OPERATOR

DOOR DOOR

PUSH PADS

120V, 20A

CIRCUIT

TYPICAL FOR SINGLE OR DOUBLE DOORS

DOOR OPERATOR WIRING - RISER DIAGRAM 6

NTS

FLOOR

12", UNLESS CEILING IS HIGHER

THAN 12'-0", THEN 24" ABOVE DOOR.

CEILING

FLOOR

WALL MOUNTED

TELEPHONE

6" TO

TOP OF

COUNTER OR

BACKSPLASH

18"

RECEPTACLE

LIGHT SWITCH

OR DIMMER

ALIGN WHERE

POSSIBLE

TELEPHONE OR

VOICE DATA OUTLET

TV OUTLET

OR CLOCK

OUTLET

FIRE ALARM DEVICES

" A

BO

VE

FL

OO

R

TO

B

OT

TO

M

OF

D

EV

IC

E

ON

C

OL

UM

NS

MOUNTING HEIGHTS OF DEVICES

FOR WALL MOUNTED UNITS:

BOTTOM

OF DEVICE

NO

T T

O

EX

CE

ED

" T

O

BO

TT

OM

NOT TO SCALE

GENERAL DETAIL NOTES:

A. PARTICULAR ATTENTION SHALL BE GIVEN TO THE ALIGNMENT OF DEVICES. WHEREVER

DEVICES, ON THIS SHEET OR OTHER SHEETS, ARE SHOWN AT GIVEN LOCATION WITH

DIFFERENT MOUNTING HEIGHTS THEY SHALL BE ALIGNED VERTICALLY. IF THEY ARE

SHOWN AT THE SAME MOUNTING HEIGHT THEY SHALL BE ALIGNED HORIZONTALLY. REFER

TO THE ARCHITECTURAL PLANS, ELEVATIONS AND DETAILS. COORDINATE WITH

ARCHITECT PRIOR TO ROUGH-IN.

B. ALL DIMENSIONS ARE TO THE CENTER LINE OF DEVICE UNLESS INDICATED OTHERWISE.

C. MOUNTING HEIGHTS SHOWN HERE ARE TYPICAL. PRIOR TO ROUGH-IN, COORDINATE WITH

ARCHITECTURAL PLANS, ELEVATIONS, AND DETAILS. IF A CONFLICT OCCURS, REQUEST

CLARIFICATION FROM ARCHITECT/ENGINEER PRIOR TO ROUGH-IN.

D. COORDINATE MOUNTING HEIGHTS WITH "OR" AND BIOMED STAFF.

6"

A

A

Section A-A

1. RATED WALL OR FLOOR ASSEMBLY - PROVIDE FIRE STOPPING

ASSEMBLY FOR PARTITION TYPE & RATING ENCOUNTERED.

2. THROUGH PENETRATION - PROVIDE FIRE STOPPING ASSEMBLY FOR

SIZE & MATERIAL OF THROUGH PENETRATION UTILIZED.

3. FIRE STOPPING MATERIAL - PROVIDE FIRE STOPPING MATERIAL FOR

WALL ASSEMBLY & THROUGH PENETRATION MATERIAL ENCOUNTERED. FILL VOIDS OR CAVITY

ACCORDING TO THE REQUIREMENTS OF THE FIRE STOPPING SYSTEM UTILIZED.

ALL RATED WALLS, PARTITIONS OR FLOORS SHALL BE PROVIDED WITH A UL LISTED FIRE STOP SYSTEM. THE SYSTEM UTILIZED SHALL MATCH THE SEPARATION PENETRATED AND THE THROUGH

PENETRATION MATERIAL.

DETAILS FOR THE INSTALLATION OF SYSTEM TYPE UTILIZED SHALL BE AVAILABLE AT THE PROJECT SITE FOR THE DURATION OF CONSTRUCTION AND SHALL BE PROVIDED TO THE AUTHORITY HAVING

JURISDICTION AND TO THE BUILDING OWNER AT THE PROJECT COMPLETION.

PROVIDE WALL OR FLOOR LABLES INDICATING THE SYSTEM MANUFACTURER AND UL LISTED

ASSEMBLY NUMBER AT EACH LOCATION WHERE THE FIRE STOPPING SYSTEM IS INSTALLED.

NOT TO SCALE

THROUGH PENETRATION FIRESTOP SYSTEM 5(PROVIDE UL…