Drawing Title
Scale:
Project Title
Date
Location
AutoCAD File Number
Contract Number
Project Number
Drawing Number
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
o n e e ig h t h in c h o n e f o o t 1
B
A
C
D
E
F t h r e e in c h e s e f o o t o n e a d a lf in c h s e f o o t o n e in e f o o t t h r q u a r t e r s in e f o o t o a lf in e f o o t t h r e e e ig h t h s in e f o o t o q u a r t e r in e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Management and Facilities
Construction
Office of
Drawn By:
Building Number:
Checked By:
Approved: VAPHS Director
Approved: Associate Director
Approved: Project Engineer
Approved: Manager Project Section
Approved: V.P. Facility Mananger
Approved: ACOS/R D&&&
2/26/2014
FULLY SPRINKLERED
FOR RECORD
UNIVERSITY DRIVE RESEARCH
OFFICE BUILDING
WET LABS
University Drive, Pittsburgh, PA 15240
646-10-100
VA244-P-1827
INFORMATION PROVIDED BY OTHERS.
RESPONSIBLE FOR ERRORS OR OMISSIONS IN
DEPARTMENTS. ADVETECT/STANTEC IS NOT
FACILITIES MANAGEMENT AND MAINTENANCE
ENCOUNTERED, PLEASE CONTACT THE VAMC
BUILDING CONTRACTORS. IF DISCREPANCIES ARE
RECORD INFORMATION PROVIDED BY THE
THIS DOCUMENT HAS BEEN UPDATED TO INCLUDE
A certified Service Disabled Veteran Owned Small Business (SDVOSB) advetect.com
(804) 282-2403
Midlothian, Virginia 23112
5700 Powell Grove Dr. Suite 100
Butler, PA. 16011
101 E. Diamond Street
400 Morgan Center
Stantec Architecture and Engineering LLC
AS-BUILT 9/6/2016
480/277V
SWITCHGEAR
DISTRIBUTION
SUBSTATION
NORMAL
EXISTING
DSBLB
SWITCHBOARD
DISTRIBUTION
NORMAL
BASEMENT
GROUND FLOOR
1ST FLOOR
2ND FLOOR
ROOF
T-6
XFMR
T-7
XFMR
GLE
PANEL
GLF
PANEL
GLG
PANEL
EQGLC
PANEL
GLH
PANEL
GLI
PANEL
1LE
PANEL
1LF
PANEL
1LG
PANEL
EQ1LC
PANEL
1LH
PANEL
1LI
PANEL
2HB
PANEL
EQ2HA
PANEL
CHILLER
BREAKER
CIRCUIT
ENCLOSED
250A
480/277V
PANEL PDPHA
DISTRIBUTION
NORMAL
EXISTING
480/277V
PDPHC-1 & 2
PANEL
EQUIPMENT
EMERGENCY
EXISTING
1 23 4 5
4N
4N
4N
4N
4N
4N
4N
4N
4N
4N
BREAKER
CIRCUIT
ENCLOSED
250A
KEY NOTES
GENERAL NOTES
RATING PLUG TO PROVIDE A 600AT DEVICE.
UTILIZE EXISTING SPARE 800AF CIRCUIT BREAKER TO SUPPLY NEW CHILLER. REPLACE
RATING PLUG TO PROVIDE A 600AT DEVICE.
UTILIZE EXISTING SPARE 800AF CIRCUIT BREAKER TO SUPPLY TRANSFORMER T-6. REPLACE 2
SUPPLY NEW PANEL 2HB.
REPLACE EXISTING 100A-3P CIRCUIT BREAKER WITH NEW 300A-3P CIRCUIT BREAKER TO
SUPPLY TRANSFORMER T-7.
REPLACE EXISTING 100A-3P CIRCUIT BREAKER WITH A NEW 300A-3P CIRCUIT BREAKER TO
CIRCUIT BREAKER. PROVIDE A 400A-3P CIRCUIT BREAKER TO SUPPLY PANEL EQ2HA.
REMOVE EXISTING SPARE CIRCUIT BREAKERS AS NECESSARY TO ACCEPT A NEW 400A-3P
EQUIPMENT NAMING CONVENTION
ALPHA NUMERIC DESIGNATION
L = 208/120V
H = 480/277VVOLTAGE:
2 = SECOND
1 = FIRST
G = GROUND
B = BASEMENTFLOOR:
EQ = EMERGENCY EQUIPMENT BRANCH
BLANK = NORMALSOURCE:
XX X X X
EP-501
ELECTRICAL RISER DIAGRAM
NTS
NTS
SCHEDULES
FEEDER AND TRANSFORMER
ELECTRICAL RISER DIAGRAM,
PROVIDE FEEDER WIRING IN EXISTING CONDUIT.
DISCONNECT. REFER TO FLOOR PLANS FOR LOCATION.
PROVIDE FEEDER WIRING AND NEW CONDUIT FROM NEW PULL BOX TO NEW CHILLER
LOCATION.
PROVIDE NEW PULL BOX TO INTERCEPT EXISTING CONDUIT. REFER TO FLOOR PLANS FOR
ROB AS-BUILT COORDINATION 9/6/13