36C24419Q0974-0004001.docx

DOCX document 17 KB Posted

Attached to
Electrical Power Distribution SystemMaintenance & Testing Pittsburgh VAMC Federal contract opportunity
Solicitation number
36C24419Q0974
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

36C24419Q0974 0004 Question and response.docx

View the file

Other files for this federal contract opportunity

Other files attached to Electrical Power Distribution SystemMaintenance & Testing Pittsburgh VAMC, newest first.
File Type Posted
-18017.docx DOCX document
36C24419Q0974-0004000.docx DOCX document
36C24419Q0974-0003001.docx DOCX document
36C24419Q0974-0003004.pdf PDF
36C24419Q0974-0003000.docx DOCX document
36C24419Q0974-0003003.xlsx XLSX spreadsheet
36C24419Q0974-0003002.docx DOCX document
36C24419Q0974-0003006.pdf PDF
36C24419Q0974-0003005.pdf PDF
36C24419Q0974-0002000.docx DOCX document
36C24419Q0974-0001001.xlsx XLSX spreadsheet
36C24419Q0974-0001000.docx DOCX document
36C24419Q0974-0001002.docx DOCX document
36C24419Q0974-016.pdf PDF
36C24419Q0974-004.xlsx XLSX spreadsheet
36C24419Q0974-014.pdf PDF
36C24419Q0974-015.pdf PDF
36C24419Q0974-023.pdf PDF
36C24419Q0974-001.docx DOCX document
36C24419Q0974-031.pdf PDF
36C24419Q0974-020.pdf PDF
36C24419Q0974-007.pdf PDF
36C24419Q0974-006.docx DOCX document
36C24419Q0974-002.pdf PDF
36C24419Q0974-010.pdf PDF
36C24419Q0974-018.pdf PDF
36C24419Q0974-025.pdf PDF
36C24419Q0974-028.pdf PDF
36C24419Q0974-011.pdf PDF
36C24419Q0974-012.pdf PDF
36C24419Q0974-032.pdf PDF
36C24419Q0974-029.pdf PDF
36C24419Q0974-003.docx DOCX document
36C24419Q0974-024.pdf PDF
36C24419Q0974-000.docx DOCX document
36C24419Q0974-008.pdf PDF
36C24419Q0974-027.pdf PDF
36C24419Q0974-005.docx DOCX document
36C24419Q0974-013.pdf PDF
36C24419Q0974-017.pdf PDF
36C24419Q0974-022.pdf PDF
36C24419Q0974-030.pdf PDF
36C24419Q0974-026.pdf PDF
36C24419Q0974-019.pdf PDF
36C24419Q0974-009.pdf PDF
36C24419Q0974-021.pdf PDF
Show all 46

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

There is still one area that needs more clarity. It is this statement below:

1. All panels and disconnects rated over 100 amps shall be maintained and tested per 3.12.1 of the solicitation’s performance work statement (PWS).

What needs clarified is if we are testing breakers 100 amps and higher. I see that panels and disconnects are listed but are we to assume breakers as well?

Response:

Electrical equipment (including, but not limited to switchgear, switchboards, distribution panels, motor control centers, panel boards, enclosed circuit breakers, disconnects, etc. and all related components) with a current rating greater than 100 amps shall be maintained and tested. For the purposes of clarity, breakers with a current rating greater than 100 amps shall be tested.