There is still one area that needs more clarity. It is this statement below:
1. All panels and disconnects rated over 100 amps shall be maintained and tested per 3.12.1 of the solicitation’s performance work statement (PWS).
What needs clarified is if we are testing breakers 100 amps and higher. I see that panels and disconnects are listed but are we to assume breakers as well?
Response:
Electrical equipment (including, but not limited to switchgear, switchboards, distribution panels, motor control centers, panel boards, enclosed circuit breakers, disconnects, etc. and all related components) with a current rating greater than 100 amps shall be maintained and tested. For the purposes of clarity, breakers with a current rating greater than 100 amps shall be tested.