About this file

36C24419Q0974 0004 ROB Additiona EP6.01 17.11.01.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Electrical Power Distribution SystemMaintenance & Testing Pittsburgh VAMC, newest first.
File Type Posted
-18017.docx DOCX document
36C24419Q0974-0004000.docx DOCX document
36C24419Q0974-0004001.docx DOCX document
36C24419Q0974-0003006.pdf PDF
36C24419Q0974-0003005.pdf PDF
36C24419Q0974-0003000.docx DOCX document
36C24419Q0974-0003003.xlsx XLSX spreadsheet
36C24419Q0974-0003002.docx DOCX document
36C24419Q0974-0003001.docx DOCX document
36C24419Q0974-0003004.pdf PDF
36C24419Q0974-0002000.docx DOCX document
36C24419Q0974-0001000.docx DOCX document
36C24419Q0974-0001002.docx DOCX document
36C24419Q0974-0001001.xlsx XLSX spreadsheet
36C24419Q0974-030.pdf PDF
36C24419Q0974-026.pdf PDF
36C24419Q0974-019.pdf PDF
36C24419Q0974-009.pdf PDF
36C24419Q0974-021.pdf PDF
36C24419Q0974-018.pdf PDF
36C24419Q0974-025.pdf PDF
36C24419Q0974-028.pdf PDF
36C24419Q0974-011.pdf PDF
36C24419Q0974-012.pdf PDF
36C24419Q0974-032.pdf PDF
36C24419Q0974-029.pdf PDF
36C24419Q0974-003.docx DOCX document
36C24419Q0974-024.pdf PDF
36C24419Q0974-000.docx DOCX document
36C24419Q0974-008.pdf PDF
36C24419Q0974-027.pdf PDF
36C24419Q0974-005.docx DOCX document
36C24419Q0974-013.pdf PDF
36C24419Q0974-017.pdf PDF
36C24419Q0974-022.pdf PDF
36C24419Q0974-016.pdf PDF
36C24419Q0974-004.xlsx XLSX spreadsheet
36C24419Q0974-014.pdf PDF
36C24419Q0974-015.pdf PDF
36C24419Q0974-023.pdf PDF
36C24419Q0974-001.docx DOCX document
36C24419Q0974-031.pdf PDF
36C24419Q0974-020.pdf PDF
36C24419Q0974-007.pdf PDF
36C24419Q0974-006.docx DOCX document
36C24419Q0974-002.pdf PDF
Show all 46

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PANEL PANEL PANEL

PANEL PANEL PANEL

PANEL

PANEL

PANEL

PACKAGED

POWER

SUPPLY

EXISTING

MANHOLE EMH#2

A B

EXISTING 4160V SWITCHGEAR LOCATED IN EXISTING

SUBSTATION BUILDING

EXISTING 5 KV

VACUUM FEEDER BREAKER No. 2E

EXISTING 5 KV

VACUUM FEEDER BREAKER No. 1E

SPARE

400A 3P

225A 3P

350A 3P

400A 3P

SPACE

DISTRIBUTION SWITCHGEAR - DSGHA UL1558 GEAR WITH UL1066

BREAKERS

(EMERGENCY ONLY-LIFE SAFETY)

1600A - 480/277V, 3�, 4W, 35KAIC

LPB

(BASEMENT

CORR.)

480/277V

LPG

(GROUND LEVEL

CORR.)

480/277V

LP1

(1ST LEVEL

CORR.)

480/277V

CHILLER

30-CH-1

(ROOF)

CHILLER

30-CH-2

(ROOF)

T-6

150 KVA

480 -208/120V

SPARE

PPB

(BASEMENT

CORR.)

208/120V

PPG

(GROUND LEVEL

CORR.)

208/120V

PP1

(1ST LEVEL

CORR.)

208/120V

SPARE SPARE

60A 3P

LS1

(RM. B05)

480/277V

OPEN TRANSITION

1200A, 65 KAIC

ATS-MDS

(RM. BA002)

500A 3P

1200A 3P

LSIG

PROVIDE

NEW

LSIG

BREAKER

MDS (BUILDING 30 EXTENSION)

LOCATED IN ROOM B05- BLDG. 30

1200A - 480/277V, 3 PHASE, 4W, 42 KAIC

MDP (BUILDING 30 EXTENSION)

LOCATED IN ROOM B05 - BLDG. 30

800A - 208/120V, 3 PHASE, 4W, 22 KAIC

400A 3P

400A 3P

250AS

200AT

3P

LSI

100A 3P

100A 3P

100A 3P

100A 3P

100A 3P

150A 3P

150A 3P

100A 3P

100A 3P

SPD

60A 3P

100A 3P

100A 3P

400A 3P

1200A 3P

LSIG

A

GROUND

WIRE SIZE (AWG/KCMIL)

WIRE AND CONDUIT SIZING SCHEDULE

CONDUCTOR PHASE &

NEUTRAL

SINGLE LINE TAG:

THIS COLUMN

COMBINED WITH "A",

"B", OR "C" COLUMN

NO. OF WIRES & CONDUIT

SIZE IN INCHES

CONDUIT SIZES SHOWN ARE TYPICAL FOR CONDUCTOR SIZES AND QUANTITY. CONDUIT AND WIRE SIZE NOTED ON THE

ELECTRICAL FLOOR PLANS AND SINGLE LINE TAKE PRECEDENCE.

1PH, 2W+G 3PH, 3W+G 3PH, 4W+G

B C

EX EXISTING FEEDERS AND CONDUIT

3/41212 3/4 3/4

3/41010 3/4 3/4

3/48 3/4 3/4

3/46 3/4 1

3/44 1

1 1/41

1/0 1 1/2

44/0

350 3

(2) 1 1/2(2) 3(2) 3/0

(2) 250

(2) 350

(2) 500

(3) 300

(3) 400

(4) 500

(2) 1/0

(2) 1

(2) 1/0

(3) 1/0

(3) 2/0

(4) 3/0

2 1/2

(2) 2

(2) 2 1/2

(2) 3

(3) 2 1/2

(3) 3

(4) 2 1/2

(2) 2 1/2

(2) 3

(2) 3 1/2

(3) 3

(3) 3

(4) 4

1 1/4

1 1/2

1 1/4

1 1/4

1 1/2

1 1/2

2 1/2

2 1/2

(2) 2 (2) 2

27C

27C

6C

16B

22C

10C

10C

20B20B

100A 3P

PROVIDE

NEW

BREAKER

PROVIDE

NEW

BREAKER

SPACE SPACE

250A 100A20A 3P

2B

LAB

WASTE

PUMP

30-PP2A

(RM. B14)

LAB

WASTE

PUMP

30-PP2B

(RM. B14)

30A 3P

CAGE

WASHER

(RM. B12)

3B

HVB

(EX. MECH. RM.

BA004)

480/277V

150A 3P

13C

20A 3P

20A 3P

2B 2B

SANITARY

EJECTOR

PUMP

30-PP1A

(DISC. IN

RM. G03)

SANITARY

EJECTOR

PUMP

30-PP1B

(DISC. IN

RM. G03)

10C 10C

13C 13C

CONTROL WIRING BACK TO GENERATOR

TO SIGNAL LOSS OF NORMAL POWER

SPARE

100A 3P

400A 3P

HVR (BUILDING 30)

LOCATED IN VFD/PUMP ROOM - BLDG. 30

400A - 480/277V, 3 PHASE, 4W, 22 KAIC

RTU

30-SF-1

(ROOF)

175A 3P

175A 3P

GENERAL

EXHAUST

30-EF-1A

(ROOF)

80A 3P

8B

80A 3P

8B

BIO-SAFETY

EXHAUST

30-EF-2A

(ROOF)

40A 3P

4B

40A 3P

FUME HOOD

EXHAUST

30-EF-3A

(ROOF)

20A 3P

2B

20A 3P

CAGE WASH

EXHAUST

30-EF-4

(ROOF)

20A 3P

RADIO-ISOTOPE

EXHAUST

30-EF-5

(ROOF)

20A 3P

CHILLED WATER

PUMPS

30-P-1A

(VFD/PUMP RM.)

40A 3P

40A 3P

40A 3P

40A 3P

RTU

30-SF-2

(ROOF)

(REDUNDANT)

GENERAL

EXHAUST

30-EF-1B

(ROOF)

(REDUNDANT)

BIO-SAFETY

EXHAUST

30-EF-2B

(ROOF)

(REDUNDANT)

FUME HOOD

EXHAUST

30-EF-3B

(ROOF)

(REDUNDANT)

CHILLED WATER

PUMPS

30-P-1B

(VFD/PUMP RM.)

(REDUNDANT)

4B2B 2B 2B

SEE SHEET

NOTE NO. 2

LIGHTING PANELS ARE TO BE LIGHTING CONTROL

PANEL-CIRCUIT BREAKER TYPE

75 75

30 30

LIGHTING PANELS

ARE TO BE

LIGHTING

CONTROL

PANEL-CIRCUIT

BREAKER TYPE

15 15 3 3 3 5

1 1 3 3

15 15

10C

PPR

(VFD / PUMP

ROOM)

208/120V

1 2 3 4 5

SPARESPARE

20A 3P

2B

6 7 8 9 10 11 12 13 14 15 18 19 20 2116 17

SPACE

100A

20B20B

8B

8B

8B

8B

4B 2B 4B2B 2B

4B 2B 2B 2B 2B

2B 3B 2B 2B2B

20A 3P

SPARE

20A 3P

SPARE

30-PCP-1

30-RTU-1

(ROOF)

30-PCP-2

30-RTU-2

(ROOF)

(REDUNDANT)

4A

4A

4A

4A

14B

14B

20C

15 KVA

408-208/120V

LS2

(RM. B05)

208/120V

4C

TYPICAL NEW MODULAR CONNECTION

1200A 3P

NEW

MANHOLE EMH A

NEW

MANHOLE EMH B

1 2 3 4 5 6

14 2/0 26 1 1/2 2

14B

14B

8 13 8 1 1 1/4

4B

4B

4B

7 8 9 10 11 12 13 14 15 16

4B

4B

20A 3P

STEAM

STERILIZER

(RM. B08)

2B

2B

EXISTING

PANELBOARD - LSBHA

LOCATED IN ROOM BA003 - BLDG. 30

(EMERGENCY ONLY-LIFE SAFETY)

400A - 480/277V, 3 PHASE, 4W, 35KAIC

EXISTING

PARALLELING EMERGENCY SWITCHGEAR

LOCATED IN SECOND FLOOR SWITCHGEAR ROOM, BUILDING #1

ATS-LS 400A

480V

4 POLE

35KAIC

(OPEN TRANSITION)

2000KVA

4160V 480/277V 3�, 4W

600A 3P 450A 3P 600A 3P 400A 3P 600A 3P 600A 3P 1000A 3P

FUTURE WET

LAB

SPARE

3000A-4P TIE

CIRCUIT BREAKER

(4 POLE) 450A 3P 600A 3P 400A 3P 800A 3P 600A 3P

FUTURE

ANIMAL LAB

SPARE

5KV

LOAD BREAK

SWITCH

3000A-3P M.C.B

5KV

LOAD BREAK SWITCH

EXISTING MAIN POWER CENTER, UL1558 SWITCHGEAR WITH UL1066

BREAKERS

2000KVA

4160V 480/277V 3�, 4W

600A 3P

3000A-3P M.C.B

SPARE

3200A, 480/277A, 65KAIC COPPER BUS 3200A, 480/277A, 65KAIC COPPER BUS

1600A 3P

PROVISION

1600A 3P

PROVISION

1600A 3P

PROVISION

EXISTING

MANHOLE EMH#1

EXISTING

MANHOLE EMH#3

TO FUTURE FISHER

HOUSE BLDG.

400A

E RATED

ELECTRIC INTERLOCK CONTROL WIRING

400A

E RATED

400A 3P

EXISTING EMERGENCY DISTRIBUTION BOARD

DP-LS LOCATED IN 2ND FLOOR SWITCHGEAR

ROOM OF BUILDING #1 FURINISH AND INSTALL

1-400A-3P 100% RATED BREAKER IN EXISTING

SPACE.

1600A 3P

PROVISION

THOMAS L. CHAPMAN, P.E.

PENNSYLVANIA LICENSE NO. PE044043R

MILLER-REMICK CORPORATION

SIGNATURE:

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

NO. 30

Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

BID DOCUMENTS - NOT FOR CONSTRUCTION

FULLY SPRINKLERED

PROFESSIONAL ENGINEER

A Serv ic e

D i s ab l e d Ve t e ran Owned Sma ll Bus iness

SDVOSB

CVE

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business www.pfa-architect.com

ARCHITECTURE, PLANNING, INTERIORS

World Trade Center 101 West Main Street, Suite 7000 Norfolk, VA 23510

Phone: 757-471-0537 Fax: 757-471-4205

PF&A DESIGN

AE - UNIVERSITY DRIVE

RESEARCH BUILDING

ADDITION

VA HEALTHCARE, PITTSBURGH PA

EP6.01

VA244-P-1749ELECTRICAL

04/30/2014 READGREGG

SINGLE LINE DIAGRAM

SHEET NOTES

1. THIS ELEMENT OF THE PROJECT HAS BEEN IDENTIFIED AS WORK TO BE INCLUDED IN DETAIL AS A

BID ITEM. SEE SPECIFICATIONS AND INSTRUCTIONS TO BIDDERS FOR A DETAILED LISTING OF

THESE ITEMS AND THE ASSOCIATED SCOPES OF WORK

2. AFTER COMPLETION OF CONSTRUCTION, CONTRACTOR TO MEASURE TRANSFORMER

SECONDARY VOLTAGE OUTPUT UNDER NORMAL LOAD CONDITIONS. CONTRACTOR TO REPORT

VOLTAGE MEASUREMENTS TO THE ENGINEER AND PROVIDE TRANSFORMER TAP ADJUSTMENTS

AS DIRECTED.

3. MOTORS INTERLOCKED SUCH THAT ONLY 1 OF 2 OPERATES AT ANY TIME.

1. SEE DWG. E0.01 & E0.02 FOR GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS.

PART OF ALTERNATE DEDUCT.

SEE SHEET NOTE 1.

PART OF ALTERNATE DEDUCT.

SEE SHEET NOTE 1.

PART OF ALTERNATE DEDUCT.

SEE SHEET NOTE 1.

PART OF ALTERNATE DEDUCT.

SEE SHEET NOTE 1.

NOTES KEY PLAN

1.

EXISTING

EXISTING

NEW

NORTH

SEE SHEET NOTE 3.

SEE SHEET NOTE 3.

PART OF ALTERNATE DEDUCT.

SEE SHEET NOTE 1.

SEE SHEET NOTE 3.

SEE SHEET NOTE 3.

NO. DESCRIPTION DATE

File details come from the government source that posted it.