36C24419B0057-0001004.pdf

PDF Posted

Attached to
693-CSI-306 Install CT/SPECT in Room 220
Solicitation number
36C24419B0057
Issued by

About this file

36C24419B0057 0001 S02 693-CSI-306 TAB Report Reference Only.pdf

View the file

Other files

File Type Posted
36C24419B0057-0002000.docx DOCX document
36C24419B0057-0002000.docx DOCX document
36C24419B0057-0001002.pdf PDF
36C24419B0057-0001000.docx DOCX document
36C24419B0057-0001003.pdf PDF
36C24419B0057-0001001.pdf PDF
36C24419B0057-0001003.pdf PDF
36C24419B0057-0001000.docx DOCX document
36C24419B0057-0001001.pdf PDF
36C24419B0057-0001004.pdf PDF
36C24419B0057-0001002.pdf PDF
36C24419B0057-004.pdf PDF
36C24419B0057-003.pdf PDF
36C24419B0057-002.pdf PDF
36C24419B0057-005.pdf PDF
36C24419B0057-001.docx DOCX document
36C24419B0057-005.pdf PDF
36C24419B0057-004.pdf PDF
36C24419B0057-003.pdf PDF
36C24419B0057-002.pdf PDF
36C24419B0057-001.docx DOCX document
36C24419B0057-000.docx DOCX document
36C24419B0057-000.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AIR APPARATUS TEST SCHEDULE

PROJECT: WILKES BARRE VA - PET/CT SITE PREP

LOCATION: ROOF SYSTEM / UNIT: RTU-1

UNIT DATA MOTOR DATA

MAKE / MODEL NO. AAON RN-009-3-0 MAKE / FRAME BALDOR 184T

TYPE / SIZE BC 22" H. P. 5.00

SERIAL NO. 201111 ANCQ04611 RPM 1760

ARR. / CLASS HORIZ I VOLTAGE 460

PHASE / HERTZ 3 60

DISCHARGE BOTTOM

F. L. AMPS 6.6

SHEAVE MAKE D.D. S. F. 1.15

SHEAVE DIAMETER D.D. MAKE SHEAVE D.D

SHEAVE BORE D.D. SHEAVE DIAMETER D.D.

NO. BELTS / TYPE / SIZE D.D. SHEAVE POSITION D.D.

NO. FILTERS / TYPE / SIZE 4 / TA / 20X25X2 SHEAVE BORE D.D.

NO. FILTERS / TYPE / SIZE 4 / TA / 20X25X4 CENTER LINE DISTANCE D.D.

TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL

TOTAL CFM 4700 4775 EXTERNAL DISCH. S. P. NA 0.36

FAN RPM 1854 1662 EXTERNAL SUCT. S. P. NA -0.57

MOTOR VOLTS 460 451 EXTERNAL S. P. 1.75 0.93

MOTOR AMPS T-1 6.6 5.2

FAN DISCH. S. P. NA 0.36

MOTOR AMPS T-2 6.6 5.2

FAN SUCT. S. P. NA -1.34

MOTOR AMPS T-3 6.6 5.2

FAN TOTAL S. P. 3.89 1.70

C. F. L. A. 6.73 B. H. P. 3.86

V.F.D. HERTZ 57.20 57.20

OUTSIDE AIR CFM 340 359 S.P. SET POINT 0.36 0.36

RETURN AIR CFM 4360 4416 MIN OA POSITION 15%

F-01

COMMENTS:

TEST DATE: 12/11 READINGS: MJ/FK PAGE 1

AIR OUTLET TEST SCHEDULE

SYSTEM / UNIT: RTU-1 TEST APPARATUS: ADM-870

AREA OUTLET DESIGN PRELIMINARY FINAL DEVIATION

SERVED NO. TYPE SIZE CFM CFM CFM CFM 0%

SUPPLY

212 1 CD3 24X24 650 863 663 663 102%

212 2 CD3 24X24 650 693 658 658 101%

212 3 CD3 24X24 650 507 709 709 109%

212 4 CD3 24X24 650 487 588 588 90%

212 5 CD3 24X24 650 724 627 627 96%

212 6 CD3 24X24 650 641 701 701 108%

211 7 CD2 24X24 350 419 368 368 105%

211 8 CD2 24X24 350 396 359 359 103%

213 9 CD1 24X24 100 154 102 102 102%

4700 4775 102%

RETURN

212 1 RG4 24X24 926 520 859 900 97%

212 2 RG4 24X24 926 608 1016 990 107%

212 3 RG4 24X24 926 623 963 920 99%

212 4 RG4 24X24 926 473 702 750 81% (1)

211 5 RG3 24X24 656 439 711 632 96%

4360 4192 96%

F-07

COMMENTS: (1) VOLUME DAMPER OPEN 100%

TEST DATE: 12/11 READINGS: MJ/FK PAGE 2

SYSTEM / UNIT: RTU-1 TEST APPARATUS: ADM-870

AREA OUTLET DESIGN PRELIMINARY FINAL DEVIATION

SERVED NO. TYPE SIZE AK CFM VEL VEL CFM VEL CFM 0%

OSA

OSA 1 WMS 22.25X44.75 6.91 340 49 31 214 52 359 106%

F-11

TEST DATE: 12/11 READINGS: MJ/FK PAGE 3

SYSTEM / UNIT: EXSISTING RETURN TEST APPARATUS: ADM-870

AREA OUTLET DESIGN PRELIMINARY FINAL DEVIATION

SERVED NO. TYPE SIZE CFM CFM CFM CFM 0%

212B 1 RG1 24X24 160 199 165 165 103%

212A 2 RG1 24X24 160 180 159 159 99%

210 3 RG1 24X24 135 222 135 135 100%

F-07

TEST DATE: 12/11 READINGS: MJ/FK PAGE 4

VAV AIR OUTLET TEST SCHEDULE

SYSTEM / UNIT: EXSISTING SUPPLY TEST APPARATUS: ADM-870

DESIGN PRELIM. FINAL DESIGN FINAL

AREA ------------ OUTLET --------- MAX MAX MAX MIN MIN DEVIATION FLOW

SERVED NO. TYPE SIZE AK CFM CFM CFM CFM CFM 0% COFF.

CAV-1 2.0

212A 1 CD1 24X24 160 159 159 160 159 99%

212B 2 CD1 24X24 160 163 163 160 163 102%

320 322 320 322 101%

CAV-2 2.96

210 1 CD1 24X24 200 183 199 200 199 100%

F-10

TEST DATE: 12/11 READINGS: MJ/FK PAGE 5

SYSTEM / UNIT: EV-94 TEST APPARATUS: ADM-870

AREA OUTLET DESIGN PRELIMINARY FINAL DEVIATION

SERVED NO. TYPE SIZE CFM CFM CFM CFM 0%

EV-94

208 1 EG1 8X8 75 (1) (1) (1)

210 2 EG1 8X8 65 (1) (1) (1)

209 3 EG1 8X10 35 (1) (1) (1)

F-07

COMMENTS: (1) EV-94 NOT RUNNING AT TIME OF BALANCE

TEST DATE: 12/11 READINGS: MJ/FK PAGE 6

FLOW INDICATOR TEST SCHEDULE

SYSTEM / UNIT: EXSISTING HOT WATER MANUFACTURER: NU-TECH

GPM GPM GAGE DELTA CIRCUIT

LOCATION SIZE SPECIFIED ACTUAL PRESSURE SET COMMENTS

212 075CH 2.60 2.59 39.0 NA RHC-1

212 125 12.90 12.50 30.0 NA RHC-2

212B 075RL 1.60 1.51 127.0 NA CAV-1

212A 075RL 0.70 0.75 31.0 NA CAV-2

F-12

TEST DATE: 12/11 READINGS: MJ/MJ PAGE 7