230553-RIB-Identification for HVAC Piping and Equipment-12-24-2025.pdf

PDF 69 KB Posted

Attached to
CBI GJ HVAC/Lighting Upgrade Project
Solicitation number
IFB1 REAA 2027000043 2
Issued by
Denver County, Denver City, Colorado

About this file

This is a technical specification section for identification systems for HVAC piping and equipment as part of project 25-388 CBI HVAC and Lighting Upgrade, reference number 230553. The specification outlines requirements for nameplates, tags, adhesive-backed duct markers, stencils, pipe markers, and ceiling tacks to be applied to various HVAC components including air handling units, control panels, ductwork, pumps, tanks, piping, valves, and dampers. Approved manufacturers are identified for each product category, including Advanced Graphic Engraving LLC, Brady Corporation, Brimar Industries Inc, Kolbi Pipe Marker Co, and Seton Identification Products. The specification mandates specific dimensions, colors, and materials, such as white letters on black background for nameplates with 1/4-inch letter height, laminated three-layer plastic tags with engraved letters, yellow and black adhesive-backed duct markers, and color-coded pipe markers complying with ASME A13.1 standards. Contractors must submit lists of wording and color coding, valve charts with tag numbers and locations, manufacturer product data, installation instructions, and project record documents indicating actual tagged valve locations.

Installation requirements specify that nameplates be affixed with corrosive-resistant fasteners or adhesive sealed with clear lacquer, tags be installed with corrosion-resistant chain, and stencil painting comply with interior painting specifications. Pipe identification on piping 3/4 inch diameter and smaller must include service type, flow direction, and pressure information, located at intervals not exceeding 20 feet on straight runs, adjacent to valves and tees, at structure penetrations, and at obstructions. Ductwork identification must include air handling unit identification numbers and areas served at the unit, structure penetrations, and obstructions. Ceiling tacks color-coded by equipment type must be located in ceiling panel corners closest to equipment to identify valves and dampers above lay-in ceilings. All materials must comply with referenced standards including ASME A13.1 and ASTM D709.

View the file

Other files

File Type Posted
233423-RIB-HVAC Power Ventilators-12-24-2025.pdf PDF
230923 Alerton Direct Digital Control System for HVAC.pdf PDF
TYPE EMX CMB-ISOLITE-Specification.pdf PDF
TYPE P2 Metalux-Cruze-Linear-Bay-spec-sheet.pdf PDF
220553-RIB-Identification for Plumbing Piping and Equipment-12-24-2025.pdf PDF
230529-RIB-Hangers and Supports for HVAC Piping and Equipment-12-24-2025.pdf PDF
260505-RIB-Selective Demolition for Electrical-12-24-2025.pdf PDF
235216-RIB-Condensing Boilers-12-24-2025.pdf PDF
230719-RIB-HVAC Piping Insulation-12-24-2025.pdf PDF
237413-RIB-Packaged Outdoor Central-Station Air-Handling Units-12-24-2025.pdf PDF
235100-RIB-Breechings, Chimneys, and Stacks-12-24-2025.pdf PDF
TYPE D3 PrentaLux-CYL6-6-Sustainable-LED-Cylinder-Luminaire-Spec-Sheet.pdf PDF
265100-RIB-Interior Lighting-12-24-2025.pdf PDF
238126.13-RIB-Small-Capacity Split-System Air Conditioners-12-24-2025.pdf PDF
TYPE P1 Corelite-Iridium-i3-Suspended-specification-sheet.pdf PDF
265600-RIB-Exterior Lighting-12-24-2025.pdf PDF
221005-RIB-Plumbing Piping-12-24-2025.pdf PDF
232114-RIB-Hydronic Specialties-12-24-2025.pdf PDF
260519-RIB-Low-Voltage Electrical Power Conductors and Cables-12-24-2025.pdf PDF
260923-RIB-Lighting Control Devices-12-24-2025.pdf PDF
230593-RIB-Testing, Adjusting, and Balancing for HVAC-12-24-2025.pdf PDF
232113-RIB-Hydronic Piping-12-24-2025.pdf PDF
230800-RIB-Commissioning of HVAC-12-24-2025.pdf PDF
262726-RIB-Wiring Devices-12-24-2025.pdf PDF
230913-RIB-Instrumentation and Control Devices for HVAC-12-24-2025.pdf PDF
265140-LUT-Luminaires-12-24-2025.pdf PDF
25388-CBI 100% CD w Add1.pdf PDF
231123-RIB-Facility Natural-Gas Piping-12-24-2025.pdf PDF
TYPE S1 iO-CoviO-Spec-Sheet.pdf PDF
220529-RIB-Hangers and Supports for Plumbing Piping and Equipment-12-24-2025.pdf PDF
TYPE IU Sure-Lites-SLX-Surface-Mount-LED.pdf PDF
CBI GJ Project Manual_VSS_R8 mm 10am.pdf PDF
230523-RIB-General-Duty Valves for HVAC Piping-12-24-2025.pdf PDF
260583-RIB-Wiring Connections-12-24-2025.pdf PDF
232123-RIB-Hydronic Pumps-12-24-2025.pdf PDF
221006-RIB-Plumbing Piping Specialties-12-24-2025.pdf PDF
Answers to Questions_IFB REAA 2027-05.pdf PDF
260553-RIB-Identification for Electrical Systems-12-24-2025.pdf PDF
233100-RIB-HVAC Ducts and Casings-12-24-2025.pdf PDF
230513-RIB-Common Motor Requirements for HVAC Equipment-12-24-2025.pdf PDF
Bid Questions - BCE Response - 05012026.pdf PDF
Building CO20260025 Mesa County MOD 1.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

25-388 CBI HVAC and Lighting Upgrade 230553 - 1 Identification for HVAC Piping and

Equipment

SECTION 230553

IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Nameplates.

B. Tags.

C. Adhesive-backed duct markers.

D. Stencils.

E. Pipe markers.

F. Ceiling tacks.

1.02 RELATED REQUIREMENTS

A. Section 099123 - Interior Painting: Identification painting.

1.03 REFERENCE STANDARDS

A. ASME A13.1 - Scheme for the Identification of Piping Systems; 2023.

B. ASTM D709 - Standard Specification for Laminated Thermosetting Materials; 2017.

1.04 SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. List: Submit list of wording, symbols, letter size, and color coding for mechanical identification.

C. Chart and Schedule: Submit valve chart and schedule, including valve tag number, location, function, and valve manufacturer's name and model number.

D. Product Data: Provide manufacturers catalog literature for each product required.

E. Manufacturer's Installation Instructions: Indicate special procedures, and installation.

F. Project Record Documents: Record actual locations of tagged valves.

PART 2 PRODUCTS

2.01 IDENTIFICATION APPLICATIONS

A. Air Handling Units: Nameplates.

B. Air Terminal Units: Tags.

C. Control Panels: Nameplates.

D. Dampers: Ceiling tacks, where located above lay-in ceiling.

E. Ductwork: Nameplates.

F. Heat Transfer Equipment: Nameplates.

G. Piping: Tags.

H. Pumps: Nameplates.

I. Tanks: Nameplates.

J. Valves: Tags and ceiling tacks where located above lay-in ceiling.

2.02 NAMEPLATES

A. Manufacturers:

1. Advanced Graphic Engraving, LLC: www.advancedgraphicengraving.com/#sle.

2. Brimar Industries, Inc: www.pipemarker.com/#sle.

3. Kolbi Pipe Marker Co: www.kolbipipemarkers.com/#sle.

4. Seton Identification Products, a Tricor Direct Company: www.seton.com/#sle.

5. Substitutions: See Section 016000 - Product Requirements.

Upgrade 230553 - 2 Identification for HVAC Piping and

Equipment

B. Letter Color: White.

C. Letter Height: 1/4 inch.

D. Background Color: Black.

E. Plastic: Comply with ASTM D709.

2.03 TAGS

A. Manufacturers:

1. Advanced Graphic Engraving; ______: www.advancedgraphicengraving.com/#sle.

2. Brady Corporation; ______: www.bradycorp.com/#sle.

3. Brimar Industries, Inc; ______: www.pipemarker.com/#sle.

4. Kolbi Pipe Marker Co; ______: www.kolbipipemarkers.com/#sle.

5. Seton Identification Products, a Tricor Company; ______: www.seton.com/#sle.

6. Substitutions: See Section 016000 - Product Requirements.

B. Plastic Tags: Laminated three-layer plastic with engraved black letters on light contrasting background color. Tag size minimum 1-1/2 inch diameter.

C. Metal Tags: Brass with stamped letters; tag size minimum 1-1/2 inch diameter with smooth edges.

D. Valve Tag Chart: Typewritten letter size list in anodized aluminum frame.

2.04 ADHESIVE-BACKED DUCT MARKERS

A. Manufacturers:

1. Brimar Industries, Inc: www.pipemarker.com/#sle.

2. Substitutions: See Section 016000 - Product Requirements.

B. Material: High gloss acrylic adhesive-backed vinyl film 0.0032 inch; printed with UV and chemical resistant inks.

C. Style: Individual Label.

D. Color: Yellow/Black.

2.05 STENCILS

A. Manufacturers:

1. Brady Corporation: www.bradycorp.com/#sle.

2. Kolbi Pipe Marker Co: www.kolbipipemarkers.com/#sle.

3. Seton Identification Products, a Tricor Company: www.seton.com/#sle.

4. Substitutions: See Section 016000 - Product Requirements.

B. Stencils: With clean cut symbols and letters of following size:

1. 3/4 to 1-1/4 inch Outside Diameter of Insulation or Pipe: 8 inch long color field, 1/2 inch high letters.

C. Stencil Paint: As specified in Section 099123, semi-gloss enamel, colors complying with ASME

A13.1.

2.06 PIPE MARKERS

A. Manufacturers:

1. Brady Corporation: www.bradycorp.com/#sle.

2. Brimar Industries, Inc: www.pipemarker.com/#sle.

3. Kolbi Pipe Marker Co: www.kolbipipemarkers.com/#sle.

4. Seton Identification Products, a Tricor Company: www.seton.com/#sle.

B. Color: Comply with ASME A13.1.

C. Plastic Pipe Markers: Factory fabricated, flexible, semi- rigid plastic, preformed to fit around pipe or pipe covering; minimum information indicating flow direction arrow and identification of fluid being conveyed.

Upgrade 230553 - 3 Identification for HVAC Piping and

Equipment

D. Underground Plastic Pipe Markers: Bright-colored continuously printed plastic ribbon tape, minimum 6 inches wide by 4 mil, 0.004 inch thick, manufactured for direct burial service.

E. Color code as follows:

1. Heating, Cooling, and Boiler Feedwater: Green with white letters.

2. Toxic and Corrosive Fluids: Orange with black letters.

3. Compressed Air: Blue with white letters.

2.07 CEILING TACKS

A. Manufacturers:

1. Craftmark: www.craftmarkid.com/#sle.

2. Substitutions: See Section 016000 - Product Requirements.

B. Description: Steel with 3/4 inch diameter color coded head.

C. Color code as follows:

1. HVAC Equipment: Yellow.

2. Fire Dampers and Smoke Dampers: Red.

3. Heating/Cooling Valves: Blue.

PART 3 EXECUTION

3.01 PREPARATION

A. Degrease and clean surfaces to receive adhesive for identification materials.

3.02 INSTALLATION

A. Install nameplates with corrosive-resistant mechanical fasteners, or adhesive. Apply with sufficient adhesive to ensure permanent adhesion and seal with clear lacquer.

B. Install tags with corrosion resistant chain.

C. Apply stencil painting in accordance with Section 099123.

D. Install plastic pipe markers in accordance with manufacturer's instructions.

E. Install plastic tape pipe markers complete around pipe in accordance with manufacturer's instructions.

F. Install underground plastic pipe markers 6 to 8 inches below finished grade, directly above buried pipe.

G. Use tags on piping 3/4 inch diameter and smaller.

1. Identify service, flow direction, and pressure.

2. Install in clear view and align with axis of piping.

3. Locate identification not to exceed 20 feet on straight runs including risers and drops, adjacent to each valve and Tee, at each side of penetration of structure or enclosure, and at each obstruction.

H. Install ductwork with plastic nameplates. Identify with air handling unit identification number and area served. Locate identification at air handling unit, at each side of penetration of structure or enclosure, and at each obstruction.

I. Locate ceiling tacks to locate valves or dampers above lay-in panel ceilings. Locate in corner of panel closest to equipment.

END OF SECTION

230553 - Identification for HVAC Piping and Equipment