Att_18_SWIFT_Intelligent_Wireless_Detector_0001.pdf

PDF 107 KB Posted

Attached to
ITM ON ALARM SYSTEMS PARKWIDE, NPS-LAVO
Solicitation number
140P8422Q0017
Issued by

View the file

Other files

File Type Posted
Breakout_of_parts_6_7_22_0002.pdf PDF
Sol_140P8422Q0017_Amd_0002.pdf PDF
Att_06_Honeywell_GWF-7075_Intelligent_Fire_Alarm_Control_Panel_0001.pdf PDF
Att_07_Honeywell_Vista-128BPT_Burglar_Alarm_Control_Panel_0001.pdf PDF
Att_12_Inovonics_EN1751_Water_Detector_0001.pdf PDF
Att_17_SWIFT_FWSG_FlashScan_0001.pdf PDF
Att_05_Honeywell_6160_Alpha_Display_Keypad_0001.pdf PDF
Att_10_Inovonics_EN1261HT_High_Traffic_Four_Element_Motion_Detector_0001.pdf PDF
Sol_140P8422Q0017_Amd_0001.pdf PDF
Att_14_Inovonics_Pendant_Transmitters_0001.pdf PDF
Att_04_ConteralP_Panoramic_Megapixel_Camera_0001.pdf PDF
Att_15_MegaBall_G2_IP_Megapixel_Camera_0001.pdf PDF
Att_20_SWIFT_Intelligent_Wireless_WSD-P_WSD-Acclimate_WTD-RH_WTD-H_Wireless_Detector_0001.pdf PDF
Att_11_Inovonics_EN1722_Temperature_Humidity_Transmitter_0001.pdf PDF
Att_02_ConteralP_Indoor_Dome_IP_Megapixel_Camera_0001.pdf PDF
Att_13_Inovonics_EN7290_Receiver_Interface_for_Honeywell_Commercial_VISTA_Panels_0001.pdf PDF
Att_16_MEGApix_4MP_LPR_IP_camera_0001.pdf PDF
Att_03_ConteralP_Micro_Bullet_IP_Megapixel_Camera_0001.pdf PDF
Att_01Honeywell_VW-GATE_Swift_Wireless_Gateway_0001.pdf PDF
Att_08_Inovonics_EN1212_Dual_Input_Universal_Transmitter_0001.pdf PDF
Att_09_Inovonics_EN1252_Long_Range_Dual_Input_Universal_Transmitter_0001.pdf PDF
Att_19_SWIFT_Intelligent_Wireless_WAV-CRL_WAV-CWL_WAV-RL_WAV-WL_Wireless_AV_Base_0001.pdf PDF
Att_21_SWIFT_WPS-DL_Wireless_Pull_Station_0001.pdf PDF
Att_04_SCA_Wage_Rates_Shasta_County.pdf PDF
Att_01_Quote.pdf PDF
Att_02_Fire_Alarm_Maintenance_SOW.pdf PDF
Sol_140P8422Q0017.pdf PDF
Att_03_SCA_Wage_Rates_Tehama_County.pdf PDF
Att_05_140P8422Q0017_Technical_Info_Form.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN-60832:C • 9/30/2015 — Page 1 of 2

SWIFT®

Intelligent Wireless Detectors

Intelligent Detectors

DN-60832:C

Intelligent Wireless Detector with B210W base

S w ift D et ec to r

B ba se .jp g

General SWIFT® wireless detectors are intelligent (addressable) detectors which provide secure, reliable communication to the Fire Alarm Control Panel (FACP) across a Class A mesh network. Wireless detectors create an opportunity for appli-cations where it is costly (concrete walls/ceilings, buried wires), obtrusive (surface mount conduit), or possibly dan-gerous (asbestos) to use traditional wired devices. In addi-tion, both wired and wireless devices can be present on the same FACP providing an integrated wired-wireless solution for increased installation potential.

The SWIFT detection line includes a photoelectric, Accli-mate®, standard fixed heat, and rate-of-rise heat detectors.

The photoelectric detectors transmit a digital representation of smoke density through a wireless mesh to a gateway and on to a FACP. The Acclimate detectors combine a photoelec-tric chamber and a 135°F fixed temperature heat detector.

Acclimate can also transmit an alarm signal due to heat per UL 521. The fixed heat detector and rate-of-rise detectors uti-lize sensors designed for open area protection with 50 foot spacing capability as approved by UL 521.

All sensors offer addressable code wheels and two LEDs.

The LEDs are controlled by the panels. Operation modes include red, green, and amber colors with various solid or blink patterns.

The mesh network within the SWIFT system creates a child-parent relationship between the devices so that each device has two parents providing a second path for communications on every device. If one device can no longer operate for any reason, the rest of the devices can still communicate with each other, directly or through one or more intermediate devices.

The SWIFT system also engages frequency hopping to pre-vent system interference whether intentional or accidental.

Features

• Wireless installation

• Class A mesh network

• Addressable code wheels

• Commercial applications

• UL 268 listed

• Frequency hopping

• Bi-directional communications

Specifications

PHYSICAL / OPERATING SPECIFICATIONS

Height: 2.4 inches (61 mm) installed in B210W base

Diameter: 6.0 inches (152mm) installed in B210W base

Device Weight (includes 4 batteries): 9.2 oz (261 g) installed in B210W base

Operating Temperature Range: Photo: 32°F to 120°F (0°C to 49°C); Acclimate with Heat: 32°F to 100°F (0°C to 38°C)

Air Velocity: Acclimate with Heat: 0 to 4,000 fpm (0 to 20 m/ sec)

Operating Humidity Range: 10% to 93% non-condensing

Thermal Ratings: Fixed Temperate Set Point: 135°F (57°C); Rate-of-Rise Detection: 15°F/min (8.3°C/min)

ELECTRICAL SPECIFICATIONS

Maximum Operating Voltage: 3.3 VDC

Maximum Standby Current: 210µA @ 3.3 VDC (one com-munication every 23.9 seconds with LED blink enabled)

Maximum Alarm Current (LED on): 5 mA @ 3.3 VDC (LED on)

Radio Frequency Range: 902-928 MHz

BATTERY SPECIFICATIONS

Battery Type: 4 Panasonic CR123A or 4 Duracell DL 123A

Battery Life: 2 years

Battery Replacement: Upon BATTERY LOW or BAT LOW display and/or during annual maintenance

Agency Listings and Approvals Each device complies with part 15 of the FCC rules meaning operation is subject to two conditions.

1) The device may not cause harmful interference and 2) The device must accept any interference received including inter-ference that may cause undesired operation.

The listings and approvals below apply to the basic intelligent wireless detector. In some cases, certain modules may not be listed by certain approval agencies or listing may be in process. Consult factory for latest listing status.

UL Listed: S635

CSFM: 7272-0028:0271, 7254-0028:0270

FM Approved

FCC ID: AUBWFSSD

IC ID: 573X-WFSSD

Page 2 of 2 — DN-60832:C • 9/30/2015

Acclimate® Plus, FlashScan®, NOTIFIER®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of Microsoft Corporation.

©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

This document is not intended to be used for installation purposes.

We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements.

All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.

www.notifier.com

Standards and Codes The SWIFT Wireless Intelligent Detectors comply with the following UL Standards and with NFPA 72 Fire Alarm System requirements.

UL 864

UL 268

Ordering Information FWD-200P: Wireless photoelectric smoke detector for use with the FWSG wireless gateway

FWD-200ACCLIMATE: Wireless Acclimate detector for use with the FWSG wireless gateway

FWH-200FIX135: Wireless fixed-temperature (135° F) heat detector for use with the FWSG wireless gateway

FWH-200ROR135: Wireless rate-of-rise (135° F) heat detector for use with the FWSG wireless gateway

FWSG: FlashScan® Wireless Gateway.

B210W: 6” wireless mounting base.

W-USB: Software interface (via USB port) for computers running the SWIFT Tools programming utility.

File details come from the government source that posted it. Updated .