DN-60832:C • 9/30/2015 — Page 1 of 2
SWIFT®
Intelligent Wireless Detectors
Intelligent Detectors
DN-60832:C
Intelligent Wireless Detector with B210W base
S w ift D et ec to r
B ba se .jp g
General SWIFT® wireless detectors are intelligent (addressable) detectors which provide secure, reliable communication to the Fire Alarm Control Panel (FACP) across a Class A mesh network. Wireless detectors create an opportunity for appli-cations where it is costly (concrete walls/ceilings, buried wires), obtrusive (surface mount conduit), or possibly dan-gerous (asbestos) to use traditional wired devices. In addi-tion, both wired and wireless devices can be present on the same FACP providing an integrated wired-wireless solution for increased installation potential.
The SWIFT detection line includes a photoelectric, Accli-mate®, standard fixed heat, and rate-of-rise heat detectors.
The photoelectric detectors transmit a digital representation of smoke density through a wireless mesh to a gateway and on to a FACP. The Acclimate detectors combine a photoelec-tric chamber and a 135°F fixed temperature heat detector.
Acclimate can also transmit an alarm signal due to heat per UL 521. The fixed heat detector and rate-of-rise detectors uti-lize sensors designed for open area protection with 50 foot spacing capability as approved by UL 521.
All sensors offer addressable code wheels and two LEDs.
The LEDs are controlled by the panels. Operation modes include red, green, and amber colors with various solid or blink patterns.
The mesh network within the SWIFT system creates a child-parent relationship between the devices so that each device has two parents providing a second path for communications on every device. If one device can no longer operate for any reason, the rest of the devices can still communicate with each other, directly or through one or more intermediate devices.
The SWIFT system also engages frequency hopping to pre-vent system interference whether intentional or accidental.
Features
• Wireless installation
• Class A mesh network
• Addressable code wheels
• Commercial applications
• UL 268 listed
• Frequency hopping
• Bi-directional communications
Specifications
PHYSICAL / OPERATING SPECIFICATIONS
Height: 2.4 inches (61 mm) installed in B210W base
Diameter: 6.0 inches (152mm) installed in B210W base
Device Weight (includes 4 batteries): 9.2 oz (261 g) installed in B210W base
Operating Temperature Range: Photo: 32°F to 120°F (0°C to 49°C); Acclimate with Heat: 32°F to 100°F (0°C to 38°C)
Air Velocity: Acclimate with Heat: 0 to 4,000 fpm (0 to 20 m/ sec)
Operating Humidity Range: 10% to 93% non-condensing
Thermal Ratings: Fixed Temperate Set Point: 135°F (57°C); Rate-of-Rise Detection: 15°F/min (8.3°C/min)
ELECTRICAL SPECIFICATIONS
Maximum Operating Voltage: 3.3 VDC
Maximum Standby Current: 210µA @ 3.3 VDC (one com-munication every 23.9 seconds with LED blink enabled)
Maximum Alarm Current (LED on): 5 mA @ 3.3 VDC (LED on)
Radio Frequency Range: 902-928 MHz
BATTERY SPECIFICATIONS
Battery Type: 4 Panasonic CR123A or 4 Duracell DL 123A
Battery Life: 2 years
Battery Replacement: Upon BATTERY LOW or BAT LOW display and/or during annual maintenance
Agency Listings and Approvals Each device complies with part 15 of the FCC rules meaning operation is subject to two conditions.
1) The device may not cause harmful interference and 2) The device must accept any interference received including inter-ference that may cause undesired operation.
The listings and approvals below apply to the basic intelligent wireless detector. In some cases, certain modules may not be listed by certain approval agencies or listing may be in process. Consult factory for latest listing status.
UL Listed: S635
CSFM: 7272-0028:0271, 7254-0028:0270
FM Approved
FCC ID: AUBWFSSD
IC ID: 573X-WFSSD
Page 2 of 2 — DN-60832:C • 9/30/2015
Acclimate® Plus, FlashScan®, NOTIFIER®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of Microsoft Corporation.
©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Standards and Codes The SWIFT Wireless Intelligent Detectors comply with the following UL Standards and with NFPA 72 Fire Alarm System requirements.
UL 864
UL 268
Ordering Information FWD-200P: Wireless photoelectric smoke detector for use with the FWSG wireless gateway
FWD-200ACCLIMATE: Wireless Acclimate detector for use with the FWSG wireless gateway
FWH-200FIX135: Wireless fixed-temperature (135° F) heat detector for use with the FWSG wireless gateway
FWH-200ROR135: Wireless rate-of-rise (135° F) heat detector for use with the FWSG wireless gateway
FWSG: FlashScan® Wireless Gateway.
B210W: 6” wireless mounting base.
W-USB: Software interface (via USB port) for computers running the SWIFT Tools programming utility.
File details come from the government source that posted it. Updated .