NOAA-Bell-M-Shimada_SuppressionScan.pdf

PDF 846 KB Posted

Attached to
NOAA Ship Bell M. Shimada Drydock Repairs Federal contract opportunity
Solicitation number
1305M219QNMAN0237
Issued by
Department of Commerce National Oceanic and Atmospheric Administration

About this file

Additional reference document

View the file

Other files for this federal contract opportunity

Other files attached to NOAA Ship Bell M. Shimada Drydock Repairs, newest first.
File Type Posted
1305M219QNMAN0237.docx DOCX document
Amendment_0005.pdf PDF
REV_Attachment_IV_-_Price_Schedule.xlsx XLSX spreadsheet
Amendment_0004.pdf PDF
Amendment_0003.pdf PDF
Amendment_0002.pdf PDF
CFR 001 Intersleek 731.pdf PDF
REV_A._Attachment_I_-_SH_FY20_5YR_Drydock_SOW.pdf PDF
CFR 132 UWB Paint QC SH Intersleek.pdf PDF
REV_A._Attachment_IV_-_Price_Schedule.xlsx XLSX spreadsheet
CFR 001 Intershield 300HS.pdf PDF
CFR 001 Intersleek 1100SR.pdf PDF
SH_640_FA27_Rev0_Sht1-8_NONE_JOINER ARRANGEMENTS PDF
Shimada Galley Cabinet Drawings.pdf PDF
20190803_130551.jpg JPG image
SH-655-FZ03-Food Services Arrangement.pdf PDF
20190803_130608.jpg JPG image
Amendment_0001.pdf PDF
NOAA-Bell-M-Shimada_SafetyScan.pdf PDF
NOAA-Bell-M-Shimada_FireScan.pdf PDF
Bell M Shimada NOAA Functional Tests.pdf PDF
Bell M Shimada Hose Hydro Testing Report.pdf PDF
Attachment_IV_-_Price_Schedule.xlsx XLSX spreadsheet
Attachment_II_-_Past_Performance_Information_Form.xlsx XLSX spreadsheet
1305M219QNMAN0237.pdf PDF
Reference_Documents.zip ZIP file
Attachment_III_-_Past_Performance_Questionnaire.docx DOCX document
Attachment_I_-_SH_FY20_5YR_Drydock_SOW.pdf PDF
SYNOPSIS.rtf RTF text file
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CERTIFICATE OF INSPECTION

For

NOAA Bell M Shimada Jan 31, 2019

Fixed Fire Suppression Systems

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Customer: Certified By:

NOAA Bell M Shimada Alexander Gow Fire Equipment

Company

2002 SE Marine Science Drive 1436 NW 53rd Street

Newport, OR 97365 Seattle, Washington 98107

Contact: Scott A. Tuttle Contact: Frank Martel

Title: Port Engineer Title: Technician

206-632-2810 www.gowfire.com

Alexander Gow Fire Equipment Company 1 02/18/2019

Executive Summary Generated by: BuildingReports.com

Property Information

Property: NOAA Bell M Shimada Contact: Scott A. Tuttle

Address: 2002 SE Marine Science Drive Phone: 541-867-8763

Address: Fax:

City/State/Zip: Newport, OR 97365 Mobile: 251-583-8824

Country: United States of America Email: Scott.Tuttle@ecstech.com

Inspection Performed By Company: Alexander Gow Fire Equipment

Company

Inspector: Frank Martel

Address: 1436 NW 53rd Street Phone: 206-632-2810

Address: Fax: 206-633-0434

City/State/Zip: Seattle, Washington 98107 Mobile: 206-718-1011

Country: United States of America Email: fmartel@gowfire.com

Systems Inspected

System Type Protected Area Devices

Carbon Dioxide Aft Propulsion Enclosure 6

Carbon Dioxide Aux/Main Machinery Room 4

Carbon Dioxide Auxiliary Machinery Room 12

Carbon Dioxide Emergency Generator Room 9

Carbon Dioxide Fwd. Propulsion Enclosure 8

Carbon Dioxide Main Machinery Room 26

Carbon Dioxide Paint Locker 8

Carbon Dioxide Trash Room 8

Clean Agent Skiff #2405 3

Gas H2S Detection 1

Kitchen Galley Fire Door 1

Kitchen Galley Hood 2

Kitchen Galley Scullery Fire Door 1

Alexander Gow Fire Equipment Company 2 02/18/2019

Inspection Summary

Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Container 49 55.06% 49 100.00% 49 100.00% 0 0%

Auxiliary 2 2.25% 2 100.00% 1 50.00% 1 50.00%

Detecting 1 1.12% 1 100.00% 1 100.00% 0 0%

Initiating 19 21.35% 19 100.00% 19 100.00% 0 0%

Pre-Engineered 1 1.12% 1 100.00% 1 100.00% 0 0%

Controls 5 5.62% 5 100.00% 5 100.00% 0 0%

Notification 12 13.48% 12 100.00% 12 100.00% 0 0%

Totals 89 100% 89 100.00% 88 98.88% 1 1.12%

Certification

Company: Alexander Gow Fire Equipment Company Property: NOAA Bell M Shimada

Inspector: Frank Martel Contact: Scott A. Tuttle

Signed: Dec 6, 2018 8:54:53 AM Signed: Dec 6, 2018 8:55:14 AM

Frank Martel Certification Type Number

Seattle Fire Department Type FA-1 Fire and Life Safety Certificate SCP-M-0621

Alexander Gow Fire Equipment Company 3 02/18/2019

Discrepancy Report

Property: NOAA Bell M Shimada The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer

Product Safety Commissions website and are subject to a recall by the manufacturer are included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall by Manufacturer

No recalled items found during this inspection.

ScanID Location Problem Reference

Kitchen Galley Scullery Fire Door

Fire Barrier

55116676 Main Deck Stbd. Galley Defective NFPA96 4.1.3.1

Code References NFPA96 4.1.3.1 Maintenance and repairs shall be performed on all components at intervals necessary to maintain good working condition.

Alexander Gow Fire Equipment Company 4 02/18/2019

Proposed Solutions Report

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

Time and Materials basis.

ScanID Location Solution Cost Fix

Fire Barrier

55116676 Main Deck Stbd. Galley Repair T/M

Alexander Gow Fire Equipment Company 5 02/18/2019

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your property. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. For more information about an item, click on the link provided.

Device Type Location Service Time Date

Passed

Carbon Dioxide Aft Propulsion Enclosure

Discharge Device Tank Top Fwd. Main Machinery Room Tested 2:47:10 PM 12/05/2018

Hose Tank Top Fwd. Main Machinery Room Inspected 2:53:41 PM 12/05/2018

Piping Tank Top Fwd. Main Machinery Room Inspected/Blew

Out

2:55:09 PM 12/05/2018

Manual Station Tank Top Fwd. Main Machinery Room Tested/Weighed 2:49:43 PM 12/05/2018

Pressure Switch Tank Top Fwd. Main Machinery Room Tested 2:50:00 PM 12/05/2018

Signage Tank Top Fwd. Main Machinery Room Inspected 2:55:35 PM 12/05/2018

Carbon Dioxide Aux/Main Machinery Room

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:05:40 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:06:40 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:06:57 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:07:19 AM 12/05/2018

Carbon Dioxide Auxiliary Machinery Room

Cartridge 01 Level Stbd. CO2 Room Weighed 9:48:12 AM 12/05/2018

Discharge Device 01 Level Stbd. CO2 Room Tested 9:41:35 AM 12/05/2018

Hose 01 Level Stbd. CO2 Room Inspected 10:17:27 AM 12/05/2018

Piping Vessel Inspected/Blew

Out

10:18:17 AM 12/05/2018

Pneumatic Time Delay 01 Level Stbd. CO2 Room Tested 1:09:44 PM 12/05/2018

Valve 01 Level Stbd. CO2 Room Tested 9:36:59 AM 12/05/2018

Valve 01 Level Stbd. CO2 Room Tested 9:37:27 AM 12/05/2018

Manual Station Tank Top Stairwell, AMR Entrance Tested/Weighed 1:22:17 PM 12/05/2018

Pressure Switch 01 Level Stbd. CO2 Room Tested 12:39:22 PM 12/05/2018

Pressure Switch 01 Level Stbd. CO2 Room Tested 12:39:52 PM 12/05/2018

Pneumatic Siren Tank Top C/L Auxiliary Machinery Room Tested 10:20:21 AM 12/05/2018

Signage Vessel Inspected/New

Warning Signs

10:16:16 AM 12/05/2018

Carbon Dioxide Emergency Generator Room

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:52:15 AM 12/05/2018

Discharge Device 01 Level Stbd. CO2 Room Tested 9:39:37 AM 12/05/2018

Hose 01 Level Stbd. CO2 Room Inspected 10:17:38 AM 12/05/2018

Piping Vessel Inspected/Blew

Out

10:19:56 AM 12/05/2018

Manual Station 01 Level C/L Passageway, EDG Entrance Tested/Weighed 10:40:06 AM 12/05/2018

Pressure Switch 01 Level Stbd. CO2 Room Tested 1:10:05 PM 12/05/2018

Pressure Switch 01 Level Stbd. CO2 Room Tested 1:10:44 PM 12/05/2018

Pneumatic Siren 01 Level Emergency Generator Room Tested 10:22:26 AM 12/05/2018

Alexander Gow Fire Equipment Company 6 02/18/2019

Signage Vessel Inspected/New

Warning Signs

10:16:26 AM 12/05/2018

Carbon Dioxide Fwd. Propulsion Enclosure

CO2 Tank Tank Top Fwd. Main Machinery Room Weighed 2:43:41 PM 12/05/2018

CO2 Tank Tank Top Fwd. Main Machinery Room Weighed 2:46:19 PM 12/05/2018

Discharge Device Tank Top Fwd. Main Machinery Room Tested 2:53:55 PM 12/05/2018

Hose Tank Top Fwd. Main Machinery Room Inspected 2:52:31 PM 12/05/2018

Piping Tank Top Fwd. Main Machinery Room Inspected/Blew

Out

2:55:00 PM 12/05/2018

Manual Station Tank Top Fwd. Main Machinery Room Tested/Weighed 2:49:33 PM 12/05/2018

Pressure Switch Tank Top Fwd. Main Machinery Room Tested 2:52:10 PM 12/05/2018

Signage Tank Top Fwd. Main Machinery Room Inspected 2:55:59 PM 12/05/2018

Carbon Dioxide Main Machinery Room

Cartridge 01 Level Stbd. CO2 Room Weighed 9:43:40 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:55:24 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:56:37 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:57:28 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:57:58 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:58:24 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:59:09 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:59:29 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:59:55 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:00:30 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:00:51 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:02:42 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:03:13 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:03:35 AM 12/05/2018

CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:05:18 AM 12/05/2018

Discharge Device 01 Level Stbd. CO2 Room Tested 9:41:07 AM 12/05/2018

Hose 01 Level Stbd. CO2 Room Inspected 10:16:46 AM 12/05/2018

Piping Vessel Inspected/Blew

Out

10:19:26 AM 12/05/2018

Pneumatic Time Delay 01 Level Stbd. CO2 Room Tested 12:37:31 PM 12/05/2018

Valve 01 Level Stbd. CO2 Room Tested 9:36:50 AM 12/05/2018

Valve 01 Level Stbd. CO2 Room Tested 9:38:01 AM 12/05/2018

Manual Station Main Deck C/L Passageway, MMR Entrance Tested/Weighed 10:55:57 AM 12/05/2018

Pressure Switch 01 Level Stbd. CO2 Room Tested 12:40:43 PM 12/05/2018

Pressure Switch 01 Level Stbd. CO2 Room Tested 12:41:13 PM 12/05/2018

Pneumatic Siren Tank Top C/L Main Machinery Room Tested 10:21:24 AM 12/05/2018

Signage Vessel Inspected/New

Warning Signs

10:18:07 AM 12/05/2018

Carbon Dioxide Paint Locker

CO2 Tank Main Deck Port Ready Room Weighed 3:43:05 PM 12/05/2018

Discharge Device Main Deck Port Ready Room Tested 3:49:19 PM 12/05/2018

Hose Main Deck Port Ready Room Inspected 4:06:46 PM 12/05/2018

Piping Main Deck Port Ready Room/Paint Locker Inspected/Blew

Out

4:07:09 PM 12/05/2018

Manual Station Main Deck Port Deck, Paint Locker Entrance Tested/Weighed/

New Install

4:03:53 PM 12/05/2018

Pressure Switch Main Deck Port Ready Room Tested 4:40:21 PM 12/05/2018

Alexander Gow Fire Equipment Company 7 02/18/2019

Pneumatic Siren Main Deck Port Trash Room Tested 4:05:11 PM 12/05/2018

Signage Main Deck Port Ready Room Inspected/New

Warning Signs

3:56:28 PM 12/05/2018

Carbon Dioxide Trash Room

CO2 Tank Main Deck Port Ready Room Weighed 3:59:51 PM 12/05/2018

Discharge Device Main Deck Port Ready Room Tested 3:49:15 PM 12/05/2018

Hose Main Deck Port Ready Room Inspected 4:06:49 PM 12/05/2018

Piping Main Deck Port Ready/Trash Room Inspected/Blew

Out

4:07:57 PM 12/05/2018

Manual Station Main Deck C/L Passageway, Trash Room

Entrance

Tested/Weighed 4:01:23 PM 12/05/2018

Pressure Switch Main Deck Port Ready Room Tested 4:39:28 PM 12/05/2018

Pneumatic Siren Main Deck Port Trash Room New Siren 4:05:50 PM 12/05/2018

Signage Main Deck Port Ready Room Inspected 4:05:22 PM 12/05/2018

Clean Agent Skiff #2405

Agent Tank Engine Compartment Inspected 2:11:51 PM 12/05/2018

Annunciator Helm Tested 2:19:11 PM 12/05/2018

Pull Station Helm Tested 2:16:19 PM 12/05/2018

Gas H2S Detection

Gas Detector Battery Locker Tested 11:14:23 AM 01/31/2019

Kitchen Galley Fire Door

Fire Barrier Main Deck Stbd. Galley Tested/Replaced

Fusible Link

9:26:31 AM 12/06/2018

Kitchen Galley Hood

Pull Station Main Deck Mess, Galley Entrance Tested 7:46:46 AM 12/06/2018

Kitchen System Main Deck Stbd. Galley Tested 7:47:32 AM 12/06/2018

Failed/Other

Kitchen Galley Scullery Fire Door

Fire Barrier Main Deck Stbd. Galley Tested/Replaced

Fusible Link

9:37:01 AM 12/06/2018

Alexander Gow Fire Equipment Company 8 02/18/2019

Auxiliary Functions Testing

Property: NOAA Bell M Shimada All Protected Areas

The Auxiliary Functions Testing section list each of the ancillary items, systems and emergency equipment that are controlled by the system control unit. The items are listed by category, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Kitchen Galley Fire Door

Fire Barrier

Roll Down Door Main Deck Stbd. Galley Passed 55116675

Kitchen Galley Scullery Fire Door

Roll Down Door Main Deck Stbd. Galley Defective 55116676

Alexander Gow Fire Equipment Company 9 02/18/2019

Notification Report

Message, signals, signage and communications for occupants of areas protected within this inspection.

Device Type Type Location Comment ScanID

Carbon Dioxide Aft Propulsion Enclosure Signage Instructions, Warnings, Labels

Tank Top Fwd. Main Machinery Room Passed 55116647

Carbon Dioxide Auxiliary Machinery Room Pneumatic Siren Tank Top C/L Auxiliary Machinery Room Passed 55116630

Signage Instructions, Warnings, Labels

Vessel Passed 55116625

Carbon Dioxide Emergency Generator Room Pneumatic Siren 01 Level Emergency Generator Room Passed 55116634

Signage Instructions, Warnings, Labels

Vessel Passed 55116626

Carbon Dioxide Fwd. Propulsion Enclosure Signage Instructions, Warnings, Labels

Tank Top Fwd. Main Machinery Room Passed 55116654

Carbon Dioxide Main Machinery Room Pneumatic Siren Tank Top C/L Main Machinery Room Passed 55116632

Signage Instructions, Warnings, Labels

Vessel Passed 55116624

Carbon Dioxide Paint Locker Pneumatic Siren Main Deck Port Trash Room Passed 55116671

Signage Instructions, Warnings, Labels

Main Deck Port Ready Room Passed 55116665

Carbon Dioxide Trash Room Pneumatic Siren Main Deck Port Trash Room Passed 55116672

Signage Instructions, Warnings, Labels

Main Deck Port Ready Room Passed 55116664

Alexander Gow Fire Equipment Company 10 02/18/2019

Time, Temperature & Level Testing

The Time, Temperature, & Level Testing section details the measurements taken from various devices that are designed to respond in a certain amount of time, respond at a certain temperature, or respond within the acceptable range of volume or level.

Type Location Comment Sec Deg Lvl ScanID

Kitchen Galley Fire Door

Fire Barrier

Roll Down Door Main Deck Stbd. Galley Passed N/A n/a 55116675

Kitchen Galley Scullery Fire Door

Roll Down Door Main Deck Stbd. Galley Defective N/A n/a 55116676

Alexander Gow Fire Equipment Company 11 02/18/2019

Agent Container Report

A container of stored agent to be used in case of a fire emergency.

Carbon Dioxide Aft Propulsion Enclosure

Discharge Device

Type Location ScanID

Local Cylinder Control Head Tank Top Fwd. Main Machinery Room 55116656

Install Date Initiator Replacement Compensator Resistance Initiator Resistance

08/01/2010 N/A N/A

Hose

Model Number & Size Location Install Date Hydro ScanID

Flexible .5” Tank Top Fwd. Main Machinery

Room

08/01/2010 03/01/2009 55116648

Piping

Type & Size Location Hangers/Braces/Identified ScanID

Galvanized .5” Tank Top Fwd. Main Machinery

Room

Normal, Normal, Normal 55116649

Carbon Dioxide Aux/Main Machinery Room

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8415170 07/01/2008 55116612

Gross Wt Capacity Liquid Level Value Puff Test Performed

274 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8415199 07/01/2008 55116611

Gross Wt Capacity Liquid Level Value Puff Test Performed

275 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8418146 07/01/2008 55116610

Gross Wt Capacity Liquid Level Value Puff Test Performed

274 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8413169 07/01/2008 55116609

Gross Wt Capacity Liquid Level Value Puff Test Performed

279 100 N/A Yes

Alexander Gow Fire Equipment Company 12 02/18/2019

Carbon Dioxide Auxiliary Machinery Room

Cartridge

Location Manufacturer Model Type Size Hydro Date ScanID

01 Level Stbd. CO2 Room Ansul Time Delay

Driver

Nitrogen LT-10-R 01/01/2018 55116595

Discharge Device

Type Location ScanID

Local Cylinder Control Heads 01 Level Stbd. CO2 Room 55116608

Install Date Initiator Replacement Compensator Resistance Initiator Resistance

08/01/2010 N/A N/A

Hose

Model Number & Size Location Install Date Hydro ScanID

Flexible .5” 01 Level Stbd. CO2 Room 08/01/2010 07/01/2008 55116628

Piping

Type & Size Location Hangers/Braces/Identified ScanID

Galvanized 1.25” Vessel Normal, Normal, Normal 55116631

Pneumatic Time Delay

Location Serial Number

Actual Time

Delay

Programmed

Time Delay ScanID

01 Level Stbd. CO2 Room N/A 33 30 Seconds 55116586

Carbon Dioxide Emergency Generator Room

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8417093 07/01/2008 55116621

Gross Wt Capacity Liquid Level Value Puff Test Performed

275 100 N/A Yes

Discharge Device

Type Location ScanID

Local Cylinder Control Head 01 Level Stbd. CO2 Room 55116622

Install Date Initiator Replacement Compensator Resistance Initiator Resistance

08/01/2010 N/A N/A

Hose

Model Number & Size Location Install Date Hydro ScanID

Flexible .5” 01 Level Stbd. CO2 Room 08/01/2010 07/01/2008 55116629

Piping

Type & Size Location Hangers/Braces/Identified ScanID

Galvanized .5” Vessel Normal, Normal, Normal 55116635

Carbon Dioxide Fwd. Propulsion Enclosure

CO2 Tank

Container Type Location Serial Number Hydro ScanID

Alexander Gow Fire Equipment Company 13 02/18/2019

High Pressure Tank Top Fwd. Main Machinery

Room

4041476 03/01/2009 55116650

Gross Wt Capacity Liquid Level Value Puff Test Performed

152 50 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure Tank Top Fwd. Main Machinery

Room

4041455 03/01/2009 55116644

Gross Wt Capacity Liquid Level Value Puff Test Performed

151 50 N/A Yes

Discharge Device

Type Location ScanID

Local Cylinder Control Head Tank Top Fwd. Main Machinery Room 55116655

Install Date Initiator Replacement Compensator Resistance Initiator Resistance

08/01/2010 N/A N/A

Hose

Model Number & Size Location Install Date Hydro ScanID

Flexible .5” Tank Top Fwd. Main Machinery

Room

08/01/2010 03/01/2009 55116651

Piping

Type & Size Location Hangers/Braces/Identified ScanID

Galvanized .5” Tank Top Fwd. Main Machinery

Room

Normal, Normal, Normal 55116652

Carbon Dioxide Main Machinery Room

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8407106 07/01/2008 55116619

Gross Wt Capacity Liquid Level Value Puff Test Performed

277 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8418054 07/01/2008 55116620

Gross Wt Capacity Liquid Level Value Puff Test Performed

274 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8416009 07/01/2008 55116618

Gross Wt Capacity Liquid Level Value Puff Test Performed

278 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8420130 07/01/2008 55116617

Alexander Gow Fire Equipment Company 14 02/18/2019

275 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8415102 07/01/2008 55116607

Gross Wt Capacity Liquid Level Value Puff Test Performed

276 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8418184 07/01/2008 55116606

Gross Wt Capacity Liquid Level Value Puff Test Performed

275 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8418147 07/01/2008 55116605

Gross Wt Capacity Liquid Level Value Puff Test Performed

275 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8411017 07/01/2008 55116604

Gross Wt Capacity Liquid Level Value Puff Test Performed

275 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8413059 07/01/2008 55116602

Gross Wt Capacity Liquid Level Value Puff Test Performed

277 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8416156 07/01/2008 55116603

Gross Wt Capacity Liquid Level Value Puff Test Performed

276 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8416115 07/01/2008 55116616

Gross Wt Capacity Liquid Level Value Puff Test Performed

275 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8418182 07/01/2008 55116615

Alexander Gow Fire Equipment Company 15 02/18/2019

274 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8416120 07/01/2008 55116614

Gross Wt Capacity Liquid Level Value Puff Test Performed

276 100 N/A Yes

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure 01 Level Stbd. CO2 Room 8411015 07/01/2008 55116613

Gross Wt Capacity Liquid Level Value Puff Test Performed

276 100 N/A Yes

Cartridge

Location Manufacturer Model Type Size Hydro Date ScanID

01 Level Stbd. CO2 Room Ansul Time Delay

Driver

Nitrogen LT-10-R 01/01/2018 55116596

Discharge Device

Type Location ScanID

Local Cylinder Control Heads 01 Level Stbd. CO2 Room 55116623

Install Date Initiator Replacement Compensator Resistance Initiator Resistance

08/01/2010 N/A N/A

Hose

Model Number & Size Location Install Date Hydro ScanID

Flexible .5” 01 Level Stbd. CO2 Room 08/01/2010 07/01/2008 55116627

Piping

Type & Size Location Hangers/Braces/Identified ScanID

Galvanized 2” Vessel Normal, Normal, Normal 55116633

Pneumatic Time Delay

Location Serial Number

Actual Time

Delay

Programmed

Time Delay ScanID

01 Level Stbd. CO2 Room N/A 76 68 Seconds 55116587

Carbon Dioxide Paint Locker

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure Main Deck Port Ready Room 4041444 03/01/2009 55116659

Gross Wt Capacity Liquid Level Value Puff Test Performed

151 50 N/A Yes

Discharge Device

Type Location ScanID

Local Cylinder Control Head Main Deck Port Ready Room 55116661

Install Date Initiator Replacement Compensator Resistance Initiator Resistance

08/01/2010 N/A N/A

Alexander Gow Fire Equipment Company 16 02/18/2019

Hose

Model Number & Size Location Install Date Hydro ScanID

Flexible .5” Main Deck Port Ready Room 08/01/2010 03/01/2009 55116668

Piping

Type & Size Location Hangers/Braces/Identified ScanID

Galvanized .5” Main Deck Port Ready Room/Paint

Locker

Normal, Normal, Normal 55116669

Carbon Dioxide Trash Room

CO2 Tank

Container Type Location Serial Number Hydro ScanID

High Pressure Main Deck Port Ready Room 7795031 05/01/2007 55116658

Gross Wt Capacity Liquid Level Value Puff Test Performed

221 75 N/A Yes

Discharge Device

Type Location ScanID

Local Cylinder Control Head Main Deck Port Ready Room 55116660

Install Date Initiator Replacement Compensator Resistance Initiator Resistance

08/01/2010 N/A N/A

Hose

Model Number & Size Location Install Date Hydro ScanID

Flexible .5” Main Deck Port Ready Room 08/01/2010 05/01/2007 55116666

Piping

Type & Size Location Hangers/Braces/Identified ScanID

Galvanized .5” Main Deck Port Ready/Trash Room Normal, Normal, Normal 55116667

Clean Agent Skiff #2405

Agent Tank

Agent Container Agent Location Serial Number Hydro ScanID

Cylinder HFC-227 Engine Compartment 20863 11/01/2015 55116640

Gross Wt Tare Wt Agent Wt Actual Wt PSI/Temp Supply Rel. Type LLV

15.2 6.6 8.6 15.4 230/45 Primary Burst

Bulb/Mechanica l

N/A

Alexander Gow Fire Equipment Company 17 02/18/2019

Carbon Dioxide Fire Suppression

Carbon Dioxide Aft Propulsion

Enclosure

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

Discharge Device Tank Top Fwd. Main Machinery

Room

Ansul Lever Operated 55116656

Hose Tank Top Fwd. Main Machinery

Room

Ansul Flexible 55116648

Piping Tank Top Fwd. Main Machinery

Room

N/A N/A 55116649

Initiating

Manual Station Tank Top Fwd. Main Machinery

Room

Ansul LT-20-L 55116645

Pressure Switch Tank Top Fwd. Main Machinery

Room

Ansul 2 Pole 55116646

Notification

Signage Tank Top Fwd. Main Machinery

N/A N/A 55116647

Alexander Gow Fire Equipment Company 18 02/18/2019

Carbon Dioxide Aux/Main

Machinery Room

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116612

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116611

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116610

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116609

Alexander Gow Fire Equipment Company 19 02/18/2019

Carbon Dioxide Auxiliary Machinery

Room

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

Cartridge 01 Level Stbd. CO2 Room Ansul Time Delay Driver 55116595

Discharge Device 01 Level Stbd. CO2 Room Ansul Lever Operated 55116608

Hose 01 Level Stbd. CO2 Room Ansul Flexible 55116628

Piping Vessel N/A N/A 55116631

Pneumatic Time Delay 01 Level Stbd. CO2 Room Ansul N2 Cartridge

Operated

55116586

Controls

Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116601

Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116599

Initiating

Manual Station Tank Top Stairwell, AMR Entrance Ansul LT-20-L 55116638

Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116592

Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116593

Notification

Pneumatic Siren Tank Top C/L Auxiliary Machinery

Room

Ansul CO2 Pressure

Operated

55116630

Signage Vessel N/A N/A 55116625

Alexander Gow Fire Equipment Company 20 02/18/2019

Carbon Dioxide Emergency

Generator Room

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116621

Discharge Device 01 Level Stbd. CO2 Room Ansul Lever Operated 55116622

Hose 01 Level Stbd. CO2 Room Ansul Flexible 55116629

Piping Vessel N/A N/A 55116635

Initiating

Manual Station 01 Level C/L Passageway, EDG

Entrance

Ansul LT-20-L 55116636

Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116588

Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116594

Notification

Pneumatic Siren 01 Level Emergency Generator

Room

Ansul CO2 Pressure

Operated

55116634

Signage Vessel N/A N/A 55116626

Alexander Gow Fire Equipment Company 21 02/18/2019

Carbon Dioxide Fwd. Propulsion

Enclosure

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

CO2 Tank Tank Top Fwd. Main Machinery

Room

Ansul CV-98 55116650

CO2 Tank Tank Top Fwd. Main Machinery

Room

Ansul CV-98 55116644

Discharge Device Tank Top Fwd. Main Machinery

Room

Ansul Lever Operated 55116655

Hose Tank Top Fwd. Main Machinery

Room

Ansul Flexible 55116651

Piping Tank Top Fwd. Main Machinery

Room

N/A N/A 55116652

Initiating

Manual Station Tank Top Fwd. Main Machinery

Room

Ansul LT-20-L 55116653

Pressure Switch Tank Top Fwd. Main Machinery

Room

Ansul 2 Pole 55116657

Notification

Signage Tank Top Fwd. Main Machinery

N/A N/A 55116654

Alexander Gow Fire Equipment Company 22 02/18/2019

Carbon Dioxide Main Machinery

Room

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

Cartridge 01 Level Stbd. CO2 Room Ansul Time Delay Driver 55116596

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116619

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116620

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116618

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116617

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116607

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116606

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116605

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116604

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116602

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116603

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116616

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116615

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116614

CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116613

Discharge Device 01 Level Stbd. CO2 Room Ansul Lever Operated 55116623

Hose 01 Level Stbd. CO2 Room Ansul Flexible 55116627

Piping Vessel N/A N/A 55116633

Pneumatic Time Delay 01 Level Stbd. CO2 Room Ansul N2 Cartridge

Operated

55116587

Controls

Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116600

Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116598

Initiating

Manual Station Main Deck C/L Passageway, MMR

Entrance

Ansul LT-20-L 55116637

Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116589

Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116590

Notification

Pneumatic Siren Tank Top C/L Main Machinery

Room

Ansul CO2 Pressure

Operated

55116632

Signage Vessel N/A N/A 55116624

Alexander Gow Fire Equipment Company 23 02/18/2019

Property: NOAA Bell M Shimada Carbon Dioxide Paint Locker

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

CO2 Tank Main Deck Port Ready Room Ansul CV-98 55116659

Discharge Device Main Deck Port Ready Room Ansul Lever Operated 55116661

Hose Main Deck Port Ready Room Ansul Flexible 55116668

Piping Main Deck Port Ready Room/Paint

Locker

Arrow N/A 55116669

Initiating

Manual Station Main Deck Port Deck, Paint Locker

Entrance

Ansul LT-20-L 55116296

Pressure Switch Main Deck Port Ready Room Ansul 2 Pole 55116663

Notification

Pneumatic Siren Main Deck Port Trash Room Ansul CO2 Pressure

Operated

55116671

Signage Main Deck Port Ready Room N/A N/A 55116665

Alexander Gow Fire Equipment Company 24 02/18/2019

Property: NOAA Bell M Shimada Carbon Dioxide Trash Room

Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.

Passed Device Type Location Manufacturer Model Number ScanID

Container

CO2 Tank Main Deck Port Ready Room Ansul CV-98 55116658

Discharge Device Main Deck Port Ready Room Ansul Lever Operated 55116660

Hose Main Deck Port Ready Room Ansul Flexible 55116666

Piping Main Deck Port Ready/Trash Room N/A N/A 55116667

Initiating

Manual Station Main Deck C/L Passageway, Trash

Room Entrance

Ansul LT-20-L 55116670

Pressure Switch Main Deck Port Ready Room Ansul 2 Pole 55116662

Notification

Pneumatic Siren Main Deck Port Trash Room Ansul CO2 Pressure

Operated

55116672

Signage Main Deck Port Ready Room N/A N/A 55116664

Alexander Gow Fire Equipment Company 25 02/18/2019

Clean Agent Fire Suppression

Property: NOAA Bell M Shimada Clean Agent Skiff #2405

Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. The agents were introduced in response to international restrictions on the production of certain halon fire-extinguishing agents under the Montreal Protocol signed September 16, 1987, as amended.

Passed Device Type Location Manufacturer Model Number ScanID

Container

Agent Tank Engine Compartment Fireboy MA20200227-BL 55116640

Controls

Annunciator Helm Fireboy LED 55116643

Initiating

Pull Station Helm Fireboy T-Handle 55116641

Alexander Gow Fire Equipment Company 26 02/18/2019

Gas Detection

Property: NOAA Bell M Shimada Gas H2S Detection

An agent that contains as primary components one or more of the gases helium, neon, argon, or nitrogen. Inert gas agents that are blends of gases can also contain carbon dioxide as a secondary component.

Passed Device Type Location Type Setting ScanID

Detecting

Gas Detector Battery Locker H2S 12.5% ppm 44352504

Alexander Gow Fire Equipment Company 27 02/18/2019

Kitchen System

A container of stored agent to be used in case of a fire emergency.

Kitchen Galley Fire Door

Kitchen Galley Hood

Kitchen System

Manufacturer Type Install Date Comment ScanID

Ansul Wet Chemical 08/01/2010 Passed 55116674

Hydro Date Links Qty PSI Underwriters Lab

01/01/2008 360 4 UL 300

Alexander Gow Fire Equipment Company 28 02/18/2019

Inventory & Warranty Report

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Item Category % of Inventory Quantity

Valve Controls 4.49% 4

Discharge Device Container 7.87% 7

Cartridge Container 2.25% 2

CO2 Tank Container 25.84% 23

Signage Notification 7.87% 7

Hose Container 7.87% 7

Piping Container 7.87% 7

Pneumatic Siren Notification 5.62% 5

Manual Station Initiating 7.87% 7

Pneumatic Time Delay Container 2.25% 2

Pressure Switch Initiating 11.24% 10

Agent Tank Container 1.12% 1

Pull Station Initiating 2.25% 2

Annunciator Controls 1.12% 1

Kitchen System Pre-Engineered 1.12% 1

Fire Barrier Auxiliary 2.25% 2

Gas Detector Detecting 1.12% 1

Device or Item Qty Model # Description Install Date

In Service - 5 Years to 10 Years

Carbon Dioxide Aft Propulsion Enclosure

Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010

Hose 1 Flexible 08/01/2010

Manual Station 1 LT-20-L Dual Action 08/01/2010

Pressure Switch 1 2 Pole Pressure Operated 08/01/2010

Piping 1 N/A Galvanized 08/01/2010

Signage 1 N/A Instructions, Warnings, Labels 08/01/2010

Carbon Dioxide Aux/Main Machinery Room

CO2 Tank 4 CV-98 High Pressure 08/01/2010

Carbon Dioxide Auxiliary Machinery Room

Cartridge 1 Time Delay

Driver

Nitrogen 08/01/2010

Discharge Device 1 Lever Operated Local Cylinder Control Heads 08/01/2010

Hose 1 Flexible 08/01/2010

Pneumatic Siren 1 CO2 Pressure

Operated

08/01/2010

Pneumatic Time Delay 1 N2 Cartridge

Operated

08/01/2010

Pressure Switch 2 2 Pole Pressure Operated 08/01/2010

Valve 1 Pressure Control Valve 08/01/2010

Alexander Gow Fire Equipment Company 29 02/18/2019

Device or Item Qty Model # Description Install Date

Operated

Valve 1 Pressure

Operated

Stop Valve 08/01/2010

Piping 1 N/A Galvanized 08/01/2010

Signage 1 N/A Instructions, Warnings, Labels 08/01/2010

In Service - 10 Years to 15 Years

Carbon Dioxide Auxiliary Machinery Room

Manual Station 1 LT-20-L Dual Action 01/01/2008

Carbon Dioxide Emergency Generator Room

CO2 Tank 1 CV-98 High Pressure 08/01/2010

Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010

Hose 1 Flexible 08/01/2010

Manual Station 1 LT-20-L Dual Action 08/01/2010

Pneumatic Siren 1 CO2 Pressure

Operated

08/01/2010

Pressure Switch 2 2 Pole Pressure Operated 08/01/2010

Piping 1 N/A Galvanized 08/01/2010

Signage 1 N/A Instructions, Warnings, Labels 08/01/2010

Carbon Dioxide Fwd. Propulsion Enclosure

CO2 Tank 2 CV-98 High Pressure 08/01/2010

Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010

Hose 1 Flexible 08/01/2010

Manual Station 1 LT-20-L Dual Action 08/01/2010

Pressure Switch 1 2 Pole Pressure Operated 08/01/2010

Piping 1 N/A Galvanized 08/01/2010

Signage 1 N/A Instructions, Warnings, Labels 08/01/2010

Carbon Dioxide Main Machinery Room

Cartridge 1 Time Delay

Driver

Nitrogen 08/01/2010

CO2 Tank 14 CV-98 High Pressure 08/01/2010

Discharge Device 1 Lever Operated Local Cylinder Control Heads 08/01/2010

Hose 1 Flexible 08/01/2010

Manual Station 1 LT-20-L Dual Action 08/01/2010

Pneumatic Siren 1 CO2 Pressure

Operated

08/01/2010

Pneumatic Time Delay 1 N2 Cartridge

Operated

08/01/2010

Pressure Switch 2 2 Pole Pressure Operated 08/01/2010

Valve 1 Pressure

Operated

Control Valve 08/01/2010

Valve 1 Pressure

Operated

Stop Valve 08/01/2010

Piping 1 N/A Galvanized 08/01/2010

Carbon Dioxide Paint Locker

Alexander Gow Fire Equipment Company 30 02/18/2019

CO2 Tank 1 CV-98 High Pressure 08/01/2010

Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010

Hose 1 Flexible 08/01/2010

Manual Station 1 LT-20-L Dual Action 08/01/2010

Pneumatic Siren 1 CO2 Pressure

Operated

08/01/2010

Pressure Switch 1 2 Pole Pressure Operated 08/01/2010

Piping 1 N/A Galvanized 08/01/2010

Signage 1 N/A Instructions, Warnings, Labels 08/01/2010

Carbon Dioxide Trash Room

CO2 Tank 1 CV-98 High Pressure 08/01/2010

Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010

Hose 1 Flexible 08/01/2010

Manual Station 1 LT-20-L Dual Action 08/01/2010

Pneumatic Siren 1 CO2 Pressure

Operated

08/01/2010

Pressure Switch 1 2 Pole Pressure Operated 08/01/2010

Piping 1 N/A Galvanized 08/01/2010

In Service - 3 Years to 5 Years

Clean Agent Skiff #2405

Agent Tank 1 MA20200227-

BL

11/01/2015

Annunciator 1 LED LED List 11/01/2015

Pull Station 1 T-Handle Dual Action 11/01/2015

In Service - 10 Years to 15 Years

Gas H2S Detection

Gas Detector 1 TXgard-IS H2S 01/01/2008

Kitchen Galley Fire Door

Fire Barrier 1 N/A Roll Down Door 08/01/2010

Kitchen Galley Hood

Kitchen System 1 R-102 Wet Chemical 08/01/2010

Pull Station 1 R-102 Single Action 08/01/2010

Fire Barrier 1 N/A Roll Down Door 08/01/2010

Alexander Gow Fire Equipment Company 31 02/18/2019

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the property inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Carbon Dioxide Aft Propulsion Enclosure 1 Pressure Switch Tank Top Fwd. Main Machinery Room Passed 55116646

Could Not Verify. No Power.

Carbon Dioxide Auxiliary Machinery Room 2 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116592

Secures Supply Ventilation.

3 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116593

Secures Fuel Oil Pumps.

Carbon Dioxide Emergency Generator Room 4 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116594

Secures Supply Ventilation.

5 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116588

Secures Emergency Generator.

Carbon Dioxide Fwd. Propulsion Enclosure 6 Pressure Switch Tank Top Fwd. Main Machinery Room Passed 55116657

Could Not Verify. No Power.

Carbon Dioxide Main Machinery Room 7 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116589

Could Not Verify. No Power.

8 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116590

Secures Port & Stbd. Supply Ventilation.

Carbon Dioxide Paint Locker 9 Pressure Switch Main Deck Port Ready Room Passed 55116663

Secures Exhaust & Supply Ventilation.

Alexander Gow Fire Equipment Company 32 02/18/2019

Note Device Type Location Comment ScanID

Carbon Dioxide Trash Room 10 Pressure Switch Main Deck Port Ready Room Passed 55116662

Secures Exhaust Ventilation.

Clean Agent Skiff #2405 11 Agent Tank Engine Compartment Passed 55116640

Alarm Indicator Operates. Could Not Verify Engine Shut Down. No Power.

Kitchen Galley Hood 12 Kitchen System Main Deck Stbd. Galley Passed 55116674

Micro-Switch Secures Deep Fat Fryer & Operates Gaylord Fire Mode.

Kitchen Galley Scullery Fire Door 13 Fire Barrier Main Deck Stbd. Galley Defective 55116676

Fire Door Gets Jammed In The Guides. Requires Repair From Fire Door Company.