CERTIFICATE OF INSPECTION
For
NOAA Bell M Shimada Jan 31, 2019
Fixed Fire Suppression Systems
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Customer: Certified By:
NOAA Bell M Shimada Alexander Gow Fire Equipment
Company
2002 SE Marine Science Drive 1436 NW 53rd Street
Newport, OR 97365 Seattle, Washington 98107
Contact: Scott A. Tuttle Contact: Frank Martel
Title: Port Engineer Title: Technician
206-632-2810 www.gowfire.com
Alexander Gow Fire Equipment Company 1 02/18/2019
Executive Summary Generated by: BuildingReports.com
Property Information
Property: NOAA Bell M Shimada Contact: Scott A. Tuttle
Address: 2002 SE Marine Science Drive Phone: 541-867-8763
Address: Fax:
City/State/Zip: Newport, OR 97365 Mobile: 251-583-8824
Country: United States of America Email: Scott.Tuttle@ecstech.com
Inspection Performed By Company: Alexander Gow Fire Equipment
Company
Inspector: Frank Martel
Address: 1436 NW 53rd Street Phone: 206-632-2810
Address: Fax: 206-633-0434
City/State/Zip: Seattle, Washington 98107 Mobile: 206-718-1011
Country: United States of America Email: fmartel@gowfire.com
Systems Inspected
System Type Protected Area Devices
Carbon Dioxide Aft Propulsion Enclosure 6
Carbon Dioxide Aux/Main Machinery Room 4
Carbon Dioxide Auxiliary Machinery Room 12
Carbon Dioxide Emergency Generator Room 9
Carbon Dioxide Fwd. Propulsion Enclosure 8
Carbon Dioxide Main Machinery Room 26
Carbon Dioxide Paint Locker 8
Carbon Dioxide Trash Room 8
Clean Agent Skiff #2405 3
Gas H2S Detection 1
Kitchen Galley Fire Door 1
Kitchen Galley Hood 2
Kitchen Galley Scullery Fire Door 1
Alexander Gow Fire Equipment Company 2 02/18/2019
Inspection Summary
Category Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Container 49 55.06% 49 100.00% 49 100.00% 0 0%
Auxiliary 2 2.25% 2 100.00% 1 50.00% 1 50.00%
Detecting 1 1.12% 1 100.00% 1 100.00% 0 0%
Initiating 19 21.35% 19 100.00% 19 100.00% 0 0%
Pre-Engineered 1 1.12% 1 100.00% 1 100.00% 0 0%
Controls 5 5.62% 5 100.00% 5 100.00% 0 0%
Notification 12 13.48% 12 100.00% 12 100.00% 0 0%
Totals 89 100% 89 100.00% 88 98.88% 1 1.12%
Certification
Company: Alexander Gow Fire Equipment Company Property: NOAA Bell M Shimada
Inspector: Frank Martel Contact: Scott A. Tuttle
Signed: Dec 6, 2018 8:54:53 AM Signed: Dec 6, 2018 8:55:14 AM
Frank Martel Certification Type Number
Seattle Fire Department Type FA-1 Fire and Life Safety Certificate SCP-M-0621
Alexander Gow Fire Equipment Company 3 02/18/2019
Discrepancy Report
Property: NOAA Bell M Shimada The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer
Product Safety Commissions website and are subject to a recall by the manufacturer are included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall by Manufacturer
No recalled items found during this inspection.
ScanID Location Problem Reference
Kitchen Galley Scullery Fire Door
Fire Barrier
55116676 Main Deck Stbd. Galley Defective NFPA96 4.1.3.1
Code References NFPA96 4.1.3.1 Maintenance and repairs shall be performed on all components at intervals necessary to maintain good working condition.
Alexander Gow Fire Equipment Company 4 02/18/2019
Proposed Solutions Report
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a
Time and Materials basis.
ScanID Location Solution Cost Fix
Fire Barrier
55116676 Main Deck Stbd. Galley Repair T/M
Alexander Gow Fire Equipment Company 5 02/18/2019
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your property. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. For more information about an item, click on the link provided.
Device Type Location Service Time Date
Passed
Carbon Dioxide Aft Propulsion Enclosure
Discharge Device Tank Top Fwd. Main Machinery Room Tested 2:47:10 PM 12/05/2018
Hose Tank Top Fwd. Main Machinery Room Inspected 2:53:41 PM 12/05/2018
Piping Tank Top Fwd. Main Machinery Room Inspected/Blew
Out
2:55:09 PM 12/05/2018
Manual Station Tank Top Fwd. Main Machinery Room Tested/Weighed 2:49:43 PM 12/05/2018
Pressure Switch Tank Top Fwd. Main Machinery Room Tested 2:50:00 PM 12/05/2018
Signage Tank Top Fwd. Main Machinery Room Inspected 2:55:35 PM 12/05/2018
Carbon Dioxide Aux/Main Machinery Room
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:05:40 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:06:40 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:06:57 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:07:19 AM 12/05/2018
Carbon Dioxide Auxiliary Machinery Room
Cartridge 01 Level Stbd. CO2 Room Weighed 9:48:12 AM 12/05/2018
Discharge Device 01 Level Stbd. CO2 Room Tested 9:41:35 AM 12/05/2018
Hose 01 Level Stbd. CO2 Room Inspected 10:17:27 AM 12/05/2018
Piping Vessel Inspected/Blew
Out
10:18:17 AM 12/05/2018
Pneumatic Time Delay 01 Level Stbd. CO2 Room Tested 1:09:44 PM 12/05/2018
Valve 01 Level Stbd. CO2 Room Tested 9:36:59 AM 12/05/2018
Valve 01 Level Stbd. CO2 Room Tested 9:37:27 AM 12/05/2018
Manual Station Tank Top Stairwell, AMR Entrance Tested/Weighed 1:22:17 PM 12/05/2018
Pressure Switch 01 Level Stbd. CO2 Room Tested 12:39:22 PM 12/05/2018
Pressure Switch 01 Level Stbd. CO2 Room Tested 12:39:52 PM 12/05/2018
Pneumatic Siren Tank Top C/L Auxiliary Machinery Room Tested 10:20:21 AM 12/05/2018
Signage Vessel Inspected/New
Warning Signs
10:16:16 AM 12/05/2018
Carbon Dioxide Emergency Generator Room
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:52:15 AM 12/05/2018
Discharge Device 01 Level Stbd. CO2 Room Tested 9:39:37 AM 12/05/2018
Hose 01 Level Stbd. CO2 Room Inspected 10:17:38 AM 12/05/2018
Piping Vessel Inspected/Blew
Out
10:19:56 AM 12/05/2018
Manual Station 01 Level C/L Passageway, EDG Entrance Tested/Weighed 10:40:06 AM 12/05/2018
Pressure Switch 01 Level Stbd. CO2 Room Tested 1:10:05 PM 12/05/2018
Pressure Switch 01 Level Stbd. CO2 Room Tested 1:10:44 PM 12/05/2018
Pneumatic Siren 01 Level Emergency Generator Room Tested 10:22:26 AM 12/05/2018
Alexander Gow Fire Equipment Company 6 02/18/2019
Signage Vessel Inspected/New
Warning Signs
10:16:26 AM 12/05/2018
Carbon Dioxide Fwd. Propulsion Enclosure
CO2 Tank Tank Top Fwd. Main Machinery Room Weighed 2:43:41 PM 12/05/2018
CO2 Tank Tank Top Fwd. Main Machinery Room Weighed 2:46:19 PM 12/05/2018
Discharge Device Tank Top Fwd. Main Machinery Room Tested 2:53:55 PM 12/05/2018
Hose Tank Top Fwd. Main Machinery Room Inspected 2:52:31 PM 12/05/2018
Piping Tank Top Fwd. Main Machinery Room Inspected/Blew
Out
2:55:00 PM 12/05/2018
Manual Station Tank Top Fwd. Main Machinery Room Tested/Weighed 2:49:33 PM 12/05/2018
Pressure Switch Tank Top Fwd. Main Machinery Room Tested 2:52:10 PM 12/05/2018
Signage Tank Top Fwd. Main Machinery Room Inspected 2:55:59 PM 12/05/2018
Carbon Dioxide Main Machinery Room
Cartridge 01 Level Stbd. CO2 Room Weighed 9:43:40 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:55:24 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:56:37 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:57:28 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:57:58 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:58:24 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:59:09 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:59:29 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 9:59:55 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:00:30 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:00:51 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:02:42 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:03:13 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:03:35 AM 12/05/2018
CO2 Tank 01 Level Stbd. CO2 Room Weighed 10:05:18 AM 12/05/2018
Discharge Device 01 Level Stbd. CO2 Room Tested 9:41:07 AM 12/05/2018
Hose 01 Level Stbd. CO2 Room Inspected 10:16:46 AM 12/05/2018
Piping Vessel Inspected/Blew
Out
10:19:26 AM 12/05/2018
Pneumatic Time Delay 01 Level Stbd. CO2 Room Tested 12:37:31 PM 12/05/2018
Valve 01 Level Stbd. CO2 Room Tested 9:36:50 AM 12/05/2018
Valve 01 Level Stbd. CO2 Room Tested 9:38:01 AM 12/05/2018
Manual Station Main Deck C/L Passageway, MMR Entrance Tested/Weighed 10:55:57 AM 12/05/2018
Pressure Switch 01 Level Stbd. CO2 Room Tested 12:40:43 PM 12/05/2018
Pressure Switch 01 Level Stbd. CO2 Room Tested 12:41:13 PM 12/05/2018
Pneumatic Siren Tank Top C/L Main Machinery Room Tested 10:21:24 AM 12/05/2018
Signage Vessel Inspected/New
Warning Signs
10:18:07 AM 12/05/2018
Carbon Dioxide Paint Locker
CO2 Tank Main Deck Port Ready Room Weighed 3:43:05 PM 12/05/2018
Discharge Device Main Deck Port Ready Room Tested 3:49:19 PM 12/05/2018
Hose Main Deck Port Ready Room Inspected 4:06:46 PM 12/05/2018
Piping Main Deck Port Ready Room/Paint Locker Inspected/Blew
Out
4:07:09 PM 12/05/2018
Manual Station Main Deck Port Deck, Paint Locker Entrance Tested/Weighed/
New Install
4:03:53 PM 12/05/2018
Pressure Switch Main Deck Port Ready Room Tested 4:40:21 PM 12/05/2018
Alexander Gow Fire Equipment Company 7 02/18/2019
Pneumatic Siren Main Deck Port Trash Room Tested 4:05:11 PM 12/05/2018
Signage Main Deck Port Ready Room Inspected/New
Warning Signs
3:56:28 PM 12/05/2018
Carbon Dioxide Trash Room
CO2 Tank Main Deck Port Ready Room Weighed 3:59:51 PM 12/05/2018
Discharge Device Main Deck Port Ready Room Tested 3:49:15 PM 12/05/2018
Hose Main Deck Port Ready Room Inspected 4:06:49 PM 12/05/2018
Piping Main Deck Port Ready/Trash Room Inspected/Blew
Out
4:07:57 PM 12/05/2018
Manual Station Main Deck C/L Passageway, Trash Room
Entrance
Tested/Weighed 4:01:23 PM 12/05/2018
Pressure Switch Main Deck Port Ready Room Tested 4:39:28 PM 12/05/2018
Pneumatic Siren Main Deck Port Trash Room New Siren 4:05:50 PM 12/05/2018
Signage Main Deck Port Ready Room Inspected 4:05:22 PM 12/05/2018
Clean Agent Skiff #2405
Agent Tank Engine Compartment Inspected 2:11:51 PM 12/05/2018
Annunciator Helm Tested 2:19:11 PM 12/05/2018
Pull Station Helm Tested 2:16:19 PM 12/05/2018
Gas H2S Detection
Gas Detector Battery Locker Tested 11:14:23 AM 01/31/2019
Kitchen Galley Fire Door
Fire Barrier Main Deck Stbd. Galley Tested/Replaced
Fusible Link
9:26:31 AM 12/06/2018
Kitchen Galley Hood
Pull Station Main Deck Mess, Galley Entrance Tested 7:46:46 AM 12/06/2018
Kitchen System Main Deck Stbd. Galley Tested 7:47:32 AM 12/06/2018
Failed/Other
Kitchen Galley Scullery Fire Door
Fire Barrier Main Deck Stbd. Galley Tested/Replaced
Fusible Link
9:37:01 AM 12/06/2018
Alexander Gow Fire Equipment Company 8 02/18/2019
Auxiliary Functions Testing
Property: NOAA Bell M Shimada All Protected Areas
The Auxiliary Functions Testing section list each of the ancillary items, systems and emergency equipment that are controlled by the system control unit. The items are listed by category, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Kitchen Galley Fire Door
Fire Barrier
Roll Down Door Main Deck Stbd. Galley Passed 55116675
Kitchen Galley Scullery Fire Door
Roll Down Door Main Deck Stbd. Galley Defective 55116676
Alexander Gow Fire Equipment Company 9 02/18/2019
Notification Report
Message, signals, signage and communications for occupants of areas protected within this inspection.
Device Type Type Location Comment ScanID
Carbon Dioxide Aft Propulsion Enclosure Signage Instructions, Warnings, Labels
Tank Top Fwd. Main Machinery Room Passed 55116647
Carbon Dioxide Auxiliary Machinery Room Pneumatic Siren Tank Top C/L Auxiliary Machinery Room Passed 55116630
Signage Instructions, Warnings, Labels
Vessel Passed 55116625
Carbon Dioxide Emergency Generator Room Pneumatic Siren 01 Level Emergency Generator Room Passed 55116634
Signage Instructions, Warnings, Labels
Vessel Passed 55116626
Carbon Dioxide Fwd. Propulsion Enclosure Signage Instructions, Warnings, Labels
Tank Top Fwd. Main Machinery Room Passed 55116654
Carbon Dioxide Main Machinery Room Pneumatic Siren Tank Top C/L Main Machinery Room Passed 55116632
Signage Instructions, Warnings, Labels
Vessel Passed 55116624
Carbon Dioxide Paint Locker Pneumatic Siren Main Deck Port Trash Room Passed 55116671
Signage Instructions, Warnings, Labels
Main Deck Port Ready Room Passed 55116665
Carbon Dioxide Trash Room Pneumatic Siren Main Deck Port Trash Room Passed 55116672
Signage Instructions, Warnings, Labels
Main Deck Port Ready Room Passed 55116664
Alexander Gow Fire Equipment Company 10 02/18/2019
Time, Temperature & Level Testing
The Time, Temperature, & Level Testing section details the measurements taken from various devices that are designed to respond in a certain amount of time, respond at a certain temperature, or respond within the acceptable range of volume or level.
Type Location Comment Sec Deg Lvl ScanID
Kitchen Galley Fire Door
Fire Barrier
Roll Down Door Main Deck Stbd. Galley Passed N/A n/a 55116675
Kitchen Galley Scullery Fire Door
Roll Down Door Main Deck Stbd. Galley Defective N/A n/a 55116676
Alexander Gow Fire Equipment Company 11 02/18/2019
Agent Container Report
A container of stored agent to be used in case of a fire emergency.
Carbon Dioxide Aft Propulsion Enclosure
Discharge Device
Type Location ScanID
Local Cylinder Control Head Tank Top Fwd. Main Machinery Room 55116656
Install Date Initiator Replacement Compensator Resistance Initiator Resistance
08/01/2010 N/A N/A
Hose
Model Number & Size Location Install Date Hydro ScanID
Flexible .5” Tank Top Fwd. Main Machinery
Room
08/01/2010 03/01/2009 55116648
Piping
Type & Size Location Hangers/Braces/Identified ScanID
Galvanized .5” Tank Top Fwd. Main Machinery
Room
Normal, Normal, Normal 55116649
Carbon Dioxide Aux/Main Machinery Room
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8415170 07/01/2008 55116612
Gross Wt Capacity Liquid Level Value Puff Test Performed
274 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8415199 07/01/2008 55116611
Gross Wt Capacity Liquid Level Value Puff Test Performed
275 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8418146 07/01/2008 55116610
Gross Wt Capacity Liquid Level Value Puff Test Performed
274 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8413169 07/01/2008 55116609
Gross Wt Capacity Liquid Level Value Puff Test Performed
279 100 N/A Yes
Alexander Gow Fire Equipment Company 12 02/18/2019
Carbon Dioxide Auxiliary Machinery Room
Cartridge
Location Manufacturer Model Type Size Hydro Date ScanID
01 Level Stbd. CO2 Room Ansul Time Delay
Driver
Nitrogen LT-10-R 01/01/2018 55116595
Discharge Device
Type Location ScanID
Local Cylinder Control Heads 01 Level Stbd. CO2 Room 55116608
Install Date Initiator Replacement Compensator Resistance Initiator Resistance
08/01/2010 N/A N/A
Hose
Model Number & Size Location Install Date Hydro ScanID
Flexible .5” 01 Level Stbd. CO2 Room 08/01/2010 07/01/2008 55116628
Piping
Type & Size Location Hangers/Braces/Identified ScanID
Galvanized 1.25” Vessel Normal, Normal, Normal 55116631
Pneumatic Time Delay
Location Serial Number
Actual Time
Delay
Programmed
Time Delay ScanID
01 Level Stbd. CO2 Room N/A 33 30 Seconds 55116586
Carbon Dioxide Emergency Generator Room
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8417093 07/01/2008 55116621
Gross Wt Capacity Liquid Level Value Puff Test Performed
275 100 N/A Yes
Discharge Device
Type Location ScanID
Local Cylinder Control Head 01 Level Stbd. CO2 Room 55116622
Install Date Initiator Replacement Compensator Resistance Initiator Resistance
08/01/2010 N/A N/A
Hose
Model Number & Size Location Install Date Hydro ScanID
Flexible .5” 01 Level Stbd. CO2 Room 08/01/2010 07/01/2008 55116629
Piping
Type & Size Location Hangers/Braces/Identified ScanID
Galvanized .5” Vessel Normal, Normal, Normal 55116635
Carbon Dioxide Fwd. Propulsion Enclosure
CO2 Tank
Container Type Location Serial Number Hydro ScanID
Alexander Gow Fire Equipment Company 13 02/18/2019
High Pressure Tank Top Fwd. Main Machinery
Room
4041476 03/01/2009 55116650
Gross Wt Capacity Liquid Level Value Puff Test Performed
152 50 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure Tank Top Fwd. Main Machinery
Room
4041455 03/01/2009 55116644
Gross Wt Capacity Liquid Level Value Puff Test Performed
151 50 N/A Yes
Discharge Device
Type Location ScanID
Local Cylinder Control Head Tank Top Fwd. Main Machinery Room 55116655
Install Date Initiator Replacement Compensator Resistance Initiator Resistance
08/01/2010 N/A N/A
Hose
Model Number & Size Location Install Date Hydro ScanID
Flexible .5” Tank Top Fwd. Main Machinery
Room
08/01/2010 03/01/2009 55116651
Piping
Type & Size Location Hangers/Braces/Identified ScanID
Galvanized .5” Tank Top Fwd. Main Machinery
Room
Normal, Normal, Normal 55116652
Carbon Dioxide Main Machinery Room
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8407106 07/01/2008 55116619
Gross Wt Capacity Liquid Level Value Puff Test Performed
277 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8418054 07/01/2008 55116620
Gross Wt Capacity Liquid Level Value Puff Test Performed
274 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8416009 07/01/2008 55116618
Gross Wt Capacity Liquid Level Value Puff Test Performed
278 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8420130 07/01/2008 55116617
Alexander Gow Fire Equipment Company 14 02/18/2019
275 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8415102 07/01/2008 55116607
Gross Wt Capacity Liquid Level Value Puff Test Performed
276 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8418184 07/01/2008 55116606
Gross Wt Capacity Liquid Level Value Puff Test Performed
275 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8418147 07/01/2008 55116605
Gross Wt Capacity Liquid Level Value Puff Test Performed
275 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8411017 07/01/2008 55116604
Gross Wt Capacity Liquid Level Value Puff Test Performed
275 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8413059 07/01/2008 55116602
Gross Wt Capacity Liquid Level Value Puff Test Performed
277 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8416156 07/01/2008 55116603
Gross Wt Capacity Liquid Level Value Puff Test Performed
276 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8416115 07/01/2008 55116616
Gross Wt Capacity Liquid Level Value Puff Test Performed
275 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8418182 07/01/2008 55116615
Alexander Gow Fire Equipment Company 15 02/18/2019
274 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8416120 07/01/2008 55116614
Gross Wt Capacity Liquid Level Value Puff Test Performed
276 100 N/A Yes
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure 01 Level Stbd. CO2 Room 8411015 07/01/2008 55116613
Gross Wt Capacity Liquid Level Value Puff Test Performed
276 100 N/A Yes
Cartridge
Location Manufacturer Model Type Size Hydro Date ScanID
01 Level Stbd. CO2 Room Ansul Time Delay
Driver
Nitrogen LT-10-R 01/01/2018 55116596
Discharge Device
Type Location ScanID
Local Cylinder Control Heads 01 Level Stbd. CO2 Room 55116623
Install Date Initiator Replacement Compensator Resistance Initiator Resistance
08/01/2010 N/A N/A
Hose
Model Number & Size Location Install Date Hydro ScanID
Flexible .5” 01 Level Stbd. CO2 Room 08/01/2010 07/01/2008 55116627
Piping
Type & Size Location Hangers/Braces/Identified ScanID
Galvanized 2” Vessel Normal, Normal, Normal 55116633
Pneumatic Time Delay
Location Serial Number
Actual Time
Delay
Programmed
Time Delay ScanID
01 Level Stbd. CO2 Room N/A 76 68 Seconds 55116587
Carbon Dioxide Paint Locker
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure Main Deck Port Ready Room 4041444 03/01/2009 55116659
Gross Wt Capacity Liquid Level Value Puff Test Performed
151 50 N/A Yes
Discharge Device
Type Location ScanID
Local Cylinder Control Head Main Deck Port Ready Room 55116661
Install Date Initiator Replacement Compensator Resistance Initiator Resistance
08/01/2010 N/A N/A
Alexander Gow Fire Equipment Company 16 02/18/2019
Hose
Model Number & Size Location Install Date Hydro ScanID
Flexible .5” Main Deck Port Ready Room 08/01/2010 03/01/2009 55116668
Piping
Type & Size Location Hangers/Braces/Identified ScanID
Galvanized .5” Main Deck Port Ready Room/Paint
Locker
Normal, Normal, Normal 55116669
Carbon Dioxide Trash Room
CO2 Tank
Container Type Location Serial Number Hydro ScanID
High Pressure Main Deck Port Ready Room 7795031 05/01/2007 55116658
Gross Wt Capacity Liquid Level Value Puff Test Performed
221 75 N/A Yes
Discharge Device
Type Location ScanID
Local Cylinder Control Head Main Deck Port Ready Room 55116660
Install Date Initiator Replacement Compensator Resistance Initiator Resistance
08/01/2010 N/A N/A
Hose
Model Number & Size Location Install Date Hydro ScanID
Flexible .5” Main Deck Port Ready Room 08/01/2010 05/01/2007 55116666
Piping
Type & Size Location Hangers/Braces/Identified ScanID
Galvanized .5” Main Deck Port Ready/Trash Room Normal, Normal, Normal 55116667
Clean Agent Skiff #2405
Agent Tank
Agent Container Agent Location Serial Number Hydro ScanID
Cylinder HFC-227 Engine Compartment 20863 11/01/2015 55116640
Gross Wt Tare Wt Agent Wt Actual Wt PSI/Temp Supply Rel. Type LLV
15.2 6.6 8.6 15.4 230/45 Primary Burst
Bulb/Mechanica l
N/A
Alexander Gow Fire Equipment Company 17 02/18/2019
Carbon Dioxide Fire Suppression
Carbon Dioxide Aft Propulsion
Enclosure
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
Discharge Device Tank Top Fwd. Main Machinery
Room
Ansul Lever Operated 55116656
Hose Tank Top Fwd. Main Machinery
Room
Ansul Flexible 55116648
Piping Tank Top Fwd. Main Machinery
Room
N/A N/A 55116649
Initiating
Manual Station Tank Top Fwd. Main Machinery
Room
Ansul LT-20-L 55116645
Pressure Switch Tank Top Fwd. Main Machinery
Room
Ansul 2 Pole 55116646
Notification
Signage Tank Top Fwd. Main Machinery
N/A N/A 55116647
Alexander Gow Fire Equipment Company 18 02/18/2019
Carbon Dioxide Aux/Main
Machinery Room
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116612
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116611
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116610
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116609
Alexander Gow Fire Equipment Company 19 02/18/2019
Carbon Dioxide Auxiliary Machinery
Room
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
Cartridge 01 Level Stbd. CO2 Room Ansul Time Delay Driver 55116595
Discharge Device 01 Level Stbd. CO2 Room Ansul Lever Operated 55116608
Hose 01 Level Stbd. CO2 Room Ansul Flexible 55116628
Piping Vessel N/A N/A 55116631
Pneumatic Time Delay 01 Level Stbd. CO2 Room Ansul N2 Cartridge
Operated
55116586
Controls
Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116601
Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116599
Initiating
Manual Station Tank Top Stairwell, AMR Entrance Ansul LT-20-L 55116638
Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116592
Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116593
Notification
Pneumatic Siren Tank Top C/L Auxiliary Machinery
Room
Ansul CO2 Pressure
Operated
55116630
Signage Vessel N/A N/A 55116625
Alexander Gow Fire Equipment Company 20 02/18/2019
Carbon Dioxide Emergency
Generator Room
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116621
Discharge Device 01 Level Stbd. CO2 Room Ansul Lever Operated 55116622
Hose 01 Level Stbd. CO2 Room Ansul Flexible 55116629
Piping Vessel N/A N/A 55116635
Initiating
Manual Station 01 Level C/L Passageway, EDG
Entrance
Ansul LT-20-L 55116636
Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116588
Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116594
Notification
Pneumatic Siren 01 Level Emergency Generator
Room
Ansul CO2 Pressure
Operated
55116634
Signage Vessel N/A N/A 55116626
Alexander Gow Fire Equipment Company 21 02/18/2019
Carbon Dioxide Fwd. Propulsion
Enclosure
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
CO2 Tank Tank Top Fwd. Main Machinery
Room
Ansul CV-98 55116650
CO2 Tank Tank Top Fwd. Main Machinery
Room
Ansul CV-98 55116644
Discharge Device Tank Top Fwd. Main Machinery
Room
Ansul Lever Operated 55116655
Hose Tank Top Fwd. Main Machinery
Room
Ansul Flexible 55116651
Piping Tank Top Fwd. Main Machinery
Room
N/A N/A 55116652
Initiating
Manual Station Tank Top Fwd. Main Machinery
Room
Ansul LT-20-L 55116653
Pressure Switch Tank Top Fwd. Main Machinery
Room
Ansul 2 Pole 55116657
Notification
Signage Tank Top Fwd. Main Machinery
N/A N/A 55116654
Alexander Gow Fire Equipment Company 22 02/18/2019
Carbon Dioxide Main Machinery
Room
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
Cartridge 01 Level Stbd. CO2 Room Ansul Time Delay Driver 55116596
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116619
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116620
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116618
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116617
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116607
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116606
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116605
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116604
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116602
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116603
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116616
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116615
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116614
CO2 Tank 01 Level Stbd. CO2 Room Ansul CV-98 55116613
Discharge Device 01 Level Stbd. CO2 Room Ansul Lever Operated 55116623
Hose 01 Level Stbd. CO2 Room Ansul Flexible 55116627
Piping Vessel N/A N/A 55116633
Pneumatic Time Delay 01 Level Stbd. CO2 Room Ansul N2 Cartridge
Operated
55116587
Controls
Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116600
Valve 01 Level Stbd. CO2 Room Ansul Pressure Operated 55116598
Initiating
Manual Station Main Deck C/L Passageway, MMR
Entrance
Ansul LT-20-L 55116637
Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116589
Pressure Switch 01 Level Stbd. CO2 Room Ansul 2 Pole 55116590
Notification
Pneumatic Siren Tank Top C/L Main Machinery
Room
Ansul CO2 Pressure
Operated
55116632
Signage Vessel N/A N/A 55116624
Alexander Gow Fire Equipment Company 23 02/18/2019
Property: NOAA Bell M Shimada Carbon Dioxide Paint Locker
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
CO2 Tank Main Deck Port Ready Room Ansul CV-98 55116659
Discharge Device Main Deck Port Ready Room Ansul Lever Operated 55116661
Hose Main Deck Port Ready Room Ansul Flexible 55116668
Piping Main Deck Port Ready Room/Paint
Locker
Arrow N/A 55116669
Initiating
Manual Station Main Deck Port Deck, Paint Locker
Entrance
Ansul LT-20-L 55116296
Pressure Switch Main Deck Port Ready Room Ansul 2 Pole 55116663
Notification
Pneumatic Siren Main Deck Port Trash Room Ansul CO2 Pressure
Operated
55116671
Signage Main Deck Port Ready Room N/A N/A 55116665
Alexander Gow Fire Equipment Company 24 02/18/2019
Property: NOAA Bell M Shimada Carbon Dioxide Trash Room
Carbon dioxide is a colorless, odorless, electrically nonconductive inert gas that is a suitable medium for extinguishing fires. Liquid carbon dioxide forms solid dry ice ("snow") when released directly into the atmosphere. Carbon dioxide gas is 1.5 times heavier than air. Carbon dioxide extinguishes fire by reducing the concentrations of oxygen, the vapor phase of the fuel, or both in the air to the point where combustion stops.
Passed Device Type Location Manufacturer Model Number ScanID
Container
CO2 Tank Main Deck Port Ready Room Ansul CV-98 55116658
Discharge Device Main Deck Port Ready Room Ansul Lever Operated 55116660
Hose Main Deck Port Ready Room Ansul Flexible 55116666
Piping Main Deck Port Ready/Trash Room N/A N/A 55116667
Initiating
Manual Station Main Deck C/L Passageway, Trash
Room Entrance
Ansul LT-20-L 55116670
Pressure Switch Main Deck Port Ready Room Ansul 2 Pole 55116662
Notification
Pneumatic Siren Main Deck Port Trash Room Ansul CO2 Pressure
Operated
55116672
Signage Main Deck Port Ready Room N/A N/A 55116664
Alexander Gow Fire Equipment Company 25 02/18/2019
Clean Agent Fire Suppression
Property: NOAA Bell M Shimada Clean Agent Skiff #2405
Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. The agents were introduced in response to international restrictions on the production of certain halon fire-extinguishing agents under the Montreal Protocol signed September 16, 1987, as amended.
Passed Device Type Location Manufacturer Model Number ScanID
Container
Agent Tank Engine Compartment Fireboy MA20200227-BL 55116640
Controls
Annunciator Helm Fireboy LED 55116643
Initiating
Pull Station Helm Fireboy T-Handle 55116641
Alexander Gow Fire Equipment Company 26 02/18/2019
Gas Detection
Property: NOAA Bell M Shimada Gas H2S Detection
An agent that contains as primary components one or more of the gases helium, neon, argon, or nitrogen. Inert gas agents that are blends of gases can also contain carbon dioxide as a secondary component.
Passed Device Type Location Type Setting ScanID
Detecting
Gas Detector Battery Locker H2S 12.5% ppm 44352504
Alexander Gow Fire Equipment Company 27 02/18/2019
Kitchen System
A container of stored agent to be used in case of a fire emergency.
Kitchen Galley Fire Door
Kitchen Galley Hood
Kitchen System
Manufacturer Type Install Date Comment ScanID
Ansul Wet Chemical 08/01/2010 Passed 55116674
Hydro Date Links Qty PSI Underwriters Lab
01/01/2008 360 4 UL 300
Alexander Gow Fire Equipment Company 28 02/18/2019
Inventory & Warranty Report
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Item Category % of Inventory Quantity
Valve Controls 4.49% 4
Discharge Device Container 7.87% 7
Cartridge Container 2.25% 2
CO2 Tank Container 25.84% 23
Signage Notification 7.87% 7
Hose Container 7.87% 7
Piping Container 7.87% 7
Pneumatic Siren Notification 5.62% 5
Manual Station Initiating 7.87% 7
Pneumatic Time Delay Container 2.25% 2
Pressure Switch Initiating 11.24% 10
Agent Tank Container 1.12% 1
Pull Station Initiating 2.25% 2
Annunciator Controls 1.12% 1
Kitchen System Pre-Engineered 1.12% 1
Fire Barrier Auxiliary 2.25% 2
Gas Detector Detecting 1.12% 1
Device or Item Qty Model # Description Install Date
In Service - 5 Years to 10 Years
Carbon Dioxide Aft Propulsion Enclosure
Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010
Hose 1 Flexible 08/01/2010
Manual Station 1 LT-20-L Dual Action 08/01/2010
Pressure Switch 1 2 Pole Pressure Operated 08/01/2010
Piping 1 N/A Galvanized 08/01/2010
Signage 1 N/A Instructions, Warnings, Labels 08/01/2010
Carbon Dioxide Aux/Main Machinery Room
CO2 Tank 4 CV-98 High Pressure 08/01/2010
Carbon Dioxide Auxiliary Machinery Room
Cartridge 1 Time Delay
Driver
Nitrogen 08/01/2010
Discharge Device 1 Lever Operated Local Cylinder Control Heads 08/01/2010
Hose 1 Flexible 08/01/2010
Pneumatic Siren 1 CO2 Pressure
Operated
08/01/2010
Pneumatic Time Delay 1 N2 Cartridge
Operated
08/01/2010
Pressure Switch 2 2 Pole Pressure Operated 08/01/2010
Valve 1 Pressure Control Valve 08/01/2010
Alexander Gow Fire Equipment Company 29 02/18/2019
Device or Item Qty Model # Description Install Date
Operated
Valve 1 Pressure
Operated
Stop Valve 08/01/2010
Piping 1 N/A Galvanized 08/01/2010
Signage 1 N/A Instructions, Warnings, Labels 08/01/2010
In Service - 10 Years to 15 Years
Carbon Dioxide Auxiliary Machinery Room
Manual Station 1 LT-20-L Dual Action 01/01/2008
Carbon Dioxide Emergency Generator Room
CO2 Tank 1 CV-98 High Pressure 08/01/2010
Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010
Hose 1 Flexible 08/01/2010
Manual Station 1 LT-20-L Dual Action 08/01/2010
Pneumatic Siren 1 CO2 Pressure
Operated
08/01/2010
Pressure Switch 2 2 Pole Pressure Operated 08/01/2010
Piping 1 N/A Galvanized 08/01/2010
Signage 1 N/A Instructions, Warnings, Labels 08/01/2010
Carbon Dioxide Fwd. Propulsion Enclosure
CO2 Tank 2 CV-98 High Pressure 08/01/2010
Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010
Hose 1 Flexible 08/01/2010
Manual Station 1 LT-20-L Dual Action 08/01/2010
Pressure Switch 1 2 Pole Pressure Operated 08/01/2010
Piping 1 N/A Galvanized 08/01/2010
Signage 1 N/A Instructions, Warnings, Labels 08/01/2010
Carbon Dioxide Main Machinery Room
Cartridge 1 Time Delay
Driver
Nitrogen 08/01/2010
CO2 Tank 14 CV-98 High Pressure 08/01/2010
Discharge Device 1 Lever Operated Local Cylinder Control Heads 08/01/2010
Hose 1 Flexible 08/01/2010
Manual Station 1 LT-20-L Dual Action 08/01/2010
Pneumatic Siren 1 CO2 Pressure
Operated
08/01/2010
Pneumatic Time Delay 1 N2 Cartridge
Operated
08/01/2010
Pressure Switch 2 2 Pole Pressure Operated 08/01/2010
Valve 1 Pressure
Operated
Control Valve 08/01/2010
Valve 1 Pressure
Operated
Stop Valve 08/01/2010
Piping 1 N/A Galvanized 08/01/2010
Carbon Dioxide Paint Locker
Alexander Gow Fire Equipment Company 30 02/18/2019
CO2 Tank 1 CV-98 High Pressure 08/01/2010
Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010
Hose 1 Flexible 08/01/2010
Manual Station 1 LT-20-L Dual Action 08/01/2010
Pneumatic Siren 1 CO2 Pressure
Operated
08/01/2010
Pressure Switch 1 2 Pole Pressure Operated 08/01/2010
Piping 1 N/A Galvanized 08/01/2010
Signage 1 N/A Instructions, Warnings, Labels 08/01/2010
Carbon Dioxide Trash Room
CO2 Tank 1 CV-98 High Pressure 08/01/2010
Discharge Device 1 Lever Operated Local Cylinder Control Head 08/01/2010
Hose 1 Flexible 08/01/2010
Manual Station 1 LT-20-L Dual Action 08/01/2010
Pneumatic Siren 1 CO2 Pressure
Operated
08/01/2010
Pressure Switch 1 2 Pole Pressure Operated 08/01/2010
Piping 1 N/A Galvanized 08/01/2010
In Service - 3 Years to 5 Years
Clean Agent Skiff #2405
Agent Tank 1 MA20200227-
BL
11/01/2015
Annunciator 1 LED LED List 11/01/2015
Pull Station 1 T-Handle Dual Action 11/01/2015
In Service - 10 Years to 15 Years
Gas H2S Detection
Gas Detector 1 TXgard-IS H2S 01/01/2008
Kitchen Galley Fire Door
Fire Barrier 1 N/A Roll Down Door 08/01/2010
Kitchen Galley Hood
Kitchen System 1 R-102 Wet Chemical 08/01/2010
Pull Station 1 R-102 Single Action 08/01/2010
Fire Barrier 1 N/A Roll Down Door 08/01/2010
Alexander Gow Fire Equipment Company 31 02/18/2019
Notes & Recommendations
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the property inspection. Notes are grouped by SystemID.
Note Device Type Location Comment ScanID
Carbon Dioxide Aft Propulsion Enclosure 1 Pressure Switch Tank Top Fwd. Main Machinery Room Passed 55116646
Could Not Verify. No Power.
Carbon Dioxide Auxiliary Machinery Room 2 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116592
Secures Supply Ventilation.
3 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116593
Secures Fuel Oil Pumps.
Carbon Dioxide Emergency Generator Room 4 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116594
Secures Supply Ventilation.
5 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116588
Secures Emergency Generator.
Carbon Dioxide Fwd. Propulsion Enclosure 6 Pressure Switch Tank Top Fwd. Main Machinery Room Passed 55116657
Could Not Verify. No Power.
Carbon Dioxide Main Machinery Room 7 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116589
Could Not Verify. No Power.
8 Pressure Switch 01 Level Stbd. CO2 Room Passed 55116590
Secures Port & Stbd. Supply Ventilation.
Carbon Dioxide Paint Locker 9 Pressure Switch Main Deck Port Ready Room Passed 55116663
Secures Exhaust & Supply Ventilation.
Alexander Gow Fire Equipment Company 32 02/18/2019
Note Device Type Location Comment ScanID
Carbon Dioxide Trash Room 10 Pressure Switch Main Deck Port Ready Room Passed 55116662
Secures Exhaust Ventilation.
Clean Agent Skiff #2405 11 Agent Tank Engine Compartment Passed 55116640
Alarm Indicator Operates. Could Not Verify Engine Shut Down. No Power.
Kitchen Galley Hood 12 Kitchen System Main Deck Stbd. Galley Passed 55116674
Micro-Switch Secures Deep Fat Fryer & Operates Gaylord Fire Mode.
Kitchen Galley Scullery Fire Door 13 Fire Barrier Main Deck Stbd. Galley Defective 55116676
Fire Door Gets Jammed In The Guides. Requires Repair From Fire Door Company.
File details come from the government source that posted it.