NOAA-Bell-M-Shimada_FireScan.pdf

PDF 624 KB Posted

Attached to
NOAA Ship Bell M. Shimada Drydock Repairs Federal contract opportunity
Solicitation number
1305M219QNMAN0237
Issued by
Department of Commerce National Oceanic and Atmospheric Administration

About this file

Additional reference document

View the file

Other files for this federal contract opportunity

Other files attached to NOAA Ship Bell M. Shimada Drydock Repairs, newest first.
File Type Posted
1305M219QNMAN0237.docx DOCX document
Amendment_0005.pdf PDF
REV_Attachment_IV_-_Price_Schedule.xlsx XLSX spreadsheet
Amendment_0004.pdf PDF
Amendment_0003.pdf PDF
Amendment_0002.pdf PDF
CFR 001 Intersleek 731.pdf PDF
REV_A._Attachment_I_-_SH_FY20_5YR_Drydock_SOW.pdf PDF
CFR 132 UWB Paint QC SH Intersleek.pdf PDF
REV_A._Attachment_IV_-_Price_Schedule.xlsx XLSX spreadsheet
CFR 001 Intershield 300HS.pdf PDF
CFR 001 Intersleek 1100SR.pdf PDF
SH_640_FA27_Rev0_Sht1-8_NONE_JOINER ARRANGEMENTS PDF
Shimada Galley Cabinet Drawings.pdf PDF
Amendment_0001.pdf PDF
NOAA-Bell-M-Shimada_SafetyScan.pdf PDF
Bell M Shimada NOAA Functional Tests.pdf PDF
Bell M Shimada Hose Hydro Testing Report.pdf PDF
NOAA-Bell-M-Shimada_SuppressionScan.pdf PDF
20190803_130551.jpg JPG image
SH-655-FZ03-Food Services Arrangement.pdf PDF
20190803_130608.jpg JPG image
Attachment_IV_-_Price_Schedule.xlsx XLSX spreadsheet
Reference_Documents.zip ZIP file
Attachment_III_-_Past_Performance_Questionnaire.docx DOCX document
Attachment_I_-_SH_FY20_5YR_Drydock_SOW.pdf PDF
Attachment_II_-_Past_Performance_Information_Form.xlsx XLSX spreadsheet
1305M219QNMAN0237.pdf PDF
SYNOPSIS.rtf RTF text file
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CERTIFICATE OF INSPECTION

For

NOAA Bell M Shimada Dec 5, 2018

Fire Alarm and Life Safety System

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Customer: Certified By:

NOAA Bell M Shimada Alexander Gow Fire Equipment

Company

2002 SE Marine Science Drive 1436 NW 53rd Street

Newport, OR 97365 Seattle, Washington 98107

Contact: Scott A. Tuttle Contact: Phil Cross

Title: Port Engineer Title: Marine Fire Alarm Technician

206-632-2810 www.gowfire.com

Alexander Gow Fire Equipment Company 1 02/18/2019

Executive Summary Generated by: BuildingReports.com

Property Information

Property: NOAA Bell M Shimada Contact: Scott A. Tuttle

Address: 2002 SE Marine Science Drive Phone: 541-867-8763

Address: Fax:

City/State/Zip: Newport, OR 97365 Mobile: 251-583-8824

Country: United States of America Email: Scott.Tuttle@ecstech.com

Inspection Performed By

Company: Alexander Gow Fire Equipment Company Inspector: Phil Cross

Address: 1436 NW 53rd Street Phone: 2066322810

Address: Fax:

City/State/Zip: Seattle, Washington 98107 Mobile:

Country: United States of America Email: pcross@gowfire.com

System Control Unit Manufacturer: Notifier Inspection Date: 12/05/2018 IDC Style: B

Model Number: AFP-200 Install Date: 03/01/2014 SLC Style: 2

Software Version: Version Date: 03/01/2005 NAC Style: Y

Location: Wheel House Mid, C/L Current Protection: Breaker

Monitoring Type: Mfg: Model #:

Test Time/Date: Restore Time:

Inspection Summary

Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Control 4 4.04% 4 100.00% 4 100.00% 0 0%

Initiating 93 93.94% 93 100.00% 93 100.00% 0 0%

Indicating 2 2.02% 2 100.00% 2 100.00% 0 0%

Totals 99 100% 99 100.00

100.00

0 0%

Certification

Company: Alexander Gow Fire Equipment Company Building: NOAA Bell M Shimada

Inspector: Phil Cross Contact: Scott A. Tuttle

Signed: Dec 5, 2018 9:54:48 AM Signed: Dec 5, 2018 9:55:04 AM

Alexander Gow Fire Equipment Company 2 02/18/2019

Inspection & Testing

Property: NOAA Bell M Shimada Control Panel: 1 - Notifier AFP-200

The Inspection & Testing section lists all of the items inspected in your property. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed

Control

Annunciator 2nd Deck Stbd Control Room Tested 8:55:41 AM 12/05/2018

Battery Wheel House In FACP New Battery 1:45:35 PM 12/04/2018

Battery Wheel House In FACP New Battery 1:47:30 PM 12/04/2018

Control Panel Wheel House Mid, C/L Tested 9:46:34 AM 12/05/2018

Indicating

Bell Wheel House Mid, C/L Tested 7:15:47 AM 12/05/2018

Horn/Strobe Mast Tested 9:53:48 AM 12/05/2018

Initiating

Heat Detector 01 Level ET Shop Tested 7:44:34 AM 12/05/2018

Heat Detector 01 Level Fan Room Above DB Panels Tested 7:46:04 AM 12/05/2018

Heat Detector 01 Level Aft Emergency Generator Room Tested 9:12:42 AM 12/05/2018

Heat Detector 01 Level Fwd DC Locker Room SCBA Room Tested 7:57:23 AM 12/05/2018

Heat Detector 01 Level Port, Fwd Reefer Machinery Room Tested 8:06:28 AM 12/05/2018

Heat Detector 01 Level Stbd, Fwd Dive Locker Room Tested 7:52:35 AM 12/05/2018

Heat Detector 01 Level Stbd, Fwd DK Locker Room Tested 7:55:56 AM 12/05/2018

Heat Detector 02 Level Aft Exterior DC Locker Room SCBA

Room

Tested 7:35:42 AM 12/05/2018

Heat Detector 2nd Deck Aft, Stbd Trawl Winch Room Tested 9:07:21 AM 12/05/2018

Heat Detector 2nd Deck C/L Main Machinery Room Tested 3:39:34 PM 12/04/2018

Heat Detector 2nd Deck Fwd Laundry Room Tested 3:14:43 PM 12/04/2018

Heat Detector 2nd Deck Fwd, Port Trawl Winch Room Tested 9:10:37 AM 12/05/2018

Heat Detector 2nd Deck Fwd, Stbd Trawl Winch Room Tested 9:05:45 AM 12/05/2018

Heat Detector 2nd Deck Port Main Machinery Room Tested 3:36:33 PM 12/04/2018

Heat Detector 2nd Deck Port, Aft Trawl Winch Room Tested 9:08:32 AM 12/05/2018

Heat Detector 2nd Deck Stbd Main Machinery Room Tested 3:38:15 PM 12/04/2018

Heat Detector Hold Deck Bow Thruster Room Tested 3:08:29 PM 12/04/2018

Heat Detector Hold Deck Aft, C/L Engine Room Tested 2:57:29 PM 12/04/2018

Heat Detector Hold Deck Fwd, C/L Engine Room Tested 3:00:56 PM 12/04/2018

Heat Detector Hold Deck Fwd, Stbd Engine Room Tested 2:59:46 PM 12/04/2018

Heat Detector Hold Deck Port, Fwd Engine Room Tested 3:05:07 PM 12/04/2018

Heat Detector Main Deck Chemical Laboratory Tested 8:21:42 AM 12/05/2018

Heat Detector Main Deck Deck Locker Tested 8:08:44 AM 12/05/2018

Heat Detector Main Deck Fan Room Tested 8:40:59 AM 12/05/2018

Heat Detector Main Deck Fwd Scientific Stores Tested 8:43:08 AM 12/05/2018

Heat Detector Main Deck Hydrographic Laboratory Tested 8:31:31 AM 12/05/2018

Heat Detector Main Deck Aft Fish Wet Laboratory Tested 8:18:20 AM 12/05/2018

Heat Detector Main Deck Aft Galley Tested 8:35:46 AM 12/05/2018

Alexander Gow Fire Equipment Company 3 02/18/2019

Heat Detector Main Deck Fwd Fish Wet Laboratory Tested 8:19:01 AM 12/05/2018

Heat Detector Main Deck Fwd Galley Tested 8:36:59 AM 12/05/2018

Heat Detector Main Deck Fwd, Port Fish Wet Laboratory Tested 8:20:16 AM 12/05/2018

Pull Station 01 Level Aft Passageway Tested 7:40:46 AM 12/05/2018

Pull Station 01 Level Fwd Passageway Tested 7:56:23 AM 12/05/2018

Pull Station 02 Level Aft Passageway Tested 7:33:16 AM 12/05/2018

Pull Station 02 Level Stbd, Fwd Passageway Tested 7:33:01 AM 12/05/2018

Pull Station 2nd Deck Exercise Room Tested 8:52:04 AM 12/05/2018

Pull Station 2nd Deck Fwd Crew Quarters Passageway Tested 3:28:23 PM 12/04/2018

Pull Station 2nd Deck Fwd Scientific Stores Tested 3:15:52 PM 12/04/2018

Pull Station 2nd Deck Port Oceanographic Winch

Room/Bosuns Stores

Tested 8:59:34 AM 12/05/2018

Pull Station 2nd Deck Port, Fwd Crew Quarters Passageway Tested 3:28:11 PM 12/04/2018

Pull Station Hold Deck Domestic Equipment Room Tested 2:47:36 PM 12/04/2018

Pull Station Hold Deck Engineers Workshop Tested 2:54:04 PM 12/04/2018

Pull Station Hold Deck Port, Fwd Engine Room Tested 2:55:50 PM 12/04/2018

Pull Station Main Deck Aft Fish Wet Laboratory Tested 8:16:58 AM 12/05/2018

Pull Station Main Deck Aft Passageway Tested 8:15:00 AM 12/05/2018

Pull Station Main Deck Fwd Passageway Tested 8:29:15 AM 12/05/2018

Pull Station Main Deck Fwd Stairwell Tested 8:44:24 AM 12/05/2018

Pull Station Main Deck Mid, Aft Passageway Tested 8:26:01 AM 12/05/2018

Pull Station Main Deck Mid, Stbd Passageway Tested 8:31:00 AM 12/05/2018

Pull Station Wheel House Stbd, Aft Tested 2:17:54 PM 12/04/2018

Smoke Detector 01 Level Lounge Area Tested 7:49:39 AM 12/05/2018

Smoke Detector 01 Level Ship's Office Tested 7:42:59 AM 12/05/2018

Smoke Detector 01 Level Aft Passageway Tested 7:47:26 AM 12/05/2018

Smoke Detector 01 Level Aft Stairwell Tested 7:37:56 AM 12/05/2018

Smoke Detector 01 Level Fwd Passageway Tested 9:26:31 AM 12/05/2018

Smoke Detector 02 Level Hospital Tested 7:32:01 AM 12/05/2018

Smoke Detector 02 Level Aft Passageway Tested 7:27:58 AM 12/05/2018

Smoke Detector 02 Level Stbd, Fwd Passageway Tested 7:26:21 AM 12/05/2018

Smoke Detector 2nd Deck Exercise Room Tested 3:21:39 PM 12/04/2018

Smoke Detector 2nd Deck C/L Control Room Tested 8:56:41 AM 12/05/2018

Smoke Detector 2nd Deck Fwd Crew Quarters Passageway Tested 3:23:43 PM 12/04/2018

Smoke Detector 2nd Deck Fwd Scientific Stores Tested 3:17:49 PM 12/04/2018

Smoke Detector 2nd Deck Fwd, Port Crew Quarters Passageway Tested 3:29:35 PM 12/04/2018

Smoke Detector 2nd Deck Fwd, Stbd Crew Quarters Passageway Tested 3:24:50 PM 12/04/2018

Smoke Detector 2nd Deck Port Control Room Tested 8:57:51 AM 12/05/2018

Smoke Detector 2nd Deck Port Control Room Tested 8:59:03 AM 12/05/2018

Smoke Detector 2nd Deck Port Oceanographic Winch

Room/Bosuns Stores

Tested 9:01:27 AM 12/05/2018

Smoke Detector 2nd Deck Port, Fwd Crew Quarters Passageway Tested 3:26:05 PM 12/04/2018

Smoke Detector 2nd Deck Stbd Control Room Tested 8:55:34 AM 12/05/2018

Smoke Detector 2nd Deck Stbd Crew Quarters Passageway Tested 3:30:37 PM 12/04/2018

Smoke Detector 2nd Deck Stbd Oceanographic Winch

Room/Bosuns Stores

Tested 9:03:33 AM 12/05/2018

Smoke Detector Hold Deck Transducer Room Tested 9:21:26 AM 12/05/2018

Smoke Detector Hold Deck Aft General Stores Tested 2:49:23 PM 12/04/2018

Smoke Detector Hold Deck Aft, Port MSD/Domestic Equipment

Room

Tested 2:47:50 PM 12/04/2018

Smoke Detector Hold Deck Fwd General Stores Tested 2:49:41 PM 12/04/2018

Smoke Detector Hold Deck Fwd, Stbd MSD/Domestic Equipment Tested 2:50:55 PM 12/04/2018

Alexander Gow Fire Equipment Company 4 02/18/2019

Room

Smoke Detector Hold Deck Port Engineers Workshop Tested 2:53:53 PM 12/04/2018

Smoke Detector Hold Deck Stbd Engineers Workshop Tested 8:53:17 AM 12/05/2018

Smoke Detector Main Deck Dry Laboratory Tested 8:32:49 AM 12/05/2018

Smoke Detector Main Deck Fwd Dry Stores Tested 8:46:07 AM 12/05/2018

Smoke Detector Main Deck Fwd Passageway Tested 8:39:25 AM 12/05/2018

Smoke Detector Main Deck Ready Room Tested 8:10:37 AM 12/05/2018

Smoke Detector Main Deck Trash Room Tested 8:12:51 AM 12/05/2018

Smoke Detector Main Deck Aft Acoustic Laboratory Tested 8:27:10 AM 12/05/2018

Smoke Detector Main Deck Aft Crew Mess Tested 8:50:09 AM 12/05/2018

Smoke Detector Main Deck Aft Passageway Tested 8:22:33 AM 12/05/2018

Smoke Detector Main Deck Fwd Acoustic Laboratory Tested 8:27:56 AM 12/05/2018

Smoke Detector Main Deck Fwd Crew Mess Tested 8:49:15 AM 12/05/2018

Smoke Detector Main Deck Fwd Stairwell Tested 8:47:45 AM 12/05/2018

Smoke Detector Wheel House Port, Aft Tested 7:16:15 AM 12/05/2018

Smoke Detector Wheel House Port, Fwd Tested 7:15:28 AM 12/05/2018

Smoke Detector Wheel House Stbd, Aft Tested 7:08:24 AM 12/05/2018

Smoke Detector Wheel House Stbd, Fwd Tested 7:09:38 AM 12/05/2018

Alexander Gow Fire Equipment Company 5 02/18/2019

Service Summary

Building: NOAA Bell M Shimada

The Service Summary section provides an overview of the services performed in this report.

No devices were found for this section of the report.

Alexander Gow Fire Equipment Company 6 02/18/2019

Auxiliary Functions Testing

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed

Heat Detector

Combination 135°F 01 Level ET Shop Passed 50558006

Combination 135°F 01 Level Fan Room Above DB Panels Passed 50558007

Fixed Temperature

190°F

01 Level Aft Emergency Generator Room Passed 50558008

Combination 135°F 01 Level Fwd DC Locker Room SCBA Room Passed 50558014

Combination 135°F 01 Level Port, Fwd Reefer Machinery Room Passed 50558013

Combination 135°F 01 Level Stbd, Fwd Dive Locker Room Passed 50558016

Combination 135°F 01 Level Stbd, Fwd DK Locker Room Passed 50558015

Combination 135°F 02 Level Aft Exterior DC Locker Room SCBA

Room

Passed 50558003

Combination 135°F 2nd Deck Aft, Stbd Trawl Winch Room Passed 50558057

Fixed Temperature

190°F

2nd Deck C/L Main Machinery Room Passed 50558047

Combination 135°F 2nd Deck Fwd Laundry Room Passed 50558071

Combination 135°F 2nd Deck Fwd, Port Trawl Winch Room Passed 50558056

Combination 135°F 2nd Deck Fwd, Stbd Trawl Winch Room Passed 50558058

Fixed Temperature

190°F

2nd Deck Port Main Machinery Room Passed 50558045

Combination 135°F 2nd Deck Port, Aft Trawl Winch Room Passed 50558059

Fixed Temperature

190°F

2nd Deck Stbd Main Machinery Room Passed 50558046

Fixed Temperature

190°F

Hold Deck Bow Thruster Room Passed 50558086

Fixed Temperature

190°F

Hold Deck Aft, C/L Engine Room Passed 50558076

Fixed Temperature

190°F

Hold Deck Fwd, C/L Engine Room Passed 50558079

Fixed Temperature

190°F

Hold Deck Fwd, Stbd Engine Room Passed 50558077

Fixed Temperature

190°F

Hold Deck Port, Fwd Engine Room Passed 50558078

Combination 135°F Main Deck Chemical Laboratory Passed 50558028

Combination 135°F Main Deck Deck Locker Passed 50558021

Fixed Temperature

190°F

Main Deck Fan Room Passed 50558041

Combination 135°F Main Deck Fwd Scientific Stores Passed 50558043

Combination 135°F Main Deck Hydrographic Laboratory Passed 50558031

Combination 135°F Main Deck Aft Fish Wet Laboratory Passed 50558023

Fixed Temperature Main Deck Aft Galley Passed 50558037

Alexander Gow Fire Equipment Company 7 02/18/2019

190°F

Combination 135°F Main Deck Fwd Fish Wet Laboratory Passed 50558022

Fixed Temperature

190°F

Main Deck Fwd Galley Passed 50558038

Combination 135°F Main Deck Fwd, Port Fish Wet Laboratory Passed 50558025

Smoke Detector

Photoelectric 01 Level Lounge Area Passed 50558011

Photoelectric 01 Level Ship's Office Passed 50558009

Photoelectric 01 Level Aft Passageway Passed 50558010

Photoelectric 01 Level Aft Stairwell Passed 50558004

Photoelectric 01 Level Fwd Passageway Passed 50558090

Photoelectric 02 Level Hospital Passed 50558001

Photoelectric 02 Level Aft Passageway Passed 50558002

Photoelectric 02 Level Stbd, Fwd Passageway Passed 50557996

Photoelectric 2nd Deck Exercise Room Passed 50558067

Photoelectric 2nd Deck C/L Control Room Passed 50558049

Photoelectric 2nd Deck Fwd Crew Quarters Passageway Passed 50558065

Photoelectric 2nd Deck Fwd Scientific Stores Passed 50558069

Photoelectric 2nd Deck Fwd, Port Crew Quarters

Passageway

Passed 50558062

Photoelectric 2nd Deck Fwd, Stbd Crew Quarters

Passageway

Passed 50558066

Photoelectric 2nd Deck Port Control Room Passed 50558050

Photoelectric 2nd Deck Port Control Room Passed 50558051

Photoelectric 2nd Deck Port Oceanographic Winch

Room/Bosuns Stores

Passed 50558053

Photoelectric 2nd Deck Port, Fwd Crew Quarters

Passageway

Passed 50558064

Photoelectric 2nd Deck Stbd Control Room Passed 50558048

Photoelectric 2nd Deck Stbd Crew Quarters Passageway Passed 50558061

Photoelectric 2nd Deck Stbd Oceanographic Winch

Room/Bosuns Stores

Passed 50558054

Photoelectric Hold Deck Transducer Room Passed 50558085

Photoelectric Hold Deck Aft General Stores Passed 50558082

Photoelectric Hold Deck Aft, Port MSD/Domestic Equipment

Room

Passed 50558084

Photoelectric Hold Deck Fwd General Stores Passed 50558083

Photoelectric Hold Deck Fwd, Stbd MSD/Domestic

Equipment Room

Passed 50558080

Photoelectric Hold Deck Port Engineers Workshop Passed 50558072

Photoelectric Hold Deck Stbd Engineers Workshop Passed 50558073

Photoelectric Main Deck Dry Laboratory Passed 50558032

Photoelectric Main Deck Fwd Dry Stores Passed 50558042

Photoelectric Main Deck Fwd Passageway Passed 50558044

Photoelectric Main Deck Ready Room Passed 50558020

Photoelectric Main Deck Trash Room Passed 50558019

Photoelectric Main Deck Aft Acoustic Laboratory Passed 50558027

Photoelectric Main Deck Aft Crew Mess Passed 50558036

Photoelectric Main Deck Aft Passageway Passed 50558026

Photoelectric Main Deck Fwd Acoustic Laboratory Passed 50558033

Photoelectric Main Deck Fwd Crew Mess Passed 50558035

Photoelectric Main Deck Fwd Stairwell Passed 50558039

Photoelectric Wheel House Port, Aft Passed 50557995

Alexander Gow Fire Equipment Company 8 02/18/2019

Photoelectric Wheel House Port, Fwd Passed 50557997

Photoelectric Wheel House Stbd, Aft Passed 50557993

Photoelectric Wheel House Stbd, Fwd Passed 50557994

Alexander Gow Fire Equipment Company 9 02/18/2019

Battery & Power Supply Testing

The Control & Power Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Comment Amps Volts

Pre

Test

Post

Test

Passed

Battery

Sealed Lead Acid Wheel House In FACP Passed 8.0 12.0 N/A N/A

Sealed Lead Acid Wheel House In FACP Passed 8.0 12.0 N/A N/A

Alexander Gow Fire Equipment Company 10 02/18/2019

Inventory & Warranty Report

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Item Category % of Inventory Quantity

Battery Control 2.02% 2

Pull Station Initiating 19.19% 19

Smoke Detector Initiating 43.43% 43

Heat Detector Initiating 31.31% 31

Bell Indicating 1.01% 1

Annunciator Control 1.01% 1

Control Panel Control 1.01% 1

Horn/Strobe Indicating 1.01% 1

Type Qty Model # Description Install Date

New (under 90 days)

Interstate Batteries

Battery 2 SLA1075 Sealed Lead Acid 01/01/2019

In Service - 3 Years to 5 Years

Notifier

Annunciator 1 LCD-80 LCD Display 03/01/2014

Control Panel 1 AFP-200 03/01/2014

Heat Detector 12 FST-851H Fixed Temperature 190°F 03/01/2014

Heat Detector 19 FST-851R Combination 135°F 03/01/2014

Horn/Strobe 1 03/01/2014

Pull Station 19 NBG-12LX Dual Action 03/01/2014

Smoke Detector 43 FSP-851 Photoelectric 03/01/2014

Wheelock

Bell 1 6 inch 03/01/2014

Alexander Gow Fire Equipment Company 11 02/18/2019

Zone Address Report

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Description ScanID

37 Heat Detector Main Deck Deck Locker Combination 135°F 50558021

61 Heat Detector Main Deck Fwd Scientific Stores Combination 135°F 50558043

D Smoke Detector 01 Level Aft Passageway Photoelectric 50558010

D Heat Detector Main Deck Fan Room Fixed Temperature

190°F

50558041

D02 Heat Detector Hold Deck Aft, C/L Engine Room Fixed Temperature

190°F

50558076

D04 Heat Detector Hold Deck Fwd, Stbd Engine Room Fixed Temperature

190°F

50558077

D05 Heat Detector Hold Deck Fwd, C/L Engine Room Fixed Temperature

190°F

50558079

D06 Heat Detector Hold Deck Port, Fwd Engine Room Fixed Temperature

190°F

50558078

D07 Smoke Detector Hold Deck Port Engineers Workshop Photoelectric 50558072

D08 Smoke Detector Hold Deck Stbd Engineers Workshop Photoelectric 50558073

D09 Smoke Detector Hold Deck Aft General Stores Photoelectric 50558082

D10 Smoke Detector Hold Deck Fwd General Stores Photoelectric 50558083

D11 Smoke Detector Hold Deck Fwd, Stbd MSD/Domestic

Equipment Room

Photoelectric 50558080

D12 Smoke Detector Hold Deck Aft, Port MSD/Domestic

Equipment Room

Photoelectric 50558084

D13 Smoke Detector Hold Deck Transducer Room Photoelectric 50558085

D14 Heat Detector Hold Deck Bow Thruster Room Fixed Temperature

190°F

50558086

D15 Heat Detector 2nd Deck Aft, Stbd Trawl Winch Room Combination 135°F 50558057

D16 Heat Detector 2nd Deck Port, Aft Trawl Winch Room Combination 135°F 50558059

D17 Heat Detector 2nd Deck Fwd, Stbd Trawl Winch Room Combination 135°F 50558058

D18 Heat Detector 2nd Deck Fwd, Port Trawl Winch Room Combination 135°F 50558056

D19 Smoke Detector 2nd Deck Stbd Oceanographic Winch

Room/Bosuns Stores

Photoelectric 50558054

D20 Smoke Detector 2nd Deck Port Oceanographic Winch

Room/Bosuns Stores

Photoelectric 50558053

D21 Smoke Detector 2nd Deck Port Control Room Photoelectric 50558050

D22 Smoke Detector 2nd Deck Stbd Control Room Photoelectric 50558048

D23 Smoke Detector 2nd Deck Port Control Room Photoelectric 50558051

D24 Smoke Detector 2nd Deck C/L Control Room Photoelectric 50558049

D26 Heat Detector 2nd Deck C/L Main Machinery Room Fixed Temperature

190°F

50558047

D27 Heat Detector 2nd Deck Stbd Main Machinery Room Fixed Temperature

190°F

50558046

D28 Heat Detector 2nd Deck Port Main Machinery Room Fixed Temperature

190°F

50558045

Alexander Gow Fire Equipment Company 12 02/18/2019

D29 Smoke Detector 2nd Deck Stbd Crew Quarters

Passageway

Photoelectric 50558061

D30 Smoke Detector 2nd Deck Fwd, Port Crew Quarters

Passageway

Photoelectric 50558062

D31 Smoke Detector 2nd Deck Port, Fwd Crew Quarters

Passageway

Photoelectric 50558064

D32 Smoke Detector 2nd Deck Fwd, Stbd Crew Quarters

Passageway

Photoelectric 50558066

D33 Smoke Detector 2nd Deck Fwd Crew Quarters

Passageway

Photoelectric 50558065

D34 Smoke Detector 2nd Deck Exercise Room Photoelectric 50558067

D35 Heat Detector 2nd Deck Fwd Laundry Room Combination 135°F 50558071

D36 Smoke Detector 2nd Deck Fwd Scientific Stores Photoelectric 50558069

D39 Heat Detector Main Deck Aft Fish Wet Laboratory Combination 135°F 50558023

D40 Smoke Detector Main Deck Ready Room Photoelectric 50558020

D41 Smoke Detector Main Deck Aft Passageway Photoelectric 50558026

D42 Smoke Detector Main Deck Trash Room Photoelectric 50558019

D43 Heat Detector Main Deck Fwd, Port Fish Wet Laboratory Combination 135°F 50558025

D46 Smoke Detector Main Deck Aft Acoustic Laboratory Photoelectric 50558027

D47 Heat Detector Main Deck Chemical Laboratory Combination 135°F 50558028

D49 Smoke Detector Main Deck Fwd Acoustic Laboratory Photoelectric 50558033

D51 Heat Detector Main Deck Hydrographic Laboratory Combination 135°F 50558031

D52 Smoke Detector Main Deck Dry Laboratory Photoelectric 50558032

D53 Smoke Detector Main Deck Aft Crew Mess Photoelectric 50558036

D54 Heat Detector Main Deck Aft Galley Fixed Temperature

190°F

50558037

D55 Smoke Detector Main Deck Fwd Crew Mess Photoelectric 50558035

D56 Heat Detector Main Deck Fwd Galley Fixed Temperature

190°F

50558038

D57 Smoke Detector Main Deck Fwd Stairwell Photoelectric 50558039

D59 Smoke Detector Main Deck Fwd Dry Stores Photoelectric 50558042

D60 Smoke Detector Main Deck Fwd Passageway Photoelectric 50558044

D62 Heat Detector 01 Level Aft Emergency Generator Room Fixed Temperature

190°F

50558008

D63 Smoke Detector 01 Level Aft Stairwell Photoelectric 50558004

D64 Heat Detector 01 Level ET Shop Combination 135°F 50558006

D65 Smoke Detector 01 Level Ship's Office Photoelectric 50558009

D67 Heat Detector 01 Level Fan Room Above DB Panels Combination 135°F 50558007

D69 Smoke Detector 01 Level Lounge Area Photoelectric 50558011

D70 Smoke Detector 01 Level Fwd Passageway Photoelectric 50558090

D73 Heat Detector 01 Level Stbd, Fwd DK Locker Room Combination 135°F 50558015

D74 Heat Detector 01 Level Stbd, Fwd Dive Locker Room Combination 135°F 50558016

D75 Heat Detector 01 Level Port, Fwd Reefer Machinery

Room

Combination 135°F 50558013

D76 Heat Detector 01 Level Fwd DC Locker Room SCBA

Room

Combination 135°F 50558014

D77 Heat Detector 02 Level Aft Exterior DC Locker Room

SCBA Room

Combination 135°F 50558003

D78 Smoke Detector 02 Level Hospital Photoelectric 50558001

D79 Smoke Detector 02 Level Aft Passageway Photoelectric 50558002

D80 Smoke Detector 02 Level Stbd, Fwd Passageway Photoelectric 50557996

D81 Smoke Detector Wheel House Port, Aft Photoelectric 50557995

D82 Smoke Detector Wheel House Stbd, Aft Photoelectric 50557993

Alexander Gow Fire Equipment Company 13 02/18/2019

D83 Smoke Detector Wheel House Stbd, Fwd Photoelectric 50557994

D84 Smoke Detector Wheel House Port, Fwd Photoelectric 50557997

M02 Pull Station Hold Deck Port, Fwd Engine Room Dual Action 50558075

M03 Pull Station Hold Deck Engineers Workshop Dual Action 50558074

M04 Pull Station Hold Deck Domestic Equipment Room Dual Action 50558081

M05 Pull Station 2nd Deck Port Oceanographic Winch

Room/Bosuns Stores

Dual Action 50558055

M06 Pull Station 2nd Deck Fwd Crew Quarters

Passageway

Dual Action 50558060

M07 Pull Station 2nd Deck Port, Fwd Crew Quarters

Passageway

Dual Action 50558063

M08 Pull Station 2nd Deck Exercise Room Dual Action 50558068

M09 Pull Station 2nd Deck Fwd Scientific Stores Dual Action 50558070

M10 Pull Station Main Deck Aft Passageway Dual Action 50558018

M11 Pull Station Main Deck Mid, Aft Passageway Dual Action 50558029

M12 Pull Station Main Deck Mid, Stbd Passageway Dual Action 50558030

M13 Pull Station Main Deck Fwd Passageway Dual Action 50558034

M14 Pull Station Main Deck Fwd Stairwell Dual Action 50558040

M15 Pull Station 01 Level Aft Passageway Dual Action 50558005

M16 Pull Station 02 Level Aft Passageway Dual Action 50557999

M17 Pull Station 02 Level Stbd, Fwd Passageway Dual Action 50558000

M18 Pull Station Wheel House Stbd, Aft Dual Action 50558017

M19 Pull Station 01 Level Fwd Passageway Dual Action 50558012

M20 Pull Station Main Deck Aft Fish Wet Laboratory Dual Action 50558024

M44 Heat Detector Main Deck Fwd Fish Wet Laboratory Combination 135°F 50558022

Zone/Circuit: NAC

Horn/Strobe Mast 50558094

Bell Wheel House Mid, C/L 50557998