CERTIFICATE OF INSPECTION
For
NOAA Bell M Shimada Dec 5, 2018
Fire Alarm and Life Safety System
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Customer: Certified By:
NOAA Bell M Shimada Alexander Gow Fire Equipment
Company
2002 SE Marine Science Drive 1436 NW 53rd Street
Newport, OR 97365 Seattle, Washington 98107
Contact: Scott A. Tuttle Contact: Phil Cross
Title: Port Engineer Title: Marine Fire Alarm Technician
206-632-2810 www.gowfire.com
Alexander Gow Fire Equipment Company 1 02/18/2019
Executive Summary Generated by: BuildingReports.com
Property Information
Property: NOAA Bell M Shimada Contact: Scott A. Tuttle
Address: 2002 SE Marine Science Drive Phone: 541-867-8763
Address: Fax:
City/State/Zip: Newport, OR 97365 Mobile: 251-583-8824
Country: United States of America Email: Scott.Tuttle@ecstech.com
Inspection Performed By
Company: Alexander Gow Fire Equipment Company Inspector: Phil Cross
Address: 1436 NW 53rd Street Phone: 2066322810
Address: Fax:
City/State/Zip: Seattle, Washington 98107 Mobile:
Country: United States of America Email: pcross@gowfire.com
System Control Unit Manufacturer: Notifier Inspection Date: 12/05/2018 IDC Style: B
Model Number: AFP-200 Install Date: 03/01/2014 SLC Style: 2
Software Version: Version Date: 03/01/2005 NAC Style: Y
Location: Wheel House Mid, C/L Current Protection: Breaker
Monitoring Type: Mfg: Model #:
Test Time/Date: Restore Time:
Inspection Summary
Category Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Control 4 4.04% 4 100.00% 4 100.00% 0 0%
Initiating 93 93.94% 93 100.00% 93 100.00% 0 0%
Indicating 2 2.02% 2 100.00% 2 100.00% 0 0%
Totals 99 100% 99 100.00
100.00
0 0%
Certification
Company: Alexander Gow Fire Equipment Company Building: NOAA Bell M Shimada
Inspector: Phil Cross Contact: Scott A. Tuttle
Signed: Dec 5, 2018 9:54:48 AM Signed: Dec 5, 2018 9:55:04 AM
Alexander Gow Fire Equipment Company 2 02/18/2019
Inspection & Testing
Property: NOAA Bell M Shimada Control Panel: 1 - Notifier AFP-200
The Inspection & Testing section lists all of the items inspected in your property. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Passed
Control
Annunciator 2nd Deck Stbd Control Room Tested 8:55:41 AM 12/05/2018
Battery Wheel House In FACP New Battery 1:45:35 PM 12/04/2018
Battery Wheel House In FACP New Battery 1:47:30 PM 12/04/2018
Control Panel Wheel House Mid, C/L Tested 9:46:34 AM 12/05/2018
Indicating
Bell Wheel House Mid, C/L Tested 7:15:47 AM 12/05/2018
Horn/Strobe Mast Tested 9:53:48 AM 12/05/2018
Initiating
Heat Detector 01 Level ET Shop Tested 7:44:34 AM 12/05/2018
Heat Detector 01 Level Fan Room Above DB Panels Tested 7:46:04 AM 12/05/2018
Heat Detector 01 Level Aft Emergency Generator Room Tested 9:12:42 AM 12/05/2018
Heat Detector 01 Level Fwd DC Locker Room SCBA Room Tested 7:57:23 AM 12/05/2018
Heat Detector 01 Level Port, Fwd Reefer Machinery Room Tested 8:06:28 AM 12/05/2018
Heat Detector 01 Level Stbd, Fwd Dive Locker Room Tested 7:52:35 AM 12/05/2018
Heat Detector 01 Level Stbd, Fwd DK Locker Room Tested 7:55:56 AM 12/05/2018
Heat Detector 02 Level Aft Exterior DC Locker Room SCBA
Room
Tested 7:35:42 AM 12/05/2018
Heat Detector 2nd Deck Aft, Stbd Trawl Winch Room Tested 9:07:21 AM 12/05/2018
Heat Detector 2nd Deck C/L Main Machinery Room Tested 3:39:34 PM 12/04/2018
Heat Detector 2nd Deck Fwd Laundry Room Tested 3:14:43 PM 12/04/2018
Heat Detector 2nd Deck Fwd, Port Trawl Winch Room Tested 9:10:37 AM 12/05/2018
Heat Detector 2nd Deck Fwd, Stbd Trawl Winch Room Tested 9:05:45 AM 12/05/2018
Heat Detector 2nd Deck Port Main Machinery Room Tested 3:36:33 PM 12/04/2018
Heat Detector 2nd Deck Port, Aft Trawl Winch Room Tested 9:08:32 AM 12/05/2018
Heat Detector 2nd Deck Stbd Main Machinery Room Tested 3:38:15 PM 12/04/2018
Heat Detector Hold Deck Bow Thruster Room Tested 3:08:29 PM 12/04/2018
Heat Detector Hold Deck Aft, C/L Engine Room Tested 2:57:29 PM 12/04/2018
Heat Detector Hold Deck Fwd, C/L Engine Room Tested 3:00:56 PM 12/04/2018
Heat Detector Hold Deck Fwd, Stbd Engine Room Tested 2:59:46 PM 12/04/2018
Heat Detector Hold Deck Port, Fwd Engine Room Tested 3:05:07 PM 12/04/2018
Heat Detector Main Deck Chemical Laboratory Tested 8:21:42 AM 12/05/2018
Heat Detector Main Deck Deck Locker Tested 8:08:44 AM 12/05/2018
Heat Detector Main Deck Fan Room Tested 8:40:59 AM 12/05/2018
Heat Detector Main Deck Fwd Scientific Stores Tested 8:43:08 AM 12/05/2018
Heat Detector Main Deck Hydrographic Laboratory Tested 8:31:31 AM 12/05/2018
Heat Detector Main Deck Aft Fish Wet Laboratory Tested 8:18:20 AM 12/05/2018
Heat Detector Main Deck Aft Galley Tested 8:35:46 AM 12/05/2018
Alexander Gow Fire Equipment Company 3 02/18/2019
Heat Detector Main Deck Fwd Fish Wet Laboratory Tested 8:19:01 AM 12/05/2018
Heat Detector Main Deck Fwd Galley Tested 8:36:59 AM 12/05/2018
Heat Detector Main Deck Fwd, Port Fish Wet Laboratory Tested 8:20:16 AM 12/05/2018
Pull Station 01 Level Aft Passageway Tested 7:40:46 AM 12/05/2018
Pull Station 01 Level Fwd Passageway Tested 7:56:23 AM 12/05/2018
Pull Station 02 Level Aft Passageway Tested 7:33:16 AM 12/05/2018
Pull Station 02 Level Stbd, Fwd Passageway Tested 7:33:01 AM 12/05/2018
Pull Station 2nd Deck Exercise Room Tested 8:52:04 AM 12/05/2018
Pull Station 2nd Deck Fwd Crew Quarters Passageway Tested 3:28:23 PM 12/04/2018
Pull Station 2nd Deck Fwd Scientific Stores Tested 3:15:52 PM 12/04/2018
Pull Station 2nd Deck Port Oceanographic Winch
Room/Bosuns Stores
Tested 8:59:34 AM 12/05/2018
Pull Station 2nd Deck Port, Fwd Crew Quarters Passageway Tested 3:28:11 PM 12/04/2018
Pull Station Hold Deck Domestic Equipment Room Tested 2:47:36 PM 12/04/2018
Pull Station Hold Deck Engineers Workshop Tested 2:54:04 PM 12/04/2018
Pull Station Hold Deck Port, Fwd Engine Room Tested 2:55:50 PM 12/04/2018
Pull Station Main Deck Aft Fish Wet Laboratory Tested 8:16:58 AM 12/05/2018
Pull Station Main Deck Aft Passageway Tested 8:15:00 AM 12/05/2018
Pull Station Main Deck Fwd Passageway Tested 8:29:15 AM 12/05/2018
Pull Station Main Deck Fwd Stairwell Tested 8:44:24 AM 12/05/2018
Pull Station Main Deck Mid, Aft Passageway Tested 8:26:01 AM 12/05/2018
Pull Station Main Deck Mid, Stbd Passageway Tested 8:31:00 AM 12/05/2018
Pull Station Wheel House Stbd, Aft Tested 2:17:54 PM 12/04/2018
Smoke Detector 01 Level Lounge Area Tested 7:49:39 AM 12/05/2018
Smoke Detector 01 Level Ship's Office Tested 7:42:59 AM 12/05/2018
Smoke Detector 01 Level Aft Passageway Tested 7:47:26 AM 12/05/2018
Smoke Detector 01 Level Aft Stairwell Tested 7:37:56 AM 12/05/2018
Smoke Detector 01 Level Fwd Passageway Tested 9:26:31 AM 12/05/2018
Smoke Detector 02 Level Hospital Tested 7:32:01 AM 12/05/2018
Smoke Detector 02 Level Aft Passageway Tested 7:27:58 AM 12/05/2018
Smoke Detector 02 Level Stbd, Fwd Passageway Tested 7:26:21 AM 12/05/2018
Smoke Detector 2nd Deck Exercise Room Tested 3:21:39 PM 12/04/2018
Smoke Detector 2nd Deck C/L Control Room Tested 8:56:41 AM 12/05/2018
Smoke Detector 2nd Deck Fwd Crew Quarters Passageway Tested 3:23:43 PM 12/04/2018
Smoke Detector 2nd Deck Fwd Scientific Stores Tested 3:17:49 PM 12/04/2018
Smoke Detector 2nd Deck Fwd, Port Crew Quarters Passageway Tested 3:29:35 PM 12/04/2018
Smoke Detector 2nd Deck Fwd, Stbd Crew Quarters Passageway Tested 3:24:50 PM 12/04/2018
Smoke Detector 2nd Deck Port Control Room Tested 8:57:51 AM 12/05/2018
Smoke Detector 2nd Deck Port Control Room Tested 8:59:03 AM 12/05/2018
Smoke Detector 2nd Deck Port Oceanographic Winch
Room/Bosuns Stores
Tested 9:01:27 AM 12/05/2018
Smoke Detector 2nd Deck Port, Fwd Crew Quarters Passageway Tested 3:26:05 PM 12/04/2018
Smoke Detector 2nd Deck Stbd Control Room Tested 8:55:34 AM 12/05/2018
Smoke Detector 2nd Deck Stbd Crew Quarters Passageway Tested 3:30:37 PM 12/04/2018
Smoke Detector 2nd Deck Stbd Oceanographic Winch
Room/Bosuns Stores
Tested 9:03:33 AM 12/05/2018
Smoke Detector Hold Deck Transducer Room Tested 9:21:26 AM 12/05/2018
Smoke Detector Hold Deck Aft General Stores Tested 2:49:23 PM 12/04/2018
Smoke Detector Hold Deck Aft, Port MSD/Domestic Equipment
Room
Tested 2:47:50 PM 12/04/2018
Smoke Detector Hold Deck Fwd General Stores Tested 2:49:41 PM 12/04/2018
Smoke Detector Hold Deck Fwd, Stbd MSD/Domestic Equipment Tested 2:50:55 PM 12/04/2018
Alexander Gow Fire Equipment Company 4 02/18/2019
Room
Smoke Detector Hold Deck Port Engineers Workshop Tested 2:53:53 PM 12/04/2018
Smoke Detector Hold Deck Stbd Engineers Workshop Tested 8:53:17 AM 12/05/2018
Smoke Detector Main Deck Dry Laboratory Tested 8:32:49 AM 12/05/2018
Smoke Detector Main Deck Fwd Dry Stores Tested 8:46:07 AM 12/05/2018
Smoke Detector Main Deck Fwd Passageway Tested 8:39:25 AM 12/05/2018
Smoke Detector Main Deck Ready Room Tested 8:10:37 AM 12/05/2018
Smoke Detector Main Deck Trash Room Tested 8:12:51 AM 12/05/2018
Smoke Detector Main Deck Aft Acoustic Laboratory Tested 8:27:10 AM 12/05/2018
Smoke Detector Main Deck Aft Crew Mess Tested 8:50:09 AM 12/05/2018
Smoke Detector Main Deck Aft Passageway Tested 8:22:33 AM 12/05/2018
Smoke Detector Main Deck Fwd Acoustic Laboratory Tested 8:27:56 AM 12/05/2018
Smoke Detector Main Deck Fwd Crew Mess Tested 8:49:15 AM 12/05/2018
Smoke Detector Main Deck Fwd Stairwell Tested 8:47:45 AM 12/05/2018
Smoke Detector Wheel House Port, Aft Tested 7:16:15 AM 12/05/2018
Smoke Detector Wheel House Port, Fwd Tested 7:15:28 AM 12/05/2018
Smoke Detector Wheel House Stbd, Aft Tested 7:08:24 AM 12/05/2018
Smoke Detector Wheel House Stbd, Fwd Tested 7:09:38 AM 12/05/2018
Alexander Gow Fire Equipment Company 5 02/18/2019
Service Summary
Building: NOAA Bell M Shimada
The Service Summary section provides an overview of the services performed in this report.
No devices were found for this section of the report.
Alexander Gow Fire Equipment Company 6 02/18/2019
Auxiliary Functions Testing
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed
Heat Detector
Combination 135°F 01 Level ET Shop Passed 50558006
Combination 135°F 01 Level Fan Room Above DB Panels Passed 50558007
Fixed Temperature
190°F
01 Level Aft Emergency Generator Room Passed 50558008
Combination 135°F 01 Level Fwd DC Locker Room SCBA Room Passed 50558014
Combination 135°F 01 Level Port, Fwd Reefer Machinery Room Passed 50558013
Combination 135°F 01 Level Stbd, Fwd Dive Locker Room Passed 50558016
Combination 135°F 01 Level Stbd, Fwd DK Locker Room Passed 50558015
Combination 135°F 02 Level Aft Exterior DC Locker Room SCBA
Room
Passed 50558003
Combination 135°F 2nd Deck Aft, Stbd Trawl Winch Room Passed 50558057
Fixed Temperature
190°F
2nd Deck C/L Main Machinery Room Passed 50558047
Combination 135°F 2nd Deck Fwd Laundry Room Passed 50558071
Combination 135°F 2nd Deck Fwd, Port Trawl Winch Room Passed 50558056
Combination 135°F 2nd Deck Fwd, Stbd Trawl Winch Room Passed 50558058
Fixed Temperature
190°F
2nd Deck Port Main Machinery Room Passed 50558045
Combination 135°F 2nd Deck Port, Aft Trawl Winch Room Passed 50558059
Fixed Temperature
190°F
2nd Deck Stbd Main Machinery Room Passed 50558046
Fixed Temperature
190°F
Hold Deck Bow Thruster Room Passed 50558086
Fixed Temperature
190°F
Hold Deck Aft, C/L Engine Room Passed 50558076
Fixed Temperature
190°F
Hold Deck Fwd, C/L Engine Room Passed 50558079
Fixed Temperature
190°F
Hold Deck Fwd, Stbd Engine Room Passed 50558077
Fixed Temperature
190°F
Hold Deck Port, Fwd Engine Room Passed 50558078
Combination 135°F Main Deck Chemical Laboratory Passed 50558028
Combination 135°F Main Deck Deck Locker Passed 50558021
Fixed Temperature
190°F
Main Deck Fan Room Passed 50558041
Combination 135°F Main Deck Fwd Scientific Stores Passed 50558043
Combination 135°F Main Deck Hydrographic Laboratory Passed 50558031
Combination 135°F Main Deck Aft Fish Wet Laboratory Passed 50558023
Fixed Temperature Main Deck Aft Galley Passed 50558037
Alexander Gow Fire Equipment Company 7 02/18/2019
190°F
Combination 135°F Main Deck Fwd Fish Wet Laboratory Passed 50558022
Fixed Temperature
190°F
Main Deck Fwd Galley Passed 50558038
Combination 135°F Main Deck Fwd, Port Fish Wet Laboratory Passed 50558025
Smoke Detector
Photoelectric 01 Level Lounge Area Passed 50558011
Photoelectric 01 Level Ship's Office Passed 50558009
Photoelectric 01 Level Aft Passageway Passed 50558010
Photoelectric 01 Level Aft Stairwell Passed 50558004
Photoelectric 01 Level Fwd Passageway Passed 50558090
Photoelectric 02 Level Hospital Passed 50558001
Photoelectric 02 Level Aft Passageway Passed 50558002
Photoelectric 02 Level Stbd, Fwd Passageway Passed 50557996
Photoelectric 2nd Deck Exercise Room Passed 50558067
Photoelectric 2nd Deck C/L Control Room Passed 50558049
Photoelectric 2nd Deck Fwd Crew Quarters Passageway Passed 50558065
Photoelectric 2nd Deck Fwd Scientific Stores Passed 50558069
Photoelectric 2nd Deck Fwd, Port Crew Quarters
Passageway
Passed 50558062
Photoelectric 2nd Deck Fwd, Stbd Crew Quarters
Passageway
Passed 50558066
Photoelectric 2nd Deck Port Control Room Passed 50558050
Photoelectric 2nd Deck Port Control Room Passed 50558051
Photoelectric 2nd Deck Port Oceanographic Winch
Room/Bosuns Stores
Passed 50558053
Photoelectric 2nd Deck Port, Fwd Crew Quarters
Passageway
Passed 50558064
Photoelectric 2nd Deck Stbd Control Room Passed 50558048
Photoelectric 2nd Deck Stbd Crew Quarters Passageway Passed 50558061
Photoelectric 2nd Deck Stbd Oceanographic Winch
Room/Bosuns Stores
Passed 50558054
Photoelectric Hold Deck Transducer Room Passed 50558085
Photoelectric Hold Deck Aft General Stores Passed 50558082
Photoelectric Hold Deck Aft, Port MSD/Domestic Equipment
Room
Passed 50558084
Photoelectric Hold Deck Fwd General Stores Passed 50558083
Photoelectric Hold Deck Fwd, Stbd MSD/Domestic
Equipment Room
Passed 50558080
Photoelectric Hold Deck Port Engineers Workshop Passed 50558072
Photoelectric Hold Deck Stbd Engineers Workshop Passed 50558073
Photoelectric Main Deck Dry Laboratory Passed 50558032
Photoelectric Main Deck Fwd Dry Stores Passed 50558042
Photoelectric Main Deck Fwd Passageway Passed 50558044
Photoelectric Main Deck Ready Room Passed 50558020
Photoelectric Main Deck Trash Room Passed 50558019
Photoelectric Main Deck Aft Acoustic Laboratory Passed 50558027
Photoelectric Main Deck Aft Crew Mess Passed 50558036
Photoelectric Main Deck Aft Passageway Passed 50558026
Photoelectric Main Deck Fwd Acoustic Laboratory Passed 50558033
Photoelectric Main Deck Fwd Crew Mess Passed 50558035
Photoelectric Main Deck Fwd Stairwell Passed 50558039
Photoelectric Wheel House Port, Aft Passed 50557995
Alexander Gow Fire Equipment Company 8 02/18/2019
Photoelectric Wheel House Port, Fwd Passed 50557997
Photoelectric Wheel House Stbd, Aft Passed 50557993
Photoelectric Wheel House Stbd, Fwd Passed 50557994
Alexander Gow Fire Equipment Company 9 02/18/2019
Battery & Power Supply Testing
The Control & Power Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Comment Amps Volts
Pre
Test
Post
Test
Passed
Battery
Sealed Lead Acid Wheel House In FACP Passed 8.0 12.0 N/A N/A
Sealed Lead Acid Wheel House In FACP Passed 8.0 12.0 N/A N/A
Alexander Gow Fire Equipment Company 10 02/18/2019
Inventory & Warranty Report
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Item Category % of Inventory Quantity
Battery Control 2.02% 2
Pull Station Initiating 19.19% 19
Smoke Detector Initiating 43.43% 43
Heat Detector Initiating 31.31% 31
Bell Indicating 1.01% 1
Annunciator Control 1.01% 1
Control Panel Control 1.01% 1
Horn/Strobe Indicating 1.01% 1
Type Qty Model # Description Install Date
New (under 90 days)
Interstate Batteries
Battery 2 SLA1075 Sealed Lead Acid 01/01/2019
In Service - 3 Years to 5 Years
Notifier
Annunciator 1 LCD-80 LCD Display 03/01/2014
Control Panel 1 AFP-200 03/01/2014
Heat Detector 12 FST-851H Fixed Temperature 190°F 03/01/2014
Heat Detector 19 FST-851R Combination 135°F 03/01/2014
Horn/Strobe 1 03/01/2014
Pull Station 19 NBG-12LX Dual Action 03/01/2014
Smoke Detector 43 FSP-851 Photoelectric 03/01/2014
Wheelock
Bell 1 6 inch 03/01/2014
Alexander Gow Fire Equipment Company 11 02/18/2019
Zone Address Report
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Description ScanID
37 Heat Detector Main Deck Deck Locker Combination 135°F 50558021
61 Heat Detector Main Deck Fwd Scientific Stores Combination 135°F 50558043
D Smoke Detector 01 Level Aft Passageway Photoelectric 50558010
D Heat Detector Main Deck Fan Room Fixed Temperature
190°F
50558041
D02 Heat Detector Hold Deck Aft, C/L Engine Room Fixed Temperature
190°F
50558076
D04 Heat Detector Hold Deck Fwd, Stbd Engine Room Fixed Temperature
190°F
50558077
D05 Heat Detector Hold Deck Fwd, C/L Engine Room Fixed Temperature
190°F
50558079
D06 Heat Detector Hold Deck Port, Fwd Engine Room Fixed Temperature
190°F
50558078
D07 Smoke Detector Hold Deck Port Engineers Workshop Photoelectric 50558072
D08 Smoke Detector Hold Deck Stbd Engineers Workshop Photoelectric 50558073
D09 Smoke Detector Hold Deck Aft General Stores Photoelectric 50558082
D10 Smoke Detector Hold Deck Fwd General Stores Photoelectric 50558083
D11 Smoke Detector Hold Deck Fwd, Stbd MSD/Domestic
Equipment Room
Photoelectric 50558080
D12 Smoke Detector Hold Deck Aft, Port MSD/Domestic
Equipment Room
Photoelectric 50558084
D13 Smoke Detector Hold Deck Transducer Room Photoelectric 50558085
D14 Heat Detector Hold Deck Bow Thruster Room Fixed Temperature
190°F
50558086
D15 Heat Detector 2nd Deck Aft, Stbd Trawl Winch Room Combination 135°F 50558057
D16 Heat Detector 2nd Deck Port, Aft Trawl Winch Room Combination 135°F 50558059
D17 Heat Detector 2nd Deck Fwd, Stbd Trawl Winch Room Combination 135°F 50558058
D18 Heat Detector 2nd Deck Fwd, Port Trawl Winch Room Combination 135°F 50558056
D19 Smoke Detector 2nd Deck Stbd Oceanographic Winch
Room/Bosuns Stores
Photoelectric 50558054
D20 Smoke Detector 2nd Deck Port Oceanographic Winch
Room/Bosuns Stores
Photoelectric 50558053
D21 Smoke Detector 2nd Deck Port Control Room Photoelectric 50558050
D22 Smoke Detector 2nd Deck Stbd Control Room Photoelectric 50558048
D23 Smoke Detector 2nd Deck Port Control Room Photoelectric 50558051
D24 Smoke Detector 2nd Deck C/L Control Room Photoelectric 50558049
D26 Heat Detector 2nd Deck C/L Main Machinery Room Fixed Temperature
190°F
50558047
D27 Heat Detector 2nd Deck Stbd Main Machinery Room Fixed Temperature
190°F
50558046
D28 Heat Detector 2nd Deck Port Main Machinery Room Fixed Temperature
190°F
50558045
Alexander Gow Fire Equipment Company 12 02/18/2019
D29 Smoke Detector 2nd Deck Stbd Crew Quarters
Passageway
Photoelectric 50558061
D30 Smoke Detector 2nd Deck Fwd, Port Crew Quarters
Passageway
Photoelectric 50558062
D31 Smoke Detector 2nd Deck Port, Fwd Crew Quarters
Passageway
Photoelectric 50558064
D32 Smoke Detector 2nd Deck Fwd, Stbd Crew Quarters
Passageway
Photoelectric 50558066
D33 Smoke Detector 2nd Deck Fwd Crew Quarters
Passageway
Photoelectric 50558065
D34 Smoke Detector 2nd Deck Exercise Room Photoelectric 50558067
D35 Heat Detector 2nd Deck Fwd Laundry Room Combination 135°F 50558071
D36 Smoke Detector 2nd Deck Fwd Scientific Stores Photoelectric 50558069
D39 Heat Detector Main Deck Aft Fish Wet Laboratory Combination 135°F 50558023
D40 Smoke Detector Main Deck Ready Room Photoelectric 50558020
D41 Smoke Detector Main Deck Aft Passageway Photoelectric 50558026
D42 Smoke Detector Main Deck Trash Room Photoelectric 50558019
D43 Heat Detector Main Deck Fwd, Port Fish Wet Laboratory Combination 135°F 50558025
D46 Smoke Detector Main Deck Aft Acoustic Laboratory Photoelectric 50558027
D47 Heat Detector Main Deck Chemical Laboratory Combination 135°F 50558028
D49 Smoke Detector Main Deck Fwd Acoustic Laboratory Photoelectric 50558033
D51 Heat Detector Main Deck Hydrographic Laboratory Combination 135°F 50558031
D52 Smoke Detector Main Deck Dry Laboratory Photoelectric 50558032
D53 Smoke Detector Main Deck Aft Crew Mess Photoelectric 50558036
D54 Heat Detector Main Deck Aft Galley Fixed Temperature
190°F
50558037
D55 Smoke Detector Main Deck Fwd Crew Mess Photoelectric 50558035
D56 Heat Detector Main Deck Fwd Galley Fixed Temperature
190°F
50558038
D57 Smoke Detector Main Deck Fwd Stairwell Photoelectric 50558039
D59 Smoke Detector Main Deck Fwd Dry Stores Photoelectric 50558042
D60 Smoke Detector Main Deck Fwd Passageway Photoelectric 50558044
D62 Heat Detector 01 Level Aft Emergency Generator Room Fixed Temperature
190°F
50558008
D63 Smoke Detector 01 Level Aft Stairwell Photoelectric 50558004
D64 Heat Detector 01 Level ET Shop Combination 135°F 50558006
D65 Smoke Detector 01 Level Ship's Office Photoelectric 50558009
D67 Heat Detector 01 Level Fan Room Above DB Panels Combination 135°F 50558007
D69 Smoke Detector 01 Level Lounge Area Photoelectric 50558011
D70 Smoke Detector 01 Level Fwd Passageway Photoelectric 50558090
D73 Heat Detector 01 Level Stbd, Fwd DK Locker Room Combination 135°F 50558015
D74 Heat Detector 01 Level Stbd, Fwd Dive Locker Room Combination 135°F 50558016
D75 Heat Detector 01 Level Port, Fwd Reefer Machinery
Room
Combination 135°F 50558013
D76 Heat Detector 01 Level Fwd DC Locker Room SCBA
Room
Combination 135°F 50558014
D77 Heat Detector 02 Level Aft Exterior DC Locker Room
SCBA Room
Combination 135°F 50558003
D78 Smoke Detector 02 Level Hospital Photoelectric 50558001
D79 Smoke Detector 02 Level Aft Passageway Photoelectric 50558002
D80 Smoke Detector 02 Level Stbd, Fwd Passageway Photoelectric 50557996
D81 Smoke Detector Wheel House Port, Aft Photoelectric 50557995
D82 Smoke Detector Wheel House Stbd, Aft Photoelectric 50557993
Alexander Gow Fire Equipment Company 13 02/18/2019
D83 Smoke Detector Wheel House Stbd, Fwd Photoelectric 50557994
D84 Smoke Detector Wheel House Port, Fwd Photoelectric 50557997
M02 Pull Station Hold Deck Port, Fwd Engine Room Dual Action 50558075
M03 Pull Station Hold Deck Engineers Workshop Dual Action 50558074
M04 Pull Station Hold Deck Domestic Equipment Room Dual Action 50558081
M05 Pull Station 2nd Deck Port Oceanographic Winch
Room/Bosuns Stores
Dual Action 50558055
M06 Pull Station 2nd Deck Fwd Crew Quarters
Passageway
Dual Action 50558060
M07 Pull Station 2nd Deck Port, Fwd Crew Quarters
Passageway
Dual Action 50558063
M08 Pull Station 2nd Deck Exercise Room Dual Action 50558068
M09 Pull Station 2nd Deck Fwd Scientific Stores Dual Action 50558070
M10 Pull Station Main Deck Aft Passageway Dual Action 50558018
M11 Pull Station Main Deck Mid, Aft Passageway Dual Action 50558029
M12 Pull Station Main Deck Mid, Stbd Passageway Dual Action 50558030
M13 Pull Station Main Deck Fwd Passageway Dual Action 50558034
M14 Pull Station Main Deck Fwd Stairwell Dual Action 50558040
M15 Pull Station 01 Level Aft Passageway Dual Action 50558005
M16 Pull Station 02 Level Aft Passageway Dual Action 50557999
M17 Pull Station 02 Level Stbd, Fwd Passageway Dual Action 50558000
M18 Pull Station Wheel House Stbd, Aft Dual Action 50558017
M19 Pull Station 01 Level Fwd Passageway Dual Action 50558012
M20 Pull Station Main Deck Aft Fish Wet Laboratory Dual Action 50558024
M44 Heat Detector Main Deck Fwd Fish Wet Laboratory Combination 135°F 50558022
Zone/Circuit: NAC
Horn/Strobe Mast 50558094
Bell Wheel House Mid, C/L 50557998
File details come from the government source that posted it.