0708-02 - Electrical Install - Drawing_Redacted.pdf
PDF 66 KB Posted
- Attached to
- ELECTRICAL INSTALL
- Solicitation number
- N0017825Q0008
About this file
This document is a power distribution diagram for the Raborn SAIL Lab Power system. The diagram illustrates a complex electrical infrastructure with multiple voltage levels and equipment configurations. Key components include a 480VAC, 60 Hz, 3PH input with a 40A breaker (requiring an upgrade to 100A), a 440VAC Delta breaker panel, a 225KVA transformer (MIT-DRY106-J-CD Maddox), and multiple receptacle cabinets. The system features three primary voltage branches: 440VAC with TI-16 cabinets (6KVA each), 208VAC Wye with VCSC cabinets (10KVA each), and 120VAC receptacles. Important operational notes specify that the 480VAC cut-off switch must be removed and the TI-16 and VCSC equipment cannot be powered concurrently. The diagram uses color coding to distinguish between customer-supplied (yellow), existing (blue), and repurposed (green) equipment, providing a comprehensive view of the power distribution layout.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| QA.docx_complete.pdf | ||
| SOW-Redacted FINAL.pdf | ||
| SF 1449 - N0017825Q0008.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
40A breaker
480VAC, 60 Hz, 3PH
440V Delta:208V
Wye
225KVA
XFmr
MIT-DRY-
106-J-CD
Maddox
440VAC
Receptacle
(x6)
TI-16
Cabinet
6KVA each (x6)
208VAC
Receptacle
(x12)
VCSC
Cabinet
10KVA each (x6)
120VAC
Receptacle
15A (x6)
Supplied by customer
Breaker Panel
440VAC, 60 Hz, 3PH Delta
Breaker Panel
208VAC, 60 Hz, 3PH Wye
J1
J2
Breaker upgrade required to 100A
Existing
Repurpose
J1
Raborn SAIL Lab Power
Note: TI-16 and VCSC equipment are not to be powered concurrently
480VAC cut off switch to be removed.
L16-30R 30A 480V
L15-30R 30A 250V