This Special Notice was published by the Department of Veterans Affairs Network Contracting Office to announce its intent to sole source an emergency contract to The Aulson Company. The notice seeks responses from other qualified sources by February 17, 2023 regarding water outage response services at the Manchester VA Medical Center in New Hampshire.

The Special Notice outlines the scope of work needed to address an unexpected facility-wide water outage at the Medical Center, including personnel for water system troubleshooting, temporary heating, portable toilets, an emergency water connection, and heat tracing of pipes in two buildings. The period of performance is 60 days. Responsible sources that feel they are qualified to provide the services outlined may submit a response by the deadline of February 17, 2023 to be considered, however award is intended for The Aulson Company. The North American Industry Classification System code for this requirement is 562910.

Notice text

NOTICE OF THE INTENT TO SOLE SOURCE TO THE AULSON COMPANY, 49 DANTON DRIVE, METHUEN, MA 01844, UNITED STATES. Response Due Date: February 17, 2023, by 10:00AM (EST) NOTICE OF THE INTENT TO SOLE SOURCE SYNOPSIS Network Contract Office 1, Procurement Office East on behalf of The Department of Veterans Affairs, Manchester VA Medical Center located at 718 Smyth Road, Manchester, NH 03104-7007 intends to award a firm-fixed contract with no options to THE AULSON COMPANY to provide emergency troubleshooting, repair, and mitigation of water system failure. This is an emergency response to an unexpected facility-wide water outage and mitigation to prevent recurrence. The proposed procurement is for services/product for which the Government intends to solicit and negotiate with only one source under the authority of FAR 6.302-1 -- Only One Responsible Source and No Other Supplies or Services Will Satisfy Agency Requirements. 41 U.S.C. 3304(a)(1). The North American Industry, Classification System code (NAICS) for this requirement is 562910. All responsible sources that feel they should be considered qualified to provide the above-mentioned products may submit a response to this notice (by the response due date shown above) to Divianna.Mathurin@va.gov. The information provided shall include detailed (and relevant) documentation to allow the government to perform adequate market research and make a proper determination. A determination by the government not to compete this proposed requirement based upon responses to this notice is solely within the discretion of the Government. Information received will be considered solely for the purpose of determining whether to conduct a competitive procurement. THIS IS NOT A REQUEST FOR COMPETITIVE PROPOSALS. THERE IS NO SOLICITATION AVAILABLE AT THIS TIME. REQUESTS FOR A SOLICITATION WILL NOT RECEIVE A RESPONSE.

Project 608-23-107

Emergency Water Outage Response

Scope of Work

Provide emergency response assistance for an unexpected water outage at the Manchester VA Medical Center.

Task 1: Provide personnel to assist with troubleshooting, water valve vault confined space entry, heater set-up and operation, altitude valve adjustment, and valve and pressure troubleshooting.

Task 2: Provide temporary heat for Building 15, Community Living Center.

Task 3: Provide heat for water valve vaults.

Task 4: Provide three portable toilets, one being handicapped accessible.

Task 5: Provide an emergency alternative water connection for the boiler plant. The intent of the connection is to be able to connect a hose run to the water tower or to a water supply tanker truck. The connection shall be on the exterior of Building 7 and be able to accept 2 , 2 ½ , and 3 hose connections. Provide signage for the connection to differentiate it from the emergency sprinkler system connection.

Part A: Tie in to an existing plug where the water line enters the building. This is a temporary connection point that can be completed quickly for immediate use.

Part B: Convert the water connection installed in Part A to feed the boiler system only, instead of the entire building. Install a backflow preventer to keep emergency boiler water, which may not be potable, from entering the building s potable water system.

Task 6: Heat trace all pipe in Building 8, the 4 city connection water vault on the far west end of the campus. Install two heat trace systems for redundancy. This will require a new electrical connection. Assume a new conduit will be run underground from Building 2.

Task 7: Heat trace all pipe in the valve vault under the water tower. Install two heat trace systems for redundancy. Power is available at one of the water towers legs.

All work to be completed in accordance with all local, state, and federal regulations, including OHSA and NFPA.

Period of performance is 60 days.

Files

File Type Posted
36C24123Q0355.docx DOCX document

Similar open opportunities

Opportunity Agency Set-aside Responses due
J066--Azenta NitroStore System PM and Support Services NAICS 811210 Veterans Integrated Service Network 4 No set-aside
J059--Building Management System-Sole Source Intent NAICS 561210 Veterans Integrated Service Network 21 No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity