J061--Automatic Transfer Switch Testing and Imaging

Closed Solicitation Posted

Solicitation number
36C24125Q0764
Agency
Responses due
Set-aside
Veteran-Owned Small Business

Opportunity facts

Place of performance
VA Boston Healthcare System (BHS) West Roxbury West Roxbury MA 02132, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1 is seeking a contractor to perform Annual Automatic Transfer Switch (ATS) Testing and Imaging services at the Boston Healthcare System, West Roxbury Division. This combined synopsis/solicitation follows FAR subpart 12.6 streamlined procedures for commercial products and services, with the solicitation document incorporating provisions and clauses from Federal Acquisition Circular 2024-03. The procurement is classified under NAICS code 811310 for Commercial and Industrial Machinery and Equipment Repair and Maintenance, with a small business size standard of $12.5 million. The government has provided supporting documentation including evaluation processes, instructions to quoters, past performance worksheets, and wage determination requirements. Quotes are due by September 3, 2025, with the solicitation having been posted on August 26, 2025.

This procurement is set aside exclusively for Veteran-Owned Small Business (VOSB) contractors, reflecting the VA's commitment to supporting veteran entrepreneurs. The contract structure includes a base year plus four option years, creating a potential five-year engagement for annual ATS testing and imaging services. Services will be performed at 150 S Huntington Ave, Boston, MA 02130, at the West Roxbury Division facility. The solicitation requests quotations for each contract year separately, allowing the government flexibility in exercising options based on performance and funding availability. While specific dollar values are not disclosed in the notice, contractors must provide unit prices and total prices for each line item covering the base year and four option years of service.

Notice text

Description

This is a combined synopsis/solicitation for commercial products and commercial services prepared in accordance with the format in Federal Acquisition Regulation (FAR) subpart 12.6, Streamlined Procedures for Evaluation and Solicitation for Commercial Products and Commercial Services, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation document will not be issued.

This solicitation is issued as an RFQ. The solicitation document and incorporated provisions and clauses are those in effect through the most current Federal Acquisition Circular. The most current Federal Acquisition Circular (FAC) 2024-03 can be found at Acquisition.gov.

This solicitation is set-aside for Veteran-Owned Small Business (VOSB).

The associated North American Industrial Classification System (NAICS) code for this procurement is 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance, with a small business size standard of $12.5 million.

The FSC/PSC is J061 Maint/Repair/Rebuild Of Equipment - Electric Wire and Power Distribution Equipment.

The Boston Healthcare System, West Roxbury Division is seeking a contractor to perform Automatic Transfer Switch (ATS) Testing and Imaging.

All interested companies shall provide quotations for the following:

Supplies/Services

Line Item

Description

Quantity

Unit of Measure

Unit Price

Total Price

0001

Base Year: Annual Automatic Transfer Switch Testing and Imaging

1

YR

1001

Option Year 1: Annual Automatic Transfer Switch Testing and Imaging

1

YR

2001

Option Year 2: Annual Automatic Transfer Switch Testing and Imaging

1

YR

3001

Option Year 3: Annual Automatic Transfer Switch Testing and Imaging

1

YR

4001

Option Year 4: Annual Automatic Transfer Switch Testing and Imaging

1

YR

Total

$

Statement of Work

Automatic Transfer Switch (ATS) Testing and Imaging

1.0 Scope of Work

The contractor will perform annual Automatic Transfer Switch testing and imaging at the Boston Healthcare System, West Roxbury Division. Contractor is responsible for all labor, materials, tools and special equipment required to perform the work.

Period of Performance

Contract shall be a base year plus 4 option years.

All Transfer Switch Testing shall occur during off hours (10:00 PM 7:00 AM)

Place of Performance

Boston Healthcare System, West Roxbury

1400 VFW Parkway

West Roxbury, MA 02132

2.0 Performance Requirements

INFRARED THERMAL IMAGING

Thermal infrared imaging of both the normal and emergency power poles shall be done during annual testing. The transfer/bypass switch shall be in the emergency position for 30 minutes, prior to the imaging pictures taken to allow for any temperature rise. Reports of anomalies shall include a color photograph of the switch being tested & a color thermal imaging print. The report information shall be similar to test report a attached and made part of this standard. Both the transfer switch & bypass contacts shall be scanned.

The following standards, as applicable, shall be part of the testing requirements:

NFPA-70 (national electric code)

NFPA-70B (electrical equipment maintenance) nfpa-70e (electrical safety in the workplace) nfpa-99 (health care facilities)

NFPA-101 (life safety code)

NFPA-110 (emergency and standby power systems) nfpa-20 (stationary pumps for fire protection) ansi/neta-mts (maintenance testing specifications) ma elevator regulations (524 cmr)

TESTING REQUIREMENTS

In-phase monitors (sync check relays)

In-phase monitors shall be checked for calibration and shall be set for + or 7 degrees maximum. Relay output contacts shall be tested, Dead bus relay outputs shall be confirmed and maximum slip rate shall be noted on the test reports.

VOLTAGE & FREQUENCY SENSORS

All voltage and frequency sensors for both normal and emergency shall be calibrated with a three-phase test set, using calibrated meters for all pickup & dropout values. All results, including as found and as left settings shall be noted on the test reports.

AUXILIARY CONTACTS & SPECIAL TIMED CONTACTS

All auxiliary position contacts shall be tested in both positions and so noted in the test reports.

All auxiliary contact functions such as Normal Power Available , Emergency Power Available , ETC. Shall be verified and noted in the test reports.

TIMER CALIBRATION AND OPERATION CHECKS

The following timers shall be checked for accuracy and so noted in the test reports:

Time delay, engine start.

Time Delay, transfer to Emergency. UMD Timer for Pre, Post, or Both. .

T3/W3 elevator presignal time delay w/ bypass.

Time delay, retransfer to normal. (set at 30 minutes) Time delay, engine cool down. (set at 300 seconds)

Time delay neutral position on Delayed transition switches.

LOAD SHED, BLOCK TRANSFER & RE-ADD CRKTS.

Special custom Load shed, Block Transfer & Re-add circuits shall be verified to be operational and be noted on the test reports (if applicable).

VERIFY TOTAL POWER FAILURE TO RESTORATION OF LOAD FROM EMERGENCY GENERATOR

Time delay, engine start = 1 or 3 seconds (Engineering Dept to specify actual time)

Time delay, transfer to emergency = .1-15 seconds (Engineering Dept to specify actual time)

Time delay, presignal = 10-20 seconds (Elevator contractor to specify actual required time)

Time delay, load shed = 1-30 seconds (Engineering Dept to specify actual required time delay)

Engine up to speed time = typical 4.5-6 seconds Retransfer to normal position = 5 minutes

Insure total transfer time on Critical or Life Safety switches do not exceed 10 seconds.

Insure that Elevator transfer switches transfer within 10 seconds, or as allowed by Mass Elevator Regulations (524 CMR) which is typically 25 seconds.

BYPASS/ISOLATION SWITCH TESTS

Provide bypass to normal and bypass to emergency operations with Isolation option for each. Ensure no load-break condition exists. (Switch must be a make-before-break arrangement) If switches are of the Load-break design, Engineering will establish the time & date for these tests.

Verify Manual Transfer switch function of Bypass switch. (Manual Transfer Switch Operation)

Ensure engine start contacts stay closed with ATS module out in Isolate position

After switch is isolated, rack ATS module back into the TEST position and cycle the switch through a complete sequence.

Follow manufacturer s instructions for returning switch to normal operating position

Verify B/I module relays are properly energized and that all blocking interlocks are operating correctly.

Verify all auxiliary and B/I engine start contacts.

QUALIFICATIONS FOR BIDDERS:

Qualified Bidders Shall be NETA certified Company and either Factory Trained & Authorized or Factory Trained on the Equipment to be tested. (General Electric, Zenith Controls, Russelectric, Pace, Asco, Westinghouse, Kohler, and Generac) and have a minimum of 20 years of experience, as many of the VA sites have older gear operating on site in excess of 15 years. Submit qualifications for technical review. All required certifications and proof of required experience must be provided to be considered for award.

The Field Engineer/Technician shall also be a Certified Level 2 or greater Thermographer.

SUBCONTRACTORS

If Prime vendor determines to utilize subcontractors, Prime vendor must be physically present at all times there are sub-contractors present, work activities are ongoing, materials are being delivered, etc. In addition, Prime vendor to submit in technical proposal the delineation of work from prime and subcontractors to include percentage (%) of work breakdown and description of work activities.

TEST REPORT REQUIREMENTS:

Test Reports are required to document results of each switch.

PREMIUM TIME WORK:

Bidders are reminded that all work must be done on premium time as designated by the contract.

PLEASE NOTE: TESTING OF BYPASS/ISOLATION SWITCHES REQUIRES ADDITIONAL TESTING CRITERIA DIFFERENT AND IN ADDITION TO A STANDARD ATS.

Bid prices shall be per unit and Campus may add or delete units from their BOM.

All services & inspections shall be scheduled thru COR.

No additional work can be performed under this contract, and no changes to this Scope of Work can be made without the authority and prior approval of the Contracting Officer.

3.0 Equipment to be serviced:

ATS Inventory

Â

Designation

Make

Model

Serial

Controller

Location

EE#

1

B1-1

Russelectric

RTBD-4004CEF

30535-1 A/8

2000

B1

82503

2

B1-2

Russelectric

RTBD-4004CEF

30535-2 C/D

2000

B1

82502

3

B1-3

Russelectric

RTBD-6004CEF

30535-2 A/8

2000

B1

82495

4

B1-4

Russelectric

RTBD-6004CEF

30535-2 C/D

2000

B1

82498

5

B1-5

Russelectric

RTBD-4004CEF

30535-1 E/F

2000

MCC431-01-WR

82501

6

B1-6 (Fire pump)

Zenith

Â

Â

Â

GD130-01-WR

56611

7

B1-7

Russelectric

RTBD-6004CEF

30535-2 E/F

2000

A3E-06 (B1)

82497

8

B1-8

Russelectric

RTBD-6004CEF

30535-2G/H

2000

A3 061 (B1)

82504

9

B1-10

Russelectric

RTBDLBCT-8004CEF

35621-2A/B

2000

B1

136551

10

B1-11

Russelectric

RTS03-ABLB6004AMF1

36512-1A/B

RPTCS

B1

147444

11

Emg Light Relays

Â

Â

Â

Â

Auditorium

Â

12

A3C-1 (ATS-2)

Russelectric

RTB-4004CEF

24509-3A/B

2000

B2

62947

13

A3C-2 (ATS-1)

Russelectric

RTB-2604CEF

24509-1A/B

2000

B2

62948

14

A3C-3 (ATS-8)

Russelectric

RTB-4004CEF

35621-1A/B

2000

B2

136550

15

A3C-4 (ATS-11)

Russelectric

RTS03-ABLB4004AMF1

39016 -1A/B

RPTCS

Â

Â

16

A3S-1 (ATS 5)

Russelectric

RTB-2604CEF

24509-1C/D

2000

B2

62945

17

A4E-1 (ATS 4)

Russelectric

RTB-4004CEF

24509-2A/B

Â

B2

62946

18

A4E-2 (ATS 6)

Russelectric

RTB-4004CEF

29772-1A/B

2000

B2

73136

19

A4E-3 (ATS 10) (Fire pump)

Zenith

Â

Â

Â

B2

72469

20

A4E-4 (ATS-3)

Russelectric

RTB-4004CEF

31010-1 A/B

Â

B2

83279

21

A4E-5 (ATS-9)

Russelectric

RTBDLB-6004CEF

35145-1 A/B

2000

B2

136549

22

A4E-7 (ATS-7)

Russelectric

RTS03-ABLB8004AMF1

36466-1A/B

RPTCS

B2

168928

23

ATS- (Mobile OR)

GE

Â

Â

Â

B2

73137

25

B8-Boiler

Russelectric

RTS03-ABLA4004AMF1

36608-1A/B

RPTCS

B8

140803

26

B20-Research

Russelectric

RTS03-ABLB8004AMF1

38472-1A/B

RPTCS

B20

Â

27

B21-Research

Russelectric

RTBDNB-6004CEF

35273-1A/B

2000

B21

136548

28

B3-1

Russelectric

RTBD-1004CEF

29772-2A/B

2000

B3

71293

29

B3-2

Russelectric

RTBDLB-4004CEF

33859-2C/D

2000

B3

104155

30

B3-3

Russelectric

RTBDLB-4004CEF

33859-2A/B

2000

B3

104153

31

B3-4

Russelectric

RTBDLB-6004CEF

33859-1A/B

2000

B3

104154

32

B3-5

Russelectric

RTBDLB-4004CEF

37890-1A/B

RPTCS

B3

167460

33

Garage

Russelectric

Â

Â

RPTCS

Garage

Â

34

Garage

Russelectric

Â

Â

RPTCS

Garage

Â

All quoters shall submit the following:

1. Questions: Any questions must be submitted in writing no later than Friday, August 29, 2025 at 10:00 AM EST. Answers to the questions will be posted the following week.

2. Quote: Offeror shall provide a quote using the table above. Offerors must also provide all applicable labor rates for the solicited services so they can be compared to the applicable wage determination for compliance with the Service Contract Labor Standards.

All quotes shall be sent to the Contract Specialist, Rosangela Pereira at Rosangela.Pereira@va.gov.

Award will be based upon a comparative evaluation of quotes in accordance with the Simplified Acquisition Procedures of FAR 13. Comparative evaluation is the side by side pairwise comparison of quotes based on factors resulting in a Contracting Officer decision for the quote most favorable to the Government.

The following are the decision factors:

Price: Quotes will be compared by price.

Technical: The offeror s quote shall be evaluated to determine if the organization has the experience and capabilities to provide the requested services IAW the Statement of Work in a timely efficient manner.Â

Contractor shall provide specification sheets for proposed equipment and include within the solicitation response.

The award will be made to the response most advantageous to the Government. Responses should contain your best terms, conditions.

Submission of your response shall be received not later than Wednesday, September 3, 2025 at 3:00 PM EST. All quotes shall be emailed to Rosangela Pereira at Rosangela.Pereira@va.gov.

Late submissions shall be treated in accordance with the solicitation provision at FAR 52.212-1.

Any questions or concerns regarding this solicitation should be forwarded in writing via e-mail to the Point of Contact listed below.

Point of Contact: Rosangela Pereira, Rosangela.Pereira@va.gov

Files

File Type Posted
Past Performance Worksheet.xlsx XLSX spreadsheet
Evaluation Process.docx DOCX document
52.212-1 Instructions to Quoters.docx DOCX document
WD 2015-4047 - Mass-Boston Rev30.pdf PDF
36C24125Q0764.docx DOCX document
LOS certification.pdf PDF

Similar open opportunities

Opportunity Agency Set-aside Responses due
J061--541 Electrical Power Distribution Equipment Testing, Inspection, and Maintenance - VAMC Cleveland Department of Veterans Affairs Louis Stokes Cleveland VA Medical Center, Ohio 44106, United States · NAICS 238210 Veterans Integrated Service Network 10 Total Small Business
657A5-26-111, Triennial Electrical Testing Marion, Illinois 62959, United States · NAICS 238210 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business Sole Source
F109--Water Management Program and Chemical Testing VAMC Boston Healthcare System Department of Veterans Affairs Vamc Boston Healthcare System Boston MA 02130, United States · NAICS 561210 Veterans Integrated Service Network 1 Service-Disabled Veteran-Owned Small Business
J061--triennial electrical maintenance FY26 amendment #3 q&a response, scope update, drawings and panel lists new deadline: 10/27/26 POP start date: 12/01/2026 Southeast Louisiana Veterans Healthcare System New Orleans Vamc New Orleans, Louisiana 77019, United States · NAICS 238210 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business