Halon Fire Supression System-Barge 727-Mississippi River Project Office

Award Notice Posted

Solicitation number
W912EK18T0025
Agency
Awarded
to Lester Construction, Inc.
Set-aside
Total Small Business

Opportunity facts

Contract number
W912EK18P0065 Federal contract award
NAICS code
238990 All Other Specialty Trade Contractors
PSC
Not on record
Place of performance
Lock and Dam 14 Pleasant Valley, Iowa 52767, United States

Notice details come from SAM.gov. Updated .

Notice text

2 versions

Update #2 · Latest ·

Removal of existing Halon fire suppression system and Design, Install, and test a suitable replacement Compressed CO2 system.

GENERAL


1) The specification details the requirements for an engineered high pressure carbon dioxide (CO2) fire suppression system. These requirements must be followed in order to produce a safe and effective fire protection and suppression system.


2) All materials and equipment shall be new and unused. Recycled products shall not be acceptable.
B. General Description


1) The high pressure CO2 suppression system shall be a Local Application System for surface fires inside the control room electrical cabinets and Local Application System for each of the onboard generators.


2) The system hardware shall consist of one or more cylinders filled with carbon dioxide at its own nominal vapor pressure of 850 psig at 70°F (58 bar gauge at 21°C) and other related equipment. The cylinders shall be connected either directly or via a common manifold to the discharge pipe network and discharged into the affected area using discharge nozzle(s).


Technical inquiries and questions relating to this solicitation are to be submitted to the Contract Specialist, Carissa McKinley, carissa.j.mckinley@usace.army.mil, no later than 23 February 2018 at 2:00pm CT.

Update #1 ·

Removal of existing Halon fire suppression system and Design, Install, and test a suitable replacement Compressed CO2 system.

GENERAL


1) The specification details the requirements for an engineered high pressure carbon dioxide (CO2) fire suppression system. These requirements must be followed in order to produce a safe and effective fire protection and suppression system.


2) All materials and equipment shall be new and unused. Recycled products shall not be acceptable.
B. General Description


1) The high pressure CO2 suppression system shall be a Local Application System for surface fires inside the control room electrical cabinets and Local Application System for each of the onboard generators.


2) The system hardware shall consist of one or more cylinders filled with carbon dioxide at its own nominal vapor pressure of 850 psig at 70°F (58 bar gauge at 21°C) and other related equipment. The cylinders shall be connected either directly or via a common manifold to the discharge pipe network and discharged into the affected area using discharge nozzle(s).


Technical inquiries and questions relating to this solicitation are to be submitted to the Contract Specialist, Carissa McKinley, carissa.j.mckinley@usace.army.mil, no later than 23 February 2018 at 2:00pm CT.

Files

File Type Posted
W912EK18T0025-0002.pdf PDF
W912EK18T0025-0001.pdf PDF
W912EK18T0025.pdf PDF
NEW_work_plan_drawing.pdf PDF
DEMO_plan_drawing.pdf PDF

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity