DEA Lab Upgrade

Award Notice Posted

Solicitation number
GS-05-P-16-FB-C-7002
Agency
Awarded
to Monaco Mechanical Inc.
Set-aside
Total Small Business

Opportunity facts

Contract number
GS05P16FBC7003 Federal contract award
NAICS code
238220 Plumbing, Heating, and Air-Conditioning Contractors
PSC
Not on record
Place of performance
Federal Building 536 S. Clark Street Chicago, Illinois 60605, United States

Notice details come from SAM.gov. Updated .

Notice text

Added: Feb 10, 2016 8:56 am  The project involves the extensive renovation of a DEA laboratory facility located at 536 South Clark Street in Chicago, IL. The project consists of the following:

1.             Provide new temperature controls.


2.             Replacing exhaust and supply air flow sensors in all labs.


3.             All new control valves, damper actuators, temperature and pressure sensor for all 6 AHUs.


4.             Replace all supply and exhaust VAV boxes including actuators and controls.


5.             Re-balancing of room air flows and all coil water flows.


6.             Remove all Pneumatic controls and pneumatic air system.


7.             Replace the 6 existing Air handling units (AHUs) with new AHUs.


8.             Replace in-duct fire alarm devices at the AHU's.


9.             Modify sprinkler piping in fan rooms to adapt to new fan and duct configurations.


10.         Replace 6 lab exhaust fans on roof with 2 new coil to coil heat recovery exhaust systems.


11.         Rebalance the supply and exhaust air systems to establish 10 air changes per hour in the lab spaces and a pressure differential of -0.05" in the laboratory to keep the laboratory negative relative to the corridor.


12.         Provide two new hot water preheat coil systems including dual pumps and converters and all controls.


13.         Provide two new glycol heat recovery coil systems including dual pumps and converters and all controls.


14.         Replace all zone perimeter hot water heating control valves.


15.         Replace and/or relocate certain supply air diffusers to improve air distribution and reduce drafts.


16.         Reprogram the BAS and add equipment to generate outgoing message to contact building maintenance.