This solicitation is for a 137th Special Operations Wing building renovation project. The solicitation number is W50S8T23B0004 and was issued by the Department of the Army National Guard. The project involves renovating Building 1001 and includes demolition work, metal stud framing, gypsum board, acoustical ceilings, flooring, painting and other finish work. The required products and services include gypsum board, metal studs, suspension systems, acoustical ceiling panels, joint compound, trim, flooring and paint. The response date is not provided in the document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDEX

PAGE

02050--1-3

02070--1-6

07270--1-8

08710--1-12

09255--1-12

09260--1-8

09511--1-7

09680--1-6

09900--1-12

15010--1-14

15030--1-5

15050--1-11

15891--1-10

15910--1-12

15932--1-4

15990-1-5

16050--1-19

16110--1-15

SECTION 02050 – DEMOLITION

SECTION 02070 – SELECTIVE DEMOLITION

SECTION 07270 – FIRESTOPPING

SECTION 08710 – FINISH HARDWARE

SECTION 09255 – GYPSUM BOARD ASSEMBLIES

SECTION 09260 – METAL STUDS AND GYPSUM BOARD ASSEMBLIES

SECTION 09511 – ACOUSTICAL PANEL CEILINGS

SECTION 09680 – CARPET

SECTION 09900 – PAINTING

SECTION 15010 - BASIC MECHANICAL REQUIREMENTS

SECTION 15030 - ELECTRICAL REQUIREMENTS FOR MECHANICAL EQUIPMENT

SECTION 15050 - BASIC MECHANICAL MATERIALS AND METHODS

SECTION 15140 - SUPPORTS AND ANCHORS

SECTION 15190 - MECHANICAL IDENTIFICATION

SECTION 15200 - NOISE AND VIBRATION CONTROL

SECTION 15250 - MECHANICAL INSULATION

SECTION 15325 - WET PIPE SPRINKLER SYSTEM

SECTION 15340 - FIRE DETECTION ALARM AND EQUIPMENT ACTIVATION

SECTION 15855 - AIR HANDLING UNITS AND CABINET FANS

SECTION 15870 - POWER AND GRAVITY VENTILATORS

SECTION 15891 - METAL DUCTWORK

SECTION 15910 - DUCTWORK ACCESSORIES

SECTION 15932 - AIR OUTLETS AND INLETS i

SECTION 15990 - TESTING, ADJUSTING, AND BALANCING

SECTION 16050 - BASIC METHODS AND REQUIREMENTS (ELECTRICAL)

SECTION 16110 - RACEWAY SYSTEMS

15140--1-10

15190--1-7

15200--1-3

15250--1-8

15325--1-8

15340--1-2

15855--1-8

15870--1-10

SECTION 16120 - WIRES AND CABLES, LOW VOLTAGE (600 Voltsand Below) 16120--1-15

SECTION 16140 - WIRING DEVICES 16140--1-4

SECTION 16450 - GROUNDING 16450--1-5

SECTION 16460 - TRANSFORMERS (GENERAL PURPOSE) 16460--1-5

SECTION 16462 - DISTRIBUTION SWITCHBOARDS 16462--1-6

SECTION 16470 - PANELBOARDS 16470--1-6

SECTION 16510 - BUILDING LIGHTING 16510--1-11

PAGE

INDEX

ii

DEMOLITION 02050 - 1

SECTION 02050 - DEMOLITION

PART 1 GENERAL

1.1 SECTION INCLUDES

A. Utility lines, and other items to be demolished and/or abandoned are as shown.

1.2 SUBMITTALS

A. Quality Control Submittals:

1. Schedule of demolition, as part of and consistent with the progress schedule specified in Section 01310, PROGRESS/CRITICAL PATH SCHEDULES.

2. Copies of any authorizations and permits required to perform Work.

PART 2 PRODUCTS (NOT USED)

PART 3 EXECUTION

3.1 PREPARATION

A. Utilities:

1. Notify CONTRACTING OFFICER or appropriate utilities to turn off affected services before starting demolition or alterations.

2. Remove utility lines exposed by demolition excavation.

3. Remove electric, sanitary, water, and storm drainage adjacent to buildings to be demolished.

4. Excavate utility lines serving buildings to be demolished and provide a permanent leak-proof closure for water and gas lines.

3.2 DEMOLITION

A. Drawings define minimum required demolition. Unless otherwise shown, rough cuts or breaks may be made exceeding limits of demolition shown.

B. Core drill floor slabs, catch basins, and other concrete improvements to remain in place below ground, or break holes at structure's lowest point to allow water to freely migrate through.

DEMOLITION 02050 - 2

C. Remove piping as shown and from any other areas that interfere with

CONTRACTOR’s work. Pipe, valves, and fittings adjacent to those to be removed may also be removed as salvage.

D. Cut off concealed or embedded conduit, boxes, or other materials a minimum of 6 inches below final finished surface.

E. Perform site cleanup daily before leaving the work site. Store equipment in a neat and orderly arrangement.

F. Abandonment of Buried Utility Piping Systems:

1. Plug pipelines at exposed excavations and at manholes or other utility structures with minimum 5-foot long concrete plug.

2. Manholes/wet wells/drainage structures:

a. Remove frames and covers/grates for salvage.

b. Remove structures shown on Drawings.

c. Backfill as described herein.

G. Demolition of utility poles, street signs and similar items:

1. Remove entire structure, including portions below ground.

2. Remove and separate items for salvage.

3. Backfill as described herein.

3.3 DISPOSAL

A. Dispose of debris and other nonsalvaged materials off base at location selected by

CONTRACTOR.

3.4 BACKFILLING

A. Demolished Areas: Backfill to existing ground level or foundation level of new construction.

B. Backfill Material and Compaction:

DEMOLITION 02050 - 3

1. Conform to Section 02220, FILL AND BACKFILL.

2. Do not use demolition debris as backfill material.

3.5 SALVAGE

A. Equipment and materials, including piping within the limits of demolition, unless otherwise specified, will become the property of the CONTRACTOR.

END OF SECTION

SELECTIVE DEMOLITION 02070 - 1

SECTION 02070 - SELECTIVE DEMOLITION

PART 1 - GENERAL

RELATED DOCUMENTS

Drawings and general provisions of Contract, including General Division 1 Specification Sections, apply to this Section.

SUMMARY

This Section includes, but is not limited to, the following:

Demolition and removal of selected site elements including site pavements and slabs-on-grade.

Disconnecting, capping or sealing, and abandoning or removing existing site utilities.

Demolition and removal of dumpster screen walls, slab-on-grade footings, and associated elements.

Demolition and removal of fencing.

Relocation of existing site utilities, including light poles.

Demolition and removal of existing underground concrete rubble. Refer to Specification Section 02200.

Demolition and removal of other above and below grade improvements to accommodate new construction.

Demolition and removal of existing trench drain.

Patching and repairing.

Demolition and removal of curb and gutter.

Related Sections: The following Sections contain requirements that relate to this Section:

Division 1 Section "Cutting and Repairing" for cutting and repairing procedures for selective demolition operations.

Division 2 Section "Site Clearing" for site clearing and removal of topsoil and vegetation.

Division 2 Section "Earthwork" for soil materials, excavating, backfilling, and site grading.

SELECTIVE DEMOLITION 02070 - 2

Division 2 Section “Landscape Work” for relocation of trees.

DEFINITIONS

Remove: Remove and legally dispose of items except those indicated to be reinstalled, salvaged, or to remain the Government’s property.

Existing to Remain: Protect construction indicated to remain against damage and soiling during selective demolition.

MATERIALS OWNERSHIP

Except for items or materials indicated to be reused, salvaged, reinstalled, or otherwise indicated to remain the Government’s property, demolished materials shall become the Contractor's property and shall be removed from the site with further disposition at the Contractor's option, unless otherwise indicated.

SUBMITTALS

Schedule indicating proposed sequence of operations for selective demolition work for review prior to start of work. Include coordination for shutoff, capping, and continuation of utility services as required.

Coordinate with adjacent facilities to permit continuing occupation of existing building and parking areas.

QUALITY ASSURANCE

Regulatory Requirements: Comply with hauling and disposal regulations of authorities having jurisdiction.

JOB CONDITIONS

Occupancy: Conduct selective demolition work in manner that will minimize need for disruption of adjacent Government’s normal operations. Provide minimum of 72 hours advance notice to Contracting Officer’s Representative of demolition activities that will affect adjacent occupied facilities.

Condition of Structures: The Government assumes no responsibility for actual condition of items or structures to be demolished.

Conditions existing at time of inspection for bidding purposes will be maintained by Government insofar as practicable.

Partial Demolition and Removal: Items indicated to be removed but of salvageable value to Contractor may be removed as work progresses. Transport salvaged items from site as they are removed.

SELECTIVE DEMOLITION 02070 - 3

Storage or sale of removed items on site will not be permitted.

Protections: Provide temporary barricades and other forms of protection to protect from injury due to selective demolition work.

Conduct operations to prevent damage to adjacent buildings, structures, sidewalks, pavements, and other facilities and to prevent injury or damage to persons or property.

Provide interior and exterior shoring, bracing, or support to prevent movement, settlement, or collapse of structure or element to be demolished and adjacent facilities or work to remain.

Remove protections at completion of work.

Damages: Promptly repair damages caused to adjacent facilities by demolition work.

Environmental Controls: Comply with governing regulations pertaining to environmental protection.

PART 2 - PRODUCTS (Not Applicable)

PART 3 - EXECUTION

EXAMINATION

Verify that utilities have been disconnected and capped.

Survey existing conditions and correlate with requirements indicated to determine extent of selective demolition required.

When unanticipated mechanical, electrical, or structural elements that conflict with the intended function or design are encountered, investigate and measure the nature and extent of the conflict. Promptly submit a written report to the Architect.

UTILITY SERVICES

Maintain existing utilities to remain in service and protect them against damage during selective demolition operations.

Do not interrupt existing utilities serving occupied or operating facilities, except when authorized in writing by Contracting Officer and authorities having jurisdiction. Provide temporary services during interruptions to existing utilities, as acceptable to Government.

SELECTIVE DEMOLITION 02070 - 4

Provide not less than 72 hours' notice to Contracting Officer if shutdown of service is required during changeover.

Utility Requirements: Locate, identify, disconnect, and seal or cap off indicated utility services.

Where utility services are required to be removed, relocated, or abandoned, provide bypass connections to maintain continuity of service to other used or occupied buildings before proceeding with selective demolition.

PREPARATION

General: Provide interior and exterior shoring, bracing, or support to preserve stability and prevent movement, settlement, or collapse of areas to be demolished.

Drain, purge, or otherwise remove, collect, and dispose of chemicals, gases, acids, or other dangerous materials before proceeding with selective demolition operations.

Conduct demolition operations and remove debris to ensure minimum interference with roads, streets, walks, and other adjacent occupied and used facilities.

Do not close or obstruct streets, walks, or other adjacent occupied or used facilities without permission from Government. Provide alternate routes around closed or obstructed traffic ways if required by governing regulations.

Conduct demolition operations to prevent injury to people and damage to adjacent buildings and facilities to remain. Ensure safe passage of people around selective demolition area.

Erect temporary protection, such as walks and fences, as needed for protection.

Protect existing site improvements, appurtenances, and landscaping to remain.

DEMOLITION

General: Perform selective demolition work in a systematic manner. Use methods required to complete work within limitations of governing regulations and as follows:

Neatly cut openings and holes plumb, square, and true to dimensions required. Use cutting methods least likely to damage construction to remain or adjoining construction. To minimize disturbance of adjacent surfaces, use hand or small power tools designed for sawing or grinding, not hammering and chopping.

Cut or drill from the exposed or finished side into concealed surfaces to avoid marring existing finished surfaces.

SELECTIVE DEMOLITION 02070 - 5

Do not use cutting torches until work area is cleared of flammable materials. At concealed spaces, such as duct and pipe interiors, verify condition and contents of hidden space before starting flame-cutting operations.

Maintain portable fire-suppression devices during flame-cutting operations.

Maintain adequate ventilation when using cutting torches.

Remove decayed, vermin-infested, or unsuitable materials and promptly dispose of off-site.

Remove structural framing members and lower to ground by method suitable to avoid free fall and to prevent ground impact or dust generation.

Return elements of construction and surfaces to remain to condition existing before start of selective demolition operations.

Locate demolition equipment throughout structure and promptly remove debris to avoid imposing excessive loads on supporting walls, floors, or framing.

Demolish concrete and masonry in small sections. Cut concrete and masonry at junctures with construction to remain, using power-driven masonry saw or hand tools; do not use power-driven impact tools.

Break up and remove concrete slabs on grade, footings, and foundations, unless otherwise shown to remain.

Completely fill below-grade areas and voids resulting from demolition work. Provide fill consisting of approved earth, gravel, or sand, free of trash and debris, stones over 6 inches in diameter, roots, or other organic matter and thoroughly compact to specified criteria per Section 02200.

DISPOSAL OF DEMOLISHED MATERIALS

Remove from building site debris, rubbish, and other materials resulting from demolition operations, unless otherwise acceptable to Contracting Officer. Transport and legally dispose off site.

If hazardous materials are encountered during demolition operations, comply with applicable regulations, laws, and ordinances concerning removal, handling, and protection against exposure or environmental pollution.

Burning of removed materials is not permitted on project site.

PATCHING AND REPAIRING

Promptly patch and repair damaged surfaces caused to adjacent construction by selective demolition operations.

SELECTIVE DEMOLITION 02070 - 6

Patching is specified in Division 1 Section "Cutting and Repairing."

Where repairs to existing surfaces are required, patch to produce surfaces suitable for new materials.

END OF SECTION 02070

FIRESTOPPING 07270 - 1

SECTION 07270 - FIRESTOPPING

RELATED DOCUMENTS

Drawings and general provisions of the Contract, including General and Division 1 Specification Sections, apply to this Section.

SUMMARY

This Section includes firestopping for the following:

Penetrations through fire-resistance-rated walls and partitions including openings containing cables, pipes, ducts, conduits, and other penetrating items.

Sealant joints in fire-resistance-rated construction.

Related Sections: The following Sections contain requirements that relate to this Section:

Division 7 Section "Building Insulation" for safing insulation and accessories.

Division 7 Section "Joint Sealants" for non-fire-resistive-rated joint sealants.

Division 15 Sections specifying ducts and piping penetrations.

Division 16 Sections specifying cable and conduit penetrations.

SYSTEM PERFORMANCE REQUIREMENTS

General: Provide firestopping systems that are produced and installed to resist the spread of fire, according to requirements indicated, and the passage of smoke and other gases.

F-Rated Through-Penetration Firestop Systems: Provide through-penetration firestop systems with F ratings indicated, as determined per ASTM E 814, but not less than that equaling or exceeding the fire-resistance rating of the constructions penetrated.

T-Rated Through-Penetration Firestop Systems: Provide through-penetration firestop systems with T ratings, in addition to F ratings, as determined per ASTM E 814, where required by code and where systems protect penetrating items exposed to contact with adjacent materials in occupiable floor areas.

T-rated assemblies are required where the following conditions exist:

Where firestop systems protect penetrations located outside of wall cavities.

FIRESTOPPING 07270 - 2

Where firestop systems protect penetrations located outside fire-resistive shaft enclosures.

Where firestop systems protect penetrations located in construction containing doors required to have a temperature-rise rating.

Where firestop systems protect penetrating items larger than a 4-inch-diameter nominal pipe or 16

sq. in. in overall cross-sectional area.

Fire-Resistive Joint Sealants: Provide joint sealants with fire-resistance ratings as determined per ASTM E 119, but not less than that equaling or exceeding the fire-resistance rating of the construction in which the joint occurs.

For firestopping exposed to view, traffic, moisture, and physical damage, provide products that do not deteriorate when exposed to these conditions.

For piping penetrations for plumbing and wet-pipe sprinkler systems, provide moisture-resistant through-penetration firestop systems.

For floor penetrations with annular spaces exceeding 4 inches or more in width and exposed to possible loading and traffic, provide firestop systems capable of supporting the floor loads involved either by installing floor plates or by other means.

For penetrations involving insulated piping, provide through-penetration firestop systems not requiring removal of insulation.

For firestopping exposed to view, provide products with flame-spread values of less than 25 and smoke-developed values of less than 450, as determined per ASTM E 84.

SUBMITTALS

General: Submit the following according to Conditions of Contract and Division 1 Specification Sections.

Product data for each type of product specified.

Certification by firestopping manufacturer that products supplied comply with local regulations controlling use of volatile organic compounds (VOCs) and are nontoxic to building occupants.

Shop drawings detailing materials, installation methods, and relationships to adjoining construction for each through-penetration firestop system, and each kind of construction condition penetrated and kind of penetrating item. Include firestop design designation of qualified testing and inspecting agency evidencing compliance with requirements for each condition indicated.

Submit documentation, including illustrations, from a qualified testing and inspecting agency that

FIRESTOPPING 07270 - 3

is applicable to each through-penetration firestop configuration for construction and penetrating items.

Fire-Test-Response Characteristics: Provide firestopping that complies with the following requirements and those specified under the "System Performance Requirements" article:

Firestopping tests are performed by a qualified testing and inspecting agency. A qualified testing and inspecting agency is UL, Warnock Hersey, or another agency performing testing and follow-up inspection services for firestop systems that is acceptable to authorities having jurisdiction.

Through-penetration firestop systems are identical to those tested per ASTM E 814 under conditions where positive furnace pressure differential of at least 0.01 inch of water is maintained at a distance of 0.78 inch below the fill materials surrounding the penetrating items in the test assembly. Provide rated systems complying with the following requirements:

Through-penetration firestop systems correspond to those indicated by reference to through-penetration firestop system designations listed by UL in their "Fire Resistance Directory," by Warnock Hersey, or by another qualified testing and inspecting agency.

Fire-resistive joint sealant systems are identical to those tested for fire-response characteristics per ASTM E 119 under conditions where the positive furnace pressure differential is at least 0.01 inch of water, as measured 0.78 inch from the face exposed to furnace fire. Provide systems complying with the following requirements:

Fire-Resistance Ratings of Joint Sealants: As indicated by reference to design designations listed by UL in their "Fire Resistance Directory" or by another qualified testing and inspecting agency.

Joint sealants, including backing materials, bear classification marking of qualified testing and inspection agency.

Single-Source Responsibility: Obtain through-penetration firestop systems for each kind of penetration and construction condition indicated from a single manufacturer.

Provide firestopping products containing no detectable asbestos as determined by the method specified in 40 CFR Part 763, Subpart F, Appendix A, Section 1, "Polarized Light Microscopy."

Coordinating Work: Coordinate construction of openings and penetrating items to ensure that designated through-penetration firestop systems are installed per specified requirements.

DELIVERY, STORAGE, AND HANDLING

FIRESTOPPING 07270 - 4

Deliver firestopping products to Project site in original, unopened containers or packages with intact and legible manufacturers' labels identifying product and manufacturer; date of manufacture; lot number; shelf life, if applicable; qualified testing and inspecting agency's classification marking applicable to Project;

curing time; and mixing instructions for multicomponent materials.

Store and handle firestopping materials to prevent their deterioration or damage due to moisture, temperature changes, contaminants, or other causes.

PROJECT CONDITIONS

Environmental Conditions: Do not install firestopping when ambient or substrate temperatures are outside limits permitted by firestopping manufacturers or when substrates are wet due to rain, frost, condensation, or other causes.

Ventilation: Ventilate firestopping per firestopping manufacturers' instructions by natural means or, where this is inadequate, forced air circulation.

PART 2 - PRODUCTS

FIRESTOPPING, GENERAL

Compatibility: Provide firestopping composed of components that are compatible with each other, the substrates forming openings, and the items, if any, penetrating the firestopping under conditions of service and application, as demonstrated by firestopping manufacturer based on testing and field experience.

Accessories: Provide components for each firestopping system that are needed to install fill materials and to comply with "System Performance Requirements" article in Part 1. Use only components specified by the firestopping manufacturer and approved by the qualified testing and inspecting agency for the designated fire-resistance-rated systems.

Applications: Provide firestopping systems composed of materials specified in this Section that comply with system performance and other requirements.

FIRE-RESISTIVE ELASTOMERIC JOINT SEALANTS

Elastomeric Sealant Standard: Provide manufacturer's standard chemically curing, elastomeric sealants of base polymer indicated that complies with ASTM C 920 requirements, including those referenced for Type, Grade, Class, and Uses, and requirements specified in this Section applicable to fire-resistive joint sealants.

Sealant Colors: Provide color of exposed joint sealants to comply with the following:

Provide selections made by Contracting Officer from manufacturer's full range of standard colors

FIRESTOPPING 07270 - 5

for products of type indicated.

Multicomponent, Nonsag, Urethane Sealant: Type M; Grade NS; Class 25; exposure-related Use NT, and joint-substrate-related Uses M, A, and (as applicable to joint substrates indicated) O.

Products: Subject to compliance with requirements, provide one of the following:

Multicomponent, Nonsag, Urethane Sealant:

Dynflex, Pecora Corp.

Dynatred, Pecora Corp.

Dynatrol II, Pecora Corp.

Sonolastic NP 2, Sonneborn Building Products Div.

ChemRex Inc.

Dymeric, Tremco Inc.

FIRE-RESISTANT JOINT SEALERS

General: Provide manufacturer's standard fire-stopping sealant, with accessory materials, having fire-resistance ratings indicated as established by testing identical assemblies per ASTM E 814 by Underwriters Laboratory, Inc. or other testing and inspecting agency acceptable to authorities having jurisdiction.

Foamed-In-Place Fire-Stopping Sealant: Two-part, foamed-in-place, silicone sealant formulated for use in a through-penetration fire-stop system for filling openings around cables, conduit, pipes and similar penetrations through walls.

Foamed-In-Place Fire-Stopping Sealant:

"Dow Corning Fire Stop Foam"; Dow Corning Corp.

"Pensil 851"; General Electric Co.

One-Part Fire-Stopping Sealant:

"3M Fire Barrier Caulk CP-25"; Electrical Products Div./3M "RTV 7403"; General Electric Co.

"Fyre Putty"; Standard Oil Engineered Materials Co.

MIXING

For those products requiring mixing prior to application, comply with firestopping manufacturer's directions for accurate proportioning of materials, water (if required), type of mixing equipment, selection of mixer speeds, mixing containers, mixing time, and other procedures needed to produce firestopping

FIRESTOPPING 07270 - 6

products of uniform quality with optimum performance characteristics for application indicated.

Examine substrates and conditions, with Installer present, for compliance with requirements for opening configurations, penetrating items, substrates, and other conditions affecting performance of firestopping.

Do not proceed with installation until unsatisfactory conditions have been corrected.

PREPARATION

Surface Cleaning: Clean out openings and joints immediately prior to installing firestopping to comply with recommendations of firestopping manufacturer and the following requirements:

Remove all foreign materials from surfaces of opening and joint substrates and from penetrating items that could interfere with adhesion of firestopping.

Clean opening and joint substrates and penetrating items to produce clean, sound surfaces capable of developing optimum bond with firestopping. Remove loose particles remaining from cleaning operation.

Remove laitance and form release agents from concrete.

Priming: Prime substrates where recommended by firestopping manufacturer using that manufacturer's recommended products and methods. Confine primers to areas of bond; do not allow spillage and migration onto exposed surfaces.

Masking Tape: Use masking tape to prevent firestopping from contacting adjoining surfaces that will remain exposed upon completion of Work and that would otherwise be permanently stained or damaged by such contact or by cleaning methods used to remove smears from firestopping materials. Remove tape as soon as it is possible to do so without disturbing firestopping's seal with substrates.

INSTALLING THROUGH-PENETRATION FIRESTOPS

General: Comply with the "System Performance Requirements" article in Part 1 and the through-penetration firestop manufacturer's installation instructions and drawings pertaining to products and applications indicated.

Install forming/damming materials and other accessories of types required to support fill materials during their application and in the position needed to produce the cross-sectional shapes and depths required to achieve fire ratings of designated through-penetration firestop systems. After installing fill materials, remove combustible forming materials and other accessories not indicated as permanent components of firestop systems.

FIRESTOPPING 07270 - 7

Install fill materials for through-penetration firestop systems by proven techniques to produce the following results:

Completely fill voids and cavities formed by openings, forming materials, accessories, and penetrating items.

Apply materials so they contact and adhere to substrates formed by openings and penetrating items.

For fill materials that will remain exposed after completing Work, finish to produce smooth, uniform surfaces that are flush with adjoining finishes.

INSTALLING FIRE-RESISTIVE JOINT SEALANTS

General: Comply with the "System Performance Requirements" article in Part 1, with ASTM C 1193, and with the sealant manufacturer's installation instructions and drawings pertaining to products and applications indicated.

Install joint fillers to provide support of sealants during application and at position required to produce the cross-sectional shapes and depths of installed sealants relative to joint widths that allow optimum sealant movement capability and develop fire-resistance rating required.

Install sealants by proven techniques that result in sealants directly contacting and fully wetting joint substrates, completely filling recesses provided for each joint configuration, and providing uniform, cross-sectional shapes and depths relative to joint width that optimum sealant movement capability. Install sealants at the same time joint fillers are installed.

Tool nonsag sealants immediately after sealant application and prior to the time skinning or curing begins.

Form smooth, uniform beads of configuration indicated or required to produce fire-resistance rating, as well as to eliminate air pockets, and to ensure contact and adhesion of sealants with sides of joint. Remove excess sealant from surfaces adjacent to joint. Do not use tooling agents that discolor sealants or adjacent surfaces or are not approved by sealant manufacturer.

CLEANING

Clean off excess fill materials and sealants adjacent to openings and joints as work progresses by methods and with cleaning materials approved by manufacturers of firestopping products and of products in which opening and joints occur.

Protect firestopping during and after curing period from contact with contaminating substances or from damage resulting from construction operations or other causes so that they are without deterioration or damage at time of Substantial Completion. If, despite such protection, damage or deterioration occurs, cut out and remove damaged or deteriorated firestopping immediately and install new materials to produce firestopping complying with specified requirements.

FIRESTOPPING 07270 - 8

END OF SECTION 07270

FINISH HARDWARE 08710 - 1

SECTION 08710 - FINISH HARDWARE

RELATED DOCUMENTS

Drawings and general provisions of Contract, including General and Division 1 Specification sections, apply to the work of this section.

DESCRIPTION OF WORK:

Definition: "Finish Hardware" includes items known commercially as finish hardware which are required for swing, sliding and folding doors, except special types of unique and non-matching hardware specified in the same section as the door and door frame.

Extent of finish hardware required is indicated on drawings and in schedules.

Types of finish hardware required include the following:

Hinges Lock cylinders and keys Lock and latch sets Bolts Exit devices Closers Overhead holders Miscellaneous door control devices Door trim units Weatherstripping for exterior doors Thresholds Smoke Gaskets

Thresholds for aluminum entrance doors are specified with entrance doors elsewhere in Division 8.

Cabinet hardware is specified in Division 6.

QUALITY ASSURANCE:

Manufacturer: Obtain each type of hardware (latch and lock sets, hinges, closers, etc.) from only one manufacturer, although several may be indicated as offering products complying with requirements.

Supplier: A recognized architectural finish hardware supplier, with warehousing facilities, who has been furnishing hardware in the project's vicinity for a period of not less than 2 years, and who is, or who employs an experienced architectural hardware consultant who is available, at reasonable times during the

FINISH HARDWARE 08710 - 2

course of the work, for consultation about project's hardware requirements, to Government, Contracting Officer and Contractor.

Fire-Rated Openings: Provide hardware for fire-rated openings in compliance with NFPA Standard No. 80 and local building code requirements. Provide only hardware which has been tested and listed by UL or FM for types and sizes of doors required and complies with requirements of door and door frame labels.

SUBMITTALS

Product Data: Submit manufacturer's technical product data for each item of hardware in accordance with Division-1 section "Submittals." Include whatever information may be necessary to show compliance with requirements, and include instructions for installation and for maintenance of operating parts and finish.

Hardware Schedule: Submit final hardware schedule in manner indicated below. Coordinate hardware with doors, frames, and related work to ensure proper size, thickness, hand, function and finish of hardware.

Final Hardware Schedule Content: Based on finish hardware indicated, organize hardware schedule into "hardware sets" indicating complete designations of every item required for each door or opening. Include the following information:

Type, style, function, size and finish of each hardware item.

Name and manufacturer of each item.

Fastenings and other pertinent information.

Location of hardware set cross-referenced to indications on Drawings both on floor plans and in door and frame schedule.

Explanation of all abbreviations, symbols, codes, etc., contained in schedule.

Mounting locations for hardware.

Door and frame sizes and materials.

Keying information.

Submittal Sequence: Submit schedule at earliest possible date particularly, where acceptance of hardware schedule must precede fabrication of other work (e.g., hollow metal frames) which is critical in the project construction schedule. Include with schedule the product data, samples, shop drawings of other work affected by finish hardware, and other information essential to the coordinated review of hardware schedule.

FINISH HARDWARE 08710 - 3

Keying Schedule: Submit separate detailed schedule indicating clearly how the Government's final instructions on keying of locks has been fulfilled.

Templates: Furnish hardware templates to each fabricator of doors, frames and other work to be factory-prepared for the installation of hardware. Upon request, check shop drawings of such other work, to confirm that adequate provisions are made for proper location and installation of hardware.

PRODUCT HANDLING:

Tag each item or package separately, with identification related to final hardware schedule, and include basic installation instructions with each item or package.

Inventory hardware jointly with representative of the hardware supplier and the hardware installer until each is satisfied that the count is correct.

Provide secure lock-up for hardware delivered to the project, but not yet installed. Control handling and installation of hardware items which are not immediately replaceable, so that completion of the work will not be delayed by hardware losses, both before and after installation.

SCHEDULED HARDWARE:

Requirements for design, grade, function, finish, size and other distinctive qualities of each type of finish hardware is indicated in the Finish Hardware Schedule at the end of this section. Products are identified by using hardware designation numbers of the following:

Manufacturer's Product Designations: One or more manufacturers are listed for each hardware type required. Provide either the product designated, or, where more than one manufacturer is listed, the comparable product of one of the other manufacturers which comply with requirements including those specified elsewhere in this section. All hardware shall comply with the Uniform Federal Accessibility Standards (UFAS).

MATERIAL AND FABRICATION:

General:

Hand of Door: Drawings show direction of slide, swing or hand of each door leaf. Furnish each item of hardware for proper installation and operation of door movement as shown.

Base Metals: Produce hardware units of basic metal and forming method indicated, using manufacturer's standard metal alloy, composition, temper and hardness, but in no case of lesser (commercially recognized) quality than specified for the applicable hardware units by applicable ANSI A156 series standard for each

FINISH HARDWARE 08710 - 4

type hardware item and with ANSI A156.18 for finish designations indicated. Do not furnish "optional" materials or forming methods for those indicated, except as otherwise specified.

Fasteners: Provide hardware manufactured to conform to published templates, generally prepared for machine screw installation. Do not provide hardware which has been prepared for self-tapping sheet metal screws, except as specifically indicated.

Furnish screws for installation, with each hardware item. Provide Phillips flat-head screws except as otherwise indicated. Finish exposed (exposed under any condition) screws to match hardware finish or, if exposed in surfaces of other work, to match finish of such other work as closely as possible, including "prepared for paint" in surfaces to receive painted finish.

Provide concealed fasteners for hardware units which are exposed when door is closed, except to extent no standard units of type specified are available with concealed fasteners. Do not use thru-bolts for installation where bolt head or nut on opposite face is exposed in other work, except where it is not feasible to adequately reinforce the work. In such cases, provide sleeves for each thru-bolt or use sex screw fasteners.

Tools and Maintenance Instructions for Maintenance: Furnish a complete set of specialized tools and maintenance instructions as needed for Government's continued adjustment, maintenance, and removal and replacement of finish hardware.

HINGES, BUTTS AND PIVOTS:

Templates: Except for hinges and pivots to be installed entirely (both leaves) into wood doors and frames, provide only template produced units.

Screws: Furnish Phillips flat-head or machine screws for installation of units, except furnish Phillips flat-head or wood screws for installation of units into wood. Finish screw heads to match surface of hinges or pivots.

Hinge Pins: Except as otherwise indicated, provide hinge pins as follows:

Steel Hinges: Steel pins.

Non-ferrous Hinges: Stainless steel pins.

Exterior Doors: Non-removable pins.

Interior Doors: Non-rising pins.

Tips: Flat button and matching plug, finished to match leaves.

Number of hinges: Provide number of hinges indicated but not less than 3 hinges for door leaf for

FINISH HARDWARE 08710 - 5

doors 90" or less in height and one additional hinge for each 30" of additional height.

LOCK CYLINDERS AND KEYING:

General: Supplier shall meet with Contracting Officer or designated representative to finalize keying requirements and obtain final instructions in writing.

Standard System: Except as otherwise indicated, provide new masterkey system on a 10-N keyway for project.

Equip locks with manufacturer's special 6-pin tumbler cylinder, with construction master key feature, which permits voiding of construction keys without cylinder removal.

Manufacturer: Subject to compliance with requirements, provide products of one of the following:

Bestlock system standard for Selfridge ANG Base, Michigan.

Metals: Construct lock cylinder parts from brass/bronze, stainless steel or nickel silver.

Comply with the Government's instructions for masterkeying and, except as otherwise indicated, provide individual change key for each lock which is not designated to be keyed alike with a group of related locks.

Permanently inscribe each key with number or lock that identifies cylinder manufacturer key symbol, and notation "U.S. GOVERNMENT DO NOT DUPLICATE."

Key Material: Provide keys of nickel silver only.

Key Quantity: Furnish 5 change keys for each lock; 5 master keys for each master system; and 5 grandmaster keys for each grandmaster system.

Deliver keys directly to Contracting Officer's representative.

Provide key control system including envelopes, labels, tags with self-locking key clips, receipt forms, 3-way visible card index, temporary markers, permanent markers, and standard metal cabinet, all as recommended by system manufacturer, with capacity for 150% of the number of locks required for the project.

LOCKS, LATCHES AND BOLTS:

Strikes: Provide manufacturer's standard wrought box strike for each latch or lock bolt, with curved lip extended to protect frame, finished to match hardware set.

Provide dust-proof strikes for foot bolts, except where special threshold construction provides non-recessed strike for bolt.

FINISH HARDWARE 08710 - 6

Provide roller type strikes where recommended by manufacturer of the latch and lock units.

Lock Throw: Provide 3/4" minimum throw of latch and locks used on pairs of doors. Comply with UL Requirements for throw of bolts and latch bolts on rated fire openings.

Provide ½" minimum throw on other latch and locks.

Provide all locks, latches, etc., with 2-3/4" backsets unless noted otherwise.

Flush Bolt Heads: Minimum of ½" diameter rods of brass, bronze or stainless steel, with minimum 12" long rod for doors up to 7'0" in height. Provide longer rods as indicated for doors exceeding 7'0" in height.

Exit Device Dogging: Except on fire-rated doors, wherever closers are provided on doors equipped with exit devices, equip the units with keyed dogging device to hold the push bar down and the latch bolt in the open position.

CLOSERS AND DOOR CONTROL DEVICES:

Size of Units: Except as otherwise specifically indicated, comply with the manufacturer's recommendations for size of door control unit, depending upon size of door, exposure to weather and anticipated frequency of use.

Where parallel arms are indicated for closers, provide closer unit one size larger than recommended for use with standard arms.

All closers on exterior doors shall be mounted on the interior face of door.

Provide drop plates or other adapter plates as required at conditions requiring them.

Combination Door Closers and Holders: Provide units designed to hold door in open position under normal usage and to release and automatically close door under fire conditions. Incorporate an integral electromagnetic holder mechanism designed for use with UL listed fire detectors, provided with normally closed switching contacts.

Combination Closer/Holder units with built-in electronic release functions shall be furnished for 24V DC current to match that of smoke detector/fire alarm system.

Connect into smoke detector/fire alarm system furnished and installed by Electrical Contractor.

Provide gray resilient parts for exposed bumpers unless indicated otherwise.

WEATHERSTRIPPING:

General: Except as otherwise indicated, provide continuous weatherstripping at each edge of every

FINISH HARDWARE 08710 - 7

exterior door leaf. Provide type, sizes and profiles shown or scheduled. Provide non-corrosive fasteners as recommended by manufacturer for application indicated.

Weatherstripping at Door Bottoms:

Provide threshold consisting of contact type resilient insert and metal housing of design and size shown.

Flexible vinyl wiper or sweep seal strip complying with CS 230-60.

Smoke and Draft Control Gasketing: Provide special silicone rubber gasketing products meeting ASTM E-152 Fire Label Standard and ASTM E-283 Air Infiltration/Smoke and Draft Control Requirements; and equal to “PEMKO” S88D “ SILICONSEAL” at head and jambs of all U.L. rated doors on this project.

THRESHOLDS:

General: Except as otherwise indicated provide standard metal threshold unit of type, size and profile as shown or scheduled.

HARDWARE FINISHES:

Provide matching finishes for hardware units at each door or opening, to the greatest extent possible, and except as otherwise indicated. Reduce differences in color and textures as much as commercially possible where the base metal or metal forming process is different for individual units of hardware exposed at the same door or opening. In general, match items to the manufacturer's standard finish for the latch and lock set for color and texture.

Provide finishes which match those established by BHMA or, if none established, match the Contracting Officer's sample.

Provide quality of finish, including thickness of plating or coating (if any), composition, hardness and other qualities complying with manufacturer's standards, but in no case, less than specified for the applicable units of hardware by referenced standards.

The designations used in schedules and elsewhere to indicate hardware finishes are those listed in ANSI A156.18 "Materials & Finishes Standard," including coordination with the traditional U.S. Finishes shown by certain manufacturers for their products.

INSTALLATION

Mount hardware units at heights indicated in "Recommended Locations for Builders Hardware for Standard Steel Doors and Frames" by the Door and Hardware Institute, except as specifically indicated or required to comply with governing regulations, and except as may be otherwise directed by Contracting Officer.

Install each hardware item in compliance with the manufacturer's instructions and recommendations.

Wherever cutting and fitting is required to install hardware onto or into surfaces which are later to be painted or finished in another way, coordinate removal, storage and reinstallation or application of surface protections with finishing work specified in the Division-9 section. Do not install surface-mounted items until finishes have been completed on the substrate.

Set units level, plumb and true to line and location. Adjust and reinforce the attachment substrate as necessary for proper installation and operation.

Drill and countersink units which are not factory-prepared for anchorage fasteners. Space fasteners and anchors in accordance with industry standards.

Set thresholds for exterior doors in full bed of butyl-rubber or polyisobutylene mastic sealant.

ADJUST AND CLEAN:

Adjust and check each operating item of hardware and each door, to ensure proper operation or function of every unit. Replace units which cannot be adjusted to operate freely and smoothly as intended for the application made.

Clean adjacent surfaces soiled by hardware installation.

FINISH HARDWARE SCHEDULE

Set 1

3 - Ea. Hinges BB81 - 4.5" x 4.5" x 652 PBB Hinge Company

1 - Office Lock-set 45H7-A-3J x 626 Best Lock Company

1 - Stop 440 x 626 Rockwood Manufacturing

3 - Silencers 608 Rockwood Manufacturing

Brand:

FINISH HARDWARE 08710 - 8

END OF SECTION 08710

GYPSUM BOARD ASSEMBLIES 09255 - 1

SECTION 09255 - GYPSUM BOARD ASSEMBLIES

PART 1 - GENERAL

RELATED DOCUMENTS

Drawings and general provisions of the Contract, including General and Division 1 Specification Sections, apply to this Section.

SUMMARY

This Section includes the following:

Non-load-bearing steel framing members for gypsum board assemblies.

Gypsum board assemblies attached to steel framing.

One hour fire-resistive ceiling assembly as scheduled.

Related Sections: The following Sections contain requirements that relate to this Section:

Division 7 Section "Firestopping" for firestopping systems and fire-resistive-rated joint sealants.

DEFINITIONS

Gypsum Board Construction Terminology: Refer to ASTM C 11 USG Systems Folder SA-923, and GA-505 for definitions of terms related to gypsum board assemblies not defined in this Section or in other referenced standards.

SUBMITTALS

Product data for each type of product specified.

QUALITY ASSURANCE

Fire-Test-Response Characteristics: Where fire-rated gypsum board assemblies are indicated, provide materials and construction identical to those of assemblies tested for fire resistance per ASTM E 119 by an independent testing and inspecting agency acceptable to authorities having jurisdiction.

Fire Resistance Ratings: As indicated by reference to GA File Numbers in GA-600 "Fire Resistance Design Manual" or to design designations in UL "Fire Resistance Directory" or in the listing of another testing and inspecting agency acceptable to authorities having jurisdiction.

Single-Source Responsibility for Steel Framing: Obtain steel framing members for gypsum board

GYPSUM BOARD ASSEMBLIES 09255 - 2

assemblies from a single manufacturer.

Single-Source Responsibility for Panel Products: Obtain each type of gypsum board and other panel products from a single manufacturer.

Single-Source Responsibility for Finishing Materials: Obtain finishing materials from either the same manufacturer that supplies gypsum board and other panel products or from a manufacturer acceptable to gypsum board manufacturer.

DELIVERY, STORAGE, AND HANDLING

Deliver materials in original packages, containers, or bundles bearing brand name and identification of manufacturer or supplier.

Store materials inside under cover and keep them dry and protected against damage from weather, direct sunlight, surface contamination, corrosion, construction traffic, and other causes. Neatly stack gypsum panels flat to prevent sagging.

Handle gypsum board to prevent damage to edges, ends, and surfaces. Do not bend or otherwise damage metal corner beads and trim.

PROJECT CONDITIONS

Environmental Conditions, General: Establish and maintain environmental conditions for applying and finishing gypsum board to comply with ASTM C 840 and with gypsum board manufacturer's recommendations.

Room Temperatures: For non-adhesive attachment of gypsum board to framing, maintain not less than 40 deg F (4 deg C). For adhesive attachment and finishing of gypsum board, maintain not less than 50 deg F (10 deg C) for 48 hours prior to application and continuously after until dry. Do not exceed 95 deg F (35 deg C) when using temporary heat sources.

Ventilation: Ventilate building spaces, as required, for drying joint treatment materials. Avoid drafts during hot dry weather to prevent finishing materials from drying too rapidly.

MANUFACTURERS

Manufacturers: Subject to compliance with requirements, provide products by one of the following:

Steel Framing and Furring:

GYPSUM BOARD ASSEMBLIES 09255 - 3

Dale Industries, Inc.

Dietrich Industries, Inc.

Gold Bond Building Products Div., National Gypsum Co.

Unimast Inc.

United States Gypsum Co.

Gypsum Board and Related Products:

Domtar Gypsum.

Georgia-Pacific Corp.

Gold Bond Building Products Div., National Gypsum Co.

United States Gypsum Co.

STEEL FRAMING COMPONENTS FOR SUSPENDED AND FURRED CEILINGS

General: Provide components complying with ASTM C 754 for materials and sizes unless otherwise indicated.

Wire for Hangers and Ties: ASTM A 641, Class 1 zinc coating, soft temper.

Channels: Cold-rolled steel, 0.05980-inch-minimum thickness of base (uncoated) metal and 7/16-inch-wide flanges, and as follows:

Carrying Channels: 1-1/2 inch deep, 475 lb per 1000 feet, unless otherwise indicated.

Finish: Rust-inhibitive paint.

Steel Rigid Furring Channels: ASTM C 645, hat-shaped, depth of 7/8 inch, and minimum thickness of base (uncoated) metal as follows:

Thickness: 0.0179 inch, unless otherwise indicated.

STEEL FRAMING FOR WALLS AND PARTITIONS

General: Provide steel framing members complying with the following requirements:

Component Sizes and Spacings: As indicated but not less than that required to comply with ASTM C 754 under the following maximum deflection and lateral loading conditions:

Maximum Deflection: L/240 at 5 lb per sq. ft.

Protective…