This solicitation is for a construction contract to perform alterations and additions to the Fire Suppression Building at the Army Aviation Support Facility in Windsor Locks, Connecticut. Work will include construction in accordance with provided contract documents, drawings and technical specifications. The project magnitude is between $1 million and $5 million. The North American Industry Classification code is 236220 for commercial and institutional building construction, and the size standard for small businesses is $39.5 million average annual revenue for the past three years. This action is set aside for total small businesses. A single award is contemplated. The bid opening date can be found in Block 13 of the solicitation. A pre-bid conference will be held on May 17th, and interested contractors are encouraged to attend. The site visit will follow. Offerors must register for the pre-bid conference and site visit in advance by email. All offerors must be registered in the System for Award Management. Drawings, specifications and other solicitation documents are available as detailed in the solicitation.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. FIRE ALARM SYSTEM SHALL COMPLY WITH UFC 3-600-01, NFPA 70, NFPA 72, NFPA 20, AND

ALL APPLICABLE CODES AND STANDARDS.

2. PENETRATIONS IN FIRE RATED ASSEMBLIES SHALL BE FIRE-STOPPED WITH LISTED

MATERIALS/ ASSEMBLIES IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.

3. FIRE SUPPRESSION SYSTEM WATERFLOW AND CONTROL VALVE SUPERVISORY

SWITCHES SHALL BE MONITORED BY THE BUILDING FIRE ALARM SYSTEM.

4. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF SYSTEM

REQUIREMENTS WITH ALL CONDITIONS OF THE BUILDING AND SITE INCLUDING, BUT NOT

LIMITED TO, BLIND SPACES, SHELVING, LIGHTS, HVAC GRILLES AND DIFFUSERS, PIPING,

DUCT WORK, DOORS, WINDOWS, EQUIPMENT PLATFORMS, WALLS (FIRE RATED AND

NON-FIRE RATED), BEAMS, JOISTS, COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS

AND EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL CONSTRUCTION, FLOORS,

AND ALL CONSTRUCTION, EQUIPMENT AND BUILDING APPURTENANCES.

5. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING,

DOCUMENTING, AND CERTIFYING REQUISITE INSPECTIONS AND TESTS IN ACCORDANCE

WITH APPLICABLE CODES AND STANDARDS FOR ALL FIRE ALARM EQUIPMENT

FURNISHED UNDER THIS PROJECT. AFTER COMPLETING THE TESTING, THE

CONTRACTOR SHALL DEMONSTRATE FULL OPERATIONAL CAPABILITY OF THE FIRE

ALARM SYSTEM, AS WELL AS FULL COMPLIANCE WITH ALL DESIGN DOCUMENTS, CODES

AND STANDARDS.

6. THE FIRE ALARM CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS MATERIAL FOR A

COMPLETE INSTALLATION.

7. EACH CONVENTIONAL FIRE ALARM DEVICE MUST HAVE ITS OWN MONITOR MODULE.

8. ALL FIRE ALARM MODULES LOCATED WITHIN 15 FEET OF A SPRINKLER/STANDPIPE

SYSTEM RISER OR FIRE PUMP SHALL BE WEATHERPROOF WITH LIQUID TIGHT CONDUIT.

9. ALL CONDUIT FROM ANY FIRE ALARM DEVICE CONNECTED TO A DEVICE THAT MAY BE IN

CONTACT WITH WATER SHALL BE LIQUID TIGHT. THIS INCLUDES, BUT IS NOT LIMITED TO,

WATERFLOW SWITCHES, PRESSURE SWITCHES, AND VALVE TAMPER SWITCHES.

10. PROVIDE A LABEL ON THE EXTERIOR OF EACH FIRE ALARM DEVICE THAT MATCHES THE

DEVICE NUMBER (ADDRESS) AT THE FACP. DEVICE ID NUMBERS SHALL BE VISIBLE FROM

THE FLOOR TO THE MAXIMUM EXTENT PRACTICAL. MONITOR MODULES AND CONTROL/

RELAY MODULES SHALL ALSO BE LABELED AS TO WHAT THEY CONTROL.

11. PULL ALL CONDUCTORS SPLICE FREE; CONDUCTORS MUST BE CONTINUOUS FROM

DEVICE TO DEVICE. THE USE OF WIRE NUTS, CRIMPED CONNECTORS, OR TWISTING OF

CONDUCTORS IS PROHIBITED.

12. SAFEGUARDING DURING CONSTRUCTION SHALL BE IN ACCORDANCE WITH ARMY CORPS

OF ENGINEERING MANUAL (EM), EM-385-1-1, SAFETY AND HEALTH REQUIREMENTS

MANUAL AND NFPA 241. CONTRACTOR SHALL COORDINATE SPECIFIC PLAN FOR FIRE

PROTECTION DURING CONSTRUCTION WITH THE CONTRACTING OFFICER.

13. PROVIDE A 520 HZ SIGNAL TEMPORAL FOUR (T4) SIGNAL FOR CARBON MONOXIDE

ALARMS IAW NFPA 72.

14. VISIBLE NOTIFICATION APPLIANCES MUST BE PROVIDED WITH A CLEAR LENS MARKED

"ALERT". THE USE OF "FIRE" IS NOT PERMITTED.

15. ALL SIGNALING LINE CIRCUITS MUST BE MIN. 18 AWG. INITIATING DEVICE AND

NOTIFICATION APPLIANCE CIRCUITS MUST BE MIN. 16 AWG.

16. ALL CONDUIT, JUNCTION/BACK BOXES, COVERS AND COUPLINGS, WHEN PROVIDED,

MUST BE FACTORY PAINTED RED.

17. PROVIDE RECHARGEABLE BATTERIES PER NFPA 72 TO OPERATE THE FIRE ALARM

SYSTEM UNDER SUPERVISORY CONDITIONS FOR 48 HOURS AND ALL ALARM DEVICES

FOR AN ADDITIONAL 15 MINUTES.

18. CONSTRUCTION (SHOP) DRAWINGS AND CALCULATIONS MUST BE PREPARED BY, OR

PREPARED UNDER THE IMMEDIATE SUPERVISION OF, THE QUALIFIED FIRE PROTECTION

ENGINEER (QFPE). THE QFPE MUST BE AN INDIVIDUAL WHO IS A REGISTERED

PROFESSIONAL ENGINEER (P.E.) WHO HAS PASSED THE FIRE PROTECTION ENGINEERING

WRITTEN EXAMINATION ADMINISTERED BY THE NATIONAL COUNCIL OF EXAMINERS FOR

ENGINEERING AND SURVEYING (NCEES) AND HAS RELEVANT FIRE PROTECTION

ENGINEERING EXPERIENCE.

19. THE QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING STAMP WITH SIGNATURE TO

THE SHOP DRAWINGS, CALCULATIONS AND MATERIAL DATA SHEETS, INDICATING

APPROVAL PRIOR TO SUBMITTING THE FIRE ALARM SYSTEM SHOP DRAWINGS TO THE

GOVERNMENT. THE QFPE MUST MONITOR THE INSTALLATION OF THE FIRE ALARM

SYSTEM AND CERTIFY IN WRITING THAT THE FIRE ALARM SYSTEM HAS BEEN

CONSTRUCTED AND OPERATE AS INTENDED IN THE DESIGN PLANS AND

SPECIFICATIONS.

FA GENERAL NOTES

C

F

M

FIRE ALARM CONTROL PANEL

TRANSIENT VOLTAGE SURGE SUPPRESSOR

MANUAL PULL STATION

SMOKE DETECTOR

SMOKE DETECTOR - DUCT

HEAT DETECTOR

HORN ONLY

HORN ONLY - WEATHER PROOF

HORN/STROBE DEVICE

- cd DENOTES CANDELA RATING

STROBE ONLY DEVICE

-cd DENOTES CANDELA RATING

WATERFLOW SWITCH

PRESSURE SWITCH

TAMPER SWITCH

ADDRESSABLE MONITOR MODULE

ADDRESSABLE CONTROL MODULE

WATERFLOW BELL

END OF LINE RESISTOR

CARBON MONOXIDE DETECTOR

RADIO TRANSMITTER

ANTENNA

CONNECT TO EXISTING

cd d

FA LEGEND

1. FIRE PROTECTION SYSTEMS SHALL COMPLY WITH PROJECT SPECIFICATIONS, UFC 3-600-01, NFPA 13, NFPA 20, AND ALL APPLICABLE CODES AND STANDARDS.

2. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE A GENERAL ARRANGEMENT OF WORK.

GENERAL DESIGN CONCEPTS INDICATED MUST BE FOLLOWED OR BETTERED. THE BID SHALL INCLUDE OFFSETS, ADDITIONAL PIPING, VALVES, AND FIRE PROTECTION EQUIPMENT AS REQUIRED TO MEET

CONSTRUCTION CONDITIONS FOR PROPER OPERATION. DEVELOP AND SUBMIT COORDINATION

DRAWINGS.

3. PIPING IS SHOWN FOR INFORMATION AND GENERAL ROUTING. THE CONTRACTOR SHALL PROVIDE

FINAL ROUTING FOR ALL PIPING AND SHALL PROVIDE SHOP DRAWINGS THAT INCLUDE: EXACT

DIMENSIONED ROUTING OF ALL PIPE, PIPE SIZES, DIMENSIONED TIE-IN LOCATIONS AT EXISTING PIPING, AND FIRE RATED CONSTRUCTION PENETRATION DETAILS. THE CONTRACTOR SHALL AVOID

INTERFERENCES WITH OTHER PIPING, EQUIPMENT, CODE REQUIRED CLEARANCES, AND THE WORK OF OTHER DISCIPLINES. FIELD ROUTED LIQUID-FILLED PIPING SHALL NOT BE ROUTED ABOVE

ELECTRICAL OR ELECTRONIC EQUIPMENT.

4. INSTALLING CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND LICENSES.

5. DESIGN AND INSTALLATION SUBJECT TO FINAL INSPECTION AND APPROVAL BY AUTHORITY HAVING

JURISDICTION.

6. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS SHALL BE DONE ONLY WITH THE

WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL ENGINEER.

7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, RATED WALLS, CEILINGS, FLOORS, ROOFS, ETC. FLASH AND COUNTERFLASH ANY ROOF PENETRATIONS.

8. METHOD OF HANGING PIPES, HEADERS, AND BRANCHLINES SHALL BE IN ACCORDANCE WITH NFPA 13.

9. ALL SUPPORTS SHALL BE ATTACHED TO THE BUILDING'S STRUCTURAL FRAME IN ACCORDANCE WITH

NFPA 13.

10. ROD STIFFENER REQUIRED FOR ALL-THREAD ROD HANGERS OVER 6'-0" IN LENGTH.

11. SEISMIC DESIGN CATEGORY IS B, REFER TO STRUCTURAL PLANS. SEISMICALLY PROTECT THE SYSTEM

PIPING AGAINST DAMAGE FROM EARTHQUAKES. THIS REQUIREMENT IS NOT SUBJECT TO

DETERMINATION UNDER NFPA 13. INSTALL THE SEISMIC PROTECTION OF THE SYSTEM PIPING IN ACCORDANCE WITH NFPA 13, NFPA 20, AND UFC 3-301-01. INCLUDE THE REQUIRED FEATURES

IDENTIFIED THEREIN THAT ARE APPLICABLE TO THE SPECIFIC PIPING SYSTEM.

12. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES INC.

AND/OR THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL" AND/OR

"FM", 175 PSI WORKING PRESSURE.

13. ALL NORMALLY OPEN VALVES ON THE FIRE PROTECTION SYSTEM SHALL BE ELECTRICALLY

SUPERVISED AND SHALL BE THE RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR.

14. PROVIDE A PERMANENTLY ATTACHED HYDRAULIC NAMEPLATE STATING THE REQUIRED DESIGN

CRITERIA FOR EACH HYDRAULICALLY DESIGNED SYSTEM IN ACCORDANCE WITH NFPA 13.

15. ONLY NEW MATERIALS SHALL BE USED IN THE INSTALLATION OF THE SPRINKLER SYSTEM.

16. PIPING 2-INCHES AND LESS MUST BE MINIMUM SCHEDULE 40. PIPING LARGER THAN 2-INCHES MUST BE

MINIMUM SCHEDULE 10 IN ACCORDANCE WITH UFC 3-600-01.

17. INSTALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.

18. SPRINKLERS INSTALLED IN HIGH HEAT AREAS, INCLUDING BUT NOT LIMITED TO, ATTIC SPACES, OR IN CLOSE PROXIMITY TO UNIT HEATERS, SHALL HAVE A TEMPERATURE CLASSIFICATION IN ACCORDANCE

WITH NFPA 13.

19. SAFEGUARDING DURING CONSTRUCTION SHALL BE IN ACCORDANCE WITH ARMY CORPS OF

ENGINEERING MANUAL (EM), EM-385-1-1, SAFETY AND HEALTH REQUIREMENTS MANUAL, NFPA 25, AND

NFPA 241. CONTRACTOR SHALL COORDINATE SPECIFIC PLAN FOR FIRE PROTECTION DURING

CONSTRUCTION WITH THE CONTRACTING OFFICER.

20. SADDLE TEES USING RUBBER GASKET FITTINGS ARE ONLY PERMITTED WHEN CONNECTING TO

EXISTING PIPING FOR ADDITIONS OR MODIFICATIONS.

21. CHANGES IN PIPE SIZES SHALL BE MADE THROUGH TAPERED REDUCING PIPE FITTINGS.

22. PROVIDE LABELING ON THE SURFACES OF THE PIPING IN THE PUMP ROOM TO SHOW THE WATER FLOW DIRECTION AND PIPE FUNCTION (E.G., "SUCTION", "DISCHARGE", "TO FIRE DEPT. CONNECTION", "TO TEST HEADER", "TO SPRINKLER SYSTEM"). PROVIDE WHITE PAINTED STENCILED LETTERS AND ARROWS, A MIN. 2" IN HEIGHT AND VISIBLE FROM AT LEAST THREE SIDES WHEN VIEWED FROM THE

FLOOR.

23. PROVIDE LABELING ON THE SURFACES OF ALL SPRINKLER FEED AND CROSS MAINS TO SHOW THE PIPE FUNCTION (E.G. "SPRINKLER SYSTEM"). FOR PIPE SIZES LESS THAN 4-INCH, PROVIDE WHITE PAINTED STENCILED LETTERS AND ARROWS, A MINIMUM 0.75-INCH IN HEIGHT AND VISIBLE FROM THE

FLOOR.

24. ALL FIRE SUPPRESSION SYSTEM VALVES MUST BE MARKED WITH PERMANENT TAGS INDICATING

NORMALLY OPEN OR NORMALLY CLOSED.

25. CONSTRUCTION (SHOP) DRAWINGS AND CALCULATIONS MUST BE PREPARED BY, OR PREPARED UNDER THE IMMEDIATE SUPERVISION OF, THE QUALIFIED FIRE PROTECTION ENGINEER (QFPE). THE QFPE MUST BE AN INDIVIDUAL WHO IS A REGISTERED PROFESSIONAL ENGINEER (P.E.) WHO HAS

PASSED THE FIRE PROTECTION ENGINEERING WRITTEN EXAMINATION ADMINISTERED BY THE

NATIONAL COUNCIL OF EXAMINERS FOR ENGINEERING AND SURVEYING (NCEES) AND HAS RELEVANT

FIRE PROTECTION ENGINEERING EXPERIENCE.

26. THE QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING STAMP WITH SIGNATURE TO THE SHOP

DRAWINGS, CALCULATIONS AND MATERIAL DATA SHEETS, INDICATING APPROVAL PRIOR TO

SUBMITTING THE FIRE PROTECTION SYSTEM SHOP DRAWINGS TO THE GOVERNMENT. THE QFPE

MUST MONITOR THE INSTALLATION OF THE FIRE PROTECTION SYSTEMS AND CERTIFY IN WRITING THAT THE FIRE PROTECTION SYSTEMS HAVE BEEN CONSTRUCTED AND OPERATE AS INTENDED IN THE

DESIGN PLANS AND SPECIFICATIONS.

FIRE PROTECTION GENERAL NOTES

FCVA

FIRE PROTECTION LEGEND

F

SP

FIRE WATER SERVICE & SUPPLY

WET-PIPE SPRINKLER MAIN

DRY-PIPE SPRINKLER MAIN

SPRINKLER DRAIN

CONTROL VALVE W/ TAMPER SWITCH

SPRINKLER FLOOR CONTROL VALVE ASSEMBLY (FCVA)

ZONE CONTROL VALVE ASSEMBLY (ZCVA)

CHECK VALVE

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

HYDRAULIC REFERENCE NODE

UPRIGHT SPRINKLER

PENDENT SPRINKLER

FS

D

DRAIN

ZCVA

WP

FACP

EXISTING FIRE PUMP DATA

PRIMARY, PUMP 1:

MAKE: PEERLESS PUMP COMPANY

MODEL: 6AEF12

TYPE: HORIZONTAL SPLIT-CASE DIESEL

RATED FLOW: 1250 GPM

RATED PRESSURE: 134 PSI

SECONDARY, PUMP 2:

MAKE: PEERLESS PUMP COMPANY

MODEL: 6AEF12

TYPE: HORIZONTAL SPLIT-CASE DIESEL

RATED FLOW: 1250 GPM

RATED PRESSURE: 134 PSI

EOL

cd

ABBREVIATIONS

AFF ABOVE FINISHED FLOOR

BFP BACKFLOW PREVENTER

CD CANDELA

CLDIP CEMENT LINED DUCTILE IRON PIPE

CP CONTROL PANEL

DB DECIBEL

FA FIRE ALARM

FAB FIRE ALARM BELL

FACP FIRE ALARM CONTROL PANEL

FDC FIRE DEPARTMENT CONNECTION

FM FM GLOBAL

FMCP FIRE ALARM MASS NOTIFICATION CONTROL PANEL

FO FIBER OPTIC

FP FIRE PROTECTION

FSD FIRE SMOKE DAMPER

GPM GALLONS PER MINUTE

IAW IN ACCORDANCE WITH

IBC INTERNATIONAL BUILDING CODE

JPCP JOCKEY PUMP CONTROL PANEL

LOC LOCAL OPERATING CONSOLE

MNS MASS NOTIFICATION SYSTEM

NAC NOTIFICATION APPLIANCE CIRCUIT

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

OS&Y OUTSIDE STEM AND YOKE

PIV POST INDICATOR VALVE

SF SQUARE FEET

SLC SIGNALING LINE CIRCUIT

SPD SURGE PROTECTION DEVICE

TD TRAVEL DISTANCE

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

UFC UNIFIED FACILITIES CRITERIA

UL UNDERWRITERS LABORATORY

WP WEATHER PROOF

RT

TVSS

APPLICABLE CODE AND STANDARDS

• 2018 INTERNATIONAL BUILDING CODE (IBC), AS REFERENCED BY UFC 1-200-01

• UFC 1-200-01, DOD BUILDING CODE (8 OCTOBER 2019)

• UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES (CHANGE 3, 1 MAY 2019)

• UFC 3-301-01, STRUCTURAL ENGINEERING (1 OCTOBER 2019)

• UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS (12 DECEMBER 2018)

• UFC 4-211-01, AIRCRAFT MAINTENANCE HANGARS (CHANGE 1, NOVEMBER 2017)

• NFPA 1, FIRE CODE (2018)

• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS (2019)

• NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION (2019)

• NFPA 22, STANDARD FOR WATER TANKS FOR PRIVATE FIRE PROTECTION (2018)

• NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR

APPURTENANCES (2019)

• NFPA 37, STANDARD FOR THE INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES AND

GAS TURBINES (2018)

• NFPA 70, NATIONAL ELECTRIC CODE (2020)

• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE (2019)

• NFPA 101, LIFE SAFETY CODE (2018)

• NFPA 409, STANDARD ON AIRCRAFT HANGARS (2016)

• NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS (2019)

Scale

Project No.

Drawing No.Date

Drawing Title

Project

360 Broad Street Hartford, CT 06105

860.493.2725 Fax 860.524.4937

Facilities Management Office

WINDSOR LOCKS, CT

REVISION

231 Main Street, Biddeford, Maine 04005 (T) 207.283.0193 (F) 207.283.4283 www.oakpoint.com

Architect/Engineer

File as:

App'd by:

Drawn by:

STATE OF CONNECTICUT

MILITARY DEPARTMENT

W917RS19R0007

1/8" = 1’−0"

F-001

FIRE PROTECTION GENERAL NOTES

FIRE SUPPRESSION BUILDING 201

ADDITIONS − ALTERATIONS

06/15/20

N. MARTIN

R. BELMONTES

Mark Date Description

1 12/19/19 30% SUBMISSION

2 03/06/20 60% SUBMISSION

3 05/19/20 90% SUBMISSION

4 06/15/20 100% FINAL DOCUMENTS

5 06/10/21 ADDENDUM #1

F

F

MM

M

M

M

M

M

M M

MM

M

M

M

M

6 6

M

TVSS TVSS

M M M

M M M

M M M

FIRE ALARM

CONTROL PANEL

M M

M M M

M

M

M

M

M M M

M M M

M M M

M M M

M

M

M

M

M

M

Scale

Project No.

Drawing No.Date

Drawing Title

Project

360 Broad Street Hartford, CT 06105

860.493.2725 Fax 860.524.4937

Facilities Management Office

WINDSOR LOCKS, CT

REVISION

231 Main Street, Biddeford, Maine 04005 (T) 207.283.0193 (F) 207.283.4283 www.oakpoint.com

Architect/Engineer

File as:

App'd by:

Drawn by:

STATE OF CONNECTICUT

MILITARY DEPARTMENT

W917RS19R0007

1/2" = 1’−0"

F-105

FIRE ALARM SYSTEM PLAN

FIRE SUPPRESSION BUILDING 201

ADDITIONS − ALTERATIONS

06/15/20

N. MARTIN

R. BELMONTES

1/2" = 1'-0"1

FIRE ALARM SYSTEM PLAN

NOT USED

FIRE WATER STORAGE TANK

WATER LEVEL AND TEMPERATURE

FIRE PUMP CONTROLLER #1

FIRE PUMP CONTROLLER #2

PRESSURE MAINTENANCE (JOCKEY) PUMP

CONTROLLER

FIRE PUMP SUCTION TAMPER SWITCH

FIRE PUMP DISCHARGE TAMPER SWITCH

TEST HEADER BYPASS TAMPER SWITCH

FIRE PUMP DISCHARGE TO SITE FIRE WATER

TAMPER SWITCH

PRESSURE MAINTENANCE (JOCKEY) PUMP

TAMPER SWITCH

SPRINKLER RISER TAMPER SWITCH

SPRINKLER RISER FLOW SWITCH

FIRE PUMP TEST HEADER TAMPER SWITCH

BUTTERFLY (THROTTLING) VALVE TAMPER

SWITCH

SURGE SUPPRESSOR TAMPER SWITCH

BACKFLOW PREVENTER TAMPER SWITCH

FIRE ALARM BELL

PROVIDE HEAT DETECTOR ABOVE FACP

PROVIDE CARBON MONOXIDE DETECTOR IAW

UFC 3-600-01 SECTION 9-19.

KEYNOTES

A. FOR GENERAL FIRE PROTECTION NOTES,

LEGEND AND SYMBOLS, SEE SHEET F-001.

B. ALL STROBES SHALL BE 75 CD UNLESS

OTHERWISE NOTED.

C. ALL MODULES LOCATED IN THE FIRE PUMP

ROOM SHALL BE WEATHERPROOF AND

PROVIDED WITH LIQUID TIGHT CONDUIT.

GENERAL NOTES

SCALE: = 1'-0"

0 2 42

1/2"

GRAPHIC SCALE

Mark Date Description

1 12/19/19 30% SUBMISSION

2 03/06/20 60% SUBMISSION

3 05/19/20 90% SUBMISSION

FIRE ALARM SYSTEM

CONTROL PANEL

BATTERIES

P U

M P

O R

C O

N T

R O

L L E

R T

R O

U B

L E

P U

M P

R U

N N

IN

G

M M

FIRE PUMP CONTROLLER #1

C O

N T

R O

L L E

R N

O T

I N

A U

T O

M

SIGNALING

LINE CIRCUIT

M MM

M M

F x2

NOTIFICATION

APPLIANCE CIRCUITx2

H

IG

H E

N G

IN

E

T E

M P

E R

A T

U R

E

F A

IL

U

R E

O F

E N

G

IN

E S

T A

R T

C R

IT

IC

A L L Y

L O

W O

IL

P

R E

S S

U R

E

M

FIRE ALARM

BELL CIRCUIT

FO

M MM

H

IG

H C

O O

L

IN

G W

A T

E R

T E

M P

E R

A T

U R

E

B A

T T

E R

Y F

A

IL

U R

E O

R M

IS

S

IN

G

B A

T T

E R

Y

S H

U T

D O

W N

F R

O M

O V

E R

S P

E E

D

M

B A

T T

E R

Y C

H A

R G

E R

F A

IL

U

R E

M

L O

W A

IR

O

R H

Y D

R A

U L

IC

P R

E S

S U

R E

M

S Y

S T

E M

O V

E R

P R

E S

S U

R E

M

L O

W F

U E

L L

E V

E L

M

F U

E L M

A

IN

T E

N A

N C

E

M

L O

W E

N G

IN

E

T E

M P

E R

A T

U R

E

M

C O

M M

O N

S U

P E

R V

IS

O

R Y

P U

M P

O R

C O

N T

R O

L L E

R T

R O

U B

L E

P U

M P

R U

N N

IN

G

M M

FIRE PUMP CONTROLLER #2

C O

N T

R O

L L E

R N

O T

I N

A U

T O

M M MM

H

IG

H E

N G

IN

E

T E

M P

E R

A T

U R

E

F A

IL

U

R E

O F

E N

G

IN

E S

T A

R T

C R

IT

IC

A L L Y

L O

W O

IL

P

R E

S S

U R

E

M MM

H

IG

H C

O O

L

IN

G W

A T

E R

T E

M P

E R

A T

U R

E

B A

T T

E R

Y F

A

IL

U R

E O

R M

IS

S

IN

G

B A

T T

E R

Y

S H

U T

D O

W N

F R

O M

O V

E R

S P

E E

D

M

B A

T T

E R

Y C

H A

R G

E R

F A

IL

U

R E

M

L O

W A

IR

O

R H

Y D

R A

U L

IC

P R

E S

S U

R E

M

S Y

S T

E M

O V

E R

P R

E S

S U

R E

M

L O

W F

U E

L L

E V

E L

M

F U

E L M

A

IN

T E

N A

N C

E

M

L O

W E

N G

IN

E

T E

M P

E R

A T

U R

E

M

C O

M M

O N

S U

P E

R V

IS

O

R Y

MMMMMM

F

IR

E P

U M

P

S

U C

T

IO

N

F

IR

E P

U M

P

D

IS

C

H A

R G

E

F

IR

E P

U M

P D

IS

C

H A

R G

E T

O S

IT

E

F

IR

E W

A T

E R

F

IR

E P

U M

P

S

U C

T

IO

N

F

IR

E P

U M

P

D

IS

C

H A

R G

E

T E

S T

H E

A D

E R

B Y

P A

S S

MMM

J O

C K

E Y

P U

M P

S U

C T

IO

N

J O

C K

E Y

P U

M P

D

IS

C H

A R

G E

J O

C K

E Y

P U

M P

C O

N T

R O

L L E

R x3 M

T A

N K

B Y

P A

S S

M

B A

C K

F L O

W P

R E

V E

N T

E R x2 M

F

IR

E P

U M

P T

E S

T H

E A

D E

R

M

S U

R G

E A

R R

E S

T O

R T

A N

K

TVSSTVSS

M

W A

T E

R T

A N

K L

O W

W A

T E

R L

E V

E L

S P

R

IN

K L E

R R

IS

E

R T

A M

P E

R

S P

R

IN

K L E

R R

IS

E

R W

A T

E R

F L O

W

M

W A

T E

R T

A N

K L

O W

T E

M P

E R

A T

U R

E

J O

C K

E Y

P U

M P

A C

P O

W E

R F

A

IL

U R

E

J O

C K

E Y

P U

M P

N O

T I

N A

U T

O

M M

J O

C K

E Y

P U

M P

R U

N N

IN

G

M

JOCKEY PUMP

CONTROLLER

DEDICATED

120 VAC TVSS

EOL

EOL

TO BLDG. 162

FACP

PROVIDE FIBER CONNECTION

BETWEEN NEW FACP AND EXIST.

FACP IN BLDG. 162. EXISTING

UNDERGROUND CONDUIT MAY BE

UTILIZED. MODIFY EXIST. FACP

TO ACCEPT FIBER CONNECTION

AS NECESSARY.

Scale

Project No.

Drawing No.Date

Drawing Title

Project

360 Broad Street Hartford, CT 06105

860.493.2725 Fax 860.524.4937

Facilities Management Office

WINDSOR LOCKS, CT

REVISION

231 Main Street, Biddeford, Maine 04005 (T) 207.283.0193 (F) 207.283.4283 www.oakpoint.com

Architect/Engineer

File as:

App'd by:

Drawn by:

STATE OF CONNECTICUT

MILITARY DEPARTMENT

W917RS19R0007

NTS

F-601

FIRE ALARM RISER

FIRE SUPPRESSION BUILDING 201

ADDITIONS − ALTERATIONS

06/15/20

N. MARTIN

R. BELMONTES

NTS1

FIRE ALARM RISER DIAGRAM

A. FOR GENERAL FIRE ALARM NOTES,

LEGEND AND SYMBOLS, SEE SHEET F-001.

B. FIRE PUMP CONTROL/MONITOR POINTS

SHALL BE IN ACCORDANCE WITH NFPA 20.

C. ACTUAL NUMBER OF DEVICES PER

NOTIFICATION CIRCUIT AND SIGNAL LINE

CIRCUIT SHALL BE DETERMINED BY THE

FIRE ALARM CONTRACTOR'S DETAILED

VOLTAGE AND BATTERY DROP

CALCULATIONS.

D. THE FIRE ALARM CONTRACTOR SHALL

PROVIDE DETAILED POINT TO POINT

WIRING DIAGRAMS WITH UNIQUE DEVICE

NAMES FOR EACH FIRE ALARM DEVICE.

E. EACH NOTIFICATION APPLIANCE CIRCUIT

SHALL INCLUDE A MINIMUM 25% SPARE

CAPACITY.

F. PROVIDE TVSS FOR ALL SIGNALING LINE

CIRCUITS, INITIATING DEVICE CIRCUITS, OR

NOTIFICATION APPLIANCE CIRCUITS THAT

LEAVE OR ENTER THE FACILITY'S

EXTERIOR ENCLOSURE.

G. PROVIDE TVSS ON ALL 120 VAC CIRCUITS

TO CONTROL PANELS, SUBPANELS,

TRANSMITTERS, AMPLIFIER PANELS, AND

BOOSTER PANELS. SPD MUST HAVE BOTH

A UL 1449 AND UL 1283 LISTING AND MUST

BE LOCATED IN AN ADJACENT HINGED

TERMINAL BOX.

H. THE EXISTING FIRE PUMP CONTROLLERS

MAY NOT BE PROVIDED WITH A

SUFFICIENT NUMBER OF CONTACTS TO

SEPARATELY MONITOR ALL OF THE

POINTS SHOWN. AT A MINIMUM, THE FIRE

ALARM SYSTEM SHALL MONITOR THE

FOLLOWING FOR EACH PUMP: THAT THE

ENGINE IS RUNNING (SEPARATE SIGNAL),

THE CONTROLLER MAIN SWITCH HAS

BEEN TURNED TO THE OFF OR MANUAL

POSITION (SEPARATE SIGNAL), AND THERE

IS TROUBLE ON THE CONTROLLER OR

ENGINER (COMMON SIGNALS).

GENERAL NOTES

Mark Date Description

1 12/19/19 30% SUBMISSION

2 03/06/20 60% SUBMISSION

3 05/19/20 90% SUBMISSION

Sheets
F-001 - FIRE PROTECTION GENERAL NOTES
F-105 - FIRE ALARM SYSTEM PLAN
F-601 - FIRE ALARM RISER