This solicitation is for a construction contract to perform alterations and additions to the Fire Suppression Building at the Army Aviation Support Facility in Windsor Locks, Connecticut. Work will include construction in accordance with provided contract documents, drawings and technical specifications. The project magnitude is between $1 million and $5 million. The North American Industry Classification code is 236220 for commercial and institutional building construction, and the size standard for small businesses is $39.5 million average annual revenue for the past three years. This action is set aside for total small businesses. A single award is contemplated. The bid opening date can be found in Block 13 of the solicitation. A pre-bid conference will be held on May 17th, and interested contractors are encouraged to attend. The site visit will follow. Offerors must register for the pre-bid conference and site visit in advance by email. All offerors must be registered in the System for Award Management. Drawings, specifications and other solicitation documents are available as detailed in the solicitation.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. FIRE ALARM SYSTEM SHALL COMPLY WITH UFC 3-600-01, NFPA 70, NFPA 72, NFPA 20, AND
ALL APPLICABLE CODES AND STANDARDS.
2. PENETRATIONS IN FIRE RATED ASSEMBLIES SHALL BE FIRE-STOPPED WITH LISTED
MATERIALS/ ASSEMBLIES IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.
3. FIRE SUPPRESSION SYSTEM WATERFLOW AND CONTROL VALVE SUPERVISORY
SWITCHES SHALL BE MONITORED BY THE BUILDING FIRE ALARM SYSTEM.
4. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF SYSTEM
REQUIREMENTS WITH ALL CONDITIONS OF THE BUILDING AND SITE INCLUDING, BUT NOT
LIMITED TO, BLIND SPACES, SHELVING, LIGHTS, HVAC GRILLES AND DIFFUSERS, PIPING,
DUCT WORK, DOORS, WINDOWS, EQUIPMENT PLATFORMS, WALLS (FIRE RATED AND
NON-FIRE RATED), BEAMS, JOISTS, COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS
AND EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL CONSTRUCTION, FLOORS,
AND ALL CONSTRUCTION, EQUIPMENT AND BUILDING APPURTENANCES.
5. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING,
DOCUMENTING, AND CERTIFYING REQUISITE INSPECTIONS AND TESTS IN ACCORDANCE
WITH APPLICABLE CODES AND STANDARDS FOR ALL FIRE ALARM EQUIPMENT
FURNISHED UNDER THIS PROJECT. AFTER COMPLETING THE TESTING, THE
CONTRACTOR SHALL DEMONSTRATE FULL OPERATIONAL CAPABILITY OF THE FIRE
ALARM SYSTEM, AS WELL AS FULL COMPLIANCE WITH ALL DESIGN DOCUMENTS, CODES
AND STANDARDS.
6. THE FIRE ALARM CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS MATERIAL FOR A
COMPLETE INSTALLATION.
7. EACH CONVENTIONAL FIRE ALARM DEVICE MUST HAVE ITS OWN MONITOR MODULE.
8. ALL FIRE ALARM MODULES LOCATED WITHIN 15 FEET OF A SPRINKLER/STANDPIPE
SYSTEM RISER OR FIRE PUMP SHALL BE WEATHERPROOF WITH LIQUID TIGHT CONDUIT.
9. ALL CONDUIT FROM ANY FIRE ALARM DEVICE CONNECTED TO A DEVICE THAT MAY BE IN
CONTACT WITH WATER SHALL BE LIQUID TIGHT. THIS INCLUDES, BUT IS NOT LIMITED TO,
WATERFLOW SWITCHES, PRESSURE SWITCHES, AND VALVE TAMPER SWITCHES.
10. PROVIDE A LABEL ON THE EXTERIOR OF EACH FIRE ALARM DEVICE THAT MATCHES THE
DEVICE NUMBER (ADDRESS) AT THE FACP. DEVICE ID NUMBERS SHALL BE VISIBLE FROM
THE FLOOR TO THE MAXIMUM EXTENT PRACTICAL. MONITOR MODULES AND CONTROL/
RELAY MODULES SHALL ALSO BE LABELED AS TO WHAT THEY CONTROL.
11. PULL ALL CONDUCTORS SPLICE FREE; CONDUCTORS MUST BE CONTINUOUS FROM
DEVICE TO DEVICE. THE USE OF WIRE NUTS, CRIMPED CONNECTORS, OR TWISTING OF
CONDUCTORS IS PROHIBITED.
12. SAFEGUARDING DURING CONSTRUCTION SHALL BE IN ACCORDANCE WITH ARMY CORPS
OF ENGINEERING MANUAL (EM), EM-385-1-1, SAFETY AND HEALTH REQUIREMENTS
MANUAL AND NFPA 241. CONTRACTOR SHALL COORDINATE SPECIFIC PLAN FOR FIRE
PROTECTION DURING CONSTRUCTION WITH THE CONTRACTING OFFICER.
13. PROVIDE A 520 HZ SIGNAL TEMPORAL FOUR (T4) SIGNAL FOR CARBON MONOXIDE
ALARMS IAW NFPA 72.
14. VISIBLE NOTIFICATION APPLIANCES MUST BE PROVIDED WITH A CLEAR LENS MARKED
"ALERT". THE USE OF "FIRE" IS NOT PERMITTED.
15. ALL SIGNALING LINE CIRCUITS MUST BE MIN. 18 AWG. INITIATING DEVICE AND
NOTIFICATION APPLIANCE CIRCUITS MUST BE MIN. 16 AWG.
16. ALL CONDUIT, JUNCTION/BACK BOXES, COVERS AND COUPLINGS, WHEN PROVIDED,
MUST BE FACTORY PAINTED RED.
17. PROVIDE RECHARGEABLE BATTERIES PER NFPA 72 TO OPERATE THE FIRE ALARM
SYSTEM UNDER SUPERVISORY CONDITIONS FOR 48 HOURS AND ALL ALARM DEVICES
FOR AN ADDITIONAL 15 MINUTES.
18. CONSTRUCTION (SHOP) DRAWINGS AND CALCULATIONS MUST BE PREPARED BY, OR
PREPARED UNDER THE IMMEDIATE SUPERVISION OF, THE QUALIFIED FIRE PROTECTION
ENGINEER (QFPE). THE QFPE MUST BE AN INDIVIDUAL WHO IS A REGISTERED
PROFESSIONAL ENGINEER (P.E.) WHO HAS PASSED THE FIRE PROTECTION ENGINEERING
WRITTEN EXAMINATION ADMINISTERED BY THE NATIONAL COUNCIL OF EXAMINERS FOR
ENGINEERING AND SURVEYING (NCEES) AND HAS RELEVANT FIRE PROTECTION
ENGINEERING EXPERIENCE.
19. THE QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING STAMP WITH SIGNATURE TO
THE SHOP DRAWINGS, CALCULATIONS AND MATERIAL DATA SHEETS, INDICATING
APPROVAL PRIOR TO SUBMITTING THE FIRE ALARM SYSTEM SHOP DRAWINGS TO THE
GOVERNMENT. THE QFPE MUST MONITOR THE INSTALLATION OF THE FIRE ALARM
SYSTEM AND CERTIFY IN WRITING THAT THE FIRE ALARM SYSTEM HAS BEEN
CONSTRUCTED AND OPERATE AS INTENDED IN THE DESIGN PLANS AND
SPECIFICATIONS.
FA GENERAL NOTES
C
F
M
FIRE ALARM CONTROL PANEL
TRANSIENT VOLTAGE SURGE SUPPRESSOR
MANUAL PULL STATION
SMOKE DETECTOR
SMOKE DETECTOR - DUCT
HEAT DETECTOR
HORN ONLY
HORN ONLY - WEATHER PROOF
HORN/STROBE DEVICE
- cd DENOTES CANDELA RATING
STROBE ONLY DEVICE
-cd DENOTES CANDELA RATING
WATERFLOW SWITCH
PRESSURE SWITCH
TAMPER SWITCH
ADDRESSABLE MONITOR MODULE
ADDRESSABLE CONTROL MODULE
WATERFLOW BELL
END OF LINE RESISTOR
CARBON MONOXIDE DETECTOR
RADIO TRANSMITTER
ANTENNA
CONNECT TO EXISTING
cd d
FA LEGEND
1. FIRE PROTECTION SYSTEMS SHALL COMPLY WITH PROJECT SPECIFICATIONS, UFC 3-600-01, NFPA 13, NFPA 20, AND ALL APPLICABLE CODES AND STANDARDS.
2. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE A GENERAL ARRANGEMENT OF WORK.
GENERAL DESIGN CONCEPTS INDICATED MUST BE FOLLOWED OR BETTERED. THE BID SHALL INCLUDE OFFSETS, ADDITIONAL PIPING, VALVES, AND FIRE PROTECTION EQUIPMENT AS REQUIRED TO MEET
CONSTRUCTION CONDITIONS FOR PROPER OPERATION. DEVELOP AND SUBMIT COORDINATION
DRAWINGS.
3. PIPING IS SHOWN FOR INFORMATION AND GENERAL ROUTING. THE CONTRACTOR SHALL PROVIDE
FINAL ROUTING FOR ALL PIPING AND SHALL PROVIDE SHOP DRAWINGS THAT INCLUDE: EXACT
DIMENSIONED ROUTING OF ALL PIPE, PIPE SIZES, DIMENSIONED TIE-IN LOCATIONS AT EXISTING PIPING, AND FIRE RATED CONSTRUCTION PENETRATION DETAILS. THE CONTRACTOR SHALL AVOID
INTERFERENCES WITH OTHER PIPING, EQUIPMENT, CODE REQUIRED CLEARANCES, AND THE WORK OF OTHER DISCIPLINES. FIELD ROUTED LIQUID-FILLED PIPING SHALL NOT BE ROUTED ABOVE
ELECTRICAL OR ELECTRONIC EQUIPMENT.
4. INSTALLING CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND LICENSES.
5. DESIGN AND INSTALLATION SUBJECT TO FINAL INSPECTION AND APPROVAL BY AUTHORITY HAVING
JURISDICTION.
6. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS SHALL BE DONE ONLY WITH THE
WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL ENGINEER.
7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, RATED WALLS, CEILINGS, FLOORS, ROOFS, ETC. FLASH AND COUNTERFLASH ANY ROOF PENETRATIONS.
8. METHOD OF HANGING PIPES, HEADERS, AND BRANCHLINES SHALL BE IN ACCORDANCE WITH NFPA 13.
9. ALL SUPPORTS SHALL BE ATTACHED TO THE BUILDING'S STRUCTURAL FRAME IN ACCORDANCE WITH
NFPA 13.
10. ROD STIFFENER REQUIRED FOR ALL-THREAD ROD HANGERS OVER 6'-0" IN LENGTH.
11. SEISMIC DESIGN CATEGORY IS B, REFER TO STRUCTURAL PLANS. SEISMICALLY PROTECT THE SYSTEM
PIPING AGAINST DAMAGE FROM EARTHQUAKES. THIS REQUIREMENT IS NOT SUBJECT TO
DETERMINATION UNDER NFPA 13. INSTALL THE SEISMIC PROTECTION OF THE SYSTEM PIPING IN ACCORDANCE WITH NFPA 13, NFPA 20, AND UFC 3-301-01. INCLUDE THE REQUIRED FEATURES
IDENTIFIED THEREIN THAT ARE APPLICABLE TO THE SPECIFIC PIPING SYSTEM.
12. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES INC.
AND/OR THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL" AND/OR
"FM", 175 PSI WORKING PRESSURE.
13. ALL NORMALLY OPEN VALVES ON THE FIRE PROTECTION SYSTEM SHALL BE ELECTRICALLY
SUPERVISED AND SHALL BE THE RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR.
14. PROVIDE A PERMANENTLY ATTACHED HYDRAULIC NAMEPLATE STATING THE REQUIRED DESIGN
CRITERIA FOR EACH HYDRAULICALLY DESIGNED SYSTEM IN ACCORDANCE WITH NFPA 13.
15. ONLY NEW MATERIALS SHALL BE USED IN THE INSTALLATION OF THE SPRINKLER SYSTEM.
16. PIPING 2-INCHES AND LESS MUST BE MINIMUM SCHEDULE 40. PIPING LARGER THAN 2-INCHES MUST BE
MINIMUM SCHEDULE 10 IN ACCORDANCE WITH UFC 3-600-01.
17. INSTALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
18. SPRINKLERS INSTALLED IN HIGH HEAT AREAS, INCLUDING BUT NOT LIMITED TO, ATTIC SPACES, OR IN CLOSE PROXIMITY TO UNIT HEATERS, SHALL HAVE A TEMPERATURE CLASSIFICATION IN ACCORDANCE
WITH NFPA 13.
19. SAFEGUARDING DURING CONSTRUCTION SHALL BE IN ACCORDANCE WITH ARMY CORPS OF
ENGINEERING MANUAL (EM), EM-385-1-1, SAFETY AND HEALTH REQUIREMENTS MANUAL, NFPA 25, AND
NFPA 241. CONTRACTOR SHALL COORDINATE SPECIFIC PLAN FOR FIRE PROTECTION DURING
CONSTRUCTION WITH THE CONTRACTING OFFICER.
20. SADDLE TEES USING RUBBER GASKET FITTINGS ARE ONLY PERMITTED WHEN CONNECTING TO
EXISTING PIPING FOR ADDITIONS OR MODIFICATIONS.
21. CHANGES IN PIPE SIZES SHALL BE MADE THROUGH TAPERED REDUCING PIPE FITTINGS.
22. PROVIDE LABELING ON THE SURFACES OF THE PIPING IN THE PUMP ROOM TO SHOW THE WATER FLOW DIRECTION AND PIPE FUNCTION (E.G., "SUCTION", "DISCHARGE", "TO FIRE DEPT. CONNECTION", "TO TEST HEADER", "TO SPRINKLER SYSTEM"). PROVIDE WHITE PAINTED STENCILED LETTERS AND ARROWS, A MIN. 2" IN HEIGHT AND VISIBLE FROM AT LEAST THREE SIDES WHEN VIEWED FROM THE
FLOOR.
23. PROVIDE LABELING ON THE SURFACES OF ALL SPRINKLER FEED AND CROSS MAINS TO SHOW THE PIPE FUNCTION (E.G. "SPRINKLER SYSTEM"). FOR PIPE SIZES LESS THAN 4-INCH, PROVIDE WHITE PAINTED STENCILED LETTERS AND ARROWS, A MINIMUM 0.75-INCH IN HEIGHT AND VISIBLE FROM THE
FLOOR.
24. ALL FIRE SUPPRESSION SYSTEM VALVES MUST BE MARKED WITH PERMANENT TAGS INDICATING
NORMALLY OPEN OR NORMALLY CLOSED.
25. CONSTRUCTION (SHOP) DRAWINGS AND CALCULATIONS MUST BE PREPARED BY, OR PREPARED UNDER THE IMMEDIATE SUPERVISION OF, THE QUALIFIED FIRE PROTECTION ENGINEER (QFPE). THE QFPE MUST BE AN INDIVIDUAL WHO IS A REGISTERED PROFESSIONAL ENGINEER (P.E.) WHO HAS
PASSED THE FIRE PROTECTION ENGINEERING WRITTEN EXAMINATION ADMINISTERED BY THE
NATIONAL COUNCIL OF EXAMINERS FOR ENGINEERING AND SURVEYING (NCEES) AND HAS RELEVANT
FIRE PROTECTION ENGINEERING EXPERIENCE.
26. THE QFPE MUST AFFIX THEIR PROFESSIONAL ENGINEERING STAMP WITH SIGNATURE TO THE SHOP
DRAWINGS, CALCULATIONS AND MATERIAL DATA SHEETS, INDICATING APPROVAL PRIOR TO
SUBMITTING THE FIRE PROTECTION SYSTEM SHOP DRAWINGS TO THE GOVERNMENT. THE QFPE
MUST MONITOR THE INSTALLATION OF THE FIRE PROTECTION SYSTEMS AND CERTIFY IN WRITING THAT THE FIRE PROTECTION SYSTEMS HAVE BEEN CONSTRUCTED AND OPERATE AS INTENDED IN THE
DESIGN PLANS AND SPECIFICATIONS.
FIRE PROTECTION GENERAL NOTES
FCVA
FIRE PROTECTION LEGEND
F
SP
FIRE WATER SERVICE & SUPPLY
WET-PIPE SPRINKLER MAIN
DRY-PIPE SPRINKLER MAIN
SPRINKLER DRAIN
CONTROL VALVE W/ TAMPER SWITCH
SPRINKLER FLOOR CONTROL VALVE ASSEMBLY (FCVA)
ZONE CONTROL VALVE ASSEMBLY (ZCVA)
CHECK VALVE
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
HYDRAULIC REFERENCE NODE
UPRIGHT SPRINKLER
PENDENT SPRINKLER
FS
D
DRAIN
ZCVA
WP
FACP
EXISTING FIRE PUMP DATA
PRIMARY, PUMP 1:
MAKE: PEERLESS PUMP COMPANY
MODEL: 6AEF12
TYPE: HORIZONTAL SPLIT-CASE DIESEL
RATED FLOW: 1250 GPM
RATED PRESSURE: 134 PSI
SECONDARY, PUMP 2:
MAKE: PEERLESS PUMP COMPANY
MODEL: 6AEF12
TYPE: HORIZONTAL SPLIT-CASE DIESEL
RATED FLOW: 1250 GPM
RATED PRESSURE: 134 PSI
EOL
cd
ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
BFP BACKFLOW PREVENTER
CD CANDELA
CLDIP CEMENT LINED DUCTILE IRON PIPE
CP CONTROL PANEL
DB DECIBEL
FA FIRE ALARM
FAB FIRE ALARM BELL
FACP FIRE ALARM CONTROL PANEL
FDC FIRE DEPARTMENT CONNECTION
FM FM GLOBAL
FMCP FIRE ALARM MASS NOTIFICATION CONTROL PANEL
FO FIBER OPTIC
FP FIRE PROTECTION
FSD FIRE SMOKE DAMPER
GPM GALLONS PER MINUTE
IAW IN ACCORDANCE WITH
IBC INTERNATIONAL BUILDING CODE
JPCP JOCKEY PUMP CONTROL PANEL
LOC LOCAL OPERATING CONSOLE
MNS MASS NOTIFICATION SYSTEM
NAC NOTIFICATION APPLIANCE CIRCUIT
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
OS&Y OUTSIDE STEM AND YOKE
PIV POST INDICATOR VALVE
SF SQUARE FEET
SLC SIGNALING LINE CIRCUIT
SPD SURGE PROTECTION DEVICE
TD TRAVEL DISTANCE
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
UFC UNIFIED FACILITIES CRITERIA
UL UNDERWRITERS LABORATORY
WP WEATHER PROOF
RT
TVSS
APPLICABLE CODE AND STANDARDS
• 2018 INTERNATIONAL BUILDING CODE (IBC), AS REFERENCED BY UFC 1-200-01
• UFC 1-200-01, DOD BUILDING CODE (8 OCTOBER 2019)
• UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES (CHANGE 3, 1 MAY 2019)
• UFC 3-301-01, STRUCTURAL ENGINEERING (1 OCTOBER 2019)
• UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS (12 DECEMBER 2018)
• UFC 4-211-01, AIRCRAFT MAINTENANCE HANGARS (CHANGE 1, NOVEMBER 2017)
• NFPA 1, FIRE CODE (2018)
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS (2019)
• NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION (2019)
• NFPA 22, STANDARD FOR WATER TANKS FOR PRIVATE FIRE PROTECTION (2018)
• NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR
APPURTENANCES (2019)
• NFPA 37, STANDARD FOR THE INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES AND
GAS TURBINES (2018)
• NFPA 70, NATIONAL ELECTRIC CODE (2020)
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
• NFPA 101, LIFE SAFETY CODE (2018)
• NFPA 409, STANDARD ON AIRCRAFT HANGARS (2016)
• NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS (2019)
Scale
Project No.
Drawing No.Date
Drawing Title
Project
360 Broad Street Hartford, CT 06105
860.493.2725 Fax 860.524.4937
Facilities Management Office
WINDSOR LOCKS, CT
REVISION
231 Main Street, Biddeford, Maine 04005 (T) 207.283.0193 (F) 207.283.4283 www.oakpoint.com
Architect/Engineer
File as:
App'd by:
Drawn by:
STATE OF CONNECTICUT
MILITARY DEPARTMENT
W917RS19R0007
1/8" = 1’−0"
F-001
FIRE PROTECTION GENERAL NOTES
FIRE SUPPRESSION BUILDING 201
ADDITIONS − ALTERATIONS
06/15/20
N. MARTIN
R. BELMONTES
Mark Date Description
1 12/19/19 30% SUBMISSION
2 03/06/20 60% SUBMISSION
3 05/19/20 90% SUBMISSION
4 06/15/20 100% FINAL DOCUMENTS
5 06/10/21 ADDENDUM #1
F
F
MM
M
M
M
M
M
M M
MM
M
M
M
M
6 6
M
TVSS TVSS
M M M
M M M
M M M
FIRE ALARM
CONTROL PANEL
M M
M M M
M
M
M
M
M M M
M M M
M M M
M M M
M
M
M
M
M
M
Scale
Project No.
Drawing No.Date
Drawing Title
Project
360 Broad Street Hartford, CT 06105
860.493.2725 Fax 860.524.4937
Facilities Management Office
WINDSOR LOCKS, CT
REVISION
231 Main Street, Biddeford, Maine 04005 (T) 207.283.0193 (F) 207.283.4283 www.oakpoint.com
Architect/Engineer
File as:
App'd by:
Drawn by:
STATE OF CONNECTICUT
MILITARY DEPARTMENT
W917RS19R0007
1/2" = 1’−0"
F-105
FIRE ALARM SYSTEM PLAN
FIRE SUPPRESSION BUILDING 201
ADDITIONS − ALTERATIONS
06/15/20
N. MARTIN
R. BELMONTES
1/2" = 1'-0"1
FIRE ALARM SYSTEM PLAN
NOT USED
FIRE WATER STORAGE TANK
WATER LEVEL AND TEMPERATURE
FIRE PUMP CONTROLLER #1
FIRE PUMP CONTROLLER #2
PRESSURE MAINTENANCE (JOCKEY) PUMP
CONTROLLER
FIRE PUMP SUCTION TAMPER SWITCH
FIRE PUMP DISCHARGE TAMPER SWITCH
TEST HEADER BYPASS TAMPER SWITCH
FIRE PUMP DISCHARGE TO SITE FIRE WATER
TAMPER SWITCH
PRESSURE MAINTENANCE (JOCKEY) PUMP
TAMPER SWITCH
SPRINKLER RISER TAMPER SWITCH
SPRINKLER RISER FLOW SWITCH
FIRE PUMP TEST HEADER TAMPER SWITCH
BUTTERFLY (THROTTLING) VALVE TAMPER
SWITCH
SURGE SUPPRESSOR TAMPER SWITCH
BACKFLOW PREVENTER TAMPER SWITCH
FIRE ALARM BELL
PROVIDE HEAT DETECTOR ABOVE FACP
PROVIDE CARBON MONOXIDE DETECTOR IAW
UFC 3-600-01 SECTION 9-19.
KEYNOTES
A. FOR GENERAL FIRE PROTECTION NOTES,
LEGEND AND SYMBOLS, SEE SHEET F-001.
B. ALL STROBES SHALL BE 75 CD UNLESS
OTHERWISE NOTED.
C. ALL MODULES LOCATED IN THE FIRE PUMP
ROOM SHALL BE WEATHERPROOF AND
PROVIDED WITH LIQUID TIGHT CONDUIT.
GENERAL NOTES
SCALE: = 1'-0"
0 2 42
1/2"
GRAPHIC SCALE
Mark Date Description
1 12/19/19 30% SUBMISSION
2 03/06/20 60% SUBMISSION
3 05/19/20 90% SUBMISSION
FIRE ALARM SYSTEM
CONTROL PANEL
BATTERIES
P U
M P
O R
C O
N T
R O
L L E
R T
R O
U B
L E
P U
M P
R U
N N
IN
G
M M
FIRE PUMP CONTROLLER #1
C O
N T
R O
L L E
R N
O T
I N
A U
T O
M
SIGNALING
LINE CIRCUIT
M MM
M M
F x2
NOTIFICATION
APPLIANCE CIRCUITx2
H
IG
H E
N G
IN
E
T E
M P
E R
A T
U R
E
F A
IL
U
R E
O F
E N
G
IN
E S
T A
R T
C R
IT
IC
A L L Y
L O
W O
IL
P
R E
S S
U R
E
M
FIRE ALARM
BELL CIRCUIT
FO
M MM
H
IG
H C
O O
L
IN
G W
A T
E R
T E
M P
E R
A T
U R
E
B A
T T
E R
Y F
A
IL
U R
E O
R M
IS
S
IN
G
B A
T T
E R
Y
S H
U T
D O
W N
F R
O M
O V
E R
S P
E E
D
M
B A
T T
E R
Y C
H A
R G
E R
F A
IL
U
R E
M
L O
W A
IR
O
R H
Y D
R A
U L
IC
P R
E S
S U
R E
M
S Y
S T
E M
O V
E R
P R
E S
S U
R E
M
L O
W F
U E
L L
E V
E L
M
F U
E L M
A
IN
T E
N A
N C
E
M
L O
W E
N G
IN
E
T E
M P
E R
A T
U R
E
M
C O
M M
O N
S U
P E
R V
IS
O
R Y
P U
M P
O R
C O
N T
R O
L L E
R T
R O
U B
L E
P U
M P
R U
N N
IN
G
M M
FIRE PUMP CONTROLLER #2
C O
N T
R O
L L E
R N
O T
I N
A U
T O
M M MM
H
IG
H E
N G
IN
E
T E
M P
E R
A T
U R
E
F A
IL
U
R E
O F
E N
G
IN
E S
T A
R T
C R
IT
IC
A L L Y
L O
W O
IL
P
R E
S S
U R
E
M MM
H
IG
H C
O O
L
IN
G W
A T
E R
T E
M P
E R
A T
U R
E
B A
T T
E R
Y F
A
IL
U R
E O
R M
IS
S
IN
G
B A
T T
E R
Y
S H
U T
D O
W N
F R
O M
O V
E R
S P
E E
D
M
B A
T T
E R
Y C
H A
R G
E R
F A
IL
U
R E
M
L O
W A
IR
O
R H
Y D
R A
U L
IC
P R
E S
S U
R E
M
S Y
S T
E M
O V
E R
P R
E S
S U
R E
M
L O
W F
U E
L L
E V
E L
M
F U
E L M
A
IN
T E
N A
N C
E
M
L O
W E
N G
IN
E
T E
M P
E R
A T
U R
E
M
C O
M M
O N
S U
P E
R V
IS
O
R Y
MMMMMM
F
IR
E P
U M
P
S
U C
T
IO
N
F
IR
E P
U M
P
D
IS
C
H A
R G
E
F
IR
E P
U M
P D
IS
C
H A
R G
E T
O S
IT
E
F
IR
E W
A T
E R
F
IR
E P
U M
P
S
U C
T
IO
N
F
IR
E P
U M
P
D
IS
C
H A
R G
E
T E
S T
H E
A D
E R
B Y
P A
S S
MMM
J O
C K
E Y
P U
M P
S U
C T
IO
N
J O
C K
E Y
P U
M P
D
IS
C H
A R
G E
J O
C K
E Y
P U
M P
C O
N T
R O
L L E
R x3 M
T A
N K
B Y
P A
S S
M
B A
C K
F L O
W P
R E
V E
N T
E R x2 M
F
IR
E P
U M
P T
E S
T H
E A
D E
R
M
S U
R G
E A
R R
E S
T O
R T
A N
K
TVSSTVSS
M
W A
T E
R T
A N
K L
O W
W A
T E
R L
E V
E L
S P
R
IN
K L E
R R
IS
E
R T
A M
P E
R
S P
R
IN
K L E
R R
IS
E
R W
A T
E R
F L O
W
M
W A
T E
R T
A N
K L
O W
T E
M P
E R
A T
U R
E
J O
C K
E Y
P U
M P
A C
P O
W E
R F
A
IL
U R
E
J O
C K
E Y
P U
M P
N O
T I
N A
U T
O
M M
J O
C K
E Y
P U
M P
R U
N N
IN
G
M
JOCKEY PUMP
CONTROLLER
DEDICATED
120 VAC TVSS
EOL
EOL
TO BLDG. 162
FACP
PROVIDE FIBER CONNECTION
BETWEEN NEW FACP AND EXIST.
FACP IN BLDG. 162. EXISTING
UNDERGROUND CONDUIT MAY BE
UTILIZED. MODIFY EXIST. FACP
TO ACCEPT FIBER CONNECTION
AS NECESSARY.
Scale
Project No.
Drawing No.Date
Drawing Title
Project
360 Broad Street Hartford, CT 06105
860.493.2725 Fax 860.524.4937
Facilities Management Office
WINDSOR LOCKS, CT
REVISION
231 Main Street, Biddeford, Maine 04005 (T) 207.283.0193 (F) 207.283.4283 www.oakpoint.com
Architect/Engineer
File as:
App'd by:
Drawn by:
STATE OF CONNECTICUT
MILITARY DEPARTMENT
W917RS19R0007
NTS
F-601
FIRE ALARM RISER
FIRE SUPPRESSION BUILDING 201
ADDITIONS − ALTERATIONS
06/15/20
N. MARTIN
R. BELMONTES
NTS1
FIRE ALARM RISER DIAGRAM
A. FOR GENERAL FIRE ALARM NOTES,
LEGEND AND SYMBOLS, SEE SHEET F-001.
B. FIRE PUMP CONTROL/MONITOR POINTS
SHALL BE IN ACCORDANCE WITH NFPA 20.
C. ACTUAL NUMBER OF DEVICES PER
NOTIFICATION CIRCUIT AND SIGNAL LINE
CIRCUIT SHALL BE DETERMINED BY THE
FIRE ALARM CONTRACTOR'S DETAILED
VOLTAGE AND BATTERY DROP
CALCULATIONS.
D. THE FIRE ALARM CONTRACTOR SHALL
PROVIDE DETAILED POINT TO POINT
WIRING DIAGRAMS WITH UNIQUE DEVICE
NAMES FOR EACH FIRE ALARM DEVICE.
E. EACH NOTIFICATION APPLIANCE CIRCUIT
SHALL INCLUDE A MINIMUM 25% SPARE
CAPACITY.
F. PROVIDE TVSS FOR ALL SIGNALING LINE
CIRCUITS, INITIATING DEVICE CIRCUITS, OR
NOTIFICATION APPLIANCE CIRCUITS THAT
LEAVE OR ENTER THE FACILITY'S
EXTERIOR ENCLOSURE.
G. PROVIDE TVSS ON ALL 120 VAC CIRCUITS
TO CONTROL PANELS, SUBPANELS,
TRANSMITTERS, AMPLIFIER PANELS, AND
BOOSTER PANELS. SPD MUST HAVE BOTH
A UL 1449 AND UL 1283 LISTING AND MUST
BE LOCATED IN AN ADJACENT HINGED
TERMINAL BOX.
H. THE EXISTING FIRE PUMP CONTROLLERS
MAY NOT BE PROVIDED WITH A
SUFFICIENT NUMBER OF CONTACTS TO
SEPARATELY MONITOR ALL OF THE
POINTS SHOWN. AT A MINIMUM, THE FIRE
ALARM SYSTEM SHALL MONITOR THE
FOLLOWING FOR EACH PUMP: THAT THE
ENGINE IS RUNNING (SEPARATE SIGNAL),
THE CONTROLLER MAIN SWITCH HAS
BEEN TURNED TO THE OFF OR MANUAL
POSITION (SEPARATE SIGNAL), AND THERE
IS TROUBLE ON THE CONTROLLER OR
ENGINER (COMMON SIGNALS).
GENERAL NOTES
Mark Date Description
1 12/19/19 30% SUBMISSION
2 03/06/20 60% SUBMISSION
3 05/19/20 90% SUBMISSION
| Sheets |
| F-001 - FIRE PROTECTION GENERAL NOTES |
| F-105 - FIRE ALARM SYSTEM PLAN |
| F-601 - FIRE ALARM RISER |