GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

PANELBOARD SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

RECEPTACLE,TELEPHONE OUTLET 305mm TO CENTER OF THE ENCL

MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL

1676mm TO CENTER OF THE ENCL

2286mm TO CENTER OF BELL

3.

4.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

7.

COORDINATED WITH THE CENTRAL FIRE DEPARTMENT SO THAT

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

ON CEILINGDETECTOR

1372mm TO CENTER OF STATIONMANUAL PULL STATION

5.

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT

THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING

TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.

DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT

F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

SCOPE OF WORKS

LEGEND, GENERAL NOTES AND

E-1

1.

SCOPE OF WORK

F/A & MNS EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE MANUFACTURER AND MODEL OF NEW F/A& MNS EQUIPMENT SHALL BE

F/A &MNS CONTROL

COMBO. SPEAKER & STROBE

3.

2.

6.

12.

13.

14.

5.

4.

A. REPAIR/MAINTENANCE ( K )

10.

11.

8.

9.

15.

SINGLE POLE TOGGLE SWITCH, 15A-125V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

S

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

T

J

THERMOSTAT (UNDER MECH. ITEM)

JUNCTION BOX

SYMBOL

SYMBOL

F FAN MOTOR (UNDER MECH. ITEM)

SAFETY SWITCH

C CONTROL CIRCUIT

3-WAY SWITCH, 15A-125V

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

CABNET TYPE, RATED WATT ON LTG SCHEDULE

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER

ON LTG SCHEDULE, WET LOCATION

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

PANELBOARD

3S

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

NEW.

W/COVER PLATES AND ASSOCIATED WIRING & CONDUIT WITH

REPLACE EXISTING CATV CABINETS & PULLBOXES, OUTLETS

CEILING.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

FIXTURE A MINIMUM DISTANCE OF 458mm.

FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING

7.

FMCP

FTR

ANTENNA

AUXILIARY

DESCRIPTION

F

TELEPHONE OUTLET

SYMBOL

CTC CATV SYSTEM CABINET

CATV OUTLET

ADDRESSABLE FA MANUAL PULL STATION

WP

F M

TTB

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL

TELEPHONE TERMINAL BOARD

TV

MOUNTED TYPE

F/A & MASS NOTIFICATION SPEAKER "WP" WALL

STROBES

WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL

CONNECTION

BUILDING TRANSMITTER UNIT FOR FIRE ALARM

SYSTEM

F FIRE ALARM SYSTEM CIRCUIT

WIRING FOR TELEPHONE LINET

BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL

WIRING CONCEALED IN THE CEILING AND WALL

F/M

8.

L

PHOTOCELL

WP

TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING

L

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

L

W/EMERGENCY UNIT

WIRING TO UPSTAIR OR DOWNSTAIR

TYPE

QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

SYSTEM WITH ASSOCIATED ACCESSORIES.

REMOVE AND REINSTALL EXISTING CCTV CAMERAS & MONITORING

9.

REMOVE EXISTING PUBLIC ADDRESS SYSTEM INCLUDING SPEAKERS.

UNITS.

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

CONDUITS WITH NEW.

SWITCHES, PHOTOCELL, LIGHTING CONTACTOR, WIRES AND

LIGHTS, EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY

REPLACE DETERIORATED EXISTING LIGHTING FIXTURES, EXIT

AND ASSOCIATED WIRING AND CONDUIT WITH NEW.

EQUIPMENT RACK AND ACCESSORIES, OUTLETS W/ COVER PLATES

REPLACE DETERIORATED EXISTING TELEPHONE TERMINAL BOARD,

16.

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING

LIGHTING CONTACTOR, SEL SW (H-O-A)

REPAIR BLDG S-473

CAMP CASEYTAK, YS

130946

LINE, HANDHOLE AND ACCESSORIES WITH NEW.

REPLACE EXISTING EXTERIOR UNDERGROUND TELECOMMUNICATION

WIRING AND CONDUIT.

REQ'D) DEVICE, LOCAL OPERATING CONSOLE AND ASSOCIATED

VISUAL SIGNAL STROBES, MICROPHONE, SPEAKER (WATTAGE AS

DETECTOR & RELAY MODULE, BUILDING TRANSMITTER, ANTENNA,

NOTIFICATION SYSTEM PANEL, MANUAL PULL STATION, SMOKE

NEW ADDRESSABLE FIRE ALARM CONTROL AND MASS

REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH

WITH NEW.

CONTROL SYSTEM, WIRES AND CONDUITS FOR HVAC SYSTEM

STARTERS, MANUAL MOTOR STARTERS, JUNCTION BOXES,

COMBINATION MOTOR STARTERS, MAGNETIC MOTOR

REPLACE DETERIORATED EXISTING SAFETY SWITCHES,

CONDUIT WITH NEW.

PLATES, CIRCUIT BREAKER, AND ASSOCIATED WIRING &

PANELBOARD FRONT COVERS, RECEPTACLES AND COVER

REPLACE EXISTING PANELBOARDS, WATT HOUR METER,

FAULT CIRCUIT INTERRUPTION TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND

FAULT CIRCUIT INTERRUPTION TYPE, WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND

VEH BR

MH25-4

MH25-4-1

B

492'

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES1.

NOTES

2.

THE CONTRACTOR SHALL VERIFY EXISTING3.

UNDERGROUND TELECOMM LINE'S ACTUAL

CONDITION PRIOR TO WORK.

SEE SHEET NO. E-1.

REPAIR BLDG NO. S-473

CAMP CASEYTAK, YS

130946

DISTRIBUTION PLAN

EXIST/NEW EXTERIOR TELECOMM

ELECTRICAL

E-2

458Z

SCALE :

1/500

EXIST/NEW EXTERIOR TELECOMM DISTRIBUTION PLAN

C

C

COMM RM

1WAY: 1-12 CORE, SINGLE MODE FIBER OPTIC CABLE IN 4-4" FABRIC INNER DUCT

NEW U/G COMM LINE 2WAY OF 103C

SEE NOTE 2 BELOW

IN EXIST TELE MANHOLE

(1-12 CORE, SINGLE MODE FIBER OPTIC CABLE)

EXIST COMM MANHOLE

(TYPICAL)

SINGLE MODE FIBER OPTIC CABLE

"MH25-4" TO "MH25-4-1)

IN EXISTING CONDUIT (TYPICAL FROM

/RESTORE GROUND AS IT IS. (TYPICAL)

1WAY: EMPTY CONDUIT W/ PULL WIRE & 4" FABRIC INNER DUCT

NEW U/G 1-12 CORE

NEW SPLICE KIT

C

(TYPICAL)

SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.

NEW 1-12 CORE, SINGLE MODE FIBER OPTIC CABLE,

NEW COMM HANDHOLE

TYPE OF SPLICE KITS AND LOCATION OF NEW HANDHOLE

SCALE: 1/100

EWC

E W

C

FEC

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

COMMO SHOP

114A 114B

JAN

STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

FEC

D

W

W

D

W/D

W/D

NBC ROOM

ARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

E W

C

FECFEC

UPDN

UPDN

REF

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

SCALE: 1/100

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-3

J

J

J

J

J J

J

J J J J

J J J

J J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J J J

JJ

J

J J

J J

J

J

J

J

J

J J

J

J

J

J

J

J J

J

J J

J

J

J

J

J J J J J

J

J

J

J

J

J

J

S

S

S

S

S

S S

S

S

3S 3S

S

S

S

S

S

J

J J

J

J

J

J

J

J

J

J

JJ

J

J

S

S

SSS

S

S

3 3 3

S

L

L

L L

LL

L

L

L

L

L

L L

L L L

LL

LL

LLL

L L

L

LL

L

LL

L

L

LL

L

L

L L

L

LLLL

L

L L L L L L L L L L L L L L L

L L

L

L

L

L

L L

L

L L L

L

L L

L L

L

LL

L L

L L

L

L

L

L L L L L L L L L L L L L L L L

L

L

L

SS S

S

S

S

S3

S3

SSSS

S

S

S

S

S

S

S

S

S

L

J

LIGHTING CIRCUIT

PARKING AREA

RECONNECT EXIST

ORIENTED FACING NORTH

600W, 120V, 1PH

PHOTOELECTRIC

FOR ARMS ROOM

REPLACE W/ NEW WALL MOUNTED LED LIGHT

1ST FLOOR LIGHTING PLAN

2ND, 3RD AND 4TH FLOOR LIGHTING PLAN

PLAN

1ST, 2ND, 3RD AND 4TH FLOOR LIGHTING

MODULE PLAN ON E-9

SEE TYPICAL BEDROOM ELECTRICAL

L

L

L

OFFICE

OFFICE

ADMIN OFFICEADMIN OFFICE

L L

LL

L

L

L

L

L L

LL

LL

SS

CONTACTOR

CONNECT TO LIGHTING

2ND FL ONLY

EXTERIOR LIGHT, TYPE "NS-12"

CIRCUIT BREAKERS

CONN. TO EXIST

CONTACTOR AND WIRING DIAGRAM FOR APPROVAL

CONTRACTOR SHALL PROVIDE SHOP DRAWING FOR LIGHTING

1EA-(H-O-A) SELECTOR SWITCH, NEMA 4X ENCL.

CONTACTS(NO), MECHANICALLY HELD LIGHTING CONTACTOR,

: LIGHTING CONTACTOR, 120V, 60HZ COIL W/2EA-20A, CONNECT TO EXISTING LIGHT CIRCUIT (TYPICAL)

W

W

W

W

D

D

D

D

LL

L L

MULTI-PURPOSE RM

ARMS RM

SS

L L

LLL

LL

L

LAUNDRY

REPAIR BLDG S-473

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-4

DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W

WALL SURFACE MOUNTED LIGHT EMITTING

NS-7

NS-4a & 4b NS-6a & 6b

NS-8

100 WALL

NS-9

245mm

254mm

NS-5a & 5b

NS-10

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,

CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED) FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES

WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

WET LOCATION SHOWER LIGHT TRIM, UL LISTED POWER UNIT

AS REQUIRED, UL LISTED POWER UNIT W/BUILT-IN PHOTOCELL, WET LOCATION TYPE, UL LISTED

CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 25W, UL LISTED, WITH CONVERTER &

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

NS-11a & NS-11b NS-12

WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT

FIXTURE, 1PH, 120V, 60 WATT, CONVERTER AND ACCESSORIES

UNDERCABINET LED LIGHT FIXTURE

1PH, 120V, 17W, CONVERTER AND ACCESSORIES,

WET LOCATIONS TYPE(IP66), UL LISTED POWER,

MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.

NS-3a & NS-3b

(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER,

SINGLE FACE(NS-3a) & DOUBLE FACE(NS-3b)

LIGHTING FIXTURE DETAILS

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER &

ACCESSORIES AS REQUIRED, (NS-4a) & WITH EM UNIT (NS-4b) FIXTURE, 1PH, 120V, 50W, UL LISTED, WITH CONVERTER &

ACCESSORIES, (NS-5a) & WITH EM UNIT (NS-5b) AS REQUIRED

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND

ACCESSORIES AS REQUIRED, (NS-6a) & EM UNIT(NS-6b)

UL LISTED POWER UNIT

ACCESSORIES AS REQUIRED, (NS-11a) & WITH EM UNIT (NS-11b)

REPAIR BLDG S-473

CAMP CASEYTAK, YS

130946

WALL MOUNTED LED LIGHT FIXTURE,

1PH, 120V, 22W LED LAMP,CONVERTER AND ACCESSORIES,

POWER UNIT

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-5

MOUNTING METHOD

LIGHTING FIXTURE SCHEDULE

LAMP

TYPENO

ROOM

NAME WATTS

COE STD DET 40-06-04

TYPE

NO

SHT

Q'TY REMARKS

- EXIT LIGHT WALL MOUNTED5NS-3a -

CEILING SURFACE1NS-3b -

DOUBLE FACE

1/4.99

SINGLE FACE,

ABOVE DOOR TOP

WITH ARROW

- EXTERIOR WALL MOUNTED3-

CEILING SURFACE6NS-3a -1/4.99

SINGLE FACE

WITH ARROW

MECH ROOM126 CEILING SURFACE4-

CEILING SURFACE1- W/EM UNIT

BEDROOM201A,B~

DAY RM215 CEILING RECESSED3-

214A,B

CEILING RECESSED1- W/EM UNIT

UNDER CABINET MTD1-

JANITOR216 CEILING SURFACE1-

LAUNDRY217 CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STAIR-1218A CEILING SURFACE2-

STAIR-2218B CEILING SURFACE2-

W/EM UNIT

W/EM UNIT

CORRIDOR219 CEILING RECESSED12-

CEILING RECESSED5- W/EM UNIT

CEILING RECESSED4-

CEILING RECESSED2-DRESS ROOM

BATH ROOM CEILING RECESSED2-

WALL MOUNTED2-

BEDROOM301A,B~

315 CEILING RECESSED3-

314A,B

CEILING RECESSED1- W/EM UNIT

JANITOR316 CEILING SURFACE1-

LAUNDRY317 CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STAIR-1318A CEILING SURFACE2-

STAIR-2318B CEILING SURFACE2-

W/EM UNIT

W/EM UNIT

CORRIDOR319 CEILING RECESSED12-

CEILING RECESSED5- W/EM UNIT

CEILING RECESSED4-

CEILING RECESSED2-DRESS ROOM

BATH ROOM CEILING RECESSED2-

WALL MOUNTED2-

BEDROOM401A,B~

MULTI-PURPOSE415 CEILING RECESSED3-

414A,B

CEILING RECESSED1- W/EM UNIT

JANITOR416 CEILING SURFACE1-

LAUNDRY417 CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STAIR-1418A CEILING SURFACE2-

STAIR-2418B CEILING SURFACE2-

W/EM UNIT

W/EM UNIT

CORRIDOR419 CEILING RECESSED12-

CEILING RECESSED5- W/EM UNIT

CEILING RECESSED4-

CEILING RECESSED2-DRESS ROOM

BATH ROOM CEILING RECESSED2-

WALL MOUNTED2-

ROOM

WALL MOUNTED7NS-12 -

NS-6a

NS-6b 45

NS-4a

NS-4b

NS-8 17

NS-7 18

NS-5a

NS-5b 50

17NS-10

NS-7 18

NS-4a 45

45NS-4b

W/EM UNIT

NS-6b

NS-6b 45

NS-11a

NS-11b 25

NS-4a 45

45NS-4b

NS-8 17

18NS-7

W/EM UNIT

DAY RM NS-5a

NS-5b 50

17NS-10

NS-7 18

NS-4a 45

45NS-4b

NS-6b

NS-6b 45

NS-11a

NS-11b 25

NS-4a 45

45NS-4b

NS-8 17

18NS-7

NS-5a

NS-5b 50

17NS-10

NS-7 18

NS-4a 45

45NS-4b

NS-6b

NS-6b 45

NS-11a

NS-11b 25

NS-9

1/4.99

- 1

UNDER CABINET MTD

UNDER CABINET MTD

ELECTRICAL

LIGHTING FIXTURE SCHEDULE

1-LED NS-4b 45125 W/EM UNITCEILING RECESSED

MOUNTING METHOD

LIGHTING FIXTURE SCHEDULE

LAMP

TYPENO

ROOM

NAME WATTS

COE STD DET 40-06-04

TYPE

NO

SHT

Q'TY REMARKS

CEILING RECESSED5-

CEILING RECESSED1-

1-

5-

STORAGE103 CEILING RECESSED

COMMUNITY ROOM104 CEILING RECESSED5-

CEILING RECESSED1- W/EM UNIT

ADMIN OFFICE105 CEILING RECESSED7-

CEILING RECESSED1- W/EM UNIT

COMM RM105A CEILING SURFACE1-

WAIT AREA106 CEILING RECESSED1- W/EM UNIT

T.O106A CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

R.O106B CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STORAGE106C CEILING SURFACE1-

C.O107 CEILING RECESSED2-

CEILING RECESSED1- W/EM UNIT

X.O108 CEILING RECESSED2-

CEILING RECESSED1- W/EM UNIT

COMM109 CEILING RECESSED2-

CEILING RECESSED1- W/EM UNIT

110 3-

1-

NBC ROOM

111 5-

1-

W/EM UNIT

W/EM UNIT

COMMO SHOP112 2-

MALE114A CEILING RECESSED1-

WALL MOUNTED1-

FEMALE114B CEILING RECESSED1-

WALL MOUNTED1-

JANITOR113 CEILING SURFACE1-

MUIL-PURPOSE

115 3-

1-

ROOM

W/EM UNIT

CEILING RECESSED5-

CEILING RECESSED1- W/EM UNIT

STORAGE

CEILING RECESSED1-117

CEILING RECESSED1-C.Q118

1-

W/EM UNIT

LAUNDRY

1-

1-

1-

1- W/EM UNIT

3-

1- W/EM UNIT

VEST120

CEILING RECESSED1-

W/EM UNIT

W/EM UNIT

W/EM UNIT

LED 50

NS-5a

NS-5b

W/EM UNIT

W/EM UNIT

NS-6b 45 1-

NS-6a 45 - 1

NS-5a

NS-5b

NS-5a

NS-5b 50

NS-6a 45

NS-5b 50

NS-5a

NS-5b 50

NS-5a

NS-5b 50

NS-6a 45

NS-5a

NS-5b 50

NS-5a

NS-5b 50

NS-5a

NS-5b 50

NS-6a

NS-6b 45

NS-6a

NS-6b 45

NS-6a 45

NS-6b 45 - 1 W/EM UNIT

NS-7 18 -

NS-4a 45

45NS-4b

NS-8 18

NS-4b

NS-8 18

NS-6a

NS-6b 45

NS-5a

NS-5b 50

45NS-4a

NS-4b 45

NS-6a

NS-6b 45

- 1

NS-4b 45

W/EM UNIT

NS-4a

NS-4b

CEILING SURFACE

CEILING RECESSED

CEILING RECESSED

CEILING RECESSEDNS-4a 45

101 ADMIN OFFICE

ADMIN OFFICE NS-5a

NS-5b CEILING RECESSED

CEILING RECESSED

W/EM UNIT

ARMS ROOM

ARMS ROOM

119A

119B

STAIR-1

STAIR-2

JANITOR

LAUNDRY

11-

6-

W/EM UNIT124 CEILING RECESSEDNS-11b 25

CORRIDOR

VEST

NS-11b

NS-4b

NS-7

NS-4b 45 - 1 CEILING RECESSED W/EM UNIT

W/EM UNIT

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

REPAIR BLDG S-473

CAMP CASEYTAK, YS

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

109110

COMMO SHOP

114A

114B

JAN

MULTI-PURPOSE RM

STORAGE

117MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

NBC ROOM

ARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

UPDN

REF

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B 318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

418B

418A

319 419

DAY RM

SCALE: 1/100

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-6

J

J

J

EWC

EWC

F

FCU

FF

FCU

F

FCU

F

FCU

F

FCU

F

FCU

F

FCU

F C

U

S

S

S

F

FCU

F

FCU

J

J

J

EWC

ER

R

RH

FF

FCU

F

TV

TV

S

S

EWC

TV

TV

J J J J JJJ

SS

2ND, 3RD & 4TH FLOOR POWER PLAN

1ST FLOOR POWER PLAN

TT

T

RH

"P1A"

"P1B"

"P2A" "P3A" "P4A"

"P2B" "P3B" "P4B"

P4B-38

T

M D

P

J

"L1"

"L2" "L3" "L4"

A/C

+1800

JF

L1-1

L1-2

L2,3,4-7

L2,3,4-6 L2,3,4-3

L2,3,4-2

L2,3,4-4

L2,3,4-5

L2,3,4-1

"P"

TO P4B-40

FROM PANELBOARD "P"

TO LOADCENTER "L1","L2"&"L3"

TO P-5

1/10HP (MECH ITEM)

EXHAUST FAN, 1PH,115V,

ADDITIONAL LEGEND (THIS SHEET ONLY)

GROUNDING TYPE AND COVER FACE PLATE

D

REPLACE EXIST RECEPTACLE20

W/NEW SINGLE RECPTACLE, 2P-3W-20A-125V,

GROUNDING TYPE, PLUG AND COVER FACE

REPLACE EXIST SINGLE RECEPTACLE

W/NEW SINGLE RECPTACLE,

PLATE FOR DRYER, 1PH-120/208V-5KW

FOR ELECTRIC WATER COOLER, 1PH-115V-1/5HP

REPLACE EXIST RECEPTACLE

EWC

W/NEW DUPLEX RECPTACLE, 2P-3W-20A-125V,

(TYPICAL)

(TYPICAL)

3P-4W-30A-125/250V, S MANUAL MOTOR STARTER

1PH-115V-1HP (MAX.)

(2P-100AF-20AT, 10000AIC)

W/O.L RELAYS, 3-POSITION SEL.

SWITCH (A-O-H) & PILOT LAMPS, NEMA 1 ENCL.

W D

D D

2#12 & 1#12(G) IN 16C

PROVIDE NEW WIRING

(TYPICAL)

SAFETY SWITCH, 2PST-240V-30A

A

B

1PH, 120V, 1/2HP

AIR HANDLING UNIT,

LOADCENTER "L2","L3","L4"

TO PANELBOARD "P" FROM

M

MAG.MOTOR STARTER, 2P-120V,

NEMA SIZE "00",

ER

GROUNDING TYPE, PLUG AND COVER FACE

REPLACE EXIST SINGLE RECEPTACLE

W/NEW SINGLE RECPTACLE,

(TYPICAL)

3P-4W-50A-125/250V, PLATE FOR ELECTRIC RANGE

RECONNECT TO EXIST

WIRING(TYPICAL)

FOR WASHER, REF., FAN COIL UNIT, MICROWAVE

M

1PH,115V,1.7FLA (MECH ITEM)

CONDENSATE DRAIN LIFT PUMP,

B

SAFETY SWITCH, 2PST-240V-30A

A

NON-FUSIBLE. NEMA 3R ENCL

NON-FUSIBLE. NEMA 1 ENCL

TO P-6

RECONNECT TO EXIST

WIRING(TYPICAL)

MDP-10

FLOOR ONLY (MECH ITEM)(TYPICAL)

ROOF FAN, 1PH, 120V, 1/15HP @ 4TH

115V, 1.5KW (MECH ITEM)

SPLIT AIR CONDITIONING UNIT, 1PH,

J

1PH,115V, 1/12HP (MECH ITEM)

EXHAUST FAN FOR TOILET,

EF5

EF4EF4EF4EF4EF4EF4EF4

EF3

EF3

EF1

EF1

"P2A", "P2B", "P3A", "P3B","P4A" & "P4B")

WITH NEW (TYPICAL FOR PANELBOARD "P1A", "P1B",

REPLACE EXIST FRONT COVER OF PANELBOARD

1ST, 2ND, 3RD & 4TH FLOOR POWER PLAN

MODULE PLAN ON E-9

SEE TYPICAL BEDROOM ELECTRICAL

70mm dia C.

4-3/0 & 1#4(G) IN

IN 36mm C.

3#4& 1#8(G)

IN 22mm C.

3#10& 1#10(G)

W,R,F,M,RH

OVEN, RANGE HOOD

W W

T

T

J

J

J

J

J

W/PULLING WIRE (TYPICAL)

EMPTY COPNDUIT 22mm C

TO PNLBD "P1B"

IN 16mmC

1-4PAIR CAT6

NOTE

1.

CONDITION.

FOR J-SIID SYSTEM WIRING TO MEET SITE

RELOCATE WIRING AND JUNCTION BOXES

CONTRACTOR IS RESPONSIBLE TO

F

FCU

F

FCU

F

FCU

F

FCU

F

FCUFCU

F

FCU

F

F

FCU

T

T T

T

T T TT

C

C

C

C

C

C

OFFICE

OFFICE

FF

TT

FF

C

C

C

C

J

L2,4-8 J

L2,4-8

FLOOR)

(TYP OF 4EA@2ND&4TH

HEATER,1PH, 208V, 2KW

ELEC. CABINET UNIT

PLATE WITH NEW (TYPICAL)

REPLACE EXIST RECEPTACLE AND COVER

(TYPICAL)

THERMOSTAT (MECH ITEM)

NEW TVSS

SURGE SUPPRESSOR)

TVSS(TRANSIENT VOLTAGE

T

T

C

C

F

FCU

C

C

F

C

C

C C

C

W

W

W

W

D

D

D

D

D

D

D

D

D

W

L1-3

L1-4

L1-5

L1-6

L1-7

L1-8

L1-9

L1-10

C

W W

W W

F

FCU

T T

C C

J J J

J

J

J

J

J

J

ARMS RM

"MDP" FOR PANELBOARD "P"

BREAKER (3P-225AF-225AT) IN

"MDP"/ REPLACE WITH NEW CIRCUIT

EXIST MAIN DIST. PANELBOARD

J

J

JJ

J

U

P

M

L

L

M

P

U

CC

SENSOR TRANSCEIVER (TYP.)

ULTRASONIC MOTION

NEW JUNCTION BOX FOR

SIGNAL PROCESSOR (TYP.)

ULTRASONIC MOTION SENSOR

NEW JUNCTION BOX FOR

(TYP.)

FOR CONTROL UNIT

NEW JUNCTION BOX

ALARM SWITCH(TYP.)

FLOOR MOUNTED LATCHING

NEW JUNCTION BOX FOR

(15 cm ABOVE DOOR )(TYP.)

BALANCED MAGNETIC SWITCH

NEW JUNCTION BOX FOR

IN 16mmC

1-4PAIR CAT6

W/PULLING WIRE (TYPICAL)

EMPTY COPNDUIT 22mm C

S

EF3

J

P-14

REPAIR BLDG S-473

CAMP CASEYTAK, YS

130946

GFCI TYPE AND COVER FACE PLATE

J

J

J

J

J J

JJ

JJJ

JJ

J

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-7

"L3 &"L4" LOAD SCHEDULE

PANELBOARD "P" & LOAD CENTER "L1","L2",

TOTAL LOAD 13115

LOAD

TOTAL

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B P AT

SIZE

AF AIC

BA N G

REMARK

360 360

1 10000100 2#12&1#12(G)20

7 8

EXH FAN-5, 83W

MTD TYPE, NEMA 1 ENCL.

60HZ, SN & GND, FLUSH

1PHASE ,3WIRE, 120/240V,

ELEC RANGE, 6470W

1 20

3#8&1#10(G)

SHUNT-TRIP

3#10&1#10(G)

HOOD FAN 2.0A & REF, 1/4HP

LOADCENTER "L2-L4" LOAD SCHEDULE

RCPTS 180VAx2

CATV RCPTS 180VA

CATV RCPTS 360VA 360

180 180

360 360

500 500SPARE

SPARE

SPARE

2#12&1#12(G)

6300 6815

3#4& 1#8(G) IN 36mm C.

TOTAL DEMAND LOAD ; 10784 (VA)

MAIN LUG 100A

ELECTRIC UNIT HEATER 1000 2#12&1#12(G)

1000 1000

SPARE

SPARE

1000 1000

500 500

WASHER

DRYER

20 2#12&1#12(G)

13 SPARE 1000 1000 -

TOTAL LOAD 26840

LOAD

TOTAL

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKERPHASE LOAD

A B P AT

SIZE

AF AIC

BA N G

REMARK

360 360

1 10000100 2#12&1#12(G)20

22504500

EXH FAN-5, 83W

MTD TYPE, NEMA 1 ENCL.

60HZ, SN & GND, FLUSH

3PHASE, 4WIRE, 120/240V,

CATV RCPTS 180VA

CATV RCPTS 360VA

1 20

3#2& 1#6(G) IN 42mm C.

TOTAL DEMAND LOAD ; 23374 (VA)

MAIN LUG 100A

SPARE 1000 1000

PANELBOARD "L1" LOAD SCHEDULE

DRYER

WASHER

DRYER

WASHER

DRYER

DRYER

DRYER

14 SPARE 1000

2250 2250

10540

2#12&1#12(G)

3#10&1#10(G)

C

WASHER

WASHER

WASHER

C

9010 7290

1 20 2#12&1#12(G)

26840

LOAD CENTER, "L2"

LOAD CENTER, "L3"

LOAD CENTER, "L4"

3PHASE ,4WIRE, 120/208V,

MTD TYPE, NEMA 1 ENCL.

100 100003

28670

REMARK

GNA CB

AICAF

SIZE

ATC PBA

PHASE LOAD

CIRCUIT BREAKER

CONNECTION

DIAGRAM

S/N

GND

CKT

NO.

LOAD DESCRIPTION

TOTAL

LOAD

206052791077185TOTAL LOAD

1000 1000

120 120

3 30

SPACE

SPACE

PANELBOARD "P" LOAD SCHEDULE 60HZ, SN & GND, FLUSH

13115 6300 6815

13115 6300 6815

13115 6300 6815

UNIT

SPLIT AIR CONDITIONING

PUMP

CONDENSATE DRAIN LIFT

EQUIPMENT RACK(LAN)

TELEPHONE TERMINAL BOARD

FMCP

FMBP#1

FMBP#2

FMBP#3

TVSS

2#12&1#12(G)

SPARE

SPACE

SPACE

TOTAL DEMAND LOAD ; 62116 (VA)

4-3/0 & 1#4(G) IN

70mm dia C.

3#2&1#6(G)

SPACE

4#10&1#10(G)

MAIN 3P-225AF-225A MAIN

W/LOCK

SPACE SPACE

3#4&1#8(G)

105409010 7290

PANELBOARD, "L1"

SPACE

SPACE

SPACE

SPACE SPACE

SPARE 1000

2#12&1#12(G)

W/LOCK

2#12&1#12(G)

1 20

1 20

EXHAUST FAN, 1/12HP

REPAIR BLDG S-473

CAMP CASEYTAK, YS

130946

BE ACTIVATED IN CASE OF FIRE ALARM CONDITION.

SHUNT TRIP COIL SHALL BE CONNECTED TO NEW FIRE ALARM CONTROL SYSTEM TO

UH

J

MJS

MJ M J

MJ

J

J

EFJ

M D

P

ADDITIONAL LEGEND (THIS SHEET ONLY)

PILOT LAMPS, NEMA 1 ENCL.

W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H) &

MAGNETIC MOTOR STARTER, 2P-120V, NEMA SIZE "00",A

NEMA 1 ENCL.

C

(UNDER MECH. ITEM)

3PH-200V-5HP

H.W.CIRC.PUMP

(UNDER MECH. ITEM)

3PH-200V-7 /2HP

CH.W.CIRC.PUMP

(UNDER MECH. ITEM)

1PH-115V-1/20HP

UNIT HEATER

M-19

(UNDER MECH. ITEM)

1PH-115V-1/4HP

D.H.W.CIRC.PUMP

(UNDER MECH. ITEM)

A

DC

D

B

3#8 & 1#8(G) IN 27C

3#12 & 1#12(G) IN 21C

(TYPICAL)

(TYPICAL)

CONTROL TRANSFORMER & PILOT LAMPS,

W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H),

NEMA 1 ENCL.

B

(TYPICAL)

1P-115V-1HP (MAX.),

MANUAL MOTOR STARTER,S

NEMA 1 ENCL.

3-POSITION SEL. SW (H-O-A), W/PILOT LAMP (GREEN),

MANUAL MOTOR STARTER, 1P-115V-1HP (MAX.),

S

1/50SCALE:

3#10 & 1#10(G) IN 21C

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-8

1/50SCALE:

D.H.W RECIR. PUMP

3PH-200V-1-1/2HP

EXIST H.W. BOILER

EXIST D.H.W. HEATER

TYPICAL BEDROOM ELECTRICAL MODULE PLAN

MDP-14

MDP-16

MDP-12

MDP-9

MDP-6

MDP-7

MECH. RM PARTIAL POWER PLAN

PLAN & MECH. RM PARTIAL POWER PLAN

TYPICAL BEDROOM ELECTRICAL MODULE

MDP-11

MDP-13

M C

B

EXIST PANELBOARD "MDP"

MAG. MOTOR STARTER, 3P-208V, NEMA SIZE "0",

W

P

W H

M

EXIST CT'S

CT'S

EXIST MAIN CIRCUIT BREAKER "MCB"

T

T THERMOSTAT (MECH ITEM)

BED ROOM A BED ROOM B

F

SB

L L

3S

S

S S

S

3S

3S

S

SJ

L

L

L L L

L

J

J J a

J b b b b b b a a a a a

SB

FCUFCU

PLATE W/NEW (TYPICAL)

TV

TV

CATV OUTLET W/"0"dB LOSS FACE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

REPLACE EXIST WALL MTD TYPE LIGHTING

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-8"

REPLACE EXIST GFCI RECEPTACLE & COVER

PLATE W/NEW (TYPICAL)

L L

REPLACE EXIST CEILING RECESSED MTD TYPE LIGHTING

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-4b"

REPLACE EXIST CEILING RECESSED MTD TYPE LIGHTING

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-4a"

FAN COIL UNIT/1PH, 115V, 1/30HP,

(TYPICAL)

& THERMOSTAT (UNDER MECH. ITEM)

JUCTION BOX

W/NEW (TYPICAL)

REPLACE EXIST 3-WAY LIGHT SWITCH & COVER PLATE

REPLACE EXIST TOGGLE SWITCH & COVER PALTE

W/NEW (TYPICAL)

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-7"

REPLACE EXIST CEILING SURFACE MTD TYPE LIGHTING

REPLACE SINGLE RECEPTACLE & COVER

REPLACE EXIST DUPLEX RECEPTACLE & COVER

PLATE W/NEW FOR FAN COIL UNIT (TYPICAL)

REPLACE EXIST SINGLE MODULAR JACK AND

& COVER PALTE W/NEW (TYPICAL)

REPLACE EXIST SMOKE DETECTOR WITH

W/ SOUNDER BASE (TYPICAL)

NEW ADDRESSABLE SMOKE DETECTOR

EXHAUST FAN FOR BATH RM, 1PH, 115V-45W

(UNDER MECH. ITEM)

VISUAL STROBE(FA+MNS) (TYPICAL)

REPLACE EXIST WALL MOUNTED SPEAKER,

T T

THERMOSTAT(MECH ITEM)

TV TV

BED ROOM A BED ROOM B

F

SB

L L

3S

S

S S

S

3S

3S

S

SJ

L

L

L L L

L

J

J J a

J b b b b b b a a a a a

SB

FCUFCU

TV

TV

L L

T T

TV TV

S b 3 Sb3

3S3S

MODULE-A MODULE-B

REPLACE SINGLE RECEPTACLE & COVER

PLATE W/NEW FOR FAN COIL UNIT (TYPICAL)

W/NEW (TYPICAL)

REPLACE EXIST 3-WAY LIGHT SWITCH & COVER PLATE

PLATE W/NEW (TYPICAL)

RECEPTACLE & COVER

REPLACE EXIST DUPLEX

REPLACE WITH NEW WALL

MTD TYPE CATV OUTLET W/

"0"dB LOSS FACE PLATE

AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm

AFF) (TYPICAL)

REPLACE EXIST SINGLE

PALTE W/NEW (TYPICAL)

MODULAR JACK AND COVER

JUCTION BOX

REPLACE EXIST SMOKE DETECTOR WITH

W/ SOUNDER BASE (TYPICAL)

NEW ADDRESSABLE SMOKE DETECTOR

VISUAL STROBE(FA+MNS) (TYPICAL)

REPLACE EXIST WALL MOUNTED SPEAKER,

THERMOSTAT(MECH ITEM)

NOTE

CONTRACTUAL WORK TO MEET SITE CONDITION.

CONTRACTOR SHALL VERIFY EXIST TYPE OF MODULES AND PROVIDE 1.

F FF F

J JJJ

JJ

WITH NEW IN THE WALL OR ABOVE CEILING (TYPICAL)

FOR FANCOIL UNIT POWER AND THERMOSTAT

REPLACE EXISTING CONDUIT AND JUNCTION BOX

WITH NEW IN THE WALL OR ABOVE CEILING (TYPICAL)

FOR FANCOIL UNIT POWER AND THERMOSTAT

REPLACE EXISTING CONDUIT AND JUNCTION BOX

(DDC COMPATIBLE TYPE), TRANSFORMER TYPE

WITH 15 MINUTES DEMAND REGISTER

FOR 3PH, 4WIRE, 120/208V, 60Hz

NEMA 3R ENCL

NEW ADVANCED DIGITAL WATTHOUR METER

NEW WIRES AS REQURED

EXIST SAFETY SWITCH

COMBINATION TYPE MAGNETIC MOTOR STARTER, 3P-208V, NEMA SIZE "1",

COMBINATION TYPE MAGNETIC MOTOR STARTER, 3P-208V, NEMA SIZE "2",

A

W/O.L RELAYS, CIRCUIT BRAKER TYPE(3P-100AF-30AT),

3-POSITION SEL. SW (A-O-H), CONTROL TRANSFORMER & PILOT LAMPS,

W/O.L RELAYS, CIRCUIT BRAKER TYPE(3P-100AF-30AT),

3-POSITION SEL. SW (A-O-H), CONTROL TRANSFORMER &

PILOT LAMPS, NEMA 1 ENCL.

REPAIR BLDG S-473

CAMP CASEYTAK, YS

REPLACE WITH NEW WALL MTD TYPE

EWC

E W

C

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

105 R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

COMMO SHOP

114A 114B

JAN

MULTI-PURPOSE RM

STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

W/D

W/D

NBC ROOM

ARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

E W

C

FECFEC

UPDN

UPDN

REF

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

SCALE: 1/100

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-9

LAN

TTB

DUAL MODULAR JACK

CAT-6, 8-PIN (RJ45 TYPE) OUTLET

FOR "TEL/DATA" (TYPICAL)

W/COVER PLATE & LUG FOR TEL

CAT-6, 8-PIN (RJ45 TYPE) OUTLET

(TYPICAL)

SOLID BOTTOM TYPE CABLE TRAY

ABOVE THE CEILING

(STEEL, 300mmW x 150mm H x LENGTH

AS REQ'D) W/O COVER

WITH SUPPORTER EVERY 3000mm

TO BE TERMINATED AT PATCH

TEL/DATA WIRE IN 27C

2-4PAIR, #24AWG, CAT-6

PANEL VIA CABLE TRAY

(TYPICAL)

REPLACE W/ NEW SINGLE MODULAR JACK

(TYPICAL)

TO BE TERMINATED AT MAIN

REPLACE EXISTING SINGLE MODULAR JACK

AND COVER PLATE WITH NEW

P-8

1ST FLOOR LAN/TEL PLAN

2ND, 3RD & 4TH FLOOR TEL PLAN

1ST, 2ND, 3RD & 4TH FLOOR LAN/TEL PLAN

T T C

W/FABRIC INNER DUCT IN 54C

1-50PAIR, #24AWG, TEL WIRE

OFFICE

OFFICE

DIAGRAM ON E-10)

AT MECH RM (SEE TEL SYSTEM

110 TERMINAL BLOCK IN TTC

DIAGRAM ON E-10)

RACK(SEE TEL SYSTEM

BOARD, EQUIPMENT

TELEPHONE TERMINAL

P EXIST PULL BOX

CABLE IN NEW 103 diaC.

EXIST 1-12CORE FIBER OPTIC

TO NEW PATCH PANEL IN EQUIPMENT RACK

TERMINATE EXIST 1-12 FIBER OPTIC CABLE

CORRIDOR

LAUNDRY

W

W

W

W

D

D

D

D

D

ARMS RM

REPAIR LOCKSET OF EXIST TTC/REPAINT ENCLOSURE OF TTC.

REPAIR BLDG S-473

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-10

(TYPICAL)

CABLE SUPPORT

EXOTHERMIC WELDING, LISTED COMPRESSION TWO-

1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR

TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE

HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE

FINISHED FLOOR AND SHALL BE PLACED WITHIN 75mm

3. ENTRANCE CONDUITS SHALL EXTEND 150mm ABOVE

NOTES:

CROSS CONNECTING

PATCH CORD AS REQ'D

110 TYPE TERMINAL BLOCK

G

NEW TELEPHONE TERMINAL BOARD (TTB)

G

GROUNDING BUSBAR (TMGB)

(100mm(W) x6.4mm(D) x450mmLG)

GROUND WIRE

NEW TELECOMMUNICATION MAIN

CONDUCTOR #6AWG

NOT TO SCALE

RACK TYPE 1-48 PORT

PATCH PANEL "DATA"

STAMP FACING OUT" TO ENSURE THAT THEY CAN BE

"PLYWOOD WILL BE INSTALLED WITH FIRE RATED

4. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT

REVISION OF THE ANSI/TIA/EIA-568.

5. LABEL ALL DROPS IAW TIA/EIA-606-A.

6. LABEL ALL GROUNDS IAW I3A.

LUGS ARE PREFERRED.

FIELD VERIFIED.

OF A WALL.

NEW GROUND BONDING

RACK TYPE 1-48 PORT

(TYPICAL)

RACK TYPE 1-48 PORT

PATCH PANEL TEL"

PATCH PANEL "DATA"

6 METER (20FEET) SLACK

W/"SC" TYPE CONNECTIONS

HUB (N.I.C)

MODE FIBER OPTIC CABLE

(TYPICAL)

SEE NOTE 2 BELOW.

NEW 2WAY OF 103dia CONDUIT

51-4PAIR, CAT-6, #24AWG FOR TEL

1WAY: 51-4PAIR, CAT-6, #24AWG FOR DATA &

1WAY: SPARE W/PULL WIRE

(TYPICAL)

END BLANKS

D

T

SURGE SUPPRESSION TYPE

QUAD-PLEX RECEPTACLE

2P-3W-125V-20A

GROUNDING TYPE WITH

DEDICATED CIRCUIT

D

T

D

T

D

T

D

T

D

T

D

T

105104 105 105

ROOM NUMBER

WHICH DEVICE IS LOCATED

(TYPICAL)

1-4PAIR, #24AWG, CAT-6

FOR TEL IN 27C

CONN TO NEW PATCH PANEL

VIA CABLE TRAY

SOLID BOTTOM TYPE CABLE TRAY

ABOVE THE CEILING

(STEEL, 300mmW x 150mm H x LENGTH

AS REQ'D) W/O COVER

WITH SUPPORTER EVERY 3000mm

TO BE TERMINATED AT PATCH

TEL/DATA WIRE IN 27C

2-4PAIR, #24AWG, CAT-6

PANEL VIA CABLE TRAY

(TYPICAL)

1500mmx2400mmx19mmTHK PLYWOODx1EA

D

T

D

T

D

T

D

T

D

T

D

T

D

T

116 110

D

T

D

T

109 107 107 107 107

DUAL MODULAR JACK

CAT-6, 8-PIN (RJ45 TYPE) OUTLET

FOR "TEL/DATA" (TYPICAL)

CONDUIT COUPLING

(TYPICAL)

NEW CONDUIT STUB-UP W/SEALING

(150mm AFF) (TYPICAL)

COMM RM 105A

2. PLYWOOD SHALL BE FIRE-RATED.

84.58"(H)"x24"(W)x34.67"(D)

(100mm(W) x6.4mm(D) x300mmLG)

NEW TELECOMMUNICATION

GROUNDING BUSBAR (TGB)

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

105 105

109 109

D

T

D

T

D

T

108 108 108 108

G

D

T

D

T

(TYPE NEMA 5-20R)

POWER RECEPTACLES

P-7

P-8

(TYPICAL)

TELECOMMUNICATION SYSTEM DIAGRAM

TELECOMMUNICATION SYSTEM DIAGRAM

7. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAIL

RACK TYPE 1-48 PORT

RACK TYPE 1-12 PORT

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

PATCH PANEL "TEL"

WIRING TO REMAIN

EXISTING TERMINAL BLOCKS AND

MECH RM 126

CONN TO NEW MAIN PANEL

GROUNDING SYSTEM

1#6 "BC" IN 27C

G

G

G

G

SEE SITE PLAN

CONDUIT COUPLING

(TYPICAL)

NEW CONDUIT STUB-UP W/SEALING

(150mm AFF) (TYPICAL)

IN MECH RM (123)

TEMINATE TO MAIN TERMINAL BLOCK AT TTC

1-50PAIR, #24AWG TEL CABLE, 54mm C.

1-50PAIR, #24AWG TEL CABLE, 54mm C. FROM TTB AT COMM RM(105A)

EXIST TEL LINE

110 TEMINAL BLOCK IN EXIST TTC

NEW 1-50 PAIR AWG#24/ CONNECT TO MAIN

EQUIPMENT RACK

D

T

D

T

D

T

D

T

NEW 1-12 STRAND SINGLE

101101101101

D

T

101 102 102102102 102 104 104 104104 104 105 106B 106B106B 106A 106A 106A

D

T

D

T

D

T

EXIST MAIN TEL LINE

PROTECTED TERMINAL BLOCK

(ENTRANCE) (1-100PAIR)

NEW

G

PTB

110 TEMINAL BLOCK IN EXIST TTC

NEW 1-100 PAIR AWG#24/ CONNECT TO

G

PRIOR TO CONSTRUCTION.

TELECOMMUNICATION SYSTEM FOR GOVENRMENT APPROVAL

OF TTC AND REPAINT ENCLOSURE.

CABINET(TTC)/REPLACE LOCKSET

EXIST TELEPHONE TERMINAL (1-100PAIR) (TYPICAL OF 4EA)

REPAIR BLDG S-473

EWC

E W

C

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

109110111

COMMO SHOP

114A 114B

JAN

MULTI-PURPOSE RM

STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

W/D

W/D

NBC ROOMARMS ROOM

COMM RM

LATRINE

MALE LATRINE

FEMALE

UPDN

UPDN

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-11

TV TV TV

TV

TV

TV

T V

T V

T V

T V

T V

C T

C

TV TV

SCALE 1/100

1-RG 11/U IN 21C

COAXIAL CABLE

(TYPICAL)

W/8-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

CATV OUTLET W/"0"dB LOSS FACE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

1-RG 6/U IN 16C

COAXIAL CABLE

W/6-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILINGSEE DIAGRAM

PROVIDE NEW CATV DIST. CABINET (CTC-1)

NEW WALL MTD TYPE

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

C T

C

6TV 4

8 8

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

P

T V

TV

TV TV

TV

TV

TV

W/4-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

W/6-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

W/8-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL OF 6)

CATV OUTLET W/"0"dB LOSS FACE

NEW WALL MTD TYPE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

1-RG 6/U IN 16C

COAXIAL CABLE

(TYPICAL)

SCALE 1/100

1-RG 11/U IN 21C

COAXIAL CABLE

(TYPICAL)

27C EMPTY CONDUIT

TO " " IN RM. 215CTC

W/PULL WIRE

TO REMAIN

EXIST ENTRANCE CAP & SEC.RACK

T V

TV

REPLACE W/ NEW CATV DIST.

CABINET (CTC-2) SEE DIAGRAM

1ST FL CATV PLAN

2ND ,3RD AND 4TH FL CATV PLAN

1ST, 2ND ,3RD AND 4TH FLOOR CATV PLAN

OFFICE

OFFICE

W

W

W

W D

D

D

D

LAUNDRY

ARMS RM

T V

TV

(TYPICAL)

T V

TV

REPAIR BLDG S-473

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-12

3F

4F

2F

1F

AMP

ROOF

2AMP

AMP

AMP

TV

106B

TV

TV TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

TV

211 210

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV TV

TV

202 203

TV

TV

TV

TV

TV

TV TV

TV

204 205

TV

TV

TV

TV

TV

TV TV

TV

206 207

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

TV

311 310

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV TV

TV

302 303

TV

TV

TV

TV

TV

TV TV

TV

304 305

TV

TV

TV

TV

TV

TV TV

TV

306 307

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

TV

411 410

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV TV

TV

402 403

TV

TV

TV

TV

TV

TV TV

TV

404 405

TV

TV

TV

TV

TV

TV TV

TV

406 407

TV

TV

TV

TV

TV

TV TV

TV

G

G G

G G

RG 6/U IN 16C

COAXIAL CABLE

(TYPICAL)

DEVICE IS LOCATED

ROOM NUMBER WHICH

(TYPICAL)

CATV OUTLET W/"0"dB LOSS FACE

NEW WALL MTD TYPE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

SURGE SUPPRESSION TYPE

DUPLEX RECEPTACLE

(2P-3W-15A-125V)

FOR AMPLIFIER

(TYPICAL)

(TYPICAL)

1#6 "BC" IN 21C

(TYPICAL)

GROUNDING TERMINAL BLOCK

W/8-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL)

W/4-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL)

W/6-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL)

2#12 & 1#12(G) IN 16C

RG 11/U IN 21C

COAXIAL CABLE

(TYPICAL)

GROUND ROD, COPPER CLAD STEEL,

19mm dia x 3000mm LONG

WITH WELDING CONNECTION AND

CONN. TO BLDG ELECTRODE

GROUNDING SYSTEM

#6 "BC"

EXIST ENTRANCE CAP & SEC. RACK

TO REMAIN

PROVIDE NEW 27C EMPTY CONDUIT

W/PULL WIRE

TV

TV

TV

TV TV

TV

TV

TV

TV TV

TV

2#12 & 1#12(G) IN 16C

2#12 & 1#12(G) IN 16C

1PH-208V

2#12 & 1#12(G) IN 16C

CATV DISTRIBUTION CABINET (CTC-2)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 4-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

2-WAY SPLITTER-1EA,

CATV DISTRIBUTION CABINET (CTC-1)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 2-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

CATV DISTRIBUTION CABINET (CTC-3)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 2-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

CATV DISTRIBUTION CABINET (CTC-4)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 2-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

CATV SYSTEM DIAGRAM

NOT TO SCALE

1PH-208V

2#12 & 1#12(G) IN 16C

TO LOADCENTER "L2", CKT NO. "L2-4"

TO LOADCENTER "L2", CKT

NO. "L2-5" 1PH-208V

TO LOADCENTER "L3", CKT NO. "L3-4"

TO LOADCENTER "L3", CKT

NO. "L3-5" 1PH-208V

TO LOADCENTER "L4", CKT

NO. "L4-5" 1PH-208V

TO LOADCENTER "L4", CKT NO. "L4-4"

CATV SYSTEM DIAGRAM

TV

TO LOADCENTER "L1", CKT NO. "L1-12"

TO LOADCENTER "L1", CKT NO. "L1-11"

REPAIR BLDG S-473

EWC

FEC

UP

UP

S/S

STORAGE

VEST

125 ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

109110111

COMMO SHOP

114A 114B

JAN

MULTI-PURPOSE RM

STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

W/D

W/D

OFFICE

NBC ROOMARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

E W

C

FECFEC

UPDN

UPDN

STAIR-1

218A

CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A 211B 210A

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A

314B 313A 313B 312A 312B 311A 311B 310A

310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A

414B 413A 413B 412A 412B 411A 411B 410A

410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-13

ADDRESSABLE FIRE ALARM

F M

C P

F T

R

F F

F

F

F F

F

F

F

F F

F

F

F

F

FF

FF

F

F

F

F

AS REQ'D. PROGRAMMABLE MODULE

RELAYS, POWER MODULE AS REQ'D,

LCD ANNUNCIATOR, SYNCHRONIZATION

CONTROL MODULE, BATTERY,

BATTERY CHARGER, NEMA 1 ENCL

SURFACE MOUNTED BUILDING TRANSMITTER

W/BATTERY & BATTERY CHARGER

NEMA 1ENCL

1/100SCALE:

ADDRESSABLE FIRE ALARM

MANUAL PULL STATION

(TYPICAL)

SMOKE DETECTOR

(TYPICAL)

F

F

F F

F F

F

F

F

F F

F

F F F F F F F F F F F F

F F

F

FF

F

FF

F

F

FF

FF

F

F

F

F

F

F

F

SB

SHSH

F

F

SBSB SB

F F

SB SB

F

SB SB

F

SB SB

F

SB SH

F

SB SB

F

SB SB

F F F F F F

F

SHSH

F

SHSH

F

SBSH

F

SBSB

F

SBSB

1/100SCALE:

SURFACE MOUNTED BOOSTER PANEL

1PH, 120VAC INPUT, 5A(MAX)@24VDC, OUTPUT

W/CLASS "A" AS REQ'D W/SLC MODULE

AS REQ'D POWER MODULE AS REQ'D

CONFIGURATION PROGRAMMABLE RELAYS.

GROUND LOOP ISOLATION ANS TRANSIENT

PROTECTION etc. NEMA 1 ENCL

ADDRESSABLE FIRE ALARM

MANUAL PULL STATION

(TYPICAL)

FFF

F M

B P

J

PSTS

J

TS

J

TS

J

TS

J

LOC

LOC

J

FS

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

/COMBO. (FA+MNS) VISUAL STROBES

(CANDELA AS REQ'D) (TYPICAL)

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

/COMBO. (FA+MNS) VISUAL STROBES

(CANDELA AS REQ'D) (TYPICAL)

LOCAL OPERATING CONSOLE

SURFACE MOUNTED ADDRESSABLE COMBINED FIRE ALARM

CONTROL AND MASS NOTIFICATION SYSTEM PANEL, W/24VDC

BULIT-IN ADDRESSABLE POINTS MODULES

BED ROOM BED ROOM

BED ROOM

(TYPICAL)

LOCAL OPERATING CONSOLE

(TYPICAL)

CO

W P

F M

W P

F M

WP

F M

F

TS

J J

FS

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

,COMBO. (FA+MNS), "WP" (TYPICAL)

1ST FL FIRE ALARM AND MASS NOTIFICATION SYSTEM PLAN

2ND, 3RD & 4TH FL FIRE AND MASS NOTIFICATION SYSTEM PLAN

AND MASS NOTIFICATION SYSTEM PLAN

1ST, 2ND, 3RD & 4TH FLOOR FIRE ALARM

SMOKE W/SOUNDER BASE (TYPICAL)

ADDRESSABLE COMBINED PHOTOELECTRIC

OFFICE

OFFICE

FF

F

F

FF

W

W

W

W D

D

D

D

ARMS RM

REPAIR BLDG S-473

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

2#12 IN 16C(FOR POWER)

12#14 IN 21C(FOR SIGNAL)

(TYPICAL)

SEE NOTE 2. BELOW

FOR NO & SIZE OF WIRE

WHICH DEVICE IS LOCATED

(TYPICAL)

ROOM NUMBER

SG

6#14 IN 16C

BOOSTER PANEL#1 (FMBP)

BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)

SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,

24VDC, BUILT-IN ADDRESSABLE POINTS MODULES

AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,

POWER MODULE AS REQ.D LCD ANNUNCIATOR,

123124101 120

EXT 124124 109 110 114B

NOT TO SCALE

(TYPICAL)

BATTERY & BATTERY CHARGER, etc. NEMA 1 ENCL

GROUND LOOP ISOLATION AND TRANSIENT PROTECTION

BOOSTER PANEL, 1PH, 120VAC INPUT, 6A(MAX)

@24VDC OUTPUT W/CLASS"A" AS REQ'D WITH

SLC MODULE AS REQ'D, POWER MODULE PANEL (AS REQ'D)

AMPLIFIER(AS REQ'D) CONFIGURATION PROGRAMMABLE RELAYS,

MANUAL PULL STATION

(TYPICAL)

W/MOUNTING BRACKET

LIGHTNING ARRESTER

OMNI-DIRECTION TYPE

W/CONNECTORS IN 16C

COAXIAL CABLE

GROUND CONDUCTOR

#6 "BC" IN 21C

W/WEATHER-PROOF ENCLOSURE

WITH WELDING CONNECTION

GROUND ROD, COPPER CLAD

STEEL, 19mmdia x 3000mmLG

BUILDING

TRANSMITTER

G ~

GROUND ROD, COPPER CLAD

#6, "BC" IN 21C

GROUNDING SYSTEM

CONN TO BLDG ELECTRODE

STEEL, 19mmdiax3000mmLG

WITH WELDING CONNECTION AND

2#12 & 1#12(G) IN 16C

G

SG

CONTROL PANEL (FMCP)

COMBINED FIRE ALARM/

ROOF

3rd FLOOR

1st FLOOR

EXT

114A

111107

124 106104

SURFACE MOUNTED COMBINED ADDRESSABLE

MODULE, POWER SUPPLY, MICROPHONE, BATTERY,

AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL

MASS NOTIFICATION

FIRE ALARM/MASS NOTIFICATION

15.

"FIRE" AND W/CLEAR LENS.

1.

"ALERT" IN RED LETTER AND W/AMBER LENS.

SAFE PATH FACILITY COMMUNICATIONS OR APPROVED EQUAL.

STROBES FOR FIRE ALARM SHALL BE MARKED

STROBES FOR MASS NOTIFICATION SHALL BE MARKED

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

MASS NOTIFICATION SYSTEM SHALL BE SIMILAR TO WHEELOCK10.

5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR THE LOCAL AREA

4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE NORMAL MAIN ENTRANCE/EXIT

2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING

1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING

ARE IN ENGLISH AND HANGUL AT LEAST FOR THE FOLLOWING ITEMS.

THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT PRERECORDED MESSAGES

WITH THE MANUFACTURER'S LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE LOCATIONS IN ACCORDANCE

THE APPLICABLE CODE, SPECIFICATIONS AND MANUFACTURER'S EQUIPMENT LISTING.

IS THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE WITH

THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE NUMBER OF DEVICES SHOWN19.

3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING

6) "ALL CLEAR" MESSAGE

PER DRAFT UFC 4-021-01.

18.

21.

20.

14. ADDITIONAL RELAY IS PROVIDED AS REQUIRED.

SYNCHRONIZED. AUDIBLE APPLIANCES SHALL PROVIDE THE

SPECIFICATION SECTION 28.31.64.00.31(FA) AND NFPA 72.

APPROVED.

ARCHITECTURAL FEATURES.

LOCATIONS IN ACCORDANCE WITH THE MANUFACTURER'S

IN ACCORDANCE WITH THE APPLICABLE CODE, SPECIFICATIONS

THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE

AND READY TO USE. THE NUMBER OF DEVICES SHOWN IS

BE PROVIDED WITH CLASS "A" MODULES

HORIZONTAL AND 305mm VERTICALLY.

TRANSMITTER AND ANTENNA.

PANEL COVER.

BREAKER AND/OR DISCONNECT SWITCH.

FOR THE FIRE ALARM AND DETECTION SYSTEM.

AUDIBILITY CALCULATION, WIRE SIZE, NO. OF WIRES

NOTES:

SHALL BE RESPONSIBLE FOR PROVIDING FIRE ALARM

THE FIRE ALARM/MASS NOTIFICATION SYSTEM CONTRACTOR

FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED LETTER

"FIRE ALARM CIRCUIT" ON THE DEDICATED POWER CIRCUIT

CIRCUIT SHALL BE INDICATED ON THE FIRE ALARM CONTROL

THE POWER CIRCUIT NUMBER DEDICATED TO FIRE ALARM4.

3.

2.

COAXIAL CABLE SHALL BE ONE PIECE BETWEEN BUILDING5.

SYSTEM SHALL BE SEPARATED BY A MINIMUM OF 1220mm

INCOMING AND OUTGOING CLASS "A" RACEWAY OF FA6.

7. ALL CLASS "A" EXCEPTIONS IN NFPA 72, 6.4.2.2.2 ARE

PROHIBITED FOR ALL IDC, NAC AND SLC.

ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE

SWITCHES AND NON-ADDRESSABLE INITIATION DEVICES SHALL

COORDINATE THE EXACT DEVICE LOCATIONS WITH ELECTRICAL

AND MECHANICAL SYSTEM EQUIPMENT AND BUILDING

ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM

ALL AUDIBLE APPLIANCES WITHIN THE BUILDING AND ALL

VISUAL APPLIANCES WITHIN THE SAME ROOM SHALL BE

STANDARD TEMPORAL PATTERN, NFPA 72.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

9.

11.

12.

13.

SHALL COMPLETE THE DESIGN AND INSTALL THE SYSTEM

8.

LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE

AND MANUFACTURER'S EQUIPMENT LISTING.

COMPLETE THE DESIGN AND INSTALL THE…