A21_Amendment_04.docx
DOCX document 32 KB Posted
- Attached to
- Installation of CCTV
- Solicitation number
- W91QVN17T0052
About this file
Amendment 04
View the file
Other files
| File | Type | Posted |
|---|---|---|
| A21_Amendment_07.docx | DOCX document | |
| A21_Amendment_06.pdf | ||
| A21_Amendment_05.docx | DOCX document | |
| A2_Drawing_4_for_Com_.Room_2F.pdf | ||
| A2_Drawing_3_for_Com_.Room_1F.pdf | ||
| A2_Drawing_1_for_unpdated_drawing_1,_ACS_7005BAACH_1st_floor_Camera_blindspots_and_existing.pdf | ||
| A2_Drawing_2_for_Regular_Floor_Drawing-7005BAACH__2nd_floor2_Camera_blindspots.pdf | ||
| A21_Amendment_03.docx | DOCX document | |
| A21_Amendment_02....docx | DOCX document | |
| A2_Regular_Floor_Drawing-7005BAACH__2nd_floor2_Camera_blindspots.pdf | ||
| A21_Amendment_01.docx | DOCX document | |
| A2_ACS_7005BAACH_1st_floor_Camera_blindspots_and_existing_(003).pdf | ||
| A21_RFQ.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W91QVN-17-T-0052
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
a. The purpose of this amendment is to answer for vendor's question on the site orientation:
Question 1: Red dotted cameras are existing cameras and do not need to be changed. Answer: Red/Green Dot Camera drawing is incorrect and needs to be updated.
Question 2: Can we have access to the hallway? Answer: Yes during scheduled work that has been coordinated with MEDDCOM.
Question 3: Is there space above the ceiling to do the work? Answer: Yes there is: approximately 2 feet, some wires are already in place. Some have wires, others wires will have to be pulled through. Those without wires, the contractor will have to install.
Question 4: Do we run wire with or without conduit? Answer: Contractors will not have to install conduits
Question 5: Power sleeve conversation needs to go here . Answer: N/A see question 12
Question 6: Wires through the barrier must be UL Listed. Answer: Yes, CMP /CAT 6, must be UL listed.
Question 7: Are the switches already in place? Or is the contractor providing the switches? (This is a question for IMD). Answer: Per network team, they are going to provide the switches.
Question 8: Can they use the cable by CMP? Answer: No. Use standard UTP. Must use stand cable for fire retardant. Cable in the room was the wrong cable and was removed. Use only specified cable. Contractor must bring the cable that is fire retardant.
Question 9: CMP certified cable must be UL listed fire retardant Category 6. Answer: See below Question 14.
Question 10: Switch room map ad communication room map – has it been provided. Answer: It is attached now.
Question 11: The cable in the box was replaced. Answer: It is not authorized to be used in the hospital. Must use power over internet. Don’t touch old cameras, just new installation with Power over internet.
Question 12: POE question? Answer: The cameras should be “PoE” cameras; “Power over Ethernet” means that power is provided thru LAN cables from network switch ports.
Question 13: Once we have the 65 inch monitor, do we have to install it on the wall. Yes. Who provides the bracket? Answer: The contrator shall place on the wall and provide the brackets.
Question 14: Are all of the wires UL rates? Answer: Yes.
Question 15: May the questions and answer period be open? Answer: Yes – we will take questions for 2 days after the posting of this amendment (All questions should be e-mailed by 17 April 2017, 2.p.m, Korea Local Time).
Question 16: Are the cameras grouped? Answer: See switch room map for cabling purposes – there are 6 switch rooms.
b. The closing date is extended from 28 April 2017 to 5 May 2017.
c. All other terms and conditions remain unchanged.
SECTION SF 1449 - CONTINUATION SHEET
SOLICITATION/CONTRACT FORM
The required response date/time has changed from 28-Apr-2017 01:00 PM to 05-May-2017 01:00 PM.
(End of Summary of Changes) image1.wmf