6.Appendix_C_Hydrant_Flow_test.pdf
PDF 43 KB Posted
- Attached to
- Modular Small Arms Range (MSAR) Federal contract opportunity
- Solicitation number
- W91364-18-R-8000
About this file
Appendix C - Hydrant Flow test
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 0.W91364-18-R-8000-0002_MSAR_Sol_Amend.pdf | ||
| Addendum_04_W91364-18-R-8000.pdf | ||
| 0.W91364-18-R-8000-0001_MSAR_Sol_Amend.pdf | ||
| Addendum_03_MSAR_W91364-18-R-8000.pdf | ||
| Addendum_02_MSAR_W91364-18-R-8000.pdf | ||
| Addendum_01_MSAR_W91364-18-R-8000.pdf | ||
| Pre_Bid_Attendance_Roster_6_Dec_17_FINAL.pdf | ||
| 0.W91364-18-R-8000_MSAR_Sol.pdf | ||
| 9.EXHIBITS_A-C_MSAR.pdf | ||
| 2-Attachment_1_MSAR_R1_SOO_20170920.pdf | ||
| 5.Appendix_B_Geotech.pdf | ||
| 4.Appendix_A_Civil_Combined-8-18-17.pdf | ||
| 1-SEC_01-General_Requirements-MSAR.pdf | ||
| 3-Attachment_2_WD_OH17109_Mod_14_date-10_27_17.pdf | ||
| 8.Appendix_E_B155_Soils_report.pdf | ||
| 7.Appendix_D_Bidding_Schedule.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MODULAR RANGE SOO
OHIO AIR NATIONAL GUARD, TOLEDO EXPRESS AIRPORT
SWANTON, OH
TOLEDO ANG MOD SM AR.DOCX B&McD No.: 94539
APPENDIX C
FIRE HYDRANT FLOW TEST
Hydrant Flow Test Report
180CES/CEF
Location H-26 NORTH 155 DATE 8JUL08
Test made by A/C ULRICK Time 830
Representative of 180CES/CEF
Witness LT. ROZICK
State purpose of test HYDRANT FLOW TEST
A1 A2 Flow hydrants: 26 Size nozzle 2.5 Pitot Reading 42 Discharge coefficient 0.9 gpm 1209
Static B 62 psi Residual B 44 psi
Projected results @ 20 psi Residualual 2123 GPM
Remarks TOTAL POTENTIAL FLOW FROM H-2 IS26 IS 2123 GPM