MODULAR RANGE SOO

OHIO AIR NATIONAL GUARD, TOLEDO EXPRESS AIRPORT

SWANTON, OH

TOLEDO ANG MOD SM AR.DOCX B&McD No.: 94539

APPENDIX C

FIRE HYDRANT FLOW TEST

Hydrant Flow Test Report

180CES/CEF

Location H-26 NORTH 155 DATE 8JUL08

Test made by A/C ULRICK Time 830

Representative of 180CES/CEF

Witness LT. ROZICK

State purpose of test HYDRANT FLOW TEST

A1 A2 Flow hydrants: 26 Size nozzle 2.5 Pitot Reading 42 Discharge coefficient 0.9 gpm 1209

Static B 62 psi Residual B 44 psi

Projected results @ 20 psi Residualual 2123 GPM

Remarks TOTAL POTENTIAL FLOW FROM H-2 IS26 IS 2123 GPM