This document is an amendment to a solicitation for the replacement of motorized and manually operated air-insulated disconnect switches at the Barkley Switchyard. The amendment extends the quote due date from May 16th to May 23rd at 1:00 PM Central Time. It provides answers to contractor questions, revises the specifications to include a list of required spare parts, and incorporates FAR Clause 52.252-3 regarding alterations to the solicitation.

The replacement work includes new switches, operators, mounting brackets, and auxiliary switches for disconnects ranging in voltage from 161kV to 15kV. Options include stainless steel hardware and additional auxiliary switches. The selected contractor will provide a firm fixed-price for the base requirements and optional items. Technical plans and specifications are attached documents. The solicitation was issued by the US Army Corps of Engineers Nashville District for the Barkley Switchyard located in Tennessee.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W38XDD30055978

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

PROJECT: Barkley Sw itchyard Disconnects PURPOSE: The purpose of this amendment is to:

1) Provide Government answ ers to contractor questions.

2) Extend quote due date from 16-May-2023 at 1:00 PM CT to 23-May-2023 at 1:00 PM CT.

3) Attach revised Specif ications "W9120523R0005_TSPECS_BAR SWITCHYARD DISCONNECTS_Amendment 0001_16MAY23.pdf"

4) FAR 52.252-3, Alterations in Solicitation, has been included and updated.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 4

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 16-May-2023

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912P523Q0022

X 9B. DATED (SEE ITEM 11)

26-Apr-2023

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

16-May-2023

CODE

CELRN-CT CONTRACTING BRANCH

110 9TH AVE S STE A405

NASHVILLE TN 37203

W912P5 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912P523Q0022

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 1449 - CONTINUATION SHEET

SOLICITATION/CONTRACT FORM

The required response date/time has changed from 16-May-2023 01:00 PM to 23-May-2023 01:00 PM.

The following have been added by full text:

Q&A AMENDMENT 0001

1.Contractor Question: Deliver all at once or partial deliveries accepted?

Government Answer: Either can be accepted.

2. Contractor Question: Who are the manufactures names of the products to be replaced?

Government Answer: All of the items being replaced have the original manufacturer’s names and model numbers in the reference drawing package.

3. Contractor Question: All or none same manufacture or will more than one manufacturer?

Government Answer: Same manufacture for each type. Would prefer for all to be the same but would be ok for each type.

4. Contractor Question: For the Option 4 Auxiliary switches, how many poles per unit will be required?

Government Answer: For the auxiliary switch, the numbers of contacts is covered in the specs in 2.4.1.2.2.1, which is 4 NO and 4 NC:

2.4.1.2.2.1 Auxiliary Switches

Provide position indicating (open/closed) auxiliary switches for manually-operated switches. Auxiliary switches must have a minimum of four normally open and four normally closed contacts; contacts shall be rated for 2 amps at 125 VDC.

See reference drawings 2-6819-5 and 1-18018-2 for existing auxiliary switches and mounting brackets.

The submitted switch appears to be an eight (8) pole application but the number of poles is not relevant. The Government is focused on the number of output contacts. Therefore, a contractor may use as many poles as necessary to meet the specification language with the switch of their choice.

5. Contractor Question: On the stainless steel hardware request it states: 1/2"x2" Stainless Steel Bolt/Washers/Silicon Bronze Nut. Does that mean that they want a set of stainless steel bolts and washers with a silicon bronze nut? A full set of bolts, washers and nuts in stainless steel would seem more likely.

Government Answer: The contract is for a stainless steel bolt, stainless steel flat, stainless steel lock washer and then a silicon bronze nut.

6. Contractor Question: The summary of work in the solicitation states “One of both the 169kV and 15.5kV disconnects will be provided as spares”, however, there is no mention of specific spares in the specifications.

Measurement and Payment Section 01 20 00, Paragraph 1.2.14.1 states “spare parts with all requirements described in Section 26 11 14.00 10, however, Section 26 11 14.00 10 does not include a list of required spare parts. Exactly what spare parts are required to be provided?

Government Answer: The spares for each type of complete disconnect are included in the total count on the bid schedule; they are just referred to as spares so that it is clear if the contractor visits the switchyard, or sees the original installed quantities on any reference drawings, that we are purchasing more disconnects than are currently installed in the switchyard. There are currently 30 disconnects installed in the switchyard and there are a total of 32 disconnects for CLINs 0001 through 0004, so that accounts for the two ‘spare’ complete disconnect assemblies referenced in the scope of work.

For section 26 11 14.00 10, a list of specific spare parts and quantities was mistakenly omitted. The specific parts and quantities required to fulfill Option 6 are as follows:

1. One complete motorized operator assembly, including motor.

2. Stationary contact fingers/jaws: 2 sets for 161kV disconnects, 1 set for 15kV disconnects.

3. Blade contact/tip: 3 sets for 161kV disconnects, 1 set for 15kV disconnects.

4. Complete blade assembly, including contact/tip: 3 for 161kV disconnects, 1 for 15kV disconnects.

5. Insulator stacks: 1 of each style and/or height used on any disconnect covered by this contract.

6. Auxiliary position switches: 2

7. Manual operating device: 2. If the 161kV and 15kV disconnects use different styles/models of manual disconnects, then the total quantity of 2 shall include one of each type. If they utilize the same model, the both spares shall be of that type.

8. MOD electrical motor: 1

9. All electrical parts in the MOD enclosure (terminal boards, contacts, push buttons, switches, etc.): 2 sets

10. If bearings are serviceable, or are located in a “housing” that can be swapped out: 3 sets for 161kV disconnects, 1 set for 15kV disconnects.

In the above list, a ‘set’ refers to enough parts to service all three phases of a disconnect.

*The Specifications have been revised to include the omitted list per question 6, above. The revised Specifications will be included with Amendment 0001 and fully incorporated into this solicitation.

7. Contractor Question: Has there been any other questions received / answered, if so, will those be released via Amendment?

Government Answer: Yes, and yes.

8. Contractor Question: Instead of giving the blanket price for the following if you would give an answer: We didn’t see the height at which the underhung mounting configuration would be installed for the disconnector. Mounting height from the ground level is missing as we need to determine the cost of the drive shaft length and its associated bearing assembly.

Government Answer: The mounting heights and driveshaft lengths for the various configurations of disconnects are detailed on the following reference drawings:

3-5048-2

3-5049-1

3-5051-2

3-6033-0

These drawings are all included in the solicitation.

52.252-3 ALTERATIONS IN SOLICITATION (APR 1984)

Portions of this solicitation are altered as follows:

Amendment 0001 PROJECT: Barkley Switchyard Disconnects PURPOSE: The purpose of this amendment is to:

1) Provide Government answers to contractor questions.

2) Extend quote due date from 16-May-2023 at 1:00 PM CT to 23-May-2023 at 1:00 PM CT.

3) Attach revised Specifications "W9120523R0005_TSPECS_BAR SWITCHYARD DISCONNECTS_Amendment 0001_16MAY23.pdf"

4) FAR 52.252-3, Alterations in Solicitation, has been included and updated.

The following have been modified:

ATTACHMENTS

The Plans and Specifications are attached separately and fully incorporated into this contract:

PLANS:

BARKLEY_SWITCHYARD DISCONNECTS_TPLAN_RTA_W9120523R0005_BARKLEY SWITCHYARD

DISCONNECTS REPLACEME_.pdf SPECIFICATIONS: (REVISED PER AMENDMENT 0001) The Specifications have been revised to incorporate the Government Answer to Question 6. The following Specifications pdf is attached seperately and are fully incorporated into this solcitation.

W9120523R0005_TSPECS_BAR SWITCHYARD DISCONNECTS_Amendment 0001_16MAY23.pdf

(End of Summary of Changes)