NO. A221-1/2" x 10" ALUMINUM
POINT. REFER TO LAYOUT AND
GENERAL NOTE "9" FOR
LOCATION.
NO. A100 ALUMINUM CABLE. COURSE
CABLE AS THE MAIN CONDUCTOR AND
CLOSE CIRCUIT WHERE REQUIRED WITH
SPLICER AS SHOWN PER DETAIL "E1".
NO. A810 ALUMINUM ADHESIVE TYPE CABLE
HOLDER. SECURE IN PLACE WITH AN
APPLICATION OF NO. P899LN ADHESIVE
COMPOUND. FASTEN CABLE 3'-0" O.C. MAX.
NO. A309-1/2" CAST ALUMINUM ADHESIVE
TYPE POINT BASE. SECURE IN PLACE WITH
AN APPLICATION OF NO. P899LN ADHESIVE
COMPOUND.
FOUR NO. S846X-#10 x 5/8"
TYPE POINT BASE. SECURE WITH
NO. A316-1/2" ALUMINUM STRAP
STAINLESS STEEL TEK SCREWS.
GENERAL NOTE "9" FOR LOCATION.
POINT. REFER TO LAYOUT AND
NO. A221-1/2" x 10" ALUMINUM
DETAIL "D", OR TO LOWER ROOF AS
TION; EXIT BELOW GRADE AS SHOWN PER
WITHIN COLUMN AND/OR WALL CONSTRUC-
COURSE CABLE, CONCEALED
NO. C120 COPPER DOWNLEAD CABLE.
SHOWN PER DETAIL "Q".
NO. C803 COPPER LOOP TYPE CABLE
S847X-#10 x 1" STAINLESS STEEL
TEK SCREW. FASTEN CABLE 3'-0"
FASTENER. SECURE WITH NO.
O.C. MAX.
NO. C120 COPPER CABLE.
TO STEEL BONDING CLAMP.
NO. C559 CAST BRONZE CABLE
NO. C619A ALUMINUM TO COPPER
FURNISHED WITH ASSEMBLY.
TIGHT WITH NEOPRENE WASHER
PENETRATION PERMANENTLY WATER
1/2"∅ x 12" ALL THREAD ROD. SEAL
NECTING ASSEMBLY, FURNISHED WITH
BIMETALLIC THRU-ROOF CABLE CON-
REQUIRED WITH SPLICER AS SHOWN
DUCTOR AND CLOSE CIRCUIT WHERE
CABLE TO THE NEAREST MAIN CON-
NO. A100 ALUMINUM CABLE. COURSE
PER DETAIL "E1".
DETAIL "K" SHEET ED4.2.
TO BELOW GRADE AS SHOWN PER
EXTERIOR WALL CONSTRUCTION
COURSE CABLE EXPOSED DOWN
COPPER DOWNLEAD CABLE.
3'-0" O.C. MAX.
DRIVE ANCHOR. FASTEN CABLE
WITH 1/4" x 1-1/4" MASONRY
CABLE ANCHOR. FUR- NISHED
COPPER LOOP TYPE MASONRY
STAINLESS STEEL SCREW. FASTEN
COPPER LOOP TYPE CABLE FASTENER.
SHOWN PER DETAIL "T" SHEET ED4.2
CIRCUIT WHERE REQUIRED WITH SPLICER AS
NEAREST MAIN CON- DUCTOR AND CLOSE
COPPER CABLE. COURSE CABLE TO THE
CABLE 3'-0" O.C. MAX.
SECURE WITH NO. #10 x 1"
STAINLESS STEEL NUT.
STEEL MACHINE SCREW AND NO. 1/4"
SECURE WITH 1/4" x 3/4" STAINLESS
CAST BRONZE TERMINAL BONDING LUG.
FASTEN CABLE 3'-0" O.C. MAX.
1-1/4" MASONRY DRIVE ANCHOR.
ANCHOR. FURNISHED WITH 1/4" x
COPPER LOOP TYPE MASONRY CABLE
BONDING WIRE.
COPPER SECONDARY
AS SHOWN PER DETAIL "T" SHEET ED4.2.
CIRCUIT WHERE REQUIRED WITH SPLICER
NEAREST MAIN CON- DUCTOR AND CLOSE
COPPER CABLE. COURSE CABLE TO THE
COMPOUND. FASTEN CABLE 3'-0"
APPLICATION OF RUBBER ADHESIVE
HOLDER. SECURE IN PLACE WITH AN
COPPER ADHESIVE TYPE CABLE
COMBINATION CABLE
CAST BRONZE PARALLEL
SPLICER.
O.C. MAX.
THIS SHEET OR TO EAVE AS SHOWN PER
TO ROOF EDGE AS SHOWN PER DETAIL "G"
EXPOSED UP EXTERIOR WALL CONSTRUCTION
COPPER DOWNLEAD CABLE. COURSE CABLE
DETAIL "E" THIS SHEET.
ROD CLAMP.
CAST BRONZE CABLE TO GROUND
THIS SHEET FOR LOCATION.
LAYOUT AND GENERAL NOTE "7"
STEEL GROUND ROD. REFER TO
3/4" x 10'-0" COPPER- CLAD
"7" SHEET____ FOR LOCATION.
REFER TO LAYOUT AND GENERAL NOTE
GRADE TO GROUND ROD CONNECTION.
COPPER CABLE. COURSE CABLE BELOW
MANNER AS SHOWN.
PROTECTOR. SPACE EVENLY IN SIMILAR
DRIVE ANCHOR. FOUR REQUIRED PER
HOLDER. SECURE WITH MASONARY
COPPER LOOP TYPE PROTECTOR PIPE
CONTINUITY.
END OF PROTECTOR TO INSURE ELECTRICAL
BELOW GRADE. SECURE SET SCREWS AT EACH
DOWNLEAD TO EXTEND A MINIMUM OF 1'-0"
PROTECTOR. ONE REQUIRED PER EACH
3/4" x 7'-0" COPPER TUBE TYPE CABLE
TO TOP OF WALL PER DETAIL "H".
EAVE AS SHOWN PER DETAIL "E" OR
AS SHOWN PER DETAIL "G" OR TO
UP EXTERIOR WALL CONSTRUCTION TO ROOF EDGE
COPPER DOWNLEAD CABLE. COURSE CABLE EXPOSED
3'-0" O.C. MAX.
DRIVE ANCHOR. FASTEN CABLE
WITH 1/4" x 1-1/4" MASONRY
CABLE ANCHOR. FURNISHED
COPPER LOOP TYPE MASONRY
APPROX.
F
INISHED G
RADE
PROFESSIONAL ENGINEERING CONSULTANTS, P.A.
CHEROKEE BUILDING 4150 S. 100TH EAST AVE., SUITE 401
TULSA, OK 74146 918-664-5400 www.pec1.com
C.O.A. #1046 PE/LS EXPIRES: JUNE 30, 2019 PEC PROJECT # 170737-000
FILE: DRAWING:
ATLAS PAGE NO: 358
L O
C A
L F
IL
E
P L O
T D
A T
E
L W
P B
J O
B N
O
C E
N T
R A
L F
IL
E
A
2 3 4 5 6 7 8 9 10
A
B
C
D
E
F
G
65%
PRELIMINARY
DESIGN
DOCUMENTS
T E
M P
L A
T E
ENGINEERING SERVICES DEPARTMENT
PROJECT NO. 170100
CITY OF TULSA, OKLAHOMA
SHEET NAME:
DATE:
SHEET OF ## SHEETS
SHEET NO.
H
I
J
B
C
D
E
F
G
H
I
J
PLANS AND ESTIMATES PREPARED BY :
PLAN SCALE:
1" = ??'
DESIGNED
SURVEY
PROFILE SCALE:
HORIZONTAL:
1" = ??'
VERTICAL:
1" = ??'
DRAWN
PROJ. MGR.
APPROVED:
LEAD ENGR.
FIELD MGR.
RECOMMENDED:
DESIGN MANAGER CITY ENGINEER
131211
1 2 3 4 5 6 7 8 9 10 131211
-0
-E
L E
C T
R
IC
A L M
O D
E L -R d e ta c h e d .r vt
/1
/2
:2 :3
A
M
CITY OF TULSA
OKLAHOMA AIR NATIONAL GUARD
138 FW MISSION TRAINING CENTER
ELECTRICAL GROUNDING DETAILS
EX501
-1
-G
F lw p b
-f ile s rv r\ F e d e ra l$
\O K
A N
G I D
IQ
T u ls a \0
M
T C
\0
D w g \0
A
R C
H \O
K A
N G
M T
C
.r vt
L W
P B
.0
ELECTRICAL
GROUNDING DETAILS
LKN
WAN 11/16/2017
11/16/2017
11/16/2017
NO SCALE
LIGHTNING- AL- ADHESIVE AIR TERMINAL
NO SCALE
LIGHTNING- ALUM- EQUIP. AIR TERMINAL
NO SCALE
LIGHTNING- ALUM- THRU-ROOF CABLE CONN.
NO SCALE
LIGHTNING- EXPOSED DOWNLEAD AT SCREENWALL
NO SCALE
LIGHTNING- EXPOSED DOWNLEAD O LOWER ROOF
NO SCALE
LIGHTNING- EXPOSED DOWNLEAD TO GROUNDING CONN.
REVISION DESCRIPTION DATE APPR