Electrical_Plans_-_Renovate_bldg_1201_(2015).pdf

PDF 2 MB Posted

Attached to
LIGHTNING PROTECTION Federal contract opportunity
Solicitation number
W912JA-17-T-0032
Issued by
Department of the Army Alabama Army National Guard

About this file

Bldg 1201 Renovate 2015

View the file

Other files for this federal contract opportunity

Other files attached to LIGHTNING PROTECTION, newest first.
File Type Posted
Lightning_Protection_SOW_-_Rev2.docx DOCX document
Aircraft_Shelter_-_electrical_panel_2.JPG JPG image
Electrical_Plans_-_1403.pdf PDF
Electrical_Plans_-_Construct_Bldg_1203.pdf PDF
Site_Visit_Roster.pdf PDF
Electrical_Plans_-_Renovate_bldg_1201_(2011).pdf PDF
Aircraft_Shelter_-_electrical_panel_1.JPG JPG image
Site_Visit_Lightning_protection.pdf PDF
Pre-bid_site_visit_-_QA_1.docx DOCX document
Lightning_Protection_SOW_-_Rev1.doc.docx DOCX document
13100_-_LIGHTING_PROTECTION.doc DOC document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E1.1

E1.1

E1.1

E1.1

EXISTING PANEL 'LP1A'

EXISTING PANEL 'L14'

EXISTING PANEL 'LIG1'EXISTING

TRANSFORMER T-'LIG1'

EXISTING PANEL 'RS480'

EXISTING PANEL 'RS208'

EXISTING PANEL 'MECH1'

EXISTING PANEL 'MDP'

EXISTING PANEL 'LP1B'

EXISTING SWITCHBOARD 'SE'

EXISTING TRANSFORMER

'T-LIG1A'

EXISTING PANEL 'LIG1A'

EXISTING PANEL 'L15'

1 2

3 4

1 2

3 4

1 2

3 4

1 2

3 4EXISTING PANEL 'LP22'

EXISTING PANEL 'PP2'

EXISTING PANEL 'LP23'

EXISTING PANEL '2-3'

EXISTING PANEL 'MECH2'

EXISTING PANEL 'LP2A'

EXISTING PANEL 'LIGA2'

EXISTING

TRANSFORMER 'T-LIGA2'

EXISTING PANEL 'LP2'

EXISTING

TRANSFORMER T-'LIG2'

EXISTING PANEL 'LIG2'

EXISTING PANEL 'L24'

E1.1 6

E1.1

E1.1

E1.1

1 2

3 4

1 2

3 4

1 2

3 4

1 2

3 4

EXISTING PANEL 'LP25'

E0.1

SCALE: 1/16"=1'-0"

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

GARNER

C O N S U L T I N G E N G I N E E R S PROJECT NO: 14-069

E0.1

SCALE: 1/16"=1'-0"

KEYED NOTES:

1. DISCONNECT ALL LIGHT FIXTURES, EMERGENCY LIGHT UNITS AND EXIT SIGNS IN

STAIRWELL (HATCHED AREA) AND MAKE EXISTING LIGHTING BRANCH CIRCUIT

WIRING SAFE FOR RE-USE. PROVIDE BLANK JUNCTION BOX COVER PLATES AS

REQUIRED.

2. CONTRACTOR SHALL IDENTIFY PANELBOARD AND CIRCUIT NUMBER SERVING

EXISTING LIGHTS AND EXIT SIGNS PRIOR TO REMOVAL AND MARK THE COVER PLATE

OF THE HOMERUN JUNCTION BOX WITH THIS INFORMATION.

3. EXISTING RECEPTACLES AND OTHER WALL MOUNTED ELECTRICAL DEVICES SHALL

BE MAINTAINED AND PROTECTED DURING CONSTRUCTION.

4. EXISTING FIRE ALARM SYSTEM SHALL BE MAINTAINED AND PROTECTED DURING

CONSTRUCTION. REMOVE EXISTING COMBINATION SMOKE/HEAT DETECTOR, STORE

AND PROTECT DEVICES FOR RE-USE AS SHOWN ON DRAWING E1.1.

5. REPLACE EXISTING RECEPTACLE WITH NEW 20A, GFI RECEPTACLE TO SUPPORT

WATER COOLER.

6. PROVIDE NEW 20A, GFI RECEPTACLE IN EXISTING JUNCTION BOX FOR CONNECTION

TO NEW WATER COOLER. PROVIDE 2#12 & 1#12(G) IN EXISTING CONDUIT BACK TO

PANELBOARD '2-3' AND CONNECT TO EXISTING CIRCUIT BREAKER 18 LABELED 'REC

WATER COOLER'.

7. EXISTING EXIT SIGN AND FLEXIBLE METALLIC CABLING TO BE REMOVED. PROVIDE

PLUG IN JUNCTION BOX AS REQUIRED.

# GENERAL NOTES FOR DEMOLITION:

1. ALL ELECTRICAL WORK AND MATERIAL SHALL CONFORM TO THE LATEST EDITION

OF THE N.E.C. AND THE REQUIREMENTS OF THE STATE AND LOCAL AUTHORITY

HAVING JURISDICTION.

2. WHERE ANY CIRCUITS HAVE BEEN INTERRUPTED DUE TO REMOVAL OF OUTLETS,

DEVICES, WALLS, ETC., THE CONTRACTOR SHALL BE RESPONSIBLE FOR

RECONNECTING OR REWIRING THE CIRCUIT AS REQUIRED TO INSURE CIRCUIT CONTINUITY

TO ALL REMAINING AND NEW DEVICES OR FIXTURES.

3. CONTRACTOR SHALL PROVIDE ALL MATERIAL NECESSARY TO FINALIZE A NEAT,

COMPLETE AND PROPERLY WORKING ELECTRICAL SYSTEM WHICH CONFORMS TO

ALL LOCAL CODES AND THE NATIONAL ELECTRICAL CODE AS PER PLANS, AND

SPECS.

4. ALL REMOVED ELECTRICAL EQUIPMENT (i.e. WIRE, CONDUIT, FIXTURES, SWITCHES, ETC.) SHALL BE PROPERLY DISPOSED OF BY THE CONTRACTOR.

5. AFTER COMPLETION OF RENOVATION WORK CONTRACTOR SHALL PROVIDE AND

INSTALL A CORRECT, TYPED DIRECTORY CARD FOR MODIFIED PANELS.

6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE SITE AND

BECOME THOROUGHLY FAMILIAR WITH ALL EXISTING CONDITIONS PRIOR TO BID

DATE, AS HE SHALL BE RESPONSIBLE FOR SAME.

7. ELECTRICAL CONTRACTOR VERIFY STATUS OF ANY ITEMS NOT SHOWN WITH

OWNER PRIOR TO REMOVAL OF ITEM.

8. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING LOADS

ON EXISTING PANELS PRIOR TO ADDING NEW LOADS.

9. ANY BREAKERS ADDED TO EXISTING PANELS SHALL HAVE THE SAME AIC RATING

AS EXISTING.

10. WHERE EXISTING CONDUIT IS INDICATED TO REMOVED IT SHALL BE PERMISSIBLE

TO ABANDON SAID CONDUIT AND REMOVE CONDUCTORS ONLY.

11. ABANDONED AND REMOVED CONDUIT SHALL HAVE WIRE PULLED FROM THEM.

12. PROVIDE AND INSTALL BLANK COVERS ON ALL REMAINING OUTLETS OR JUNCTION

BOXES WHERE DEVICES OR FIXTURES HAVE BEEN REMOVED.

F1

X

F1

OC

F

EX

F

RL

EX

EX

6 PP

LV

F1

F1

OC

RL

LEX

PP

LV

X

F1

F1

OC

OC

F

EX

F

RL

EX

EX5

WA

PP

LV

LV

F1

F1

OC

RL

L EX

PP

LV

X

F1

F1

OC

F

EX

F

RL

EX

X

EX

PP

LV

F1

F1

OC

RL

3 4

L

EX

PP

LV

X

F1

F1

OC

OC

F EX

F

RL

EX

EX

EX

EX

4WA

PP

LV

LV

F1

F1

OC

RL

L

EX

EX

PP

LV

E1.1

SCALE: 1/4"=1'-0"

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

GARNER

C O N S U L T I N G E N G I N E E R S PROJECT NO: 14-069

E1.1

E1.1

SCALE: 1/4"=1'-0"

E1.1

E1.1

SCALE: 1/4"=1'-0"

E1.1

SCALE: 1/4"=1'-0"

E1.1

E1.1

SCALE: 1/4"=1'-0"

SCALE: 1/4"=1'-0"

SCALE: 1/4"=1'-0"

SCALE: 1/4"=1'-0"

KEYED NOTES:

1. CONTRACTOR SHALL MAKE CONNECTION TO EXISTING CIRCUIT

IN SPACE AS REQUIRED.

2. CONTRACTOR SHALL CONNECT POWER TO LIGHT FIXTURE

CIRCUIT AS SHOWN IN DETAIL 2 ON SHEET E2.1 SUCH THAT

ACTIVATION OF ANY SENSOR WILL CAUSE THE STAIRWELL

LIGHTS TO COME UP TO 100% BRIGHTNESS. STAIRWELL LIGHTS

SHALL NEVER DROP BELOW 50% ILLUMINATION.

3. CONTRACTOR SHALL RE-INSTALL EXISTING COMBINATION

SMOKE/HEAT DETECTOR (REMOVED AND STORED UNDER

DEMOLITION WORK) IN NEW LAY-IN CEILING AND EXTEND

EXISTING FIRE ALARM CIRCUIT AS REQUIRED. EXISTING FIRE

ALARM SYSTEM SHALL BE RE-TESTED AND RE-CERTIFIED IN

AREAS WHERE WORK WAS PERFORMED/COMPLETED.

4. EXISTING FIRE ALARM DEVICE TO BE MAINTAINED AND

PROTECTED DURING CONSTRUCTION.

5. EXISTING ELECTRIC HEATER TO BE MAINTAINED AND

PROTECTED DURING CONSTRUCTION.

6. EXISTING RECEPTACLE TO BE MAINTAINED AND PROTECTED

DURING CONSTRUCTION.

7. RELOCATE EXISTING MC CABLES ABOVE NEW CEILING AND

PATCH HOLES AS REQUIRED TO MAINTAIN FIRE RATING OF

WALL.

8. EXISTING 'BRIEFING IN PROGRESS' SIGN TO BE MAINTAINED AND

PROTECTED DURING CONSTRUCTION.

9. RE-USE EXISTING JUNCTION BOX FOR MOUNTING OF FIXTURE.

EXISTING MANUEL TRANSFER

SWITCH TO BE REMOVED. INSTALL

NEW MANUEL TRANSFER SWITCH

IN SAME LOCATION. REUSE EXISTING

FEEDER CONDUIT. REFER TO RISER

DIAGRAM FOR ADDITIONAL INFORMATION.

REFER TO RISER DIAGRAM

FOR ELECTRICAL WORK

REQUIRED.

GENERATOR PAD

SEE DETAIL FOR

REQUIREMENTS.

GP

REFER TO RISER DIAGRAM

FOR MORE INFORMATION.

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

GARNER

C O N S U L T I N G E N G I N E E R S PROJECT NO: 14-069

FIRST FLOOR PLAN - POWER

SCALE: 3/32"=1'-0"

E2.1

'L24'

'LIG2'

5 5

3 1

'LP2'

L26-1,3,5

SEE NOTE #1 UNDER

ELECTRICAL RENOVATION

NOTES

L26-2

SEE NOTE #1 UNDER

ELECTRICAL RENOVATION

NOTES

L26-4,6,8

SEE NOTE #1 UNDER

ELECTRICAL RENOVATION

NOTES

1. DISCONNECT EXISTING CIRCUIT FROM PANEL 'L24' AND EXTEND EXISTING CIRCUIT AND

RECONNECT TO NEW BREAKERS IN PANEL 'L26' AS INDICATGED BY CIRCUIT NUMBERS.

NEW PANEL 'L26'

NEW PANEL 'EM'

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

GARNER

C O N S U L T I N G E N G I N E E R S PROJECT NO: 14-069

SECOND FLOOR PLAN - POWER

SCALE: 3/32" = 1'-0"

E2.2

SEE NOTE #3 UNDER

ELECTRICAL RENOVATION

NOTES.

RPMC-20/1P

SEE NOTE #2 UNDER

ELECTRICAL RENOVATION

NOTES.

SEE NOTE #1 UNDER

ELECTRICAL RENOVATION

NOTES.

L26-7 L26-9

1. DISCONNECT EXISTING CIRCUIT FROM 20/1P BREAKER AND EXTEND EXISTING

CONDUCTORS TO NEW BREAKER IN PANEL 'L26'.

2. PROVIDE A 20/1P, 120V, CIRCUIT FROM SPARE BREAKER IN EXISTING PANEL 'RPMC'

TO SERVE EXISTING LIGHTS.

3. DISCONNECT EXISTING LIGHTING CIRCUIT FROM PANEL 'LP2'. EXISTING BREAKER SHALL

BECOME SPARE AND REMOVE CONDUCTORS FROM EXISTING CONDUIT. CONDUIT SHALL

REMAIN IN PLACE.

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

GARNER

C O N S U L T I N G E N G I N E E R S PROJECT NO: 14-069

SECOND FLOOR PLAN - LIGHTING

SCALE: 3/32"=1'-0"

E3.1

T-IG2

PANEL

"LIG2"

WITH A PHASE METER PRIOR TO CONNECTING LOADS.

LOADING . CONTRACTOR SHALL TEST EACH FEEDER AND EQUIPMENT FEEDERS

OF ALL POWER FEEDER CONDUCTORS FOR THE PROPER PHASE SEQUENCE AND

2. CONTRACTOR IS RESPONSIBLE FOR THE CONNECTING, INSTALLATION, AND MARKING

1. INSTALLATION AND CONNECTION OF ALL DEVICES SHALL BE IN ACCORDANCE WITH

NEC, MANUFACTURER'S RECOMMENDATIONS, AND STATE AND LOCAL CODES.

PROJECT PRIOR TO BID. CONTRACTOR SHALL THEN PROVIDE THE PROPERLY SIZED OVERCURRENT

3. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING AND VERIFYING WITH ALL DIVISIONS

THE ACTUAL NAMEPLATE DATA OF ALL EQUIPMENT AND DEVICES SUPPLIED ON THIS

DEVICES (CIRCUIT BREAKERS, CONDUCTORS, DISCONNECTS, FUSES, ETC.) TO PROPERLY PROTECT

THE EQUIPMENT PER THE NEC. ENGINEER'S DESIGN BASED ON DATA GIVEN TO HIM BY

DESIGNERS OF OTHER DIVISIONS, ACTUAL NAMEPLATE DATA COULD DIFFER.

BEEN INSTALLED.

4. SEAL ALL CONDUITS FROM THE EXTERIOR WITH A SEALING COMPOUND, ONCE ALL CABLING HAS

0/3

4# 3/0

1#

6( G)

- E

XI

ST

IN

G 2"

C

4 #3/0 & 1 #6(G) - EXISTING 2"C

SP

AR

E

EXIST.

EXIST.

EXIST.

200/3/1

PANEL

"L26"

NEW

PANEL

"EM"

NEW

4 #3/0 & 1 #6(G) - 2"C

4# 3/0

1#

8( G)

1 1

/4" C

NEW MANUEL TRANSFER SWITCH 'MTS'

200 AMP, 3 POLE, SN, NEMA 3R

FUSED AT 200 AMPS. MOUNTED IN SAME

LOCATION WHERE EXISTING TRANSFER

SWITCH HAS BEEN REMOVED. REUSE

EXISTING FEEDER CONDUIT.

INSTALL NEW 200 AMP, 3 POLE

BREAKER. EXISTING SWITCHBOARD

IS 2500 AMP MAIN CIRCUIT

BREAKER, 120/208V, 3 POLE, 4W.

PANEL

"RPMC"

SEE POWER PLAN FOR LOCATIONS OF PANELS.

DISCONNECT FEEDER FROM BREAKER AND REMOVE CONDUCTORS TO DISCONNECT SWITCH.

DISCONNECT SWITCH SHALL REMAIN. EXISTING BREAKER SHALL BECOME A SPARE.

DISCONNECT CONDUCTORS AND REMOVE EXISTING 100/3 P BREAKER.

EXISTING 2" CONDUIT TO REMAIN AND BE REUSED. REMOVED CONDUCTORS AND REROUTE CONDUIT

AS REQUIRED.

REMOVE EXISTING CONDUCTORS FROM TRANSFER SWITCH LOCATION TO PANEL. EXISTING CONDUIT

SHALL BE ABANDON AND LEFT IN PLACE.

EXISTING MANUAL TRANSFER SWITCH SHALL BE REMOVED.

EXISTING PANEL 'RPMC' SHALL REMAIN IN PLACE. SEE RISER BELOW FOR NEW FEEDER SERVICE.

EXISTING PANEL 'LIG2', TRANSFORMER AND DISCONNECT SWITCH SHALL REMAIN IN PLACE. SEE RISER

PLAN BELOW FOR NEW FEEDER SERVICE.

4 #3 & 1 #8(G) - 1 1/4"C

3#1/0 & 1#6(G) - 2"C

DEMOLITION POWER RISER DIAGRAM

NOT TO SCALE

E4.1

REVISED POWER RISER DIAGRAM

NOT TO SCALE

E4.1

POWER RISER DIAGRAM NOTES: SHEET NOTES:

CONNECT TO EXISTING

DISCONNECT SWITCH

AS REQUIRED.

CONNECT TO EXISTING

PANEL AS REQUIRED.

X

X

X

GP

CONTRACTOR TO PROVIDE 200A PLUG,

EQUAL TO HUBBELL #HBL5200PSIWR WITH

25' OF TYPE W CORD, 5W, 3/0 CONNECTED

TO IT. THE OWNER WILL BE RESPONSIBLE

FOR MAKING FINAL CONNECTION TO

OWNER FURNISHED GENERATOR.

CONTRACTOR TO PROVIDE 200A RECEPTACLE,

EQUAL TO HUBBELL #HBL5200RSIWR MOUNTED

IN BOX EQUAL TO HUBBELL #MB2004W AT

LEAST 18"A.F.G.

4 #3/0 & 1 #6(G) - 2"C

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

GARNER

C O N S U L T I N G E N G I N E E R S PROJECT NO: 14-069

P A N E L B O A R D S C H E D U L E PANEL 'L26'

DIRECTORY LOAD (VOLT*AMPS) CKT

NO

BRKR

AMPS

BRKR

AMPS

CKT

NO

LOAD (VOLT*AMPS) DIRECTORY

A B C A B C

RECEPTS. 600 1 20 20 2 400 RECEPTS.

RECEPTS. 800 3 20 20 4 400 RECEPTS.

RECEPTS. 800 5 20 20 6 600 RECEPTS.

LIGHTS 1120 7 20 20 8 400 RECEPTS.

LIGHTS 1540 9 20 10

11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

SUB-TOTAL 1720 2340 800 800 400 600 SUB-TOTAL

VOLTAGE : 120/208, 3PH, 4W PANEL TYPE: AQ TOTAL VA - A 2520 LOCATION

MAIN BREAKER : MLO MAIN BUS: 125A TOTAL VA - B 2740 ELEC. ROOM

MOUNTING: SURFACE A.I.C. RATING: 10K TOTAL VA - C 1400 TOTAL CONNECTED LOAD

NOTES: ENCLOSURE: NEMA 1 TOTAL VA 6660 18.50 A

PANELBOARD SCHEDULE NOTES (APPLYS TO ALL PANELS)

1. PANELBOARD DESIGNATIONS INDICATED IN ABOVE SCHEDULE ARE THOSE OF G.E COMPANY EQUAL EQUIPMENT BY OTHER MANUFACTURERS WILL BE CONSIDERED IF OTHER MANUFACTURER'S PANELS ARE TO BE USED, CONTRACTOR

SHALL BE RESPONSIBLE FOR VERIFYING ALL SPACE REQUIREMENTS.

2. EACH PANELBOARD SHALL HAVE AN INTEGRATED EQUIPMENT RATING EQUAL TO THE LOWEST A.I.C. OF ANY CIRCUIT

BREAKER IN PANEL.

3. WHERE CURRENT LIMITING CIRCUIT BREAKERS ARE USED. THEY SHALL BE SERIES RATED FOR DOWNSTREAM PROTECTION. SUBMITTAL DATA SHALL INCLUDE A CURRENT U.L. APPROVED TABLE OF SERIES CONNECTED RATINGS OF

ALL CIRCUIT BREAKERS TO BE USED.

4. ALL BRANCH CIRCUIT BREAKERS SHALL BE BOLT ON TYPE.

5. ALL CIRCUIT BREAKERS 100A AND ABOVE SHALL BE SOLID STATE.

6. ALL 120/208V, 3PH, 4W PANELS SHALL BE SERIES RATED UNLESS NOTED OTHERWISE.

7. CONTRACTOR TO PROVIDE ALL BRANCH CIRCUIT NUMBERS USING PERMANENT CIRCUIT MARKERS WITH THE PROPER CIRCUIT NUMBER ATTACHED NEXT TO EACH BREAKER. STICK ON NUMBERS WILL NOT BE APPROVED. ON SPECTRA BRANCH BREAKERS, CONTRACTOR TO PROVIDE FIELD MOUNTED PHENOLIC NAMEPLATE INDICATING EACH LOAD.

8. PANEL SHALL HAVE SURGE PROTECTION DEVICE. SURGE PROTECTION DEVICE MUST BE INSTALLED INTERNALLY TO THE ELECTRICAL DISTRIBUTION EQUIPMENT AND SHIPPED FROM THE MANUFACTURER'S FACTORY AS A COMPLETE U.L. LISTED ASSEMBLY. PANELBOARD SPDS SHALL BE GENERAL ELECTRIC TMENVNE/100/200. OR EQUAL. VOLTAGES FOR DEVICES SHALL BE INDICATED ON THE PANELBOARD SCHEDULES AND SINGLE LINE DIAGRAM. THIS NOTE ONLY APPLIES TO PANELS

NOTED SO

9. ALL BLANK SPACES SHALL BE ASSUMED BUSSED SPACE FOR EACH PANELBOARD.

10. A.I.C. RATING, SR STANDS FOR SERIES RATED.

6'-0"

9"

3" 3"

8'-0"

1" BEVEL (TYPICAL)

1" CHAMFER (TYPICAL)

KEYED NOTES:

1. CONCRETE PAD. CONCRETE TO DEVELOP 3000 PSI COMPRESSIVE STRENGTH WITHIN 28 DAYS.

2. COMPACTED GRAVEL FILL. PAD SHOULD BE POURED AGAINST A 3 INCH MINIMUM COMPACTED

GRAVEL FILL THAT IS PLACED ON WELL COMPACTED EARTH.

3. #6 REBAR (GRADE 60) EQUALLY SPACED 12" EACH WAY.

4. #2/0 STRANDED BARE COPPER, CONTINUOUS GROUND BUS WIRE TO BE FURNISHED AND

INSTALLED BY CONTRACTOR.

TYPICAL GENERATOR PAD DETAIL

NOT TO SCALE

NOTES:

1. VERIFY GENERATOR SIZES WITH OWNER. IF GENERATOR SIZES ARE DIFFERENT THAN WHAT

IS SHOWN, ADJUST ALL MEASUREMENTS SO THAT THE CLEARANCES ARE THE SAME AND THE

PAD IS PLACED IN GENERALLY THE SAME AREA.

E4.2

GENERATOR

AND ENCLOSURE

12"4"

18"

9"

GENERATOR

AND ENCLOSURE

BY OWNER

P A N E L B O A R D S C H E D U L E PANEL 'EM'

DIRECTORY LOAD (VOLT*AMPS) CKT

NO

BRKR

AMPS

BRKR

AMPS

CKT

NO

LOAD (VOLT*AMPS) DIRECTORY

A B C A B C

EXISTING PANEL 'LIG2' 13000 1 150/3 60/3 2 2220 PANEL 'L26'

| 13000 3 | | 4 2220 | | 13000 5 | | 6 2220 |

7 100/3 8 4733 EXISTING PANEL 'RPMC'

9 | 10 4733 | 11 | 12 4733 | 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

SUB-TOTAL 13000 13000 13000 6953 6953 6953 SUB-TOTAL

VOLTAGE : 120/208, 3PH, 4W PANEL TYPE: AQ TOTAL VA - A 19953 LOCATION

MAIN BREAKER : MLO MAIN BUS: 225A TOTAL VA - B 19953 ELEC. ROOM

MOUNTING: SURFACE A.I.C. RATING: 10K TOTAL VA - C 19953 TOTAL CONNECTED LOAD

NOTES: ENCLOSURE: NEMA 1 TOTAL VA 59859 166.28 A

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

ELECTRICAL LEGEND

F1

RECESSED LIGHT FIXTURE. SUBSCRIPT 'F1' REPRESENTS FIXTURE TYPE (SEE LIGHTING FIXTURE

SCHEDULE).

WALL MOUNTED LIGHT FIXTURE. SUBSCRIPT 'WA' REPRESENTS FIXTURE TYPE (SEE LIGHTING

FIXTURE SCHEDULE).

EXIT LIGHT SURFACE MOUNTED ON CEILING. IF NO ARROWS ARE SHOWN, THEN ALIGN FACE INTO

CORRIDOR OR OPEN ROOM WITH NO ARROWS.

DUAL TECHNOLOGY OCCUPANCY SENSOR (SENSORSWITCH #CM PDT 9), CEILING MOUNTED, FOR

STEP-DIMMING OF STAIRWELL LIGHT FIXTURES.

POWER PACK (SENSORSWITCH #PP20).

TRANSFORMER.

LIGHTING OR POWER BRANCH CIRCUIT PANELBOARD.

BRANCH CIRCUIT, CONCEALED ABOVE CEILING OR IN WALL, 1/2"c. UNLESS NOTED, WITH GREEN

GROUNDING ELECTRODE CONDUCTOR IN ADDITION TO CIRCUIT SHOWN, MINIMUM #12 AWG

COPPER.

BRANCH CIRCUIT WIRING (1 HOT, 1 NEUTRAL, 1 SWITCH LEG).

LOW VOLTAGE WIRING (PER MAUFACTURER'S RECOMMENDATIONS).

DUPLEX RECEPTACLE. SUBSCRIPT 'EX' DENOTES EXISTING TO REMAIN.

FIRE ALARM SYSTEM PULL STATION. SUBSCRIPT 'EX' DENOTES EXISTING TO REMAIN.

FIRE ALARM SYSTEM COMBINATION SMOKE/HEAT DETECTOR. SUBSCRIPT 'RL' DENOTES RELOCTAED

EXISTING DEVICE.

FIRE ALARM SYSTEM COMBINATION HORN/STROBE. SUBSCRIPT 'EX' DENOTES EXISTING TO REMAIN.

FIRE ALARM SYSTEM STROBE. SUBSCRIPT 'EX' DENOTES EXISTING TO REMAIN.

SYMBOL MANUFACTURE & CATALOG # REMARKSLAMP WATTS MOUNTING VOLTS

LIGHTING FIXTURE SCHEDULE

F1 COLUMBIA #LJT24-40MLG-FSA12125-ESD-U-ELL14

EQUAL BY: LITHONIA

COOPER

LED

4000K

52 RECESSED 120 RECESSED 2'X4' LUMINAIRE WITH: STEEL HOUSING (PAINTED WHITE); 0.125" ACRYLIC PRISMATIC

LENS; STEP-LEVEL DIMMER AND 90 MINUTE EMERGENCY BALLAST (SEE NOTE 6).

FIXTURE SCHEDULE NOTES:

1. ALL FIXTURES WITH EMERGENCY BATTERY PACKS SHALL BE FACTORY INSTALLED.

2. ALL LUMINAIRES AND INSTALLATION SHALL BE IN ACCORDANCE WITH NEC, NFPA, AND LOCAL CODES. ALL LUMINAIRES SHALL BE UL LISTED AND INSTALLED IN ACCORDANCE WITH THE UL LISTING.

3. ALL LUMINAIRE DEVICES, COMPONENTS, FITTINGS, SUPPORTS, ETC. SHALL BE COORDINATED TO PROVIDE A COMPLETE UL LISTED INSTALLATION.

4. ALL LUMINAIRE BALLASTS, DRIVERS, LAMPS, ETC. SHALL BE COMPATIBLE WITH THE LIGHTING CONTROL SYSTEM OR DIMMING CONTROLS SYSTEM PROVIDED.

5. SECURE EACH LAY-IN LUMINAIRE AT TWO LOCATIONS TO THE CEILING GRID. PROVIDE BOLTS, SCREWS, RIVETS OR APPROVED CLIPS FOR USE WITH THE TYPE PF CEILING GRID AND LUMINAIRE INSTALLED.

6. ALL EXIT SIGNS AND LUMINAIRES DESIGNATED AS EMERGENCY SHALL BE PROVIDED WITH A MINIMUM OF 1100 LUMEN EMERGENCY BATTERY BALLAST CAPABLE OF 90 MINUTES OF OPERATION.

WA HUBBELL #LMC-30LU-4K-3-035-1-B0C277/PC(120)

EQUAL BY: LITHONIA

METALUX

LED

4000K

43 SURFACE 120 ARCHITECTURAL WALL PACK: DIE-CAST ALUMINUM HOUSING (BRONZE); CLEAR GLASS LENS;

PHOTOCELL; AND 90 MINUTE EMERGENCY BALLAST, ZERO DEGREES.

E4.3

LAY-IN FIXTURE SUPPORT DETAIL

NOT TO SCALE

NOTES:

1. INDEPENDENT SUPPORT WIRES MUST BE MARKED (PAINTED) SO THAT THEY CAN BE

DISTINGUISHABLE AS NON CEILING SUPPORT WIRES PER N.E.C.

2. INDEPENDENT SUPPORT WIRES SHALL NOT HAVE AN ANGLE OF MORE THAN 45° FROM THE

CEILING GRID.

STRAP CONDUIT WITHIN 3' OF BOX

AND A MAXIMUM OF 10' THERE-AFTER

AS PER N.E.C.

JUNCTION BOX.

LIGHTING FIXTURE SUPPORT WIRE ATTACHED

TO STRUCTURAL MEMBERS SO THAT FIXTURE

IS SUPPORTED INDEPENDENT OF CEILING.

WIRE TO BE A MIN. OF #14 GAGE

PRESTRAIGHTENED GALV. ATTACHED AT

DIAGONAL CORNERS. (SEE NOTE 1.)

CEILING SUPPORT WIRE (TYP).

FLEXIBLE CONNECTION TO FIXTURE.

ATTACH TO STRUCTURE TO PREVENT

FLEX FROM RESTING ON CEILING.

CONDUIT.

LAY-IN LIGHT FIXTURE.

CEILING GRID.

ELECTRICAL CONTRACTOR SHALL

ATTACH FLEX CONDUIT WITH

APPROVED STRAP OR HANGER.

OC

GENERAL ELECTRICAL NOTES:

1. EXISTING SERVICES ARE 120/208 VOLT, 3 PHASE, 4 WIRE, WYE.

2. INSTALLATION SHALL COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND

MANUFACTURER'S RECOMMENDATIONS.

3. ALL CONDUIT SIZES SHALL BE A MINIMUM OF 1/2" UNLESS OTHERWISE NOTED ON THE DRAWINGS.

4. CHECK ALL LIGHTING FIXTURES FOR EXACT TYPE MOUNTING AND SPACE REQUIRED BEFORE

ROUGHING IN. SUPPORT OF ALL LIGHT FIXTURES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL

CONTRACTOR. FIXTURES SHALL BE SUPPORTED INDEPENDENT OF CEILING FROM STRUCTURAL

MEMBERS OF THE BUILDING.

5. ALL CONDUIT SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED/SHOWN EXPOSED.

6. A GREEN EQUIPMENT GROUNDING CONDUCTOR (SIZED PER N.E.C.) SHALL BE INSTALLED IN EACH AND

EVERY CONDUIT. INCLUDING BUT NOT LIMITED TO; BRANCH CIRCUITS, SWITCH LEGS, FEEDERS. ETC.

7. WHERE EXPOSED CONDUITS ARE NECESSARY, ELECTRICAL CONTRACTOR SHOULD MAKE HIS/HER

BEST EFFORT TO HAVE CONDUITS NEATLY (PARALLEL, PERPENDICULAR, STRAIGHT, ETC...) RUN

AGAINST WALLS.

8. PROVIDE MEANS BY DEFINITION TO FURNISH AND INSTALL.

9. FIRE ALARM SYSTEM SHALL BE RE-TESTED AND RE-CERTIFIED IN AREAS WHERE WORK WAS

PERFORMED/COMPLETED.

10. WIRING SYSTEM SHALL CONSIST OF COPPER WIRING INSTALLED IN CONDUIT, MINIMUM WIRE SIZE

SHALL BE #12 AWG.

11. ALL CONDUCTORS SHALL BE TYPE THHN.

12. CONDUIT ABOVE CEILINGS, IN WALLS, ETC., SHALL BE EMT WHERE NOT EXPOSED TO MOISTURE OR

DAMAGE. CONDUIT SUBJECT TO DAMAGE OUTSIDE BUILDING SHALL BE GALVANIZED RIGID CONDUIT.

CONDUIT SHALL BE SIZED IN ACCORDANCE WITH TABLE 1, CHAPTER 9 OF N.EC.

13. OUTLET BOXES SHALL BE GALVANIZED OR SHERADIZED SHEET-STEEL BOXES, AT LEAST 1-1/2" DEEP

AND SIZED AS PER N.E.C.

14. OUTLET BOXES AND ENCLOSURES WITH CONCENTRIC RING KNOCKOUTS SHALL BE PROVIDED WITH

BONDING JUMPERS FROM BUSHING TO ENCLOSURE.

15. ALL CONDUCTORS SHALL BE 99% COPPER (NO ALUMINUM CONDUCTORS BE ACCEPTED).

16. ALL ELECTRICAL EQUIPMENT IS TO BE FURNISHED BY ELECTRICAL CONTRACTOR.

17. THE ELECTRICAL CONTRACTOR SHALL CAREFULLY COORDINATE HIS WORK WITH OTHER

CONTRACTORS, THROUGH THE GENERAL CONTRACTOR, FOR SPACE REQUIREMENTS, FOR

EQUIPMENT AND LIGHTING FIXTURES AND LOCATIONS OF ELECTRICAL CONNECTIONS.

18. CONTRACTOR SHALL PROVIDE ALL MATERIAL NECESSARY TO FINALIZE A NEAT, COMPLETE AND

PROPERLY WORKING ELECTRICAL SYSTEM WHICH CONFORMS TO ALL LOCAL CODES AND THE

NATIONAL ELECTRICAL CODE AS PER PLANS, AND SPECS.

19. ANY BREAKERS ADDED TO EXISTING PANELS SHALL HAVE THE SAME AIC RATING AS EXISTING.

L

F

F

T

EX

EX

RL

EX

EX

X

X DUAL-LITE #LX-U-R-W-E-I

EQUAL BY: LITHONIA

COOPER

LED

W/UNIT

5 SURFACE 120 EXIT SIGN WITH: WHITE, THERMOPLASTIC HOUSING; RED LETTERING; INTEGRAL NICKEL CADMIUM

BATTERY AND CHARGER AND SELF-TESTING/SELF-DIAGNOSTIC ELECTRONICS (SEE NOTE 6).

PP

WA

LV

E4.3

STEP-DIMMING WIRING DIAGRAM

NOT TO SCALE

NOTES:

1. CIRCUIT 'SLA' IS ALWAYS ON.

2. CIRCUIT 'SLB' IS ON ONLY WHEN THE OCCUPANCY SENSOR DETECTS A PERSON IN THE

STAIRWELL.

G

N

H

POWER PACK MOUNTED

TO JUNCTION BOX.

LED LIGHT FIXTURE WITH

STEP-DIMMING

MODULE/DRIVER.

N

SLB (50% ILLUMINATION)

EXISTING

120V CIRCUIT

(INCOMING)

EXISTING JUNCTION BOX.

G

SLA (50% ILLUMINATION)

LVOC

B

903 SOUTH PERRY STREET

MONTGOMERY, AL 36104

T. (334) 269-0329 www.bordenandmorris.com

BORDEN

MORRIS

E0.1
E1.1
E2.1
E2.2
E3.1
E4.1
E4.2
E4.3

File details come from the government source that posted it. Updated .