Fan Questions Set 2
1. 260' plus is quite a ways for 24vac. My recommendation would be to use a
24vac coil contactor at the fire panel or it could be placed at the closest control point to ship 120vac to control the fan contactors.
ANSWER: Minimum size wire for the 24vdc will be #12awg. Fire Alarm manufacture and fan manufacture agree that 300feet separation is no problem.